A7_Amendment_2.pdf
PDF 7 MB Posted
- Attached to
- FY19 RRAD General Purpose Warehouse Federal contract opportunity
- Solicitation number
- W9126G19B0007
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| C1_SF_1409_Abstract_of_Offerors.pdf | ||
| A7_Amendment_5.pdf | ||
| A7_Amendment_4.pdf | ||
| Amendment_3.pdf | ||
| Site_Visit.pdf | ||
| A10_FF&E_Package_(GPW)_FINAL.pdf | ||
| B3_Amendment_1.pdf | ||
| FFE_Package_(GPW)_FINAL.pdf | ||
| Drawings_(Part_7_of_9).pdf | ||
| Drawings_(Part_1_of_9).pdf | ||
| Drawings_(Part_2_of_9).pdf | ||
| Drawings_(Part_9_of_9).pdf | ||
| Drawings_(Part_8_of_9).pdf | ||
| Drawings_(Part_3_of_9).pdf | ||
| Drawings_(Part_4_of_9).pdf | ||
| Drawings_(Part_5_of_9).pdf | ||
| Drawings_(Part_6_of_9).pdf | ||
| B3_W9126G19B0007_(Part_3_of_4).pdf | ||
| B3_W9126G19B0007_(Part_4_of_4).pdf | ||
| B3_W9126G19B0007_(Part_1_of_4).pdf | ||
| B3_W9126G19B0007_(Part_2_of_4).pdf |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04 EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The Solicitation for DLA General Purpose Warehouse; Red River Army Depot, Texas is amended as follows.
See SF30 Continuation Sheet(s)
NOTE: Proposal Receipt date is 26 April 2019; at 10:00 a.m.,CST, as previously announced.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 3
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA 15C. DATE SIGNED 15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer) (Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X 9A. AMENDMENT OF SOLICITATION NO.
W912619B0007
X 9B. DATED (SEE ITEM 11)
26-Mar-2019
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
16 -Apr-2019
CODE
US ARMY ENGINEER DISTRICT, FORT WORTH
ATTN: CESWF-CT
819 TAYLOR ST, ROOM 2A19
P.O. BOX 17300
FORT WORTH TX 76102-0300
W9126G 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODE CODE
EMAIL: TEL:
W9126G19B0007
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
CHANGES TO SOLICITATION W9126G19B0007
CHANGES TO THE SPECIFICATIONS
1. New Sections - Add the following accompanying new sections, each bearing the notation W9126G19B007, AMENDMENT 0002.
09 96 00 HIGH-PERFORMANCE COATINGS
10 51 13 METAL LOCKERS
12 48 13 ENTRANCE FLOOR MATS AND FRAMES
2. Replacement Sections - Replace the following sections with the accompanying new sections of the same number and title, bearing the notation W9126G19B007, AMENDMENT 0002:
05 50 13 MISCELLANEOUS METAL FABRICATIONS
06 20 00 FINISH CARPENTRY
08 81 00 GLAZING
10 14 00.10 EXTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 28 13 TOILET ACCESSORIES
11 13 19.13 LOADING DOCK LEVELERS
CHANGES TO THE DRAWINGS
3. Replacement Drawings.- Replace the drawings listed below with the attached new drawings(s) of the same number, W9126G19B007, AMENDMENT 0002 :
A-101 - OVERALL FLOOR PLAN
A-102 - PARTIAL FLOOR PLAN A
A-103 - PARTIAL FLOOR PLAN B
A-104 - PARTIAL FLOOR PLAN C
A-105 - PARTIAL FLOOR PLAN D
A-106 - PARTIAL FLOOR PLAN E
A-107 - PARTIAL FLOOR PLAN F
A-108 - PARTIAL FLOOR PLAN G
A-109 - PARTIAL FLOOR PLAN H
A-110 - PARTIAL FLOOR PLAN ADMIN AREA
A-131 - PARTIAL REFLECTED CEILING PLAN A
A-133 - PARTIAL REFLECTED CEILING PLAN C
A-134 - PARTIAL REFLECTED CEILING PLAN D
A-135 - PARTIAL REFLECTED CEILING PLAN E
A-136 - PARTIAL REFLECTED CEILING PLAN F
A-137 - PARTIAL REFLECTED CEILING PLAN G
A-138 - PARTIAL REFLECTED CEILING PLAN H
A-201 - OVERALL ELEVATIONS
A-202 - NORTH PARTIAL ELEVATIONS
A-203 - SOUTH PARTIAL ELEVATIONS
A-301 - OVERALL BUILDING SECTIONS
A-302 - ENLARGED LONGITUDINAL SECTIONS
A-310 - WALL SECTIONS I
A-311 - WALL SECTION II
W9126G19B0007
A-312 - WALL SECTION III
A-401 - RESTROOM PLAN & ELEVATIONS
A-402 - ENLARGED FLOOR PLANS
A-410 - ENLARGED ELEVATIONS I
A-411 - ENLARGED ELEVATIONS II
A-420 - STAIR PLANS AND SECTIONS
A-501 - PLAN DETAILS I
A-502 - PLAN DETAILS II
EG601 - GROUNDING RISER DIAGRAM
EL505 - LIGHTING DETAIL 5
EL506 - LIGHTING DETAILS 6
ET102 - TELECOMMUNICATIONS PLAN - AREA B
ET103 - TELECOMMUNICATIONS PLAN - AREA C
ET106 - TELECOMMUNICATIONS PLAN - AREA F
ET107 - TELECOMMUNICATIONS PLAN - AREA G
I-601 - INTERIOR FINISH SCHEDULE
S-501 - DETAILS I
End of Summary of Changes
FY19 DLA General Purpose Warehouse RD19DLA
SECTION 09 96 00
HIGH-PERFORMANCE COATINGS
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
MASTER PAINTERS INSTITUTE (MPI)
MPI ASM (2004) Architectural Painting Specification Manual
SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC 7/NACE No.4 (2007; E 2004) Brush-Off Blast Cleaning
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Equipment List; G
SD-03 Product Data
Epoxy Coatings; G
Polyurethane Coatings; G
SD-04 Samples
Color Chips; G
SD-07 Certificates
Epoxy Coatings; G
Polyurethane Coatings; G
Manufacturer's Printed Instructions; G
1.3 QUALITY CONTROL
Comply with Master Painters Institute (MPI) Standards indicated and listed in "MPI Approved Products List." Comply with the requirements in "MPI
SECTION 09 96 00 Page 1
W9126G19B007, AMENDMENT 0002
Architectural Painting Specification Manual" before any project is started.
Submit an equipment list consisting of a list of proposed equipment to be used in performance of construction work.
Submit three color chips 3-inch by 4-inch or manufacture's pull-down of each finish color and gloss as scheduled.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver special coating materials to the project in their original containers bearing manufacturer's name, descriptive label, and coating formulations. Provide new and unopened containers.
Store special coating materials in tightly closed containers in a covered, well-ventilated area where they are not exposed to excessive heat, fumes, sparks, flame, or direct sunlight. Protect water-based coatings against freezing.
Store solvents, thinners, and equipment cleaners with the same care as the coating materials with ambient temperatures continuously maintained at a minimum 45 degrees F.
PART 2 PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
Submit manufacturer's catalog data including manufacturer's name and identification. Include detailed data analysis of each special coating material required for the project, with all the coating constituents measured as percentages of the total weight of the coating. Also provide manufacturer's data concerning application, thinning, and average coverage per gallon
2.2 MATERIALS
2.2.1 Epoxy Coatings
Conform to MPI ASM, No. 116 for epoxy coatings and epoxy block filler, as modified.
Resins for finish coats are based on a polyamide-cured, epoxy-resin material. Apply finish coats with a dry-film thickness of not less than 4 mils per coat. Finish color and gloss are as indicated.
2.2.1.1 Concrete Surface Coatings
Apply a epoxy coating system in conformance with MPI ASM, No. 77 or water-based epoxy coating system in conformance with MPI ASM, No. 115 for vertical concrete surfaces. Apply an epoxy slip-resistant deck coating system in conformance with MPI ASM, No. 82. Apply a prime coat to fill concrete surface pores with a total dry-film thickness of not less than 2 mils.
2.2.1.2 Masonry Surfaces Coatings
Apply a Water-Based, Light-Industrial Coating System in conformance with MPI ASM, No. 110 . Apply a block filler to fill surface pores with a total dry-film thickness of not less than 7 mils.
SECTION 09 96 00 Page 2
2.2.1.3 Ferrous and Galvanized Metal Surface Coatings
Coatings on ferrous and galvanized metal surfaces consist of a prime coat and not less than two finish coats. Comply with MPI ASM, No. 101 for an epoxy zinc primer with a metallic-zinc pigment for the substrate to be coated and the end use of the coated surface. Ensure resin solids and zinc pigment are not less than 80 percent of the total weight of the coating material. Apply prime coat with a total dry-film thickness of not less than 4 mils. Provide an epoxy-based finished coat as specified.
2.2.1.4 Aluminum Surface Coatings
Apply an Epoxy Coating System in conformance with MPI ASM, No. 80 and MPI ASM, No. 77. Apply a prime coat with a total dry-film thickness of not less than 4 mils.
2.2.2 Polyurethane Coatings
Ensure polyurethane coatings conform to MPI ASM for each substrate indicated.
Resins for finish coats are based on a two-part, prepolymer, catalytic-cured, polyurethane material. Apply catalytic-cured coatings with a total dry-film thickness of not less than 10 mils per coat.
Indicate finish color and gloss on the schedules.
2.2.2.1 Concrete Surface Coatings
Apply a Polyurethane, Clear, Two-Component Coating System in conformance with MPI ASM, No. 78. Ensure the prime coat fills surface pores with a total dry-film thickness of not less than 2 mils. Finish coats are polyurethane-based material as specified.
2.2.2.2 Masonry Surface Coatings
Apply a polyurethane, clear, two-component coating system in conformance with MPI ASM, No. 78. Apply block filler to fill surface pores with a total dry-film thickness of not less than 7 mils. Finish coats are polyurethane-based material as specified.
2.2.2.3 Ferrous and Galvanized Metal Surface Coatings
Apply a high-performance architectural latex coating system in conformance with MPI ASM, No. 134, No. 138, and MPI ASM, No. 140. Apply a prime coat with a dry-film thickness of not less than 2 mils. Finish coats are polyurethane-based material as specified.
2.2.2.4 Aluminum Surface Coatings
Apply a water base, light industrial coating system in conformance with MPI ASM, No. 95, MPI ASM, No. 77 and MPI ASM, No. 80 for epoxy coating MPI ASM, No. 80 for polyurethane coats on aluminum surfaces. Prime coat is a polyurethane-resin material as recommended by the coating manufacturer for the substrate to be coated. Apply prime coat with a dry-film thickness of not less than 2 mils. Finish coats are polyurethane-based material as specified.
SECTION 09 96 00 Page 3
2.2.2.5 Wood Surface Coatings
Apply a clear polyurethane two-component coating in conformance with MPI ASM, No. 13 and MPI ASM, No. 78. Apply prime coat with a dry-film thickness of not less than 5 mils. Finish coats are polyurethane-based material as specified.
2.2.3 Concrete Surface Coatings
Apply a minimum three coats on concrete surfaces. Provide prime coats with a chlorinated-rubber resin material as recommended by the coating manufacturer for the substrate to be coated and the end use of the coated surfaces. Ensure the prime coat fills concrete surface pores with a total film thickness of not less than 2 mils. Finish coats are chlorinated-rubber-based coatings as specified.
2.2.4 Masonry Surface Coatings
Apply a minimum of two finish coats of masonry block filler on masonry surfaces. Block fillers are based on an epoxy-ester resin material as recommended by the coating manufacturer for the substrate and end use of the coated surface. Fill surface pores with block filler at a total film thickness of not less than 7 mils. Finish coats are chlorinated-rubber-based coatings as specified.
2.2.5 Ferrous and Galvanized Metal Surface Coatings
Apply a minimum two coats of high performance architectural latex coating in conformance with MPI ASM, No. 79 on ferrous and galvanized metal surfaces. Apply prime coat with a dry-film thickness of not less than 3 mils. Finish coats are chlorinated rubber-based coatings as specified.
2.2.6 Aluminum Surface Coatings
Apply a minimum three coats of quick drying primer for aluminum surfaces.
Ensure prime coats conform to MPI ASM, No. 80 for aluminum coating system.
PART 3 EXECUTION
3.1 PREPARATION
3.1.1 Surface Preparation
Protect adjacent materials and equipment against damage from spillage, dripping, and spatter of coating materials. Leave clean building materials and equipment with all damaged surfaces corrected. Provide "WET PAINT" signs to indicate newly painted surfaces.
Protect work of other trades against damage from coating operation.
Correct damage by cleaning, repairing, replacing, and recoating, as approved by the Contracting Officer, and leave in an undamaged condition.
At completion of construction activities of other trades, touch up and restore damaged or defaced coated surfaces.
Provide forced ventilation for interior spaces during application and drying of coatings to prevent the buildup of toxic or explosive concentrations of solvent vapors.
SECTION 09 96 00 Page 4
Provide fire extinguishers of the required quantity and correct type to combat flammable liquid fires.
Dispose of rags that are used to wipe up coating materials, solvents, and thinners by drenching with water and placing them in a covered metal container
3.1.2 Cleaning
At end of each workday, remove rubbish, empty cans, rags, and other discarded materials from Project site.
After completing coating application, clean spattered surfaces. Remove spattered coatings by washing, scraping, or other methods. Do not scratch or damage adjacent finished surfaces.
Clean application equipment promptly and thoroughly with a suitable solvent after each use and stored in a clean, covered, well-ventilated container.
3.1.3 Concrete Surfaces
Conform to MPI ASM for substrates indicated. Remove plates, machined surfaces, and similar items already in place that are not to be coated.
Provide surface-applied protection before surface preparation and coating where removal is impractical or impossible. After completing coating operations, reinstall items that were removed.
Clean dirt, oil, grease, and incompatible paints from substrates to ensure bonding. Coordination of shop-applied prime coats with high-performance coatings is critical. Remove incompatible primers. Reprime substrate with compatible primers as required to produce coating systems indicated.
3.1.3.1 Concrete Substrates
Remove release agents, curing compounds, efflorescence, and chalk. Maximum allowable moisture content of concrete is 12 percent. Measure moisture content with an electronic moisture meter.
Clean surfaces with pressurized water. Use pressure range of 1500 to 4000 psi at 6 inch to 12 inch.
Comply with SSPC 7/NACE No.4 (NACE No. 4), "Brush-Off Blast Cleaning" for abrasive cleaning.
3.1.3.2 Steel Substrates
Remove rust and loose mill scale. Clean using methods recommended in writing by coating manufacturer. Conform to SSPC 7/NACE No.4 for blast cleaning.
3.1.3.3 Galvanized-Metal Substrates
Remove grease and oil residue from galvanized sheet metal fabricated from coil stock by mechanical methods to produce clean, lightly etched surfaces that promote adhesion of subsequently applied coatings.
3.1.3.4 Aluminum Substrates
Remove surface oxidation.
SECTION 09 96 00 Page 5
3.1.3.5 Wood Substrates
Wood substrates that contain small surface knots are prepped by sanding surfaces smooth. Apply a thin coat of knot sealer before applying an interior latex-based wood primer. Prime edges, ends, faces, undersides, and back sides of wood. After priming, fill holes and crevices to the finished surface with putty or plastic wood filler. After finished surface is dry, smooth surface by sanding, for a finished product.
3.1.4 Coating Material Preparation
Mix and prepare coating materials in accordance with the coating manufacturer's printed instructions for applying the particular material and coat. Keep materials which are not in actual use in closed containers.
Coating materials that have been mixed with an automatic shaker are allowed to stand to let air bubbles escape, then given a final hand mixing before application. Stir materials so as to produce a mixture of uniform density. Stir at frequent intervals during application to prevent skinning. Do not stir film which may form on the surface of the material.
Remove film and strain, if necessary.
3.1.4.1 Thinning
Thinning is done in accordance with coating manufacturer's printed directions for the particular material and coat.
3.1.4.2 Tinting
Ensure prime and intermediate coats of paint are slightly different tints from the finish coat to facilitate identification of each coat. Tinting is done by the coating manufacturer and clearly identified as to color and coat.
3.2 APPLICATION
Do not perform exterior painting in damp or rainy weather. Interior painting is not allowed until the building is enclosed and has thoroughly dried out. Painting is not allowed below 50 degrees F or above 95 degrees F. Apply paint in accordance with the coating manufacturer's recommendations, and as specified.
Ensure coating application is done by skilled applicators. Apply coatings to clean and properly prepared surfaces. Apply coatings with clean, high-quality application equipment. Allow sufficient time between coats to ensure complete drying and curing. Sand and dust surfaces between coatings, as required, to produce a surface free of visible defects.
Lightly sand high gloss coatings and clear finishes between coats to ensure bond of following coats.
Apply coats to the surfaces in an even film. Cloudiness, spotting, holidays, laps, application marks, runs, sags, and other similar surface imperfections are not acceptable. Remove defective coating applications and re-coat as directed.
Ensure coating lines such as wainscots are sharp, true, and well-defined.
Tape may be used to establish coating lines, providing tape is removed before ragging or sawtooth edges form.
SECTION 09 96 00 Page 6
Ensure surfaces, including edges, corners, crevices, welds, and other similar changes in surface plane, meet the dry-film thickness not less than specified.
3.2.1 Brush Application
Use clean, proper size brushes for high-quality application of the specified coating materials. Brush out slow-dry coatings. Brush out quick-dry coatings only enough to spread out evenly.
3.2.2 Roller Application
Use clean roller covers of the proper nap length, nap texture, and material for high-quality application of the specified coating materials.
Ensure roller application is equivalent in all respects to the same coats applied by high-quality brush application.
3.2.3 Spray Application
Do not allow spray application of coatings.Spray application equipment is limited to airless-spray equipment and electrostatic-spray equipment.
Ensure equipment is clean and operated by workmen skilled in high quality application of coating materials.
Spray application of coatings is limited to finish coats on metal frame works, siding, decking, wire mesh, and other surfaces where hand work would be inferior. Apply spray coatings as equivalent in all respects to the same coats applied by high quality brush application. Permit each spray coat to cure before the succeeding coat is applied. Do not double back with application equipment, for the purpose of building up film thickness of two coats in one operation.
Cover surfaces adjacent to sprayed areas to prevent damage from overspray, coating rebound, and spray drift.
3.3 FIELD QUALITY CONTROL
3.3.1 Field Test
Government may take dry-film tests from time to time on finished surfaces.
Apply additional coatings to surfaces where there is less than the minimum specified dry-film thickness.
3.3.2 Repairing
Remove damaged and unacceptable portions of completed work and replace with new work to match adjacent surfaces at no additional cost to the Government.
-- End of Section --
SECTION 09 96 00 Page 7
SECTION 10 51 13
METAL LOCKERS
AMENDMENT NO. 0002
(AM#0002)
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A924/A924M (2017) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM D6386 (2016) Standard Practice for Preparation of Zinc (Hot-Dip Galvanized) Coated Iron and Steel Product and Hardware Surfaces for Painting
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-PRF-22750 (2011; Rev G) Coating, Epoxy, High Solids
MIL-PRF-23377 (2012; Rev K) Primer Coatings: Epoxy, High Solids
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FS AA-L-00486 (Rev J) Lockers, Clothing, Steel
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Types; G
Location; G
SECTION 10 51 13 Page 1
Installation
Numbering system
SD-03 Product Data
Material
Locking Devices
Lock Control Chart
Handles
Finish
Locker components
Assembly instructions
SD-04 Samples
Color chips; G
1.3 DELIVERY, HANDLING, AND STORAGE
Deliver lockers and associated materials in their original packages, containers, or bundles bearing the manufacturer's name and the name of the material. Protect from weather, soil, and damage during delivery, storage, and construction.
1.4 FIELD MEASUREMENTS
To ensure proper fits, make field measurements prior to the preparation of drawings and fabrication. Verify correct location
1.5 QUALITY ASSURANCE
1.5.1 Color Chips
Provide a minimum of three color chips, not less than 3 inches square, of each color scheduled.
Government may request performance-characteristic tests on assembled lockers. Tests and results must conform to FS AA-L-00486. Lockers not conforming will be rejected.
PART 2 PRODUCTS
2.1 TYPES
Locker must have the following type and size in the location and quantities indicated. Locker finish colors will be as scheduled.
2.1.1 Double-Tier
Double-tier lockers must be as follows:
SECTION 10 51 13 Page 2
Type DTC-1: Double-tier locker 12 inches wide, 12 inches deep, and 72 inches high, attached to a 6-inch high closed base
2.2 MATERIAL
2.2.1 Galvanized Steel Sheet
ASTM A653/A653M and ASTM A924/A924M, commercial quality, minimized spangle, galvanized steel sheet with not less than G60 zinc coating. Prepare surface of sheet for painting in accordance with ASTM D6386, Method A.
Minimum uncoated sheet thickness .060 inches.
2.2.2 Chromium Coating
Nickel and chromium electrodeposited on the specified base metal. Conform to ASTM B456, SC-3, as applicable to the base metal.
2.2.3 Finish
Primer, MIL-PRF-23377; topcoat, MIL-PRF-22750.
2.2.3.1 Color
Manufactures standard black.
2.3 COMPONENTS
2.3.1 Built-In Locks
Built-in locks are not required.
2.3.2 Coat Hooks
FS AA-L-00486, chromium plated.
2.3.3 Hanger Rods
FS AA-L-00486.
2.3.4 Door Handles
FS AA-L-00486. Provide zinc alloy or steel handles with a chromium coating.
2.3.5 Doors
FS AA-L-00486, not less than 0.0598 inch thick steel sheet.
2.3.5.1 Hinges
In addition to the requirements of FS AA-L-00486, provide 5-knuckle hinges, minimum 2 inches high. Fabricate knuckle hinges from not less than 0.0787 inch thick steel sheet. A full height piano hinge may be provided if standard with the manufacturer. Weld or bolt hinges to the door frame.
Weld, bolt, or rivet hinges to the door.
2.3.5.2 Latching Mechanisms
FS AA-L-00486.
SECTION 10 51 13 Page 3
2.3.6 Latch Strikes
FS AA-L-00486. Fabricate from not less than 0.0787 inch thick steel sheet, except latch strike may be continuous from top to bottom and fabricated as part of the door framing.
2.3.7 Silencers
FS AA-L-00486.
2.3.8 Back and Side Panels, Tops, and Bottoms
FS AA-L-00486, not less than 0.0474 inch thick steel sheet.
2.3.9 Sloping Locker Tops
Provide sloping locker tops in addition to the locker-section flat tops.
Sloping tops must be continuous in length. Provide fillers or closures at the exposed end of sloping tops. Fabricate sloping tops from not less than 0.0478-inch thick steel sheet.
2.3.10 Shelves
FS AA-L-00486. Fabricate from not less than 0.0598 inch thick steel sheet.
2.3.11 Base Panels
FS AA-L-00486.
2.3.12 Number Plates
FS AA-L-00486. Aluminum. Provide consecutive numbers .
2.3.13 Fastening Devices
Provide bolts, nuts, and rivets as specified in FS AA-L-00486.
PART 3 EXECUTION
3.1 ASSEMBLY AND INSTALLATION
Assemble lockers according to the locker manufacturer's instructions.
Align lockers horizontally and vertically. Bolt adjacent lockers together. Adjust doors to operate freely without sticking or binding and to ensure they close tightly.
3.2 NUMBERING SYSTEM
Install number plates on lockers consecutively with odd numbers on top and even numbers on bottom.
3.3 FIELD QUALITY CONTROL
3.3.1 Testing
Government may request performance-characteristic tests on assembled
SECTION 10 51 13 Page 4 lockers in accordance with FS AA-L-00486. Lockers not conforming will be rejected.
3.3.2 Repairing
Remove and replace damaged and unacceptable portions of completed work with new.
3.3.3 Cleaning
Clean surfaces of the work, and adjacent surfaces soiled as a result of the work, in an approved manner. Remove equipment, surplus materials, and rubbish from the site.
(/AM#0002)
-- End of Section --
SECTION 10 51 13 Page 5
SECTION 12 48 13
ENTRANCE FLOOR MATS AND FRAMES
AMENDMENT NO. 0002
(AM#0002)
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM D2047 (2017) Standard Test Method for Static Coefficient of Friction of Polish-Coated Floor Surfaces as Measured by the James Machine
ASTM E648 (2017a) Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
1.2 SUSTAINABILITY REPORTING
Materials in this technical specification may increase contract compliance with sustainability requirements.
1.2.1 EPA Comprehensive Procurement Guidelines
See Section 01 33 29 SUSTAINABILITY REPORTING for requirements associated with EPA-designated products.
1.2.2 USDA Biobased
See Section 01 33 29 SUSTAINABILITY REPORTING for requirements associated with USDA Biobased products.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office
SECTION 12 48 13 Page 1 that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Installation Drawings;
Detail Drawings;
SD-03 Product Data
Entrance Floor Mats and Frames;
Adhesives and Concrete Primers;
SD-04 Samples
Entrance Floor Mats and Frames;
SD-08 Manufacturer's Instructions
Manufacturer's Instructions
SD-10 Operation and Maintenance Data
Protection, Maintenance, and Repair Information
1.4 QUALITY CONTROL
Comply with 36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines for installed entrance floor mats and frames.
Ensure that entrance floor mats and frames are slip-resistant in accordance with ASTM D2047, with a minimum 0.60 coefficient of friction, for accessible routes and are structurally capable of withstanding a wheel load of 350 lb/wheel. Ensure that flammability is in accordance with ASTM E648, Class 1, Critical Radiant Flux, minimum 0.45 watts/square meter.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the project site in their original packages or containers bearing labels clearly identifying the manufacturer, brand name, and quality or grade.
Store materials in their original unbroken packages or containers in the area in which they will be installed. Unwrap, inspect, and place mats at indicated locations. Remove all excess packing materials.
SECTION 12 48 13 Page 2
PART 2 PRODUCTS
2.1 MANUFACTURED UNITS
2.1.1 Entrance Floor Mats and Frames
Submit the manufacturer's catalog data. Submit samples of assembled sections of floor mats showing corners, intersections, and other details of construction. Submit samples of exposed floor mats, frame finishes, and accessories.
2.1.1.1 Rubber Mats
Provide mats 3/8 inches thick with square edges for recessed installations. Provide mats with standard wide-wale corrugated top profile and standard knob-base bottom surface. Ensure that mats are made of a nonslip prime-quality compound free of calendaring and curing defects, and resistant to weather aging and ozone in normal concentrations.
2.1.1.2 Floor Grids
Provide a floor grid consisting of a series of aluminum tread rails spaced 1 1/2 inches on center and running counter to the traffic flow. Ensure that floor grids allow debris to fall to the subfloor. Rest grid assemblies on a continuous vinyl cushion mounted to each continuous foot. Provide all anchors, fasteners, accessories, and other parts required for a complete installation.
2.1.1.3 Frames
Provide recessed frames in extruded aluminum Alloy 6061-T6 or Alloy 6063-T5 ASTM B221. Ensure that the frame depth accommodates the mat and system specified. Frame color is clear . Ensure that edge-frame members are fabricated in single lengths or with the fewest pieces possible, with hairline joints equally spaced and pieces spliced together by straight connecting pins. Ensure that any concealed surfaces of aluminum frames that contact cementous material are coated with the manufacturer's standard protective coating. Ensure that frames include accessories and devices required for a complete installation.
2.1.1.4 Tread Insert Options
Provide tread inserts consisting of recycled rubber .
2.1.2 Adhesives and Concrete Primers
Provide adhesives and concrete primers, where required, according to the manufacturer's recommendations.
2.1.3 Color and Size
Ensure that color is in accordance with Section 09 06 00 SCHEDULES FOR FINISHES. Ensure that the size of mat is as indicated.
PART 3 EXECUTION
3.1 EXAMINATION
Comply with the manufacturer's requirements for substrates and floor
SECTION 12 48 13 Page 3 conditions affecting installation of floor mats and frames. Ensure that all unsatisfactory conditions have been corrected before installation.
3.2 INSTALLATION
Submit detail drawings, and custom graphics drawings as required. Provide installation drawings. Provide the manufacturer's protection, maintenance, and repair information.
Install floor mats and frames according to manufacturer's instructions.
Set mat tops at the height recommended by the manufacturer for the most effective cleaning action. Provide clearance between bottoms of doors and tops of mats. Coordinate recess frame installation with concrete construction to ensure that frame anchorage is correct and that the base is level and flat. Install grout and fill around frames and, if required to set mat tops at proper elevations, in recesses under mats. Finish grout and fill smooth and level.
(/AM#0002)
-- End of Section --
SECTION 12 48 13 Page 4
SECTION 05 50 13
MISCELLANEOUS METAL FABRICATIONS
AMENDMENT NO. 0002
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 303 (2016) Code of Standard Practice for Steel Buildings and Bridges
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7 (2010; Errata 2011; Supp 1 2013) Minimum Design Loads for Buildings and Other Structures
AMERICAN SOCIETY OF SAFETY ENGINEERS (ASSE/SAFE)
ASSE/SAFE A10.3 (2013) Operations - Safety Requirements for Powder Actuated Fastening Systems
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
ASME INTERNATIONAL (ASME)
ASME B18.2.1 (2012; Errata 2013) Square and Hex Bolts and Screws (Inch Series)
ASME B18.2.2 (2010) Nuts for General Applications:
Machine Screw Nuts, Hex, Square, Hex Flange, and Coupling Nuts (Inch Series)
ASME B18.21.1 (2009; R 2016) Washers: Helical Spring-Lock, Tooth Lock, and Plain Washers (Inch Series)
ASME B18.6.2 (1998; R 2010) Slotted Head Cap Screws, Square Head Set Screws, and Slotted Headless Set Screws: Inch Series
SECTION 05 50 13 Page 1
ASME B18.6.3 (2013) Machine Screws, Tapping Screws, and Machine Drive Screws (Inch Series)
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2013) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A307 (2014) Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
ASTM A47/A47M (1999; R 2014) Standard Specification for Ferritic Malleable Iron Castings
ASTM A48/A48M (2003; R 2012) Standard Specification for Gray Iron Castings
ASTM A500/A500M (2013) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A780/A780M (2009; R 2015) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A786/A786M (2015a) Standard Specification for Hot-Rolled Carbon, Low-Alloy, High-Strength Low-Alloy, and Alloy Steel Floor Plates
ASTM A924/A924M (2016a) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM B108/B108M (2015) Standard Specification for Aluminum-Alloy Permanent Mold Castings
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
SECTION 05 50 13 Page 2
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B26/B26M (2014; E 2015) Standard Specification for Aluminum-Alloy Sand Castings
ASTM C1513 (2013) Standard Specification for Steel Tapping Screws for Cold-Formed Steel Framing Connections
ASTM D1187/D1187M (1997; E 2011; R 2011) Asphalt-Base Emulsions for Use as Protective Coatings for Metal
MASTER PAINTERS INSTITUTE (MPI)
MPI 79 (Oct 2009) Alkyd Anti-Corrosive Metal Primer
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM MBG 531 (2009) Metal Bar Grating Manual
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 211 (2016) Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances
SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC SP 3 (1982; E 2004) Power Tool Cleaning
SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fabrication Drawings of Structural Steel Door Frames; G
Access Doors and Panels, Installation Drawings; G
(AM#0002) Cover Plates and Frames, Installation Drawings; G(/AM#0002)
Expansion Joint Covers, Installation Drawings; G
(AM#0002) Wheel Guards, Installation Drawings; G(/AM#0002)
SECTION 05 50 13 Page 3
Embedded Angles and Plates, Installation Drawings; G
Roof Hatch; G
Submit fabrication drawings showing layout(s), connections to structural system, and anchoring details as specified in AISC 303.
Submit templates, erection and installation drawings indicating thickness, type, grade, class of metal, and dimensions. Show construction details, reinforcement, anchorage, and installation with relation to the building construction.
Extruded Floor Mat Frames
Metal Safety Nosings
SD-03 Product Data
Access Doors and Panels
(AM#0002) Cover Plates and Frames(/AM#0002)
Control-Joint Covers
Expansion Joint Covers
Structural Steel Door Frames
(AM#0002) Wheel Guards(/AM#0002)
Roof Hatch
SD-04 Samples
Expansion Joint Covers
Control-Joint Covers
Provide full size samples , taken from manufacturer's stock, and be complete as required for installation in the structure.
Samples may be installed in the work, provided each sample is clearly identified and its location recorded.
Extruded Floor Mat Frames
Metal Safety Nosings
1.3 QUALIFICATION OF WELDERS
Qualify welders in accordance with AWS D1.1/D1.1M. Use procedures, materials, and equipment of the type required for the work.
1.4 DELIVERY, STORAGE, AND PROTECTION
Protect from corrosion, deformation, and other types of damage. Store items in an enclosed area free from contact with soil and weather. Remove
SECTION 05 50 13 Page 4 and replace damaged items with new items.
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Structural Carbon Steel
ASTM A36/A36M.
2.1.2 Structural Tubing
ASTM A500/A500M.
2.1.3 Steel Pipe
ASTM A53/A53M, Type E or S, Grade B.
2.1.4 Fittings for Steel Pipe
Standard malleable iron fittings ASTM A47/A47M.
2.1.5 Gratings
a. Gray cast iron ASTM A48/A48M, Class 40.
b. Metal plank grating, non-slip requirement, aluminum ASTM B209, 6061-T6;
steel ASTM A653/A653M, G90.
c. Metal bar type grating NAAMM MBG 531.
2.1.6 Floor Plates, Patterned
Floor plate ASTM A786/A786M. Steel plate shall not be less than 14 gage.
2.1.7 Anchor Bolts
ASTM A307. Where exposed, shall be of the same material, color, and finish as the metal to which applied.
2.1.7.1 Post-Installed Anchors
Provide post-installed anchors as indicated on the strucutral drawings.
2.1.7.2 Lag Screws and Bolts
ASME B18.2.1, type and grade best suited for the purpose.
2.1.7.3 Toggle Bolts
ASME B18.2.1.
2.1.7.4 Bolts, Nuts, Studs and Rivets
ASME B18.2.2 or ASTM A307.
SECTION 05 50 13 Page 5
2.1.7.5 Powder Actuated Fasteners
Follow safety provisions of ASSE/SAFE A10.3.
2.1.7.6 Screws
ASME B18.2.1, ASME B18.6.2, ASME B18.6.3 and ASTM C1513.
2.1.7.7 Washers
Provide plain washers to conform to ASME B18.21.1. Provide beveled washers for American Standard beams and channels, square or rectangular, tapered in thickness, and smooth. Provide lock washers to conform to ASME B18.21.1.
2.1.8 Aluminum Alloy Products
Conform to ASTM B209 for sheet plate, ASTM B221 for extrusions and ASTM B26/B26M or ASTM B108/B108M for castings, as applicable. Provide aluminum extrusions at least 1/8 inch thick and aluminum plate or sheet at least 0.050 inch thick.
2.2 FABRICATION FINISHES
2.2.1 Galvanizing
Hot-dip galvanize items specified to be zinc-coated, after fabrication where practicable. Galvanizing: ASTM A123/A123M, ASTM A153/A153M, ASTM A653/A653M or ASTM A924/A924M, G90, as applicable.
2.2.2 Galvanize
Anchor bolts, grating fasteners, washers, and parts or devices necessary for proper installation, unless indicated otherwise.
2.2.3 Repair of Zinc-Coated Surfaces
Repair damaged surfaces with galvanizing repair method and paint conforming to ASTM A780/A780M or by application of stick or thick paste material specifically designed for repair of galvanizing, as approved by Contracting Officer. Clean areas to be repaired and remove slag from welds. Heat surfaces to which stick or paste material is applied, with a torch to a temperature sufficient to melt the metallics in stick or paste; spread molten material uniformly over surfaces to be coated and wipe off excess material.
2.2.4 Shop Cleaning and Painting
2.2.4.1 Surface Preparation
Blast clean surfaces in accordance with SSPC SP 6/NACE No.3. Surfaces that will be exposed in spaces above ceiling or in attic spaces, crawl spaces, furred spaces, and chases may be cleaned in accordance with SSPC SP 3 in lieu of being blast cleaned. Wash cleaned surfaces which become contaminated with rust, dirt, oil, grease, or other contaminants with solvents until thoroughly clean. Steel to be embedded in concrete shall be free of dirt and grease. Do not paint or galvanize bearing surfaces, including contact surfaces within slip critical joints, but coat with rust preventative applied in the shop.
SECTION 05 50 13 Page 6
2.2.4.2 Pretreatment, Priming and Painting
Apply pretreatment, primer, and paint in accordance with manufacturer's printed instructions. On surfaces concealed in the finished construction or not accessible for finish painting, apply an additional prime coat to a minimum dry film thickness of 1.0 mil. Tint additional prime coat with a small amount of tinting pigment.
2.2.5 Nonferrous Metal Surfaces
Protect by plating, anodic, or organic coatings.
2.2.6 Aluminum Surfaces
2.2.6.1 Surface Condition
Before finishes are applied, remove roll marks, scratches, rolled-in scratches, kinks, stains, pits, orange peel, die marks, structural streaks, and other defects which will affect uniform appearance of finished surfaces.
2.2.6.2 Aluminum Finishes
Unexposed sheet, plate and extrusions may have mill finish as fabricated.
Sandblast castings' finish, medium, AA DAF45. Unless otherwise specified, provide all other aluminum items with a anodized finish. Provide a coating thickness not less than that specified for protective and decorative type finishes for items used in interior locations or architectural Class I type finish for items used in exterior locations in AA DAF45. Provide a polished satin finish on items to be anodized.
2.3 ACCESS DOORS AND PANELS
Provide flush type access doors and panels unless otherwise indicated.
Fabricate frames for access doors of steel not lighter than 14 gage with welded joints and anchorage for securing into construction. Provide access doors with a minimum of 14 by 20 inches and of not lighter than 14 gage steel, with stiffened edges and welded attachments. Provide access doors hinged to frame and with a flush-face, turn-screw-operated latch.
2.4 CONTROL-JOINT COVERS
Provide control-joint covers to be located on wall surfaces of concrete, masonry and tile work. Provide protective coating on the surface in contact with concrete, masonry or tile.
2.5 CORNER GUARDS AND SHIELDS
For jambs and sills of openings and edges of platforms provide steel shapes and plates anchored in masonry or concrete with welded steel straps or end-weld stud anchors. Form corner guards for use with glazed or ceramic tile finish on walls with 0.0625 inch thick corrosion-resisting steel with polished or satin finish, extend 5 feet above the top of cove base or to the top of the wainscot, whichever is less, and securely anchor to the supporting wall. Corner guards on exterior shall be galvanized.
(AM#0002)
2.6 COVER PLATES AND FRAMES
Fabricate cover plates of 1/4 inch thick rolled steel weighing not more than
SECTION 05 50 13 Page 7
100 pounds per plate with a slip-resistant, carbon steel conforming to ASTM A283/A283M having a minimum static coefficient of friction of 0.50 when tested in accordance with ASTM D2047. On wearing surfaces provide aluminum oxide or silicon carbide. Plate shall be galvanized. Frames shall be structural steel shapes and plates, with bent steel bars or headed anchors welded to frame for anchoring to concrete securely fastened to the structure as indicated. Miter and weld all corners. Butt joint straight runs. Allow for expansion on straight runs over 15 feet. Provide holes for lifting tools. Provide flush drop handles for removal formed from 1/4 inch round stock where indicated. Remove sharp edges and burrs from cover plates and exposed edges of frames. Weld all connections and grind top surface smooth. Weld bar stops every six inches. Provide 1/8 inch clearance at edges and between cover plates.
(/AM#0002)
2.6 EXPANSION JOINT COVERS
Provide expansion joint covers constructed of extruded aluminum with anodized satin aluminum finish for walls and ceilings and with standard mill finish for floor covers and exterior covers. Furnish plates, backup angles, expansion filler strip and anchors as indicated on the drawings.
Providefire rated expansion joint systems with hourly rating as indicated on the drawings.
2.7 EXTRUDED FLOOR MAT FRAMES
Provide recess frames for roll-up floor mats of extruded 6063-T5 aluminum, in sizes shown. Miter corners to ensure accurate fitting. Determine depth of recess by the mat thickness. Anchor frames in concrete with anchor pins or bolts. Provide roll-up mats of aluminum construction with carpet abrasive surface. Provide roll-up mats for use in level surface area.
Show construction details of recessed areas on the drawings.
2.8 METAL SAFETY NOSINGS
Between stringers, provide abrasive cast metal safety nosings, 4 inches wide by the full length of the step. Fabricate nosings to the thickness, profile, and surface pattern indicated. Equip each nosing with integral anchors for embedding in the concrete stair tread, and space the anchors not more than 4 inches from each end and not more than 15 inches on center.
(AM#0002)
2.9 GAS-TIGHT MANHOLE COVER AND FRAME
Provide a heavy duty type made of ductile cast-iron with bolted lid, machined bearing surfaces and gasket grooves, continuous neoprene gasket, counter sunk bronze hex head cap screws, and concealed watertight pickholes. Provide frame with a 30 inch diameter clear opening. Maximum weight of frame and cover together to be 530 pounds.
(/AM#0002)
2.9 GUARD POSTS (BOLLARDS/PIPE GUARDS)
As indicated on the drawings, provide prime coated standard weight steel pipe as specified in ASTM A53/A53M. Anchor posts in concrete as indicated and fill solidly with concrete with minimum compressive strength of 2500 psi.
SECTION 05 50 13 Page 8
2.10 MISCELLANEOUS PLATES AND SHAPES
Provide for items that do not form a part of the structural steel framework, such as lintels, sill angles, miscellaneous mountings and frames. Provide lintels fabricated from structural steel shapes over openings in masonry walls and partitions as indicated and as required to support wall loads over openings. Provide with connections and fasteners and welds. Construct to have at least 8 inches bearing on masonry at each end.
Provide angles and plates, ASTM A36/A36M, for embedment as indicated.
Galvanize embedded items exposed to the elements according to
ASTM A123/A123M.
(AM#0002)
2.11 SAFETY CHAINS
Construct safety chains of galvanized steel, straight link type, 3/16 inch diameter, with at least twelve links per foot, and with snap hooks on each end. Test safety chain in accordance with ASTM A467/A467M, Class CS.
Provide snap hooks of boat type. Provide galvanized 3/8 inch bolt with 3/4 inch eye diameter for attachment of chain, anchored as indicated. Supply two chains, 4 inches longer than the anchorage spacing, for each guarded area. Locate safety chain where indicated. Mount the top chain feet 6 inches above the floor and mount the lower chain 2 feet above the floor.
2.12 SECURITY GRILLES
Fabricate of channel frames with not less than two masonry anchors at each jamb and 1/2 inch hardened steel bars spaced not over 4 inches both ways and welded to frame. Provide 18 by 16 mesh screen and two layers of 1/4 inch hardware cloth clamped to frame.
(/AM#0002)
2.11 STRUCTURAL STEEL DOOR FRAMES
a. Provide frames as indicated. If not otherwise shown, construct frames of structural shapes, or shape and plate composite, to form a full depth channel shape with at least 1 1/2 inchoutstanding legs. For single swing doors, provide continuous 5/8 by 1 1/2 inch bar stock stops at head and jambs.
b. Where track, guides, hoods, hangers, operators, and other such accessories are required, provide support as indicated.
c. Provide jamb anchors near top, bottom, and at not more than 24 inch intervals. Provide the bottom of each jamb member with a clip angle welded in place with two 1/2 inchdiameter floor bolts for adjustment.
d. Provide spreaders between…