LRXQ212501 Fire Alarm Panel Site Visit Q & A
1 July 2021
1. Updated Wetlands Map. Near Building 237 conduit must go above ground to avoid wetlands.
2. See attached for the specifications/data in regards to the type of junction box/pull box we are requesting to be installed during the trenching and boring. Please note that the sizes may vary depending on the amount of wire/conductors that will be installed in the boxes. Brand Name or Equal to Quazite or any product with similar specifications.
3. The Fire Alarm Panel in Building 200 WILL NOT require mass notification due to the size of the facility and the amount of occupants that are within the facility at any given circumstance.
However per the SOW in section VI-A, we are still requesting to “Upgrade the 4100 fire alarm panel from a 4100+ to 4100ES panel.”