122-001ES

Number of Poles

Location: 33.19318, -106.58231

Ownership: WSMR

Nearest Site: RAMS (located inside fenced facility)

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 1

Jumper Insulation: 9

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 3

Bushing Covers: 0

Pothead Covers: 3

Switch Discs: 0

Comments: RAM Site. LOCATION

APPROXIMATE

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C7 OHNProject: Y

122-006ES

Poles

Location: 33.19410, -106.57481

Ownership: WSMR

Nearest Site: RAMS (located inside fenced facility)

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 3

Jumper Insulation: 0

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 3

Bushing Covers: 0

Pothead Covers: 3

Switch Discs: 0

Comments: LOCATION APPROXIMATE

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: C7 GPProject: Y

123-002ES

Poles

Location: 33.19370, -106.55440

Ownership: WSMR

Nearest Site: RAMS

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 0

Jumper Insulation: 9

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 3

Bushing Covers: 0

Pothead Covers: 3

Switch Discs: 0

Comments: Center phase up.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

123-003ES

Poles

Location: 33.19370, -106.55263

Ownership: WSMR

Nearest Site: RAMS

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 0

Jumper Insulation: 9

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 3

Bushing Covers: 0

Pothead Covers: 3

Switch Discs: 0

Comments: Center phase up.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

123-009ES

Poles

Location: 33.19078, -106.54574

Ownership: WSMR

Nearest Site: RAMS (located inside fenced facility)

Groundwire Molding: 1

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 3

Jumper Insulation: 12

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments: CO'S OPEN, LINE TO N DE-

ENERGIZED. IMAGES 8625, 8628, 8629

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C8 OHN

C7

Project: Y

123-016ES

Poles

Location: 33.19029, -106.54706

Ownership:

Nearest Site:

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 0

Jumper Insulation: 18

Cutout Covers: 0

Loadbreak Cutout Covers: 6

Arrester Caps: 6

Bushing Covers: 3

Pothead Covers: 0

Switch Discs: 0

Comments: INSTALL GWM AS NEEDED

TO ADDRESS COVERAGE

DEFICIENCIES, DOUBLE CHECK

ADEQUACY OF POTHEAD INSULATION

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C7 OHNProject: Y

RAMS (located inside fenced facility)

WSMR

135-028ES

Poles

Location: 33.17728, -106.55903

Ownership:

Nearest Site:

Groundwire Molding: 1

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 0

Jumper Insulation: 6

Cutout Covers: 2

Loadbreak Cutout Covers: 0

Arrester Caps: 2

Bushing Covers: 2

Pothead Covers: 0

Switch Discs: 0

Comments: BOTH BUSHINGS ON XFMR

ENERGIZED

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C1-1 OHNProject: Y

RAMS (located inside fenced facility)

147-007ES

Poles

Location: 33.10409, -106.52406

Ownership: WSMR

Nearest Site: Laura

Groundwire Molding: 1

Guy Links: 0

Conductor Covers: 1

Deadend Covers: 1

Jumper Insulation: 6

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments: CC = 2-pin; guys OK.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C9 OHN

C7 OHN

Project: N

147-009ES

Poles

Location: 33.09432, -106.53002

Ownership: WSMR

Nearest Site: Laura

Groundwire Molding: 1

Guy Links: 0

Conductor Covers: 1

Deadend Covers: 1

Jumper Insulation: 6

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments: CC = 2-pin. Insulating link already installed in upper guy.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C9 OHN

219-004ES

Poles

Location: 32.69113, -106.46233

Ownership: WSMR

Nearest Site: SW 30

Groundwire Molding: 2

Guy Links: 0

Conductor Covers: 2

Deadend Covers: 0

Jumper Insulation: 12

Cutout Covers: 0

Loadbreak Cutout Covers: 0

Arrester Caps: 3

Bushing Covers: 6

Pothead Covers: 0

Switch Discs: 6

Comments: Vertical mount switch. Install 6 switch discs. Install horiz arrester caps.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: C9-1/C9-1 OHNProject: N

219-005ES

Poles

Location: 32.69132, -106.46233

Ownership: WSMR

Nearest Site: SW 30

Groundwire Molding: 1

Guy Links: 0

Conductor Covers: 1

Deadend Covers: 1

Jumper Insulation: 6

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments: Top energized; C7 disconnected. CC = 2-pin. Guys OK.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C9-1 OHN

219-008ES

Poles

Location: 32.74837, -106.46358

Ownership: WSMR

Nearest Site: J-104

Groundwire Molding: 2

Guy Links: 0

Conductor Covers: 1

Deadend Covers: 1

Jumper Insulation: 6

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments: C7 disconnected. CC on C9 OHN = 2-pin. Insulating link already installed in upper guy.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C9 OHN

238-016bEA

Poles

Location: 32.60311, -106.41285

Ownership:

Nearest Site:

Groundwire Molding: 29

Guy Links: 0

Conductor Covers: 29

Deadend Covers: 0

Jumper Insulation: 0

Cutout Covers: 0

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments:

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C9-1 OHNProject: Y

238-024ES

Poles

Location: 32.60307, -106.38709

Ownership: WSMR

Nearest Site: Kay

Groundwire Molding: 1

Guy Links: 1

Conductor Covers: 1

Deadend Covers: 1

Jumper Insulation: 6

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments: Install perch discourager.

Install insulating link in upper guy wire.

CC = 2-pin.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C9 OHN

247-001ES

Poles

Location: 32.51484, -106.42605

Ownership: WSMR

Nearest Site: L 531

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 1

Jumper Insulation: 0

Cutout Covers: 0

Loadbreak Cutout Covers: 1

Arrester Caps: 1

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments:

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: A5 OHNProject: Y

247-004ES

Poles

Location: 32.51583, -106.42849

Ownership: WSMR

Nearest Site: L 531

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 1

Deadend Covers: 0

Jumper Insulation: 0

Cutout Covers: 0

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments: Center of CC missing and broken off. REPLACE.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: AP-1 GPProject: Y

247-026ES

Poles

Location: 32.51682, -106.42545

Ownership: WSMR

Nearest Site: L 531

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 1

Jumper Insulation: 0

Cutout Covers: 0

Loadbreak Cutout Covers: 1

Arrester Caps: 1

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments:

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: A5 GPProject: Y

247-027ES

Poles

Location: 32.51683, -106.42748

Ownership: WSMR

Nearest Site: L 531

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 0

Jumper Insulation: 0

Cutout Covers: 0

Loadbreak Cutout Covers: 3

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 3

Switch Discs: 0

Comments: 2 PHASES DE, 1 TAN. 10'

ARM. ENSURE CC COVERAGE 36"

DOWNLINE FROM CROSSARM

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: ~C9 GPProject: Y

247-029ES

Poles

Location: 32.51683, -106.42846

Ownership: WSMR

Nearest Site: L 531

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 3

Deadend Covers: 1

Jumper Insulation: 0

Cutout Covers: 0

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments: REPLACE EXISTING CC W

LONGER LIVED PRODUCT

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Retrofitting Recommendations*

Configuration: C9 GP

A5

Project: Y

255-061ES

Poles

Location: 32.48115, -106.43510

Ownership: WSMR

Nearest Site: Conn

Groundwire Molding: 1

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 2

Jumper Insulation: 3

Cutout Covers: 0

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments:

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: C8 OHNProject: Y

262-019EA

Poles

Location: 32.38750, -106.45250

Ownership: WSMR

Nearest Site: ETS

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 21

Deadend Covers: 0

Jumper Insulation: 0

Cutout Covers: 0

Loadbreak Cutout Covers: 0

Arrester Caps: 0

Bushing Covers: 0

Pothead Covers: 0

Switch Discs: 0

Comments: Each pole has 1 existing CC.

CC wings falling off.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: 3 PH OHNProject: N

262-020ES

Poles

Location: 32.38459, -106.45192

Ownership: WSMR

Nearest Site: ETS

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 1

Jumper Insulation: 9

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 3

Bushing Covers: 0

Pothead Covers: 3

Switch Discs: 0

Comments:

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: C7 OHNProject: N

262-038ES

Poles

Location: 32.37392, -106.49395

Ownership: WSMR

Nearest Site: 100K

Groundwire Molding: 1

Guy Links: 0

Conductor Covers: 1

Deadend Covers: 0

Jumper Insulation: 0

Cutout Covers: 1

Loadbreak Cutout Covers: 0

Arrester Caps: 1

Bushing Covers: 1

Pothead Covers: 0

Switch Discs: 0

Comments: Golf course. GHOW use likely.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: C9-1 OHNProject: N

262-039ES

Poles

Location: 32.37387, -106.49395

Ownership: WSMR

Nearest Site: 100K

Groundwire Molding: 0

Guy Links: 0

Conductor Covers: 0

Deadend Covers: 1

Jumper Insulation: 7

Cutout Covers: 3

Loadbreak Cutout Covers: 0

Arrester Caps: 3

Bushing Covers: 1

Pothead Covers: 0

Switch Discs: 0

Comments: Gold course; 2 BCs installed too low. Incomplete IJ.

*Recommendations should be modified as necessary based on field conditions to meet avian-friendly standards.

Retrofits will be completed/approved only when they meet this standard

Configuration: C7 OHNProject: N