W911YN18B0002_QA_8-31-2018.xlsx

XLSX spreadsheet 19 KB Posted

Attached to
Construction Projects NVZR062031 and NVZR132003 MacDill AFB Federal contract opportunity
Solicitation number
W911YN18B0002
Issued by
Department of the Army National Guard National Capital Region Integrated Air Defense System

About this file

Solicitation Questions and Answers provided as of August 31, 2018

View the file

Other files for this federal contract opportunity

Other files attached to Construction Projects NVZR062031 and NVZR132003 MacDill AFB, newest first.
File Type Posted
OF1419_W91YN18B0002_signed.pdf PDF
Bid_Opening_Attendance_Sheet_23Oct18.pdf PDF
W911YN18B00020008.pdf PDF
ASK-01.pdf PDF
SSK-01.pdf PDF
W911YN18B00020007.pdf PDF
W911YN18B0002_QA_10-5-2018.xlsx XLSX spreadsheet
W911YN18B00020006.pdf PDF
W911YN18B00020005.pdf PDF
W911YN18B0002_QA_9-28-2018.xlsx XLSX spreadsheet
W911YN18B00020004.pdf PDF
W911YN18B00020003.pdf PDF
W911YN18B0002_QA_9-4-2018.xlsx XLSX spreadsheet
Site_visit_23Aug18_attendance.pdf PDF
W911YN18B0002_QA_8-20-18.xlsx XLSX spreadsheet
W911YN18B00020002.pdf PDF
Site_visit_1Aug18_attendance.pdf PDF
W911YN18B00020001.pdf PDF
Pre-Bid_Site_Visit_Minutes_W911YN18B0002.pdf PDF
W911YN18B0002.pdf PDF
Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Question-Comment and Response W911YN18B0002 - Bidding Questions/Response

Comment NumberDateDisciplineSpec/ ReportSheetQuestion/CommentResponseResponse ByOn Date
17/30/18Roof framing05 16 50Retrofit Framings Section 05 16 50 – 1.03 – A – 2. “Approval shall have been granted to any manufacturing facility producing the retrofit roof framing system components by the MBMA and IAS (International Accreditation Services), for quality assurance in manufacturing operations. A letter from the manufacturer certifying compliance will accompany the product approval submittals.” We ask to waive this approval in lieu of our Factory Mutual accreditation, which is similar in requirements. Or as an alternate accreditation. We recently did a retrofit project for at Avon Park Air Force Range, FL with similar requirements.
Atkins will not recommend waiving these industry accepted standards/accreditation. These associations set a minimum standard in an objective manner which is generally accepted in the Metal building manufacturing industry.Atkins8/16/18
28/9/18T-102; E-001BUILDING 1885, Re: Drawings T-102 and Legend on E-001 and Spec Div 27. Is there any equipment to be provided or is the work strictly the wiring, conduits and boxes? If so, please clarify/specify the equipment to be provided.Contractor shall comply with the requirements indicated on the drawings and in specification section 271000 Building TelecommunicationCabling System.Work includes, cabling, conduits, supports, back boxes, data outlets and testing. No other telecommunication equipment is included.Atkins8/16/18
38/24/18Fire AlarmAre we required to meet the requirements of the UFC regarding mass notification systems? The plans and specification do not make any reference to mass notification.The project inculudes a new Fire Alarm System as indicated on the drawings and specifications section 283163.00. There is no Mass Notification System.Atkins8/31/18
48/24/18Fire AlarmAre we to include the required dual-lens strobes? (Clear for fire and amber for MNS).Please see response above.Atkins8/31/18
58/24/18Fire AlarmAre we to include the required local operator’s console or LOC?Please see response above.Atkins8/31/18
68/24/18Fire AlarmAre we to include the required Monaco radio transmitter capable of mass notification?Please see response above.Atkins8/31/18
78/28/18CivilC-103The drawings show a transition from 8” pvc to 8” HDPE, then back. That typically implies a directional drill for that area of pipe. This work may require a site contractor to obtain a separate sub to mobilize. It is a relatively short run and could be very expensive. Please confirm if that area must be directional drilled or if it can be open-cut like the remainder of the water line?That section is to be directional drill. See callout 33.07. This area is shown to be directionally drilled to limit the impacts of Southshore Avenue. If that area is to be open cut, the roadway will have to be closed until the roadway is stabilized for traffic.Atkins8/31/18
88/28/18CivilC-502; C-106Limits of work for Milling and Resurfacing of Asphalt -- Reference Drawing Sheet C-502, Typical Paving Detail and Drawing Sheet C-106, SITE PLAN. We recognize the Milling and Resurfacing needed at open cuts per Sheet C-502, but please clarify that the Parking Lot on Sheet C-106 only gets new striping (no Milling and resurfacing)?Milling and resurfacing are NOT included in the scope.Atkins8/31/18
98/28/1833 11 00The specs for the Fire Hydrants call for “Wet Barrel”. According to one of our suppliers, the only place they know on the east coast of the USA that has Wet Barrel Hydrants is at Disney World. All other hydrants are “Dry Barrel”, including all the existing Hydrants at MacDill. Wet Barrel Hydrants are commonly used out west where frost is not an issue. Please confirm that Hydrant status since a Wet Barrel Hydrant is much more expensive than a Dry Barrel.It is acceptable to provide dry barrel fire hydrants.Atkins8/31/18
108/29/1801 00 00Reference is made to Section 01 00 00 General Requirements, Paragraph 36, Key Personnel Descriptions states “An individual Key Team Member may not hold more than one key role. The following are minimum qualifications for the key personnel” The Key Personnel include Project Manager, Site Superintendent, Quality Control Manager, and Safety Manager. Reference is also made to Section 01 45 00.00 10 Quality Control, 3.4 Quality Control Organization, 3.4.1 Personnel Requirements states “The Safety and Health Manager will also serve as a member of the CQC Stall Personnel”. It also states “The Contractor’s CQC staff must maintain a presence at the site at all times during progress of the work”. It is our interpretation the project staff shall include full time Superintendent, QC Manager, and Safety Manager and they shall be On-Site at all time during construction. The staff also shall include a Project Manager but he does not have to be On-Site at all times during construction. Please confirm this is correct?Required on-site staff includes Superintendent and SSOH. QC Manager and Project Manager are not required to be on-site at all times.FLNG8/29/18
118/29/1802 82 14Both projects (Buildings 1885 and 1886) call for a preconstruction building survey for asbestos-containing materials. This is confirmed in Section 01 11 00 Summary of Work and 02 82 14.00 10 Asbestos Hazard Control Activities. In Section 02 82 14.00 10 Asbestos Hazard Control Activities, Part 1 General it states “Should the Contractor’s survey indicate presence of ACM, the abatement and remediation work will be performed as additional project scope under the provisions of the specification.” It is our interpretation is that the General Contractor shall include the cost of an asbestos survey in our bid and if after the survey asbestos remediation is required the work will be performed as a change order to the contract. Please confirm this is correct?CorrectFLNG8/29/18
128/29/1802 85 00.00 20; 02 41 00Both projects (Buildings 1885 and 1886) include Section 02 85 00.00 20 Mold Remediation. The specification makes reference to a mold survey being performed (see 02 41 00 page 3, "the contractor shall provide a Microbial Assessment Visual Field Report for each work area and material within the work area") and for actual mold remediation work as well (see 02 41 00 page 3, "If contaminents are identified, the remediation shall be performed as base scope in accordance with the provisions of Section 02 85 00.00 20 MOLD REMEDIATION"). This is confusing in what we are actually to include in our bid. It is impossible to properly price mold remediation work if the bidder does not know the extent of the mold. The extent of the mold is unknown until a survey is performed. It is our interpretation that for the bid we are only to include the cost of a mold survey and that any actual mold remediation work will be performed by a change order to the contract? Please confirm this is correct?Your interpretation is correct. Mold Remediation, 02 85 00.00 20 SHALL NOT be included in bids. The contractor SHALL provide a Microbial Assessment Visual Field Report in accordance with 02 41 00. If contaminants are identified, the Government will then discuss a remediation plan/solution with the contractor including negotiations regarding the additional work effort and services associated with the approved remediation plan.Atkins8/31/18
138/29/18G-001Just want to confirm the only area that may be occupied on-site during construction is the area designated on sheet G-001 Construction Access?Yes, confirmed. Including haul route/construction access to the building site.Atkins8/31/18
148/29/18A-514Reference is made to sheet A-514 Details, Detail 11/A-514 Monument Sign Elevation Detail states “Monument sign to have Brazil Nut colored stucco finish to match base design standards.” This is the only exterior color I found that is indicated. It has been our experience on other construction projects located at MacDill AFB that all of the exterior colors will match the base design standards. Please confirm this is correct?Correct.Atkins8/31/18
15
16
17
18
19
20
21
22

Williams, Brian J MSG MIL USA: Williams, Brian J MSG MIL USA:

Need A/E input for "LEED AP Wast Manager, Commissioning Authority" requirements.