Pre Action Systems_Redacted.pdf

PDF 201 KB Posted

Attached to
H312--Fire Suppression and Sprinkler Services Federal contract opportunity
Solicitation number
36C24223Q0714
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

View the file

Other files for this federal contract opportunity

Other files attached to H312--Fire Suppression and Sprinkler Services, newest first.
File Type Posted
First Floor Kitchen_Redacted.pdf PDF
Ground Floor Kitchen_Redacted.pdf PDF
CO2 System Insp_Redacted.pdf PDF
WD 2015-4187 Rev. 24.pdf PDF
Dry Pipe Systems_Redacted.pdf PDF
Dry Chem Sys in Radioactive Storage_Redacted.pdf PDF
36C24223Q0714.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date: June 15, 2021

Tech:

Safe-Tech Inc. Phone:

Address

Phone

Manufacturer

FM-200 HALON CO2 Inergen Dry Chem Water 2 x 12v 7 AH Load Test

24V 12V 110V Pneumatic Cable Battery

Start 1:00 PM Restore 2:00 PM Operator ID

VIA VIA

Size 4" Supply PSI 110 Seat PSI 115 Solenoid OK Comments:

Zone Air PSI 5 NA LoAir 3 PSI System Loc.

Size AC On PSI 4 AC Off PSI 5 Comments:

Zone 1 Type Fenwal Serial No 135* FT Heat Sensativity NA GA NA Comments:

Zone 2 Type MPS Serial No NA Sensativity NA GA NA Comments:

Zone 3 Type Lo Air Serial No NA Sensativity GA NA Comments:

Zone Type Tamper Serial No NA Sensativity 2 Turns GA NA

Zone Alarm Type Pressure Serial No NA Sensativity NA GA NA Comments:

NAC Alarm 1 Bell ANY Comments:

2 Solenoid Comments:

Comments:

Comments:

Comments:

Date

Reliable Model B-S1

Customer Signature 6/15/2021

Printed Name

Direct to Class "E" panel

Reliable Model B

There are 25 devices +/-

GEM

Fire Suppression Inspection Report

Pre-Action Sprinkler Mechanical Information

Signing Below will constitute acceptance of the Inspection & Fire Services Noted:

Comments: NO DEFECTS FOUND.

James J. Peters VA Medical Center

GEM VALVE

Closet by MRI Computer Room

OK

Alarm + Trouble to Class "E" Panel

Inspected/actuated OK

OK at 3 PSI

Direct to Class "E" panel - SET PROPERLY

Comments: SAFETY 718.584.9000 * 3644 or 3436 or Rick *6605

Building FACP

Left 162 Mhos; Rt 118 Mhos

NA

Battery Backup

Detection Information

Customer

Contact

System Type

Notifications Central Station

Shutdowns NA

Closet by MRI Computer RmSystem Location

Agent

City, State, Zip Bronx, NY 10468

Protected Area

Control Panel

Ground Floor MRI Suite

Potter PFC 100RC

130 W. Kingsbridge