Pre Action Systems_Redacted.pdf
PDF 201 KB Posted
- Attached to
- H312--Fire Suppression and Sprinkler Services Federal contract opportunity
- Solicitation number
- 36C24223Q0714
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Ground Floor Kitchen_Redacted.pdf | ||
| CO2 System Insp_Redacted.pdf | ||
| Dry Pipe Systems_Redacted.pdf | ||
| Dry Chem Sys in Radioactive Storage_Redacted.pdf | ||
| 36C24223Q0714.docx | DOCX document | |
| WD 2015-4187 Rev. 24.pdf | ||
| First Floor Kitchen_Redacted.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date: June 15, 2021
Tech:
Safe-Tech Inc. Phone:
Address
Phone
Manufacturer
FM-200 HALON CO2 Inergen Dry Chem Water 2 x 12v 7 AH Load Test
24V 12V 110V Pneumatic Cable Battery
Start 1:00 PM Restore 2:00 PM Operator ID
VIA VIA
Size 4" Supply PSI 110 Seat PSI 115 Solenoid OK Comments:
Zone Air PSI 5 NA LoAir 3 PSI System Loc.
Size AC On PSI 4 AC Off PSI 5 Comments:
Zone 1 Type Fenwal Serial No 135* FT Heat Sensativity NA GA NA Comments:
Zone 2 Type MPS Serial No NA Sensativity NA GA NA Comments:
Zone 3 Type Lo Air Serial No NA Sensativity GA NA Comments:
Zone Type Tamper Serial No NA Sensativity 2 Turns GA NA
Zone Alarm Type Pressure Serial No NA Sensativity NA GA NA Comments:
NAC Alarm 1 Bell ANY Comments:
2 Solenoid Comments:
Comments:
Comments:
Comments:
Date
Reliable Model B-S1
Customer Signature 6/15/2021
Printed Name
Direct to Class "E" panel
Reliable Model B
There are 25 devices +/-
GEM
Fire Suppression Inspection Report
Pre-Action Sprinkler Mechanical Information
Signing Below will constitute acceptance of the Inspection & Fire Services Noted:
Comments: NO DEFECTS FOUND.
James J. Peters VA Medical Center
GEM VALVE
Closet by MRI Computer Room
OK
Alarm + Trouble to Class "E" Panel
Inspected/actuated OK
OK at 3 PSI
Direct to Class "E" panel - SET PROPERLY
Comments: SAFETY 718.584.9000 * 3644 or 3436 or Rick *6605
Building FACP
Left 162 Mhos; Rt 118 Mhos
NA
Battery Backup
Detection Information
Customer
Contact
System Type
Notifications Central Station
Shutdowns NA
Closet by MRI Computer RmSystem Location
Agent
City, State, Zip Bronx, NY 10468
Protected Area
Control Panel
Ground Floor MRI Suite
Potter PFC 100RC
130 W. Kingsbridge