Amendment W911YN18B00020007
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| OF1419_W91YN18B0002_signed.pdf | ||
| Bid_Opening_Attendance_Sheet_23Oct18.pdf | ||
| W911YN18B00020008.pdf | ||
| ASK-01.pdf | ||
| SSK-01.pdf | ||
| W911YN18B0002_QA_10-5-2018.xlsx | XLSX spreadsheet | |
| W911YN18B00020006.pdf | ||
| W911YN18B00020005.pdf | ||
| W911YN18B0002_QA_9-28-2018.xlsx | XLSX spreadsheet | |
| W911YN18B00020004.pdf | ||
| W911YN18B00020003.pdf | ||
| W911YN18B0002_QA_9-4-2018.xlsx | XLSX spreadsheet | |
| Site_visit_23Aug18_attendance.pdf | ||
| W911YN18B0002_QA_8-31-2018.xlsx | XLSX spreadsheet | |
| W911YN18B0002_QA_8-20-18.xlsx | XLSX spreadsheet | |
| W911YN18B00020002.pdf | ||
| Site_visit_1Aug18_attendance.pdf | ||
| W911YN18B00020001.pdf | ||
| Pre-Bid_Site_Visit_Minutes_W911YN18B0002.pdf | ||
| W911YN18B0002.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
This Amendment incorporates by reference the solicitation questions and responses, numbers 1 through 46, as of October 5, 2018, and sketches ASK-01 and SSK-01 are added, in accordance w ith FAR provision 52.214-6--Explanation to Prospective Bidders.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 12
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 05-Oct-2018
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W911YN18B0002
X 9B. DATED (SEE ITEM 11)
20-Jul-2018
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
05-Oct-2018
CODE
USPFO FOR FLORIDA
P O BOX 1008
189 MARINE STREET
ST AUGUSTINE FL 32085-1008
W911YN 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W911YN18B0002
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE
The following have been added by full text:
QUESTIONS AND ANSWERS
W911YN18B0002 ‐ Bidding Questions/Response
Comment Number
Date Discipline Spec/ Report
Sheet Question/Comment Response
1 7/30/2018 Roof framing
05 16
Retrofit Framings Section 05 16 50 – 1.03 – A – 2. “Approval shall have been granted to any manufacturing facility producing the retrofit roof framing system components by the MBMA and IAS (International Accreditation Services), for quality assurance in manufacturing operations. A letter from the manufacturer certifying compliance will accompany the product approval submittals.” We ask to waive this approval in lieu of our Factory Mutual accreditation, which is similar in requirements. Or as an alternate accreditation. We recently did a retrofit project for at Avon Park Air Force Range, FL with similar requirements.
Atkins will not recommend waiving these industry accepted standards/accreditation.
These associations set a minimum standard in an objective manner which is generally accepted in the Metal building manufacturing industry.
2 8/9/2018 T‐102;
E‐001
BUILDING 1885, Re: Drawings T‐102 and Legend on E‐001 and Spec Div 27. Is there any equipment to be provided or is the work strictly the wiring, conduits and boxes? If so, please clarify/specify the equipment to be provided.
Contractor shall comply with the requirements indicated on the drawings and in specification section 271000 Building TelecommunicationCabling System.Work includes, cabling, conduits, supports, back boxes, data outlets and testing. No other telecommunication equipment is included.
3 8/24/2018 Fire Alarm Are we required to meet the requirements of the UFC regarding mass notification systems? The plans and specification do not make any reference to mass notification.
The project inculudes a new Fire Alarm System as indicated on the drawings and specifications section
283163.00. There is no
Mass Notification System.
4 8/24/2018 Fire Alarm Are we to include the required dual‐lens strobes? (Clear for fire and amber for MNS).
Please see response above.
5 8/24/2018 Fire Alarm Are we to include the required local operator’s console or
LOC?
Please see response above.
6 8/24/2018 Fire Alarm Are we to include the required Monaco radio transmitter capable of mass notification?
Please see response above.
7 8/28/2018 Civil C‐103 The drawings show a transition from 8” pvc to 8” HDPE, then back. That typically implies a directional drill for that area of pipe. This work may require a site contractor to obtain a separate sub to mobilize. It is a relatively short run and could be very expensive. Please confirm if that area must be directional drilled or if it can be open‐cut like the remainder of the water line?
That section is to be directional drill. See callout
33.07. This area is shown
to be directionally drilled to limit the impacts of Southshore Avenue. If that area is to be open cut, the roadway will have to be closed until the roadway is stabilized for traffic.
8 8/28/2018 Civil C‐502;
C‐106
Limits of work for Milling and Resurfacing of Asphalt ‐‐ Reference Drawing Sheet C‐ 502, Typical Paving Detail and Drawing Sheet C‐106, SITE PLAN. We recognize the Milling and Resurfacing needed at open cuts per Sheet C‐502, but please clarify that the Parking Lot on Sheet C‐106 only gets new striping (no Milling and resurfacing)?
Milling and resurfacing are NOT included in the scope.
9 8/28/2018 33 11
The specs for the Fire Hydrants call for “Wet Barrel”.
According to one of our suppliers, the only place they know on the east coast of the USA that has Wet Barrel Hydrants is at Disney World.
It is acceptable to provide dry barrel fire hydrants.
All other hydrants are “Dry Barrel”, including all the existing Hydrants at MacDill.
Wet Barrel Hydrants are commonly used out west where frost is not an issue.
Please confirm that Hydrant status since a Wet Barrel Hydrant is much more expensive than a Dry Barrel.
10 8/29/2018 01 00
Reference is made to Section 01 00 00 General Requirements, Paragraph 36, Key Personnel Descriptions states “An individual Key Team Member may not hold more than one key role. The following are minimum qualifications for the key personnel” The Key Personnel include Project Manager, Site Superintendent, Quality Control Manager, and Safety Manager. Reference is also made to Section 01 45 00.00 10 Quality Control, 3.4 Quality Control Organization, 3.4.1 Personnel Requirements states “The Safety and Health Manager will also serve as a member of the CQC Stall Personnel”. It also states “The Contractor’s CQC staff must maintain a presence at the site at all times during progress of the work”. It is our interpretation the project staff shall include full time Superintendent, QC Manager, and Safety Manager and they shall be On‐Site at all time during construction. The staff also shall include a Project Manager but he does not have to be On‐Site at all times during construction. Please confirm this is correct?
Required on‐site staff includes Superintendent and SSOH. QC Manager and Project Manager are not required to be on‐site at all times.
11 8/29/2018 02 82
Both projects (Buildings 1885 and 1886) call for a preconstruction building survey for asbestos‐containing materials. This is confirmed in Section 01 11 00 Summary of Work and 02 82 14.00 10 Asbestos Hazard Control Activities. In Section 02 82
14.00 10 Asbestos Hazard Control Activities, Part 1 General it states “Should the Contractor’s survey indicate presence of ACM, the abatement and remediation work will be performed as additional project scope under the provisions of the specification.” It is our interpretation is that the General Contractor shall include the cost of an asbestos survey in our bid and if after the survey asbestos remediation is required the work will be performed as a change order to the contract.
Please confirm this is correct?
Correct
12 8/29/2018 02 85 00.00 20;
02 41 00
Both projects (Buildings 1885 and 1886) include Section 02 85 00.00 20 Mold Remediation.
The specification makes reference to a mold survey being performed (see 02 41 00 page 3, "the contractor shall provide a Microbial Assessment Visual Field Report for each work area and material within the work area") and for actual mold remediation work as well (see 02 41 00 page 3, "If contaminents are identified, the remediation shall be performed as base scope in accordance with the provisions of Section 02 85 00.00 20 MOLD REMEDIATION"). This is confusing in what we are actually to include in our bid. It is impossible to properly price mold remediation work if the
Your interpretation is correct. Mold Remediation, 02 85 00.00 20 SHALL NOT be included in bids. The contractor SHALL provide a Microbial Assessment Visual Field Report in accordance with 02 41 00. If contaminants are identified, the Government will then discuss a remediation plan/solution with the contractor including negotiations regarding the additional work effort and services associated with the approved remediation plan.
bidder does not know the extent of the mold. The extent of the mold is unknown until a survey is performed. It is our interpretation that for the bid we are only to include the cost of a mold survey and that any actual mold remediation work will be performed by a change order to the contract? Please confirm this is correct?
13 8/29/2018 G‐001 Just want to confirm the only area that may be occupied on‐ site during construction is the area designated on sheet G‐ 001 Construction Access?
Yes, confirmed. Including haul route/construction access to the building site.
14 8/29/2018 A‐514 Reference is made to sheet A‐ 514 Details, Detail 11/A‐514 Monument Sign Elevation Detail states “Monument sign to have Brazil Nut colored stucco finish to match base design standards.” This is the only exterior color I found that is indicated. It has been our experience on other construction projects located at MacDill AFB that all of the exterior colors will match the base design standards. Please confirm this is correct?
Correct.
15 8/30/2018 Div 8 A‐101 Bldg 1886‐‐Note 8.09 indicates “NEW 3’4”h x 7’4”w PAINTED
METAL FRAME OPENING ON
EXISTING WALL PARTITION”
between 014 REPAIR and 018 ALLIED WORKSHOP (no mark#).
Is this to be a Hollow Metal Borrowed light? Cased Opening? If so, is it to be knock down or welded?
Cased opening, welded frame per specification 08 11 13
16 8/30/2018 Div 8 A‐602 Bldg 1886‐‐ This Door Schedule appears to be more accurate than Door/Hardware Index at the end of Spec section 08 71
00. Which should be used for estimating purposes?
Use Door Schedule.
17 8/30/2018 Div 10 A‐401 Bldg 1886‐‐There are no Shower Curtain Rods on the plans (T‐16, T‐17) but 4 curtains. Confirm the contractor is to supply.
Confirmed
18 8/30/2018 Div 8 A‐603 Bldg 1885‐‐This Door Schedule appears to be more accurate than Door/Hardware Index at the end of Spec section 08 71
00. Which should be used for estimating purposes?
Use Door Schedule
19 8/30/2018 Div 8 A‐103 Bldg 1885‐‐Doors 006, 032A, and 034 are drawn as new doors. Door 006 is noted as Existing in Door Schedule (A‐ 601); 032A and 034 have no info in Door Schedule (other than size and 45 min label). Are these new doors? If so, to what hardware set do they belong?
See separate tab for response
20 8/30/2018 Div 8 A‐103 Bldg 1885‐‐Note 8.09 indicates “NEW 3’4”h x 7’4”w PAINTED
METAL FRAME OPENING ON
EXISTING WALL PARTITION”
between OFFICE 015 and
MATERIAL/CONTROL 018
(mark#015B). Is this to be a Hollow Metal Borrowed light?
Cased Opening? If so, is it to be knock down or welded?
Cased opening, welded frame per specification 08 11 13
21 8/30/2018 Div 10 A‐402 Bldg 1885‐‐Sheet A‐402 ‐‐‐ There are a number of Toilet Accessories that appear to be missing: There are no Shower Curtain Rods on the plans (T‐
16) but 4 curtains; there are no hand dryers in the men’s room (3 would be indicated); only 2 Toilet Tissue Dispenser (T‐1) but 7 toilets; only 2 Sanitary Napkin Disposal (T‐9) but 3 women’s toilets; Men’s ADA stall appears to be missing T‐4, T‐5, T‐7, and T‐8. Please confirm the contractor is to supply.
Confirmed to provide shower curtain rods, Confirmed to provide total 6 hand dryers 2 hand dryers for men’s roof by sinks(shown in drawings, but not tagged), 1 hand dryer in men’s ADA stall, place on center of North East wall (Drawing 6/A403), (not shown in drawings) 2 hand dryers for women’s by sinks,(shown and tagged in drawings) 1 hand dryer in women’s ADA Restroom(shown and tagged in drawings) Confirmed total of 7 Toilet Tissue Dispensers.
Confirmed total of 3 Sanitary Napkin Dispensers(two shown on drawing and tagged, one shown on drawing, but not tagged) Confirmed to supply T‐4, T‐ 5, T‐7 and T‐8 in men’s ADA stall.
22 9/18/2018 Div 10 A‐302, S‐406
B1885: Please confirm the specification section 10 26 41 for blast resistant panels is only for the exterior soffit sheathing identified by note 7.14 on A‐ 302, and confirm that same sheathing’s basis of design is Sure‐Board as noted on details on S‐406.
Confirmed. SURE‐Board Exterior Blast Resistant Panels Series 200B shall be the basis of design, follow manufacturer’s installation instructions. Section 10 26 41 is not applicable for Blast resistant panels.
23 9/18/2018 A‐302 B1885: Please clarify the extent of the blast resistant panels: is it required only at EIFS soffits on metal stud framing as shown on structural drawings? Or is it also required vertically behind the cmu wall as shown on detail 4/A‐302?
It is not required behind the CMU. Only at exterior soffit locations with metal framing and Fascia locations with metal framing.SURE‐Board Exterior Blast Resistant Panels Series 200B shall be the basis of design, follow manufacturer’s installation instructions. Section 10 26 41 is not applicable for Blast resistant panels.
24 9/18/2018 Div 10 B1885: Please specify whether interior signs are metal or plastic, section 10 14 00.20 does not state which material to use.
Plastic.
25 9/18/2018 Civil C‐106 Please confirm the detectable warning strips, note 2.24 on C‐ 106, are new and part of this contract.
Yes, detectable warning strips are new and part of this contract.
26 9/18/2018 Civil are the sidewalk ramps at the detectable warning strips existing? or are they new and part of this contract?
The sidewalk ramps are new and part of this contract.
27 9/18/2018 Please confirm that in specifications where LEED submittals are required if there is a “basis of design” product listed it will comply with the LEED requirements.
Overall project LEED objectives and related construction activity documentation are clarified within 01 33 29 and 01 81 13, with the project subject to an ANG design goal of "Meritable". Please provide materials and equipment that match/comply with the basis of design.
28 9/18/2018 Div 23 Specification section 23 08
00.00 10 – 1.3.2 says to provide as many LEED credits as possible to support LEED Silver certification of the project, but section 01 33 29‐
1.3.1 says the project will not require certification, and the LEED project checklist does not add up to Silver. Please clarify.
Overall project LEED objectives and related construction activity documentation are clarified within 01 33 29 and 01 81 13, with the project subject to an ANG design goal of "Meritable".
29 9/18/2018 Is it in the Contractor’s scope of work to remove the user’s furniture and equipment?
There is no specific requirement found within the plans and specifications for for removal of furniture and equipment, with the exception of some specific items called out in Demolition notes.
However, where furniture and equipment is within the buildings and not specifically called out to be removed/demolished, it is the contractor's responsibility to protect government property from damage as a result of construction activities in accordance with FAR clause 52.236‐9. If the existance of equipment or furniture unreasonably interferes with the work required under the contract then the Contractor should notify the Government to make arrangements for removal.
30 9/18/2018 S‐408 B1885: Please provide an elevation view of the platform on 1/S‐408. There are two top of steel elevations shown (0’‐4” and 12’‐4”) indicating two levels, but the section cut 4/A‐ 201 shows only one level.
Please clarify.
Top of structural steel at the equipment platform is 0'‐4". There is also steel framing above the DOAS unit at 12' 4', which supports ductwork.
31 9/18/2018 S‐408 B1885: From where on the floor plan is detail 9/S‐408 taken?
9‐S408 should be named 8/S‐408 . See detail 2/S‐408
32 9/21/2018 Wiill the contractor be allowed to work on B1885 and B1886 at the same time?
Yes
33 9/21/2018 S‐104 B1885: Is it an existing column that the two new W12x14 attach to at GL 9.9 & A.6 on S‐ 104?
Yes
34 9/21/2018 S‐404 B1885: From where on the floor plan is detail 7/S404 taken? The note says it is for existing openings, would that be all existing openings such as overhead doors, windows, interior personnel doors?
This is a standard detail which only applies to window openings in a CMU wall.
35 9/21/2018 S‐401 B1886: Details on S‐401 are for reinforcing the jambs at new windows, but there appear to be no new windows for this building. Should the structural details on S‐401 be included even if there are no new windows?
Sheet S‐401 does not relate to windows. Sheet S‐404 "Window Support Details" includes details for reinforcement of window openings subjected to blast loads. Refer to Architectural drawings for location information.
36 9/21/2018 A‐201 B1885: per the elevations 1 &2 on A‐201 it appears that the new mezzanine has a fence around it, but there is not one shown on the floor plan.
Please clarify.
It is shown on floor plan A‐
102. For Clarification:
Height of Fence on North and West Side to be 16’ high. Fence on South Side to be 8’ High with 6’ wide double gate to align with stairs.
37 9/25/2018 10 26
B1885: Spec 10 26 41 "Blast Resistant Panels". The specs are labeled "Blast Resistant Panels", however, the wording through the spec refers to Bullet or Ballistic Resistant Fiberglass Panels. I am being told by different manufacturers that there is a difference in
No amendment of the specification is required.
The bullet resistive material provides the degree of blast resistance required at the soffits. The Section title is appropriate.
Blast vs Bullet Resistant.
Please clarify the requirement and amend the specification if necessary.
38 9/25/2018 10 26
B1885: Are the panels going on the block or just the stud framing?
Panels are going on stud framing only.
39 9/25/2018 06 10
B1886: Specification section 06 10 00, at paragraph 3.2, refers to Section 10 24 16 "BLAST RESISTANT PANELS". The specifications do not include section 10 24 16 or any other section entitled "BLAST RESISTANT PANELS". Please clarify or provide referenced specification section.
This is a typo. Correct reference is to Section 10 26
41 BULLET RESISTANT
PANELS. SURE‐Board Exterior Blast Resistant Panels Series 200B shall be the basis of design for the blast resistant panels, follow manufacturer’s installation instructions.
Section 10 26 41 is not applicable for Blast resistant panels.
40 9/25/2018 06 10
B1886: Specification section 06 10 00, at paragraph 3.3.1, refers to Section 07 21 13
"BOARD AND BLOCK
INSULATION". The specifications do not include section 07 21 13 or any other section entitled "BOARD AND BLOCK INSULATION". Please clarify or provide referenced specification section.
Reference to 07 21 13 is incorrect. Correct reference is to section 07 22 00 ROOF
AND DECK INSULATION.
41 9/26/2018 Paint B1886: Will the contractor be required to move the moveable sheds, currently placed against exterior walls, in order to paint exterior walls or will the Government move them?
The Government will move.
42 9/26/2018 AD105;
S‐406
B1885: The legend on sheet AD105 calls for the soffit assemblies to be removed, and on sheet A‐302 note 5.13 calls for new soffit framing, but the soffit sections on S‐406 call for the existing soffit framing to remain. Please clarify which is correct.
Provide new soffit framing due to it being a part of the Roof retro‐fit system.
43 9/28/2018 B1885: The response to RFI 22 and 23 note that Sure Board does not meet the requirements of section 10 26 41, please list the basis of design product that does meet the specification. Also, note that the specification calls for ¼ sheets, but detail 7/A‐511 shows ½” sheets.
Response to 22 and 23 are updated. Please provide blast resistant panels as defined on the Structural Drawing, S‐406. SURE‐ Board Exterior Blast Resistant Panels Series 200B shall be the basis of design, follow manufacturer’s installation instructions. Section 10 26 41 is not applicable for Blast resistant panels.
44 9/28/2018 B1885: The response to RFI 31 says that detail 9/S‐408 should be 8/S‐408 and it comes from 2/S‐408, but that does not help clarify the construction. The verticals on 9/S‐408 are not labeled. A note says bracing at 3 bays each side, but only one is shown on plan. A note calls for (4) L3x3x3/8, but only two are shown. There needs to be elevations of two sides to make the platform construction legible.
Please see attached sketch SSK‐01 for clarification.
45 9/28/2018 The response to RFI 35 says to look at S‐404, but there is no sheet S‐404 in B1886 set. The question is for B1886, is reinforcing the window jambs per S‐401 part of the contract work?
No, do not provide reinforcing for window jambs for B1886.
46 9/28/2018 B1885: The response to RFI 36 says the fence at the mezzanine is shown on A‐102, but that is not correct. There is no fence shown, and there is no item on the key description box on the page that references a fence. Please show on the plan the extents of the fence.
Please see attached sketch ASK‐1 for clarification.
(End of Summary of Changes)