Updated_Drawings_Building_35.pdf
PDF 4 MB Posted
- Attached to
- Painting and Bathroom Renovations at B35
- Solicitation number
- W911PT-19-B-0001
About this file
Updated Drawings
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W911PT-19-B-0001-0003.pdf | ||
| W911PT-19-B-0001-0002.pdf | ||
| W911PT-19-B-0001-0001.pdf | ||
| Photos_(Representative_of_conditions).pdf | ||
| Bathrooms_(New)_Photos.pdf | ||
| Updated_Drawings_Building_35_8_16_2019.pdf | ||
| Drawings_Bldg_35_Paint_Package.pdf | ||
| SOW___7PW129_Complete_Rev_1_August.pdf | ||
| W911PT-19-B-0001.docx | DOCX document | |
| NY20190001_DATED_5.10.2019.pdf | ||
| Specifications_Combined_7PW129.docx | DOCX document | |
| SITEVISIT.doc | DOC document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WAT E RV L 1 E T ARSENAL
1 Buffington St.
WATERVLIET, NEW YORK 12189
Work Order #: W07PWI 29
€t'= CANADA
____ _ ME
=.. =_=_=_== NH
NEW YORK
_ _ __ _ MA ____
CT
PROJECT SITE
PENNSYLVANIA
NJ ::
'~ C~2 Ia o
1-4 W Ul A Z
O
Cn E-i
UM
H w w
H 0 Fri Z y
E-i 14 a
~~yy F+L
DRAWING INDEX
SHEET N0. DESCRIPTION
T1 TITLE SHEET
T2 GENERAL NOTES
BASEMENT ROOMS 8000 & 8001 ROOMS „D and ,,, X1 DEMO PLAN X1 DEMO PLAN
Al FLOOR PLAN Al FLOOR PLAN
A2 ELEVATIONS A2 ELEVATIONS :ABBREVIATIONS:
A3 ELEVATIONS A3 ELEVATIONS
A4 ELEVATIONS A4 ROOM AND DOOR SCHEDULE
f PLUS OR MINUS EXT EXTERIOR PLUMB PLUMBING ak AND FD FLOOR DRAIN PLYWD PLYWOOD o AT FDN FOUNDATION PNT PAINT, PAINTED
ADJ ADJACENT FE FIRE EXTINGUISHER PREFAB PREFABRICATED
AFF ABOVE FINISH FLOOR FF FINISH FLOOR PT PRESSURE TREATED
ALUM ALUMINUM FFE FINISH FLOOR ELEVATION RDNF REINFORCED
ASTM AMERICAN SOCIETY OF TESTING FIN FINISH RO ROUGH OPENING
AND MATERIALS FL FLR FLOOR S SOUTH/ STANDARD
BLDG BUILDING FT FOOT, FEET SAT SUSPENDED ACOUSTICAL TILE
BOT BOTTOM GA GAUGE SIM SIMILAR
CL CENTERLINE GALV GALVANIZED SF SQUARE FEET
CLG CEILING GIP BD GYPSUM BOARD SS STAINLESS STEEL
CLR CLEAR H. HGT HEIGHT STD STANDARD
CMU CONCRETE MASONRY UNIT HM HOLLOW METAL STL STEEL
COL COLUMN HORIZ HORIZONTAL STRUCT STRUCTURAL
CONC CONCRETE IN INCHES, INCH SYS SYSTEM
CONN CONNECTION INSUL INSULATION, INSULATED TYP TYPICAL
CONT CONTINUOUS INT INTERIOR LION UNLESS OTHERWISE NOTED
COORD COORDINATE MAX MAXIMUM VERT VERTICAL
DIA DIAMETER MECH MECHANICAL VIF VERIFY IN FIELD
DN DOWN MFR MANUFACTURER W WEST, WIDE
DWG DRAWING MIN MINIMUM W/ WITH
E EAST MO MASONRY OPENING YA WOOD
EA EACH MTL METAL
EJ EXPANSION JOINT N NORTH
ELEC ELECTRIC NIC NOT IN CONTRACT
ELEV ELEVATION N0.1 NUMBER
EO EQUAL OC ON CENTER
EXIST EXISTING PLAM PLASTIC LAMINATE
DEMO PLAN
A5 ROOM AND DOOR SCHEDULE ELI REFLECTED CEILING PLAN
ELI ELECTRIC PLAN P1 PLUMBING PLAN
P1 PLUMBING PLAN
VICINITY MAP NOT TO SCALE
ROOMS 000, 001 AND 002 ROOMS 116 and 117 _
/ j l
1-4 ww
X1 ASBESTOS DEMO PLAN X1 ASBESTOS DEMO PLAN
X2 DEMO PLAN X2 DEMO PLAN
Al FLOOR PLAN Al FLOOR PLAN
A2 ELEVATIONS A2 ELEVATIONS
A3 ROOM AND DOOR SCHEDULE A3 ELEVATIONS
ELI REFLECTED CEILING PLAN A4 ELEVATIONS
E2 ELECTRIC PLAN A5 ROOM AND DOOR SCHEDULE
P, PLUMBING PLAN El REFLECTED CEILING PLAN t—
E2 ELECTRIC PLAN
ROOMS 007-008 P1 PLUMBING PLAN
X1
Al FLOOR PLAN
A2 ELEVATIONS
A3 ELEVATIONS
• ARCHITECTURAL SYMBOLS
PKG
ROOM 107
ROOMS 108,109,109A AND 109
ROOMS 110 AND 111
ROOMS 007 AND 008
ROOMS 116 AND 117
3 5 A ROOMS 000 AND 001
I
R U A D
ROOMS BODO AND 8001
p 0, RKER
X SHEET M ~►
o U w w
A4 ROOM AND DOOR SCHEDULE
ELI REFLECTED CEILING PLAN
WTM M SECTION
WTAILM
ELEVATION
x ~ M
WINDOW NUMBER
X ~ ~ DETAIL
x MrT Nm z REVISION NUMBER
XXX — MEN WE
XXX _ WONa~ ROOM NUMBER n DOOR NUMBER
ELECTRIC PLAN
E2 ELECTRIC PLAN
Pi PLUMBING PLAN
ROOMS 107,107A AND 107B
X1 DEMO PLAN
Al FLOOR PLAN
A2 ELEVATIONS L Niue
A3 ELEVATIONS
ROOM AND DOOR SCHEDULE
xX- mr. a".
A4 INTERIOR ELEVATION
El REFLECTED CEILING PLAN
P1 PLUMBING PLAN
COVER
SHEET ROOMS 108,109,109A AND 1098
X1 DEMO PLAN r~u NTS .mrm B.M.B.
Al FLOOR PLAN m 04/01/19
A2 ELEVATIONS
A3 ROOM AND DOOR SCHEDULE ,
ELI
P1 ROOM AND DOOR SCHEDULE NMI ft
W07PW129
sea= I•
T1
LOCATION PLAN NOT TO SCALE
GENERAL NOTES GYPSUM BOARD AND ASSEMBLIES
1. CONSTRUCTION IS DIMENSIONED TO FACE OF STUD WALL UNLESS NOTED 12. THE CONTRACTOR WILL PROVIDE COMPLETED ASBESTOS DISPOSAL DOCUMENTATION 1. ALL FIRE-RATED ASSEMBLIES SHALL MEET THE WRITTEN REQUIREMENTS
ALL EXTERIOR DIMENSIONS: TO IMP-E PROVIDED BY THE LISTING ORGANIZATION.
ARE TO OUTSIDE OF FOUNDATION WALL (U.N.O.)
2. PROTECT PENETRATIONS OF FIRE RATED ASSEMBLIES WITH A JOINT
13. CONTRACTOR WILL INSTALL NEW WINDOWS PER ARSENAL SPECIFICATIONS
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS. THE CONTRACTOR SHALL AND CONTACT COR FOR INSPECTION AFTER INSTALLATION. ASSEMBLY APPROVED BY A RECOGNIZED LISTING ORGANIZATION AND NOT SCALE FROM THE DRAWINGS for FIELD WORK. DIMENSIONS and DETAILS APPROPRIATE FOR THE ASSEMBLY PENETRATED. SUBMIT JOINT SYSTEM TO THE U) ARE BASED ON THE BEST AVAILABLE INFORMATION. THE CONTRACTOR SHALL 14. COVER AND PROTECT SMOKE DETECTORS THAT ARE LEFT IN PLACE. ARSENAL FOR APPROVAL.
BE RESPONSIBLE FOR VERIFYING FIELD DIMENSIONS BEFORE ORDERING c MATERIALS and PREFABRICATED ITEMS.
M E C H A N I C A L NOTES
REAS
3 EXPOSED rTO WATER, SU
OISTURE
ICH AS BATHROOM SHOWER AND
STANT GYPSUM BOARD AT ALLI
TUBCEILINGS,
E-1 3. PLUS OR MINUS (f) NOTATIONS ARE USED IN DIMENSION STRINGS TO ACCOUNT BATHROOM WALLS, AT THE CLOTHES WASHER VALVE BOX, AND AT KITCHEN
WET WALLS x O` FOR VARIATIONS BETWEEN DRAWINGS and EXISTING FIELD CONDITIONS. THE 1. ALL HVAC WORK, MATERIALS, AND EQUIPMENT SHALL BE IN ACCORDANCE
WITH ALL ORDINANCES, REGULATIONS, AND CODES AS ADOPTED BY THE
E-1 CONTRACTOR SHALL VERIFY ALL t DIMENSIONS DURING LAYOUT AND INFORM
4. SEE WALL SECTIONS O
THE ARCHITECT/ ENGINEER OF ANY DISCREPANCIES OR NECESSARY MODIFICATIONS GOVERNING AUTHORITIES. THE CONTRACTOR SHALL PERFORM ALL WORK IN a
BEFORE PROCEEDING WITH CONSTRUCTION. ACCORDANCE WITH THESE REQUIREMENTS WHETHER OR NOT INFORMATION
5. ALL GYPSUM BOARD SHALL BE TAPED, JOINT COMPOUNDED, SANDED and AND/OR WORK IS SPECIFICALLY SHOWN ON THE DRAWINGS.
PAINTED, UNLESS OTHERWISE NOTED. R4 U 4. THE CONTRACTOR SHALL INSPECT THE PROJECT AND ITS EXISTING W ~Zq M H CONDITIONS PRIOR TO START OF WORK. THE CONTRACTOR SHALL MAKE THE 2. ALL HVAC WORK SHALL BE IN ACCORDANCE WITH THE BUILDING CODE OF a ARSENAL AWARE OF ANY DISCREPANCIES OR PROBLEMS THAT CONFLICT WITH NEW YORK STATE, THE MECHANICAL CODE OF NEW YORK STATE, THE FUEL GAS
~ THE INTENT OF THESE DRAWINGS AND/OR SPECIFICATIONS. CODE OF NEW YORK STATE, AND THE ENERGY CONSERVATION CONSTRUCTION a
CODE OF NEW YORK STATE. W
5. THE CONTRACTOR IS NOT RESPONSIBLE TO ASCERTAIN THAT THE CONTRACT
DOCUMENTS ARE IN ACCORDANCE WITH APPLICABLE LAWS, STATUTES, 3. CHECK ANY THERMOSTAT'S AND HEATING VALVES BEFORE AND AFTER PAINTING
ORDINANCES, CODES, AND RULES AND REGULATIONS. HOWEVER IF THE
CONTRACTOR OBSERVES THAT PORTIONS OF THE CONTRACT DOCUMENTS ARE 4. INSTALL NEW INSULATION ON ANY EXPOSED PIPING.
AT VARIANCE THEREWITH, THE CONTRACTOR SHALL PROMPTLY NOTIFY THE
S
ENAL IN
APPROPRIATE
WRITING
MODIFICCATION SS F RTHEHCONTRACTOR
ANGES
L
BE ACCOMPLISHED
BY FAILS TO PROMPTLY ELECTRICAL NOTES
NOTIFY THE ARSENAL AS DESCRIBED THE CONTRACTOR SHALL PAY SUCH
COSTS AS WOULD OF BEEN AVOIDED IF THE CONTRACTOR HAD PERFORMED 1. ALL ELECTRICAL WORK, MATERIALS AND EQUIPMENT SHALL BE IN SUCH OBLIGATIONS. ACCORDANCE WITH ALL ORDINANCES, REGULATIONS, AND CODES AS ADOPTED BY
THE GOVERNING AUTHORITIES. THE CONTRACTOR SHALL PERFORM ALL WORK E-
6. WORK, MATERIALS, EQUIPMENT, MEANS AND METHODS SHALL BE IN STRICT IN ACCORDANCE WITH THESE REQUIREMENTS WHETHER OR NOT INFORMATION
W w ACCORDANCE WITH ALL CODES, RULES, REGULATIONS, AND ORDINANCES HAVING AND/OR WORK IS SPECIFICALLY SHOWN ON THE DRAWINGS.
AUTHORITY. THIS SHALL INCLUDE THE BUILDING CODE of NEW YORK STATE, THE ENERGY CONSERVATION CONSTRUCTION CODE of NEW YORK STATE, the 2. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH THE BUILDING O AMERICAN's with DISABILITIES ACT, ANSI A117.1, OSHA AND REGULATIONS OF THE CODE OF NEW YORK STATE, THE NATIONAL ELECTRICAL CODE, AND THE NEW YORK STATE LABOR DEPARTMENT. ENERGY CONSERVATION CONSTRUCTION CODE OF NEW YORK STATE.
cy7) C
7. MATERIALS AND EQUIPMENT SHALL BE INSTALLED ACCORDING TO THE 3. THE CONTRACTOR SHALL FURNISH THE OWNER AN INDEPENDENT INSPECTION
MANUFACTURER'S WRITTEN SPECIFICATIONS AND/OR INSTRUCTIONS. WORK AGENCY'S CERTIFICATE OF APPROVAL FOR BUILDING.
SHALL BE PERFORMED ACCORDING TO THE BEST PRACTICES OF THE TRADE,
AND IN A PROFESSIONAL MANNER BY MECHANICS SKILLED IN THEIR 4. CONTRACTOR TO IDENTIFY, LABEL ALL SWITCH COVERS AND PANEL BREAKERS. ~--~
RESPECTIVE TRADE.
PLUMBING NOTES 8. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK, USING THE
CONTRACTOR'S BEST SKILL AND ATTENTION. THE CONTRACTOR SHALL BE
SOLELY RESPONSIBLE FOR AND HAVE CONTROL OVER MEANS, METHODS, 1. ALL PLUMBING WORK, MATERIALS, AND EQUIPMENT SHALL BE IN
TECHNIQUES, SEQUENCES, AND PROCEDURES AND FOR COORDINATING ALL ACCORDANCE WITH ALL ORDINANCES, REGULATIONS, AND CODES AS ADOPTED BY
PORTIONS OF THE WORK. THE GOVERNING AUTHORITIES. THE CONTRACTOR SHALL PERFORM ALL WORK
IN ACCORDANCE WITH THESE REQUIREMENTS WHETHER OR NOT INFORMATION WN
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSPECTION OF PORTIONS AND/OR WORK IS SPECIFICALLY SHOWN ON THE DRAWINGS.
OF WORK ALREADY PERFORMED TO DETERMINE THAT SUCH PORTIONS ARE IN
PROPER CONDITION TO RECEIVE SUBSEQUENT WORK. 2. ALL PLUMBING WORK SHALL BE IN ACCORDANCE WITH BUILDING CODE
OF NEW YORK STATE, THE PLUMBING CODE OF NEW YORK STATE, AND THE
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING A CLEAN ENERGY CONSERVATION CONSTRUCTION CODE OF NEW YORK STATE.
ONiIN6:
WORK SITE AT ALL TIMES. AT COMPLETION OF THE WORK THE CONTRACTOR GENERAL
SHALL REMOVE FROM THE PROJECT SITE WASTE MATERIALS, RUBBISH, AND THE
E I R PROTECTION NOTES
NTs CONTRACTOR'S TOOLS, EQUIPMENT, MACHINERY AND SURPLUS MATERIALS.
o~M B.M.B.
11. THE ARSENAL WILL NOT HAVE CONTROL OVER OR CHARGE OF, NOR BE
1. ALL FIRE PROTECTION, MATERIALS, AND EQUIPMENT SHALL BE IN
ACCORDANCE WITH ALL ORDINANCES, REGULATIONS, AND CODES AS ADOPTED BY
an: 04/01/19
RESPONSIBLE FOR, THE CONSTRUCTION MEANS, METHODS, TEQUENIQUES, THE GOVERNING AUTHORITIES. THE CONTRACTOR SHALL PERFORM ALL WORK SEQUENCES OR PROCEDURES, OR FOR THE SAFETY PRECAUTIONS AND PROGRAMS IN ACCORDANCE WITH THESE REQUIREMENTS WHETHER OR NOT INFORMATION IN CONNECTION WITH THE WORK. THE ARSENAL WILL NOT BE RESPONSIBLE FOR AND/OR WORK IS SPECIFICALLY SHOWN ON THE DRAWINGS.
FE
THE CONTRACTOR'S FAILURE TO PERFORM THE WORK IN ACCORDANCE WITH THE PPAIRLT N0.
REQUIREMENTS OF THE CONTRACT DOCUMENTS. 2. ALL FIRE PROTECTION WORK SHALL BE IN ACCORDANCE WITH BUILDING CODE W07PW129
D- No. OF NEW YORK STATE, THE FIRE CODE OF NEW YORK STATE.
3. IF REQUIRED, CONTRACTOR TO HAVE FIRE PROTECTION HEADS ALIGNED OR MOVED TO NEW CEILING GRID. T2
3'-4"
FLUSH HOLLOW
M ETAL
n i~ rmur\ u,i ~ BOTH SIDES
FINISH LEGEND
CODE MANUFACTURER PRODUCT INFORMATION
PT-1 SHERMAN WILLIAM'S WALLS: PROVIDE 1 COAT PRIMER
OR EQUAL. AND 2 COATS OF FINISH
FURNISH AND APPLY TWO FULL BODY COATS OF RUST
PT-2 INHIBITING SEMI—GLOSS ENAMEL TO ALL HOLLOW
METAL DOORS
EP-1 DUR—A—FLEX OR EQUAL 1/8" SLIP RESISTANT OR APPROVED EQUAL
ACT-1 ARMSTRONG OR EQUAL 24"X24"X3/4", ACOUSTIC, CLASS A FIRE RATING
954 CLASSIC FIN AND RESISTANT TO MOLD AND MILDEW
M co
O ~
O
E-+ a
FLUSH HOLLOW
M ETAL
Type 1A hardware set at all single interior doors.
a. 1 1/2 Pair #TA2714-26D 4.5 x 4.5 hinges by
McKinney.
b.#GL97 Series, 26D finish, by Arrow Lock or equivalent
c. #9304—BF—ALU door closer by Norton.
d. #409-32D wall stop by Rockwood.
e. #FS45526D—kick stop by Ives.
ADA compliant, to receive 6 pin core both sides.
LOUVER
I
— KICK PLATE BOTH SIDES
DOOR SCHEDULE
NO. DESC. SIZE TYP. DOOR MATERIAL DOOR FINISH RATING FRAME MATERIAL FRAME FINISH HARDWARE GLASS MANUFACTURER REMARKS
BOOA FLUSH HOLLOW METAL 3'-0" x 7'-0" 1 18 GA. INSULATED STEEL ENAMEL — 16 GA. STEEL ENAMEL 1A — MOHAWK OR EQUAL
BOOB FLUSH HOLLOW METAL 2'-6" x 7'-0" 2 18 GA. INSULATED STEEL ENAMEL — 16 GA. STEEL ENAMEL 1A — MOHAWK OR EQUAL
B001A FLUSH HOLLOW METAL 3'-0" x 7'-0" 1 18 GA. INSULATED STEEL ENAMEL — 16 GA. STEEL ENAMEL 1A — MOHAWK OR EQUAL
B001B FLUSH HOLLOW METAL 3'-0" x 7'-0" 1 18 GA. INSULATED STEEL ENAMEL — 16 GA. STEEL ENAMEL 1A — MOHAWK OR EQUAL
ROOM FINISH SCHEDULE
RM. NO. ROOM NAME FLOOR FINISH BASE N. WALL FINISH S. WALL FINISH E. WALL FINISH W. WALL FINISH FIN. CLG. FIN. CLG. HGT.
8000 MENS EP-1 EP-1 EPDXY/GYP EPDXY/GYP EPDXY/GYP EPDXY/GYP PAINTED CEILING 11'-6 1/2"t
B001 MENS EP-1 EP-1 EPDXY/GYP EPDXY/GYP EPDXY/GYP EPDXY/GYP PAINTED CEILING 11'-6 1/2"f
TILE HEIGHT PER INTERIOR ELEVATION DRAWING A2 AND A3
DB~~➢tC
ROOM AND DOOR SCHEDULE
ROOMS 8000 AND BOOt
NTS
D9lRt m: B.M.B.
D,TE: n4/nl/l-q
PN . N0.
W07PWI29
➢el1IXD N➢.
EXISTING V.T.R.
/_Z_ WC-1 f /
/I /~/ _ i
N WC-1
UR-2 /
-~~ lit
9~ -----~ N UR-2~II(j 111 L~ 1 `"
L-1`V co I / co
-~1 `" UR-2 L-1
V̀ UR-2 i i i
MENS LOCKER ROOM
GENERAL NOTES: (DOMESTIC)
1. ALL DOMESTIC COLD AND HOT WATER PIPING SHALL BE RUN IN CEILING
SPACE SCREWED OR SOLDERED.
2. ALL DOMESTIC WATER PIPING ABOVE GROUND SHALL BE TYPE 'L' COPPER
ASSEMBLED WITH LEAD FREE SOLDER & INSULATED WITH MIN. 3/4" VINYL
JACKED FIBERGLASS INSULATION.
3. PROVIDE SHUTOFFS AT ALL FIXTURES.
GENERAL NOTES: (SANITARY)
1. ALL PLUMBING SYSTEMS SHALL BE INSTALLED IN COMPLIANCE WITH
ALL APPLICABLE CODES
2. ALL SANITARY PIPING UNDERGROUND SHALL BE PVC
3. ALL SANITARY AND VENT PIPING ABOVE GROUND SHALL BE PVC
4. PROVIDE CLEAN-OUTS MAX. 50'-0" O.C.
6. CONTRACTOR TO PROVIDE ELECTRIC FLUSHOMETER FOR ALL TOILETS
AND URNALS
7. CONTRACTOR TO SAW CUT TO DRAIN AND REPLACE WITH NEW FLOOR
DRAIN AND PRIMER.
8. ALL WATER, SANITARY AND VENTING TO BE REPLACED.
..Mo.
PLUMBING FLOOR PLAN DENS AND DENS
LOCKER ROOMS 8000 and 8001 ~.a NTS ac~rx sr: B.M.B.
nin: 04 /Ot /19
MENS ROOM
13000
SEE SITE PLAN FOR SEWER LOCATION
OUTSIDE OF THE BUILDING
i
NOTE: ALL FAUCETS TO HAVE FLOW AERATORS INSTALLED FLOWING NO MORE THAN .5 GPM.
PLUMBING PLAN NOTE: BEFORE DISPOSAL OF FIXTURES, PW WOULD LIKE THE OPPORTUNITY TO REVIEW AND SAVE
P1 N.T.S. FIXTURES AND PARTS AS NEEDED.
PLUMBING FIXTURE SCHEDULE FIXTURE SCHEDULE
NO. TYPE MAKE AND MODEL # REMARKS ACCESSORIES DESIGNATION ITEM DRAIN I SUPPLIES VENT
WC-1 WATER CLOSET AMERICAN STANDARD MADERA
1.6 GPF.
1 1/2" TOP SPEED WALL OUTLET
SIPHON JET, MOUNTING HEIGHT 15"
SLOAN ROYAL #111 ESS HARDWIRED FLUSH VALVE
SENSOR. CHURCH # 295, BLACK SEAT OPEN
FRONT.
WC-1 WATER CLOSET 4" DIA. 1" DIA. 1 1/2"
WC-2 WATER CLOSET (HC) 4" DIA. 1" DIA. 1 1/2"
L-1 LAV 1 1/4" DIA. 1/2" DIA. 1 1/2"
WC-2 WATER CLOSET
(HC)
AMERICAN STANDARD MADERA
1.6 GPF.
1 1/2" TOP SPEED WALL OUTLET
SIPHON JET, MOUNTING HEIGHT 19"
INSTALL SUPPORTS ON FLUSH VALVE
SLOAN ROYAL #111 ESS HARDWIRED FLUSH VALVE
SENSOR. CHURCH # 295, BLACK SEAT OPEN
FRONT.
L-2 LAV (HC) 11/4" DIA. 1/2" DIA. 1 1/2"
SH-1 SHOWER 2" DIA. 1/2" DIA. 1 1/2"
C.O. WALL CLEAN OUT 3" DIA. -
UR-1 URNAL (HC) AMERICAN STANDARD
TRIMBROOK WATER SAVER
#6560.105
WALL HUNG
SIPHON JET, LIP HEIGHT 17"
SLOAN ROYAL #180 ESS HARDWIRED FLUSH VALVE
J.R. SMITH #637 CARRIER
F.C.O. FLOOR CLEAN OUT 3" DIA. -
F.D. FLOOR DRAIN 3" DIA. - 3"
COLD SUPPLY MAIN 1" DIA.
UR-2 URNAL AMERICAN STANDARD
TRIMBROOK WATER SAVER
WALL HUNG
SIPHON JET, LIP HEIGHT 24"
SLOAN ROYAL #180 ESS HARDWIRED FLUSH VALVE
J.R. SMITH #637 CARRIER
HOT SUPPLY MAIN FROM WATER HEATER 3/4" DIA.
#6560.105
L-1 LAVATORY AMERICAN STANDARD WALL HUNG CHICAGO FAUCET ITEM # 48YD58
OVALYN UNDERCOUNTER SINK SIPHON JET, LIP HEIGHT 24" #2411.015 PERFORATED GRID DRAIN
#4418.026 ADJ. P-TRAP
PROVIDE ADA LAV GUARD UNDER SINK PIPE
COVER
0a0t.1CNl4'11
No.
W07PW129
P1
DEMO NOTES
CONTRACTOR TO REMOVE ALL PLUMBING FIXTURE'S, ALL PIPING IN WALLS, CARRIERS, SINKS, AND
ACCESSORIES IN BOTH RESTROOM'S.
cc
2 CONTRACTOR TO REMOVE ALL PARTITION'S BOTH BATHROOM'S. Z C\2 ao
CONTRACTOR TO REMOVE ALL CEILING SHEET ROCK AND GRID SYSTEM IN BOTH BATHROOM'S. AND ROOM 002 W
O
13 NEW PULL STATION AND THERMOSTAT LOCATION 4❑ CONTRACTOR TO REMOVE LIGHTING, FIXTURES TO BE TURNED OVER TO ARSENAL
Nx~ CONTRACTOR TO REMOVE EXISTING OUTLET'S AND SWITCHES BOTH RESTROOM'S, TO BE REPLACED W P4 ~?'- W
WITH NEW GFI AND SENSOR SWITCHES a O Z
CONTRACTOR TO CAREFULLY REMOVE PAPER TOWEL'S AND SOAP DISPENSER'S IN BOTH RESTROOM'S = U 6 ] 44 W
WOMENS MENS
THE FIXTURE'S WILL BE RE-INSTALLED WHEN CONSTRUCTION IS COMPLETE. CONTRACTOR TO INSTALL. a a
000 001 7 CONTRACTOR TO REMOVE EXHAUST FAN COVERS, TO BE REPLACED WITH NEW. SEE CEILING PLAN.
OFFICE a' w 002 1
F_
❑ g CONTRACTOR TO REMOVE WALL TILE AND SHEET ROCK COMPLETE BACK TO STUDS, PREPARE EXISTING WALL
TO RECEIVE NEW TILE AND SHEET ROCK. REMOVE SHEET ROCK ROOM 002
ALL SMOKE DETECTORS, SENSORS, TO BE PROTECTED AND COVERED DURING CONSTRUCTION. C>l C:o F-I F9 I
TO BE PLACED IN TROUBLE MODE WITH FIREHOUSE. RE-PLACED AFTER NEW FINISHES ARE COMPLETE.
i~
10 CONTRACTOR TO REMOVE DOORS COMPLETE. PREPARE OPENING FOR 3'-4" X 7'-4" OPENING u p
PROVIDE NEW LINTEL PER -LINTEL SCHEDULE.
11 CONTRACTOR TO REMOVE EXHAUST DUCT IN ROOM 002. CAP AND COVER AT ROOF DECK AND CLOSE
PENETRATION. W
:14]—NOTE: BEFORE DISPOSAL OF FIXTURES, PW WOULD LIKE THE OPPORTUNITY TO REVIEW AND SAVE p Q FIXTURES AND PARTS AS NEEDED. CONTRACTOR TO BRING FIXTURES TO LOADING DOCK BUILDING 120
[12] CONTRACTOR TO REMOVE STEAM COVERS AND REPLACE WITH NEW IN ROOMS 000, 001 AND 002. p w c"D
13 CONTRACTOR TO REMOVE AND RELOCATE PULL STATION AND THERMOSTAT FOR NEW DOOR OPENING.
14 EXISTING STEAM LINE AND COVERS TO BE REMOVED. CONTRACTOR TO RE- PIPE TO NEW LOCATIONS INDICATED oa~rac:
DEMO FLOOR PLAN
ROOMS 000,001 AND 002
NTS
Darr sr: B.M.B.
wm 04 /01 /19
1 DEMO PLAN
X2 N.T.S. -ex . xo.
W07PW129
nnarixc xo.
X2
FIN TUBE
TUBE SIZE FIN SIZE FIN SPACING NO. OF TIERS BTU/HR.- PER LIN. FT.
1 1/4" 4 1/2"X 4 1/2"X
ALUMINUM
34 1 1830
ROOM 000, 001 3500/ 2 FT.
NEW STEAM PIPING SHALL BE SCHEDULE 80 BLACK STEEL WITH STANDARD CAST IRON FITTINGS. NEW STEAM PIPING
ENCLOSED IN WALLS SHALL BE SCHEDULE 80 WITH 3000 LBS SOCKET WELDED FITTINGS.
CONTRACTOR TO INSULATE PIPING WITH INSULATION AND PROVIDE LABELING.
---_-- EXISTING DECK —_—_----__
f1~il cc
LL
ao
C/D N a' LL
Q x
W~ U)
GY CD w \ Q Z
CEILING SYSTEM w O w
PER SCHEDULE 6'
E-4 W Q o
METAL STUDS TO REMAIN
~04 O Z Z
TILE HEIGHT PER A2 "
FASTEN BOTTOM TRACK TO SLAB a a
ALL WALL FINISHES INCLUDING
BASE PER SCHEDULE
GENERAL NOTES
1. CONTRACTOR TO PROVIDE, AT RATED FIRE SEPARATIONS:
FIRE CAULKING AND FIRE SAFING AT ALL PENETRATIONS,
AND ALONG TOP of PARTITIONS BETWEEN GYP. BD. & DECK.
ALL OTHER TRADES TO PROVIDE SAME FOR: PIPING, PLUMBING, ELECTRICAL,
HVAC, ETC. EACH TRADE TO RESEARCH REQUIREMENTS FOR
PENETRATIONS THROUGH WALLS.
2, ALL INTERIOR DIMENSIONS ARE TO:
-EDGE OF INTERIOR PARTITION to EDGE OF INTERIOR PARTITION.
E-~ W
3. SEE DRAWING A2 FOR INTERIOR ELEVATIONS
NOTES & DETAILS
W
4. SEE DRAWING A3 FOR DOOR AND FINISH SCHEDULE. O
5. PROVIDE REQUIRED WOOD BLOCKING IN WALLS FOR ALL TOILET
W p' ROOM ACCESSORIES, FIXTURES AND CASEWORK.
6. EXISTING DUCTWORK TO REMAIN. CONTRACTOR TO CLEAN DUCTWORK AND SPRAY
WITH ANTIMICROBIAL PAINT. FOGGED WITH SANITIZER AND ENCAPSULATE
7, CONTRACTOR TO PROVIDE NEW ROOM SIGNAGE FOR UNISEX BATHROOMS
PARTITION TYPES:
TYPICAL INTERIOR WALL
~ A
NEW FIN TUBE LOCATIONS
CONTRACTOR TO PAINT EXTERIOR WALL
COORDINATE FINAL COLORS WITH CDR
CONTRACTOR TO MOVE FURNITURE AND
AND BELONGINGS FROM ROOM 002
AND PLACE BACK WHEN ROOM IS COMPLETE
-3 5/8" STN. 20 ga. METAL STUDS ® 16" O.C. W/ 20 ga. TRACK
FROM SLAB to DECK
-TAPED 5/8" GYPSUM MOISTURE BOARD.
-TILE PER FINISH SCHEDULE AND HEIGHT PER A2
EXISTING INTERIOR WALL
-NEW TAPED 5/8" GYPSUM TYPE "X" (1 LAYER)
-EXTERIOR WALL TO BE PATCHED AND PAINTED PER SCHEDULE
EXISTING BLOCK WALL
DW"D:
NEW FLOOR PLAN
ROOMS 000,001 AND 002
NTS
Dunn Dr: B.M.B.
04 /01 /19
FLOOR PLAN
Al N.T.S.
-TILE PER FINISH SCHEDULE AND HEIGHT PER A2 '
-BLOCK IN ROOM 002 WILL BE PAINTED PER SCHEDULE. PSO [G2 ND.
W07PW129
EXISTING WALLS ROOMS 000, 001 AND 002 (NOT TAGGED) DY.—.N..
-TAPED 5/8" GYPSUM MOISTURE BOARD. Al
-TILE PER FINISH SCHEDULE AND HEIGHT PER A2
12" x 24" SKYBRIDGE
GLAZED CERAMIC
COMMERCIAL GRADE TILE
WITH REVEAL IMAGE
OR APPROVED EQUAL.
COAT HOOKS BY BOBRICK
MODEL# B-76717 OR EQUAL
SURFACE MOUNTED
TOWEL HOLDER
1> INTERIOR ELEVATION
A2
N.T.S.
PAINTED
GYP. BD.
FLOOR PLAN
A2 N.T.S.
PAINTED
GYP. BD.
MIRROR
SOAP DISPENSER
GRAB BARS
L_ 1D A2 1B
1C
UNISEX
WC-1
PAINTED
GYP. BD.
12" x 24" SKYBRIDGE
GLAZED CERAMIC
COMMERCIAL GRADE TILE
WITH REVEAL IMAGE
OR APPROVED EQUAL.
a
COAT HOOKS BY BOBRICK
MODEL# B-76717 OR EQUAL
SURFACE MOUNTED
TOWEL HOLDER
L-1 L-1
UNISEX 2A
2D A2 2
2C ~ X a-w
UP
ACCESSIBLE FIXTURES DETAIL
AL
N.T.S.
ELONGATED
RIM URINAL
WALL MOUNT DUAL
HEIGHT H.C. DRINKING
FOUNTAIN
INSTALL PER
A.D.A REQUIREMENTS
H.C. DRINKING
FOUNTAIN —\
,B
INTERIOR ELEVATION
A2 N.T.S.
PAINTED
GYP. BD.
WC-1
INTERIOR ELEVATION
A2
N.T.S.
t
WC-1
INTERIOR
ELEVATION
A~- N.T.S
MIRROR
SOAP DISPENSER
GRAB BARS
PAINTED
GYP. BD.
L-1
INTERIOR
rp
INTERIOR ELEVATION 2A INTERIOR ELEVATION 2B INTERIOR ELEVATION 26 ELEVATION
A2 A2 A2 A2 N.T.S. N.T.S. N.T.S. N.T.S.
WC-1 L-1
PROVIDE WOOD BLOCKING IN WALLS -INSTALL TOILET PAPER HOLDER
n I
N OTES: . GENERAL
FOR ALL: PER FIELD LOCATION. SEE FLOOR PLAN DRAWING
-FIXTURES -SEE ACCESSIBLE FIXTURES DETAIL Al FOR ACTUAL TOILET
Water Closets
-TOILET ACCESSORIES BELOW FOR ACTUAL A.D.A. REQUIREMENTS
-& COUNTER TOP
ROOM ORENTATION.
- General.
-PROVIDE NECESSARY SIGNAGE AND DESIGNATION OF
Water closets shall be mounted adjacent to a side wall or partition.
BATHROOMS FOR GENDER AND HANDICAPPED ACCESSIBIUTY.
The distance from the side wall or partition to the centerline of the water closet Lavatories & Sinks:
shall be 18 in. - Lavatories shall be mounted with the rim 34 in maximum above the floor and with a clearance of 29
- Clear Floor Space. in minimum from the floor to the bottom of the front edge of the apron.
Clear floor space for water closets not in stalls shall be 48 in minimum in front of - Sinks shall be mounted with the counter or rim 34 in maximum above the floor. Sinks shall be 6 the water closet and 42 in from the center line of the water closet on the side not adjacent to the wall, in deep maximum
- Height. The top of water closet seats shall be 17 in to 19 in above the floor. Seats shall not be Clearances:
sprung to return to a lifted position. - Knee & toe Clearances. Fixtures shall extend 17 in minimum from the wall. Clearance between the
Grab Bars. bottom of the front edge of the apron and the floor shall be 20 in minimum. The clear knee space shall
Grab bars shall be provided on the rear wall and on the side wall closest to the water closet. be 8 in in depth minimum at 27 in minimum above the floor or ground and 11 in in depth minimum at
Side wall grab bar shall be 42 in long minimum located 12 in maximum from the rear wall and 9 in minimum above the floor or gound. The dip of the overflow shall be ignored when checking the extending 54 in minimum from the rear wall. The rear wall grab bar shall be 24 in long minimum, clearances.
centered on the water closet. Where space permits, the bar shall be 36 in long minimum, with the - Clear Floor Space. Clear floor space, 30 in by 48 in minimum, shall be provided in front of a additional length provided on the transfer side of the water closet. lavatory or sink to allow a forward approach and shall extend 19 in maximum under the lavatory or
Flush controls. Flush controls shall be hand operated. sink.
- Dispensers. Toilet paper dispensers shall be installed between 7 in and 9 in in front of the water - Exposed Pipes & Surfaces. Water supply and drain pipes under lavatories or sinks shall be insulated closet. The outlet of the dispenser shall be located between 15 in and 48 in above the floor. There or otherwise configured to protect against contact. There shall be no sharp or abrasive surfaces under shall be a clearance of 1 in minimum below and 12 in minimum above the grab bar. Dispensers shall lavatories or sinks.
not be of a type that control delivery, or that do not allow continuous paper flow. - Faucets. Self-closing faucets, when used, shall remain open for 10 seconds minimum.
OYI~N(Gt
ELEVATIONS
ROOMS 000,001 AND 002
+s NTS a4..x sr: B.M.B.
wn: 04 t /19 eN . No.
W07PW129
oNam a N.
I, I m
O .~-1
W m P~ O
W~ZW
a
C ~Lq
~~w E-1
E a4 a
E_
Type 1A hardware set at all single interior S.
1 1/2 Pair #TA2714-26D 4.5 x 4.5 hinges by nney.
OL97 Series, 26D finish, by Arrow Lock or equivalent #9304—BF—ALU door closer by Norton.
#409-32D wall stop by Rockwood.
#FS45526D—kick stop by Ives.
ompliant, to receive 6 pin core both sides.
FINISH LEGEND
CODE MANUFACTURER PRODUCT INFORMATION
PT-1 SHERMAN WILLIAM'S WALLS: PROVIDE 1 COAT PRIMER
OR EQUAL. AND 2 COATS OF FINISH
FURNISH AND APPLY TWO FULL BODY COATS OF RUST
PT-2 INHIBITING SEMI—GLOSS ENAMEL TO ALL HOLLOW
METAL DOORS
EP-1 DUR—A—FLEX OR EQUAL 1/8" SLIP RESISTANT OR APPROVED EQUAL
ACT-1 ARMSTRONG OR EQUAL 24"X24"X3/4", ACOUSTIC, CLASS A FIRE RATING
954 CLASSIC FIN AND RESISTANT TO MOLD AND MILDEW
TILE SKYBRIDGE GLAZED 12"X24", REVEAL IMAGING OR EQUAL
CERAMIC
FLUSH HOLLOW
M ETAL
DOOR SCHEDULE
NO. DESC. SIZE TYP. I DOOR MATERIAL DOOR FINISH RATING FRAME MATERIAL I FRAME FINISH HARDWARE GLASS MANUFACTURER REMARKS
000 FLUSH HOLLOW METAL 3'-0" x 7'-0" 1 18 GA. INSULATED STEEL ENAMEL — 16 GA. STEEL ENAMEL 1A — MOHAWK OR EQUAL
001 FLUSH HOLLOW METAL 3'-0" x 7'-0" 1 18 GA. INSULATED STEEL ENAMEL — 16 GA. STEEL ENAMEL 1A — MOHAWK OR EQUAL
ROOM FINISH SCHEDULE
RM. NO. ROOM NAME FLOOR FINISH BASE N. WALL FINISH S. WALL FINISH E. WALL FINISH W. WALL FINISH FIN. CLG. FIN. CLG. HGT.
000 UNISEX ROOM EP-1 EP-1 TILE/GYP TILE/GYP TILE/GYP TILE/GYP ACT-1 8'-0"
001 UNISEX ROOM EP-1 EP-1 TILE/GYP TILE/GYP TILE/GYP TILE/GYP ACT-1 8'-0"
002 OFFICE EP-1 EP-1 GYP GYP GYP GYP ACT-1 8'-0"
TILE HEIGHT PER INTERIOR ELEVATION DRAWING A2
D"ma
ROOM AND DOOR SCHEDULE
ROOMS 000,001 AND 002
sis NTS Dins sr: B.M.B.
D+*~= 04/01/19
P➢ m N0.
M7PW129
OIIlN@ N0.
A3
O
NOTE: BEFORE DISPOSAL OF FIXTURES, PW WOULD LIKE THE OPPORTUNITY TO REVIEW AND SAVE FIXTURES AND PARTS AS NEEDED. CONTRACTOR TO BRING FIXTURES TO LOADING DOCK BUILDING 120 m
E- tm9Q m._
DEMO MOTES
1 CONTRACTOR TO REMOVE ALL PLUMBING FIXTURE'S, ALL PIPING IN WALLS, SINKS, AND
ACCESSORIES IN BOTH RESTROOM'S.
CONTRACTOR TO REMOVE ALL PARTITION'S BOTH BATHROOM'S.
3 CONTRACTOR TO REMOVE GRID SYSTEM IN ROOM 007 COMPLETE.
F4 I CONTRACTOR TO REMOVE LIGHTING IN ROOM 007, FIXTURES TO BE RE-INSTALLED AFTER NEW
GRID CEILING IS INSTALLED. LIGHTING IN ROOM 008 TO BE PROTECTED WHILE WORK IS COMPLETED.
CONTRACTOR TO REMOVE EXISTING OUTLET'S AND SWITCHES BOTH RESTROOM'S, TO BE REPLACED
WITH NEW GFI AND SENSOR SWITCHES FOR LIGHTING AND FANS
6]
CONTRACTOR TO CAREFULLY REMOVE PAPER TOWEL'S AND SOAP DISPENSER'S IN BOTH RESTROOM'S THE FIXTURE'S WILL BE RE-INSTALLED WHEN CONSTRUCTION IS COMPLETE. CONTRACTOR TO INSTALL.
7 CONTRACTOR TO REMOVE EXISTING EXHAUST FANS AND COVERS, TO BE REPLACED WITH NEW.
8 CONTRACTOR TO REMOVE LOCKERS AND RE-INSTALL AFTER ROOM IS COMPLETED.
ALL SMOKE DETECTORS, SENSORS, EXIT LIGHTING TO BE REMOVED. SMOKE AND FIRE ALARM
1-91 TO BE PLACED IN TROUBLE MODE WITH FIREHOUSE. RE-PLACED AFTER NEW FINISHES ARE COMPLETE.
1 0
CONTRACTOR TO REMOVE DOORS COMPLETE. PREPARE OPENING FOR 3'-4" X 7'-4" OPENING
PROVIDE NEW LINTEL PER LINTEL SCHEDULE.
CONTRACTOR TO SAW CUT SLAB FOR NEW PLUMBING REQUIREMENTS AT HATCHED AREA'S.
11 EXISTING SLAB 6" WITH 6/6 WELDED WIRE MESH. NEW SLAB TO BE 6" WITH 6/6 WELDED WIRE
MESH. DRILL AND EPDXY #4 BAR @ 24"O.0 AT AREA'S THAT ARE DISTURBED.
[12] CONTRACTOR TO MODIFY WALL FOR NEW PLUMBING. REPAIR WALL AS NEEDED TO RECEIVE EPDXY.
1 3 CONTRACTOR TO CAREFULLY REMOVE CONCRETE PAD.
[14] CONTRACTOR TO CAREFULLY REMOVE SLOP SINK AND PROVIDE NEW.
15 CONTRACTOR TO REMOVE FLOOR DRAIN COVERS AND CLEAN OUT COVERS TO BE REPLACED WITH NEW
1 6 CONTRACTOR TO REPAIR TILE WALL AS NEEDED.
[17] CONTRACTOR TO DISCONNECT DRINKING FOUNTAIN AND EYE WASH STATION OUTSIDE OF ROOM
008. PLUMBING TO BE RE CONNECTED AFTER NEW PLUMBING IS INSTALLED IN ROOM 008.
10'-42" 21'-102"
DN~~DiC:
DEMO FLOOR PLAN
ROOMS 007 and 008 a..r NTS DH1~t1 er: R_M_R.
1 DEMO PLAN _
X1 N.T.S.
eaaacr xo.
W07PW129
DYIIDIG ND.
X1
EXISTING DECK
w 00
~ O ,~.~ 00 E-
ME x o W
1 1 EXISTING DECK 0-1
Q Z O
10-42 21-102 ----_ ~ ~ Cn z E1 W Q
Li ° o a O w Z > w w ~ O E~
Q z W 4 W
ED
WOMENS 2A Q w 01 Ui
~ o `-~ J
007 ® o o CD CD ¢ ~L, a 1
A 2D A3 2B
MENS >~ (D cn o o
CL x -r- A B 008 o w w
1D
V/
A2 1B 2 a_
'-10"
1c ~ GENERAL DOTES w
1. CONTRACTOR TO PROVIDE, AT RATED FIRE SEPARATIONS:
F Tl FIRE CAULKING AND FIRE SAFING AT ALL PENETRATIONS, 007 AND ALONG TOP of PARTITIONS BETWEEN GYP. BD. & DECK. E-+
ALL OTHER TRADES TO PROVIDE SAME FOR: PIPING, PLUMBING, ELECTRICAL,
W w HVAC, ETC. EACH TRADE TO RESEARCH REQUIREMENTS FOR
PENETRATIONS THROUGH WALLS. W
o r̀ 2. ALL INTERIOR DIMENSIONS ARE TO: O i co -EDGE OF INTERIOR PARTITION to EDGE OF INTERIOR PARTITION.
cy'D
3. SEE DRAWING A2 AND A3 FOR INTERIOR ELEVATIONS
CONTRACTOR TO PAINT EXTERIOR WALL NOTES & DETAILS c2)
COORDINATE FINAL COLORS WITH COR ~0__
4. SEE DRAWING A4 FOR DOOR AND FINISH SCHEDULE.
CONTRACTOR TO MOVE LOCKER AND
AND BENCH. PLACE BACK WHEN ROOM IS COMPLETE 5. PROVIDE REQUIRED WOOD BLOCKING IN WALLS FOR ALL TOILET
1 FLOOR PLAN
ROOM ACCESSORIES, FIXTURES AND CASEWORK.
Al N.T.S.
6. EXISTING DUCTWORK TO REMAIN. CONTRACTOR TO CLEAN DUCTWORK AND SPRAY
FOGGED WITH SANITIZER AND ENCAPSULATE WITH ANTIMICROBIAL PAINT. _
^rte
PARTITION TYPES:
EXISTING TNTE~RIORALLS AT ROOM 007 WOMENS ROOM EXISTING INTERIOR WALLS AT ROOM 008 MENS ROOM NEw FLOOR PLAN ROOMS 007 and 008
-ORIGINAL ILE -ORIGINAL TILE A.F.F. 7-0 f ~..r NTS
-MACHINE GRIND AND COAT WALL / PREP -MACHINE GRIND AND COAT WALL / PREP
B.M.B.
o+n 04/01/19
-EPDXY CLEAR PRIMER -EPDXY CLEAR PRIMER
-EPDXY COLORED BASE -EPDXY COLORED BASE
-MULTI COLORED CHIPS -MULTI COLORED CHIPS ,
-URETHANE SEALANT -URETHANE SEALANT
PLASTER / WALLS 7'-0"f TO 16'-10 1/2" A.F.F.
xo.
W07PWt29
-PATCH AND PAINT ALL WALLS AND PIPING / EXHAUST DUCT
Al
EP0 EPDXY
WC-2 WC-1 WC-1
1B
INTERIOR ELEVATION 1C INTERIOR ELEVATION
A2 A2 N.T.S. N.T.S.
WOMENS
1A
1D A2 1B
1C r
SURFACE MOUNTED
TOWEL HOLDER
E
L-1 WC-1
INTERIOR ELEVATION
1A
A2 N.T.S.
o-
C> LLL
r X a_ W a
A
FLOOR PLAN
1 _
A2 N.T.S.
1D
INTERIOR ELEVATION
A2 N.T.S.
MIRROR
SOAP DISPENSER
L-1 L-1
ACCESSIBLE FIXTURES DETAIL
AL
NTS_
54' MIN.
72"
ELONGATED
RIM URINAL
WALL MOUNT DUAL
HEIGHT H.C. DRINKING
FOUNTAIN
INSTALL PER
A.D.A REQUIREMENTS
H.C. DRINKING
FOUNTAIN —\
DUWT
ELEVATIONS
ROOMS 007 annd 008
NTS
oswx Dr, B.M.B.
wn: 04/01/19 eDonn xo.
W07PW129
DHIipG xD.
A2
PROVIDE WOOD BLOCKING IN WALLS -INSTALL TOILET PAPER HOLDER
I I GENERAL NOTES: FOR ALL: PER FIELD LOCATION. SEE FLOOR PLAN DRAWING
-FIXTURES -SEE ACCESSIBLE FIXTURES DETAIL Al FOR ACTUAL TOILET
Water Closets
-TOILET ACCESSORIES BELOW FOR ACTUAL A.D.A. REQUIREMENTS
& COUNTER TOP
ROOM ORIENTATION.
- General.
-PROVIDE NECESSARY SIGNAGE AND DESIGNATION OF
BATHROOMS FOR (ENDER AND HANDICAPPED ACCESSIBIUTY.
Water closets shall be mounted adjacent to a side wall or partition.
The distance from the side wall or partition to the centerline of the water closet Lavatories & Sinks:
shall be 18 in. - Lavatories shall be mounted with the rim 34 in maximum above the floor and with a clearance of 29
- Clear Floor Space. in minimum from the floor to the bottom of the front edge of the apron.
Clear floor space for water closets not in stalls shall be 48 in minimum in front of - Sinks shall be mounted with the counter or rim 34 in maximum above the floor. Sinks shall be 6 the water closet and 42 in from the center line of the water closet on the side not adjacent to the wall. in deep maximum
- Height. The tap of water closet seats shall be 17 in to 19 in above the floor. Seats shall not be Clearances:
sprung to return to a lifted position. - Knee & tae Clearances. Fixtures shall extend 17 in minimum from the wall. Clearance between the
Grab Bars. bottom of the front edge of the apron and the floor shall be 20 in minimum. The clear knee space shall
Grab bars shall be provided on the rear wall and on the side wall closest to the water closet. be 8 in in depth minimum at 27 in minimum above the floor or ground and 11 in in depth minimum at
Side wall grab bar shall be 42 in long minimum located 12 in maximum from the rear wall and 9 in minimum above the floor or gound. The dip of the overflow shall be ignored when checking the extending 54 in minimum from the rear wall. The rear wall grab bar shall be 24 in long minimum, clearances.
centered on the water closet. Where space permits, the bar shall be 36 in long minimum, with the - Clear Floor Space. Clear floor space, 30 in by 48 in minimum, shall be provided in front of a additional length provided on the transfer side of the water closet. lavatory or sink to allow a forward approach and shall extend 19 in maximum under the lavatory or
Flush controls. Flush controls shall be hand operated. sink.
Dispensers. Toilet paper dispensers shall be installed between 7 in and 9 in in front of the water - Exposed Pipes & Surfaces. Water supply and drain pipes under lavatories or sinks shall be insulated closet. The outlet of the dispenser shall be located between 15 in and 48 in above the floor. There or otherwise configured to protect against contact. There shall be no sharp or abrasive surfaces under shall be a clearance of 1 in minimum below and 12 in minimum above the grab bar. Dispensers shall lavatories or sinks.
not be of a type that control delivery, or that do not allow continuous paper flow. - Faucets. Self-closing faucets, when used, shall remain open for 10 seconds minimum.
ELECTRICAL GENERAL NOTES:
1. ALL ELECTRICAL TO BE INSTALLED PER CODE.
2. PROVIDE FLUSH MOUNTED SENSOR FOR LIGHTING AND EXHAUST FANS.
co
FIRE ALARM STROBE O
C ,~-~
~E~
DOOR FRAME W
THERMOSTAT, INTERCOM OR 2ND ROW OF Q ~?'- O
/ I RECEPTACLES CENTER OVER CLUSTER
C) BELOW WHEN USING DIMMERS, LOCATE
THERMOSTAT AT OPP. SIDE OF DOOR). C_~ W
-i _ LIGHT SWITCH, DIMMERS, EGRESS BUTTON, a O Z
`0 INTERCOM BUTTON, CARD READER, ETC. > P'~+
`9 (SEE PLAN FOR QUANTITY OF EACH
pq U
~- 00''- CLUSTER) ALL UNDER COMMON FACE PLATE.
Q \ DOOR LEVER, PULL
FINISH FLOOR a W
LINE OF FINISHED FLOOR RECEPTACLE d'
TYP. LOCATION FOR LIGHT SWITCHES, DIMMERS, EGRESS BUTTONS, THERMOSTATS, ETC.
FIXTURE LEGEND
INDICATES SUSPENDED METAL CEILING GRID EMERGENCY LIGHT
W/ BATTERY BACK-UP
E- INCLUDED W/UNIT
INDICATES 2'X4' LED LIGHTING
SURFACE WALL 8' A.F.F. W
[Z3
P/N: EU-3-LED-W ~ W
http://astralitelighting.com/EU3.html 0
® CONTRACTOR TO PROVIDE NEW EXHAUST FANS W
PROVIDE MIN. 8 AIR EXCHANGES PER HOUR.
TIE INTO EXISTING DUCT WORK
~O,'
NEW EXHAUST FAN GRILLS (CONTRACTOR TO PROVIDE
FLEXIBLE INSULATED DUCT TO EXISTING DUCT WORK)
$ FAN AND LIGHT SWITCH SENSOR
STROBE, WALL MOUNT RED, ALERT, AMBER LENS W
CONTRACTOR TO REMOVE EXISTING FIXTURE AND REINSTALL. p~
CONTRACTOR TO PAY SIMPLEX TO RE PROGRAM EXISTING FIXTURE
TO SYSTEM. ,
SO
ADDRESSABLE STROBE, WALL MOUNT RED, ALERT, AMBER LENS MW
I EXIT/EMERGENCY LIGHT
W/ BATTERY BACK-UP
INCLUDED W/UNIT
SURFACE WALL 8' A.F.F. REFLECTED CEILING PLAN
P/N: EEU-3-R-W-LED ROOMS 007 and 008 http://ostralitelighting.com/EEU3.HTML NTS Ovan sr: B.M.B.
wn: 04/01/19 eaoncf NO.
W07PW129
REFLECTED CEILING PLAN 041'0(6 HO.
E1 N.T.S. E1
SYMBOL LEGEND
GFI 20A-125 V DUPLEX RECEPTACLE, (SET 18" A.F.F.)
Q: SURFACE MOUNTED
GENERAL NOTES
1. ALL SURFACE CONDUIT SHALL BE A MINIMUM OF 3/4" TRADE SIZE,
UNLESS OTHERWISE NOTED.
2. ALL CONDUCTORS SHALL BE A MINIMUM OF #12 COPPER WITH
THHN INSULATION UNLESS OTHERWISE NOTED.
3. ALL EXPOSED CONDUITS OR CONDUITS ABOVE HUNG CEILINGS
SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO BUILDING LINES.
4. ALL ELECTRIC TO BE LABELED AT DEVICE AND PANEL.
5. CONTRACTOR IS RESPONSIBLE FOR ALL FIRE PROTECTION AND / OR CONTROL WIRING
TO—FROM EQUIPMENT PROVIDED.
6. CONTRACTOR SHALL UPDATE ALL PANEL SCHEDULES AS PER REQUIRED PER 26 05 53
IDENTIFICATION OF ELECTRICAL SYSTEMS.
7. PULL, JUNCTION AND TERMINAL BOXES PROVIDED SHALL BE UL LISTED AND CONFORM TO
SPECIFICATION 26 05 33.33
CONSTRUCTf ON GENERAL NOTES
1. ALL RECEPTACLES, TELEPHONE, ETC. ARE TO BE FLUSH MOUNTED AT 18" OR 48"
A.F.F. AND BE PROVIDED WITH AN IVORY THERMOPLASTIC COVER PLATE
TO MATCH THE DEVICE UNLESS OTHERWISE SPECIFIED. ALL BACK TO BACK
DEVICES TO BE OFFSET HORIZONTALLY 6" MINIMUM.
2. THE EXACT LOCATION OF ALL SWITCHES, OUTLETS, ETC. ARE TO BE
COORDINATED WITH OWNER OR AS DETAILED OR DIMENSIONED ON
DRAWINGS WHERE APPLICABLE.
ELECTRIC PLAN
E2
N.T.S.
DBIT[XCt
ELECTRIC PLAN
ROOMS 007 and 008
NTS
DS,RI ar. B.M.B.
D+n 04/01 19 rsona ND.
W07PW129
Dvm+D No.
E2
1'-3" 2'-6" 2'-6" 4'-421, 2-7" 2'-7
.~ .~ HW
L71 \ Li1 \ Lr2\ U yu- yu -wc-1 I ~ I ~ I— L I_
----- --- ------- ---~— 1-- L--- ,--- ----, EXISTING VTR WOMEN' S
V//
I / Wd-1 A-1 Wd-2 i SL1 /
WC-2
MENS
O
NOTE: ALL FAUCETS TO HAVE FLOW AERATORS INSTALLED FLOWING NO MORE THAN .5 GPM.
FIXTURE SCHEDULE
DESIGNATION ITEM DRAIN SUPPLIES VENT
WC-1 WATER CLOSET 4" DIA. 1" DIA. 1 1/2"
WC-2 WATER CLOSET (HC) 4" DIA. 1" DIA. 1 1/2"
L-1 LAV 1 1/4" DIA. 1/2" DIA. 1 1/2"
L-2 LAV (HC) 1 1/4" DIA. 1/2" DIA. 1 1/2"
C.O. WALL CLEAN OUT 3" DIA. -
F.C.O. FLOOR CLEAN OUT 3" DIA. -
F.D. FLOOR DRAIN 3" DIA. - 3"
COLD SUPPLY MAIN 1" DIA.
HOT SUPPLY MAIN FROM WATER HEATER 3/4" DIA.
GENERAL NOTES: (DOMESTIC)
ALL DOMESTIC COLD AND HOT WATER PIPING SHALL BE RUN IN CEILING
SPACE SCREWED OR SOLDERED.
6 ALL DOMESTIC WATER PIPING ABOVE GROUND SHALL BE TYPE 'L' COPPER
ASSEMBLED WITH LEAD FREE SOLDER & INSULATED WITH MIN. 3/4" VINYL
JACKED FIBERGLASS INSULATION.
3 PROVIDE SHUTOFFS AT ALL FIXTURES.
GENERAL NOTES: (SANITARY)
1. ALL PLUMBING SYSTEMS SHALL BE INSTALLED IN COMPLIANCE WITH
ALL APPLICABLE CODES
2. ALL SANITARY PIPING UNDERGROUND SHALL BE PVC
3. ALL SANITARY AND VENT PIPING ABOVE GROUND SHALL BE PVC
4. PROVIDE CLEAN-OUTS MAX. 50'-0" O.C.
6. CONTRACTOR TO PROVIDE ELECTRIC FLUSHOMETER FOR ALL TOILETS AND URNALS
7. CONTRACTOR TO SAW CUT TO DRAIN AND REPLACE WITH NEW FLOOR DRAIN AND PRIMER.
8. ALL WATER, SANITARY AND VENTING TO BE REPLACED.
PLUMBING FIXTURE SCHEDULE
N0, TYPE MAKE AND MODEL # REMARKS ACCESSORIES
WC-1 WATER CLOSET AMERICAN STANDARD MADERA 1 1/2" TOP SPEED WALL OUTLET SLOAN ROYAL #111 ESS HARDWIRED FLUSH VALVE
1.6 GPF. SIPHON JET, MOUNTING HEIGHT 15" SENSOR. CHURCH # 295, BLACK SEAT OPEN
FRONT.
WC-2 WATER CLOSET AMERICAN STANDARD MADERA 1 1/2" TOP SPEED WALL OUTLET SLOAN ROYAL #111 ESS HARDWIRED FLUSH VALVE
(HC) 1.6 GPF. SIPHON JET, MOUNTING HEIGHT 19" SENSOR. CHURCH # 295, BLACK SEAT OPEN
INSTALL SUPPORTS ON FLUSH VALVE FRONT.
UR-1 URNAL (HC) AMERICAN STANDARD WALL HUNG SLOAN ROYAL #180 ESS HARDWIRED FLUSH VALVE
TRIMBROOK WATER SAVER SIPHON JET, LIP HEIGHT 17" J.R. SMITH #637 CARRIER
WALL HUNG
I J.R.
SLOAN ROYAL #180 ESS HARDWIRED FLUSH VALVE
SIPHON JET, LIP HEIGHT 24" SMITH #637 CARRIER
CHICAGO FAUCET ITEM # 48YD58
#2411.015 PERFORATED GRID DRAIN
#4418.026 ADJ. P-TRAP
PROVIDE ADA LAV GUARD UNDER SINK PIPE
COVER
MOUNTING HEIGHT 34" CHICAGO FAUCET ITEM # 48YD58
#2411.015 PERFORATED GRID DRAIN
#4418.026 ADJ. P-TRAP
PROVIDE ADA LAV GUARD UNDER SINK PIPE
COVER
- CHICAGO FAUCET
ITEM # 29RR72
MODEL # 897-MPRCF
E---- P3:4
~ w O ~ w ►s'D c~
~ w
PLUMBING PLAN
"'N" ROOMS 007 and 008 sc~ N I S ona~x Dr: B.M.B.
wn: 04 /M /14
#6560.105
UR-21 URNAL AMERICAN STANDARD
TRIMBROOK WATER SAVER
#6560.105
L-1 I LAVATORY AMERICAN STANDARD
MAKE # 1VNW3
MODEL # 0355012.020
L-2 I LAVATORY AMERICAN STANDARD
MAKE # 1VNW3
MODEL # 0355012.020
S-1 I MOP SINK AMERICAN STANDARD
SINK BASE
MSBID2424
1 PLUMBING PLAN
P1
N.T.S.
P80I ND.
W07PW129
D➢ITNo ND.
GENERAL NOTES
1. DEMO NOTES PER PAGE ARE FOR ROOMS
107, 107A AND 1078. PLEASE REVIEW SCOPE OF WORK.
10'-12' 6'-82'
DRAWINGS ARE PART OF SCOPE OF WORK. m co
2. CONTRACTOR SHOULD BECOME FAMILIAR WITH DRAWINGS Z
AND SCOPE OF WORK. .--1
cn W ~> cn
JAN. Q o ® 107B WOMEN' DEMO NOTES Cn E-
1 07A wozz CONTRACTOR TO REMOVE ALL PLUMBING FIXTURE'S, ALL PIPING IN WALLS, CARRIERS, SINKS, AND
ACCESSORIES IN BOTH RESTROOM'S.
HW Wap~P4
2 CONTRACTOR TO REMOVE ALL PARTITION'S BOTH BATHROOM'S.
17'-32° a W
❑ 3 CONTRACTOR TO REMOVE ALL PLASTER AND LATH GRID SYSTEM IN ALL ROOMS SHOWN
g
~4 CONTRACTOR TO REMOVE LIGHTING FIXTURES.
CD
5'-42' 5'-41'
WOMEN S 5 CONTRACTOR TO REMOVE EXISTING OUTLET'S AND SWITCHES, TO BE REPLACED
2; WITH NEW GFI AND SENSOR SWITCHES
co F1
CONTRACTOR TO REMOVE PAPER TOWEL'S AND SOAP DISPENSER'S IN RESTROOM E—
O O W
13 7 CONTRACTOR TO REMOVE EXHAUST FAN COVERS, TO BE REPLACED WITH NEW, SEE CEILING PLAN.
W~ C:o O
O g CONTRACTOR TO REMOVE DOORS AND FRAMES. PREP OPENINGS FOR NEW DOORS co
ALL SMOKE DETECTORS, SENSORS, TO BE PROTECTED AND COVERED DURING CONSTRUCTION.
cn TO BE PLACED IN TROUBLE MODE WITH FIREHOUSE. RE-PLACED AFTER NEW FINISHES ARE COMPLETE.
CD coN
10 CONTRACTOR TO REMOVE INDUSTRIAL WASH SINK, CAP EXISTING LINES TO THE MAIN.
W W
1 1 11
CONTRACTOR TO REMOVE STEAM COVER AND REPLACE WITH NEW.
co F _ I «. ~.
CONTRACTOR TO ABATE WINDOW, TANK INSULATION AND PIPE INSULATION
PER WVA 02 82 13 SPECIFICATION
CONTRACTOR TO REMOVE SLAB IN ROOM 107, REMOVE ALL UNDERGROUND PLUMBING BACK TO MAIN LINE. °..~
SEE PLUMBING DRAWING FOR MAIN LINE LOCATION. DEMO FLOOR PLAN
ROOMS 107,107A AND 1078
NTS
CONTRACTOR TO PROVIDE BLOCK PENATRATION AT BACK SIDE OF TOILETS TO REPLACE °H1TM HTe B.M.B.
°+n: 04/01/19
DEMO P E A N 12
4]
WATER LINES AND VALVES.
X1 N.T.S.
NOTE: BEFORE DISPOSAL OF FIXTURES, PW WOULD LIKE THE OPPORTUNITY TO REVIEW AND SAVE ' N O.
W07M29
FIXTURES AND PARTS AS NEEDED. CONTRACTOR TO BRING FIXTURES TO LOADING DOCK BUILDING 120
O cn
O
CD
W a'1 Z W a~ r wz
C~ a ~
M
N r EUUK [---- LAIN Al
N.T.S.
EXISTING DECK
PROVIDE SLIP TRACK
CEILING SYSTEM
PER
J (/ MATCHC
HEDULE
TILEE HEIGHT
METAL STUDS TO REMAIN
TILE HEIGHT PER A2 & A3
FASTEN BOTTOM TRACK TO SLAB
ALL WALL FINISHES INCLUDING
BASE PER SCHEDULE
GENERAL NOTES
1. CONTRACTOR TO PROVIDE, AT RATED FIRE SEPARATIONS:
FIRE CAULKING AND FIRE SAFING AT ALL PENETRATIONS,
AND ALONG TOP of PARTITIONS BETWEEN GYP. BD. & DECK.
ALL OTHER TRADES TO PROVIDE SAME FOR: PIPING, PLUMBING, ELECTRICAL,
HVAC, ETC. EACH TRADE TO RESEARCH REQUIREMENTS FOR
PENETRATIONS THROUGH WALLS.
2. ALL INTERIOR DIMENSIONS ARE TO:
—FACE OF EXTERIOR WALLS to EDGE OF INTERIOR PARTITION.
3. SEE DRAWING A2 FOR INTERIOR ELEVATIONS
NOTES & DETAILS
4. SEE DRAWING A3 FOR DOOR AND FINISH SCHEDULE.
TYPES:
TYPICAL INTERIOR WALL TO UNDERSIDE OF EXISTING DECK
-3 5/8" STN. 20 ga. METAL STUDS @ 16" O.C. W/ 20 ga. TRACK
FROM SLAB to EXISTING DECK
-TAPED 5/8" DUROCK
-TILE TO HEIGHT A.F.F. 6'-4" (MATCH EXISTING HEIGHT)
EXISTING BLOCK WALLS
-SCRAPE WALL AND PAINT PER SCHEDULE
EXISTING INTERIOR WALLS WITH TILE 6'-2" f WITH PLASTER ABOVE
ORIGINAL TILE
MACHINE GRIND AND COAT WALL / PREP
EPDXY CLEAR PRIMER
EPDXY COLORED BASE
MULTI COLORED CHIPS
URETHANE SEALANT
PATCH AND PAINT, SEE ROOM SCHEDULE
W
F—
X L0
WALL TYPE "A"
o:-H
J N Q
Y
W W Z c~)
Dum c.
FLOOR PLAN
ROOMS 107,107A AND 1078
s NTS Daum Dr: B.M.B.
DAL 04/01/1.9
r~ncr xo.
W07PW129
Dn~mra xo.
WALL MOUNT DUAL
HEIGHT H.C. DRINKING
FOUNTAIN
INSTALL PER
A.D.A REQUIREMENTS
H.C. DRINKING
FOUNTAIN ---
na~mva.
INTERIOR ELEVATIONS
ROOMS 107,107A AND 1078
NTS
B.M.B.
afi na/ni /14 exwccr xo.
W07PWI29
..M. N0.
ACCESSIBLE FIXTURES DETAII
AL
5'-T
36' MIN.
PROVIDE WOOD BLOCKING IN WALLS -INSTALL TOILET PAPER HOLDER
GENERAL NOTES:
FOR ALL: PER FIELD LOCATION. SEE FLOOR PLAN DRAWING
-FIXTURES -SEE ACCESSIBLE FIXTURES DETAIL Al FOR ACTUAL TOILET
Water Closets
-TOILET ACCESSORIES BELOW FOR ACTUAL A.D.A. REQUIREMENTS ROOM ORIENTATION.
- General.
& COUNTER TOP -PROVIDE NECESSARY SIGNAGE AND DESIGNATION OF
BATHROOMS FOR GENDER AND HANDICAPPED ACCESSIBILITY.
Water closets shall be mounted adjacent to a side wall or partition.
The distance from the side wall or partition to the centerline of the water closet Lavatories & Sinks:
shall be 18 in. - Lavatories shall be mounted with the rim 34 in maximum above the floor and with a clearance of 29
- Clear Floor Space. in minimum from the floor to the bottom of the front edge of the apron.
Clear floor space for water closets not in stalls shall be 48 in minimum in front of - Sinks shall be mounted with the counter or rim 34 in maximum above the floor. Sinks shall be 6 the water closet and 42 in from the center line of the water closet on the side not adjacent to the wall. in deep maximum
- Height. The top of water closet seats shall be 17 in to 19 in above the floor. Seats shall not be Clearances:
sprung to return to a lifted position. - Knee & toe Clearances. Fixtures shall extend 17 in minimum from the wall. Clearance between the
- Grab Bars. bottom of the front edge of the apron and the floor shall be 20 in minimum. The clear knee space shall
Grab bars shall be provided on the rear wall and on the side wall closest to the water closet. be 8 in in depth minimum at 27 in minimum above the floor or ground and 11 in in depth minimum at
- Side wall grab bar shall be 42 in long minimum located 12 in maximum from the rear wall and 9 in minimum above the floor or gound. The dip of the overflow shall be ignored when checking the extending 54 in minimum from the rear wall. The rear wall grab bar shall be 24 in long minimum, clearances.
centered on the water closet. Where space permits, the bar shall be 36 in long minimum, with the - Clear Floor Space. Clear floor space, 30 in by 48 in minimum, shall be provided in front of a additional length provided on the transfer side of the water closet. lavatory or sink to allow a forward approach and shall extend 19 in maximum under the lavatory or
Flush controls. Flush controls shall be hand operated. sink.
- Dispensers. Toilet paper dispensers shall be installed between 7 in and 9 in in front of the water - Exposed Pipes & Surfaces. Water supply and drain pipes under lavatories or sinks shall be insulated closet. The outlet of the dispenser shall be located between 15 in and 48 in above the floor. There or otherwise configured to protect against contact. There shall be no sharp or abrasive surfaces under shall be a clearance of 1 in minimum below and 12 in minimum above the grab bar. Dispensers shall lavatories or sinks.
not be of a type that control delivery, or that do not allow continuous paper flow. - Faucets. Self-closing faucets, when used, shall remain open for 10 seconds minimum.
M
L-1 K-1 WC-1 WC-1 WC-1 WC-2 L-1 L-1 L-2
WC-1 WC-1 WC-1 WC-1
M co
Q a ~ ~T.
E_
PAINT PER SCHEDULE
EPDXY —
1B INTERIOR ELEVATION
A2
N.T.S.
A
INTERIOR ELEVATION
A2
N.T.S.
PAINT PER
SCHEDULE
WC-2
1D INTERIOR ELEVATION
A2
N.T.S.
1C
INTERIOR ELEVATION
A2 N.T.S.
Type 1 hardware set at all single interior doors.
a. 1 1/2 Pair #TA2714-26D 4.5 x 4.5 hinges by
McKinney.
b. #GL97 Series, 26D finish, by Arrow Lock or equivalent
c. #9304—BF—ALU door closer by Norton.
d. #409-32D wall stop by Rockwood.
e. #FS45526D—kick stop by Ives.
Type 1A hardware set at all single interior doors.
a. 1 1/2 Pair #TA2714-26D 4.5 x 4.5 hinges by
McKinney.
d.#L1 1—SR Series, 26D finish, by Arrow Lock or equivalent
c. #9304—BF—ALU door closer by Norton.
d. #409-32D wall stop by Rockwood.
e. #FS45526D—kick stop by Ives.
m
~ O CQ
W Cn
O a O Z
E-1
1.4 a w H nnnR ':~rHFM 11 F NO. DESC. SIZE TYP. DOOR MATERIAL DOOR FINISH RATING FRAME MATERIAL FRAME FINISH HARDWARE GLASS MANUFACTURER REMARKS
107 FLUSH HOLLOW METAL 3'-0" x 7'-0" 1 18 GA. INSULATED STEEL ENAMEL — 16 GA. STEEL ENAMEL 1 — MOHAWK OR EQUAL
107A FLUSH HOLLOW METAL 3'-0" x 7'-0" 1 18 GA. INSULATED STEEL ENAMEL — 16 GA. STEEL ENAMEL 1 — MOHAWK OR EQUAL
107B FLUSH HOLLOW METAL 3'-0" x 7'-0" 1 18 GA. INSULATED STEEL ENAMEL — 16 GA. STEEL ENAMEL 1A — MOHAWK OR EQUAL
4-
R
FNI~11 PLATE BOTH SIDES
FLUSH HOLLOW
M ETAL
F1
ADA compliant, to receive 6 pin core both sides.
NOTE: LEVER MUST ACCEPT" BEST 6—PIN CORE"
FINISH LEGEND
CODE MANUFACTURER PRODUCT INFORMATION
PT-1 SHERMAN WILLIAM'S WALLS: PROVIDE 1 COAT PRIMER
OR EQUAL. AND 2 COATS OF FINISH
FURNISH AND APPLY TWO FULL BODY COATS OF RUST
PT-2 INHIBITING SEMI—GLOSS ENAMEL TO ALL HOLLOW
METAL DOORS
EP-1 DUR—A—FLEX OR EQUAL 1/8" SLIP RESISTANT OR APPROVED EQUAL
RFP CRANE COMPOSITE COLOR TO BE DETERMINED
OR EQUAL PROVIDE ALL TRIM ACCESSORIES
TILE SKYBRIDGE GLAZED 12"X24", REVEAL IMAGING OR EQUAL
CERAMIC
ACT-1 ARMSTRONG OR EQUAL 24"X48"X3/4", ACOUSTIC, CLASS A FIRE RATING
954 CLASSIC FIN AND RESISTANT TO MOLD AND MILDEW
ROOM FINISH SCHEDULE
RM. NO. ROOM NAME FLOOR FINISH BASE N. WALL FINISH S. WALL FINISH E. WALL FINISH W. WALL FINISH FIN. CLG. FIN. CLG. HGT. REMARKS ..mo
DOOR AND ROOM SCHEDULE
107 WOMEN'S ROOM EP-1 EP-1 EPDXY / PT-1 EPDXY / PT-1 EPDXY / PT-1 EPDXY / PT-1 ACT-1 7'-11"f ROOMS 107,107A AND 1078
107A WOMEN'S ROOM EP-1 EP-1 EPDXY / PT-1 EPDXY / PT-1 EPDXY / PT-1 EPDXY / PT-1 ACT-1 7'-11"f NTS
107B JANITORIAL ROOM EP-1 EP-1 EPDXY / PT-1 EPDXY / PT-1 EPDXY / PT-1 EPDXY / PT-1 ACT-1 7'-11" B.M.B.
04/01/19
NOTE: SEE INTERIOR ELEVATIONS FOR HEIGHTS
PR9A4T x0.
W07PW129
ns~m`a xo.
JAN. 1. ALL ELECTRICAL TO BE INSTALLED PER CODE.
10 7B 2. PROVIDE FLUSH MOUNTED SENSOR FOR LIGHTING AND EXHAUST FANS.
3. All FIRE ALARM MOUNTED CONDUIT ATTACHED TO CEILING WILL BE REMOVED AND PLACED ABOVE co
NEW CEILING. Z
m FIRE ALARM STROBE '_:I O
DOOR FRAME W
cn
WOMEN'S THERMOSTAT, INTERCOM OR 2ND ROW OF
Q Z O
1 0 A /
Irlv,-
RECEPTACLES CENTER OVER CLUSTER
N BELOW (WHEN USING DIMMERS, LOCATE
THERMOSTAT AT OPP. SIDE OF DOOR). E-1 ' 4 ~
C:) Z
LIGHT SWITCH, DIMMERS, EGRESS BUTTON,
. w
FTl -co
INTERCOM BUTTON, CARD READER, ETC.
`9 (SEE PLAN FOR QUANTITY OF EACH O pq p w
S r t \ i CLUSTER) ALL UNDER COMMON FACE PLATE.
WOMEN 'S ~' ¢
DOOR LEVER, PULL
107 07 FINISH FLOOR p., N
LINE OF FINISHED FLOOR RECEPTACLE
TYP. LOCATION FOR LIGHT SWITCHES, DIMMERS, EGRESS BUTTONS, THERMOSTATS, ETC.
- FIXTURE LEGEND
INDICATES SUSPENDED METAL CEILING GRID LJ EMERGENCY LIGHT w
W/ BATTERY BACK-UP
E---
INCLUDED W/UNIT
w w
LITHONIA LIGHTING 2'X4' TROFFER NUMBER SURFACE WALL 8' A.F.F. W
GT41_41W MV OR APPROVED EQUAL P/N: EU-3-LED-W o g=~ http://astralitelighting.com/EU3.html w
O
® CONTRACTOR TO PROVIDE NEW EXHAUST FAN EXIT/EMERGENCY LIGHT
PROVIDE MIN. 8 AIR EXCHANGES PER HOUR. W/ BATTERY BACK-UP cy'D
TIE INTO EXISTING DUCT WORK INCLUDED W/UNIT
NEW EXHAUST FAN GRILLS (CONTRACTOR TO PROVIDE SURFACE WALL 8' A.F.F.
FLEXIBLE INSULATED DUCT TO EXISTING DUCT WORK) P/N: EEU-3-R-W-LED ~--~
http://ostralitelighting.com/EEU3.HTML
® $ FAN AND LIGHT SWITCH SENSOR
~3 w
❑S STROBE, WALL MOUNT. PROTECT DURING CONSTRUCTION
&;ot
~s SMOKE DETECTOR. PROTECT DURING CONSTRUCTION `""""r NA "°"
Z
DxNiG
REFLECTED CEILING PLAN
ROOMS 107,107A AND 107B
1 REELECTED CEILING PLAN ~.,r M.B.Da~`x Dr: B.M.
ota:
E1 04 01 19
N.T.S.
PD01[CI N0.
W07PW129
D➢~1D1c xD.
E1
GENERAL MOTES: (DOMESTIC)
1. ALL DOMESTIC COLD AND HOT WATER PIPING SHALL BE RUN IN CEILING
SPACE SCREWED OR SOLDERED. m
2. ALL DOMESTIC WATER PIPING ABOVE GROUND SHALL BE TYPE 'L' COPPER cc
ASSEMBLED WITH LEAD FREE SOLDER & INSULATED WITH MIN. 3/4" VINYL Z '--i
CQ
JACKED FIBERGLASS INSULATION. O
,I 3. PROVIDE SHUTOFFS AT ALL FIXTURES. cn S-1 JAN. w 5_ n_-
1 07B WOMEN' __ Q z 0 k-N
GENERAL MOTES: (SANITARY) O
~x~
I 1. ALL PLUMBING SYSTEMS SHALL BE INSTALLED IN COMPLIANCE WITH W A4 Z W
I ALL APPLICABLE CODES '"' O
LOCATION OF I 2. ALL SANITARY PIPING UNDERGROUND SHALL BE PVC > '~' w
EXISTING 3. ALL SANITARY AND VENT PIPING ABOVE GROUND SHALL BE PVC
W ~ W SANITARY LINE , i / i 4. PROVIDE CLEAN-OUTS MAX. 50'-0" O.C.
L-2 TWO M i 6. CONTRACTOR TO PROVIDE ELECTRIC FLUSHOMETER FOR ALL TOILETS AND URNALS W .~
I 7. ALL WATER, SANITARY AND VENTING TO BE REPLACED. a N i 8. CONTRACTOR TO PROVIDE FLOOR DRAIN PRIMERS AT ALL FLOOR DRAINS.
~N
PLUMBING FIXTURE SCHEDULE
J N0. TYPE MAKE AND MODEL # REMARKS ACCESSORIES
WC-1 WATER CLOSET AMERICAN STANDARD MADERA 1 1/2" TOP SPEED WALL OUTLET SLOAN ROYAL #111 ESS HARDWIRED FLUSH
1.6 GPF. SIPHON JET, MOUNTING HEIGHT 15' VALVE SENSOR. CHURCH # 295, BLACK W
~T~ ( SEAT OPEN FRONT.
J `--- -- EXISTING V. WC-2 WATER CLOSET AMERICAN STANDARD MADERA 1 1/2" TOP SPEED WALL OUTLET SLOAN ROYAL #111 ESS HARDWIRED FLUSH
WC-2 WCi (HC) 1.6 GPF. SIPHON JET, MOUNTING HEIGHT 19" VALVE SENSOR. CHURCH # 295, BLACK E_
In i INSTALL SUPPORTS ON FLUSH VALVE SEAT OPEN FRONT.
W i L-1 LAVATORY AMERICAN STANDARD CHICAGO FAUCET ITEM # 48YD58 W
_…