AUSTIN TE-10.pdf
PDF 18 KB Posted
- Attached to
- Operations and Maintenance Services
- Solicitation number
- TIRMS10R00005
About this file
Technical Exhibit 10
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AUSTIN PWS 7-14-10.rtf | RTF text file | |
| Vendor Questions AUSTIN.rtf | RTF text file | |
| Austin Site Visit Sign In.pdf | ||
| RMS10R00005-A0002 1 .rtf | RTF text file | |
| TIRMS10R00005 7-14-10.rtf | RTF text file | |
| HSPD_12_PIV Procedures Manual.pdf | ||
| TIRMS10R00005-A0001 1 .pdf | ||
| TIRMS10R00005 Amendment 1.pdf | ||
| Wage Determination 6-22-10 Austin.pdf | ||
| AUSTIN TE-2.pdf | ||
| TIRMS10R00005.pdf | ||
| AUSTIN PWS FINAL.pdf | ||
| AUSTIN TE-9.pdf | ||
| Key personnel CMMS Administrator attachment.rtf | RTF text file | |
| QUALITY ASSURANCE SURVEILLANCE PLAN.pdf | ||
| AUSTIN TE-8.pdf | ||
| AUSTIN TE-4.pdf | ||
| AUSTIN TE-6.pdf | ||
| AUSTIN TE-3.xls | XLS spreadsheet | |
| AUSTIN TE-12.pdf | ||
| Key personnel Supervisory attachment.rtf | RTF text file | |
| AUSTIN TE-11.pdf | ||
| AUSTIN TE-5.xls | XLS spreadsheet | |
| AUSTIN TE-1.pdf | ||
| NOTICE TO CONTRACTORS OM Austin.pdf | ||
| AUSTIN TE-7 REV 5-4-2010 AB.pdf | ||
| Cover Letter.pdf | ||
| Key personnel Program Manager attachment.rtf | RTF text file | |
| Wage Determination.pdf |
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IRS Building Delegations Performance Work Statement
TECHNICAL EXHIBIT TE -10
Infrared Testing Requirements
IRS PM
CHECK DESCRIPTION FREQUENCY
E-26 Molded Case Breakers Less than 600 Volts and Greater than 400 amps
One time in three years
E-28 Motor Starters Less Than 100 Hp One time in three years
E-30A Switchboards, Medium Voltage, (per cubicle) One time in three years
E-30B Switchboards Low Voltage, (per cubicle), One time in three years
E-37C Bus Duct, Low Voltage, & Connectors Copper - Per disconnect One time in three years
E-37D Bus Duct, Low Voltage, & Connectors Copper - Per 10 foot bus duct section
One time in three years
E-36 Automatic Transfer Switch One time in three years
E-33A High Voltage Network and, Power Type Transformer Dry Type Transformer - - Power Type Annual
E-33B High Voltage Network and, Power Type Transformer Dry Type Transformer - - Network Type Annual
E-34A Disconnects or Isolating Switch, Per Switch, Under 200 amps >600 VOLTS Annual
E-34B Disconnect or isolating switch, low voltage (fused/non- fused, 200 amps and up) - - 200 To 500 Amps Annual
E-34C Disconnect or isolating switch, low voltage (fused/non- fused, 200 amps and up) - - Over 500 Amps Annual
E-37A Bus Duct, Low Voltage, & Connectors Aluminum - Per disconnect Annual
E-37B Bus Duct, Low Voltage, & Connectors Aluminum - Per 10 foot bus duct section
Annual
E-37AA
Bus Duct, Metal Enclosed, & Connectors Aluminum: - Per disconnect
Annual
E37BB Bus Duct, Metal Enclosed, & Connectors Aluminum: - Per 10 foot bus duct section Annual
E-37CC Bus Duct, Metal Enclosed, & Connectors Aluminum: - Outdoors: Per disconnect Annual
E-37DD Bus Duct, Metal Enclosed, & Connectors Aluminum: - Outdoors: Per 10 foot bus duct section Annual
E-59 Uninterruptible Power System, Static Annual
E-35A Motor Control Center (MCC), under 100 hp - - 5 or fewer starters Annual
E-35B Motor Control Center (MCC), under 100 hp - - Each additional motor starter Annual
E-58 Power Distribution Unit Annual