This document contains an addendum and questions and answers related to a solicitation for repair work on BE Admin and Shops buildings B4210-4211. The solicitation is seeking a single firm fixed-price contract to provide all plant, labor, transportation, materials, tools, equipment, appliances, and supervision necessary for repairs. Required work includes replacement of water heaters with electric storage models similar to Bradford White CEA units, installation of automatic flush valves for toilets and sinks, and modifications to the existing main distribution panel which is a Square D or QED brand. The pre-bid conference is scheduled for January 26, 2024 at 0930 local time with the site visit to follow. Interested contractors must follow registration and base access requirements in the solicitation. The response due date is not provided. The solicitation is set aside 100% for small businesses with a NAICS code of 236220 and magnitude between $5 million to $10 million.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CYQL152003 Repair BE Admin Vendor Ques�ons

SOLICITATION W50S6Y-24-B-0003 Repair BE Admin

Addendum 01 Q&A

Date 2/6/24

1. Is a Florida Construc�on license required for the work performed to repair BE Admin B4210- 4211?

Yes

2. May you please provide the model number for the water heaters? Specs do not appear to list any brands.

As products cannot be iden�fied to a sole source therefore, we did not specify make or model for the water heaters on the plans/specs. However, the Bradford White “CEA” model was used as basis of design. Other electric storage water heaters that are equal in performance/features may be provided.

3. What kind of water, sewer, air pipes are required? Can we use Sch 40 and PVC piping?

See specifica�on 22 00 00 sec�on 3.10 TABLES for appropriate piping materials. Table 1 indicates drainage, waste, vent, etc. materials and Table 2 indicates pressure piping materials.

4. Please clarify if all toilet and sink fixtures will use automa�c flush valves as stated in Volume 2 Specifica�ons, page 20, Sec�on 22, 2.4.1 “Flushing and faucet systems shall consist of solenoid-ac�vated valves with light beam sensors. Flush valve for water closet shall include an override pushbuton. Flushing devices shall be provided as described in paragraph FIXTURES

AND FIXTURE TRIMMINGS.”

Confirmed, provide automa�c flush valves as indicated in specifica�ons. Also see plumbing fixture schedule notes 4 and 5 on sheet P-601 which indicate use of automa�c flush valves.

5. If we send our proposal via FEDEX, are we to have it delivered to the following address: 202d Red Horse Squadron, Bldg. 4210, 5269 SR 16W, Starke, FL 32091. If this is not correct, please provide a delivery address, person of contact and phone number.

Ensure the delivery is PRIOR to the date and �me set forth in the Solicita�on:

202D RED HORSE Squadron

BLDG 4200

5629 FL-16W

Starke, FL 3091

6. We have to add breakers and do modifica�ons to the exis�ng MDP. What brand is the exis�ng MDP? If pictures can be provided it would be appreciated.

Square D, QED. See atached photos.