National Fire Protection Association (NFPA) Suppression Fire Protection System
Report of Inspection, Testing, and Maintenance of Suppression Fire Protection Systems
Inspector: SEMI-ANNUAL Inspection Date: January 09, 2023 Service Ticket #: 184336
Site: System Inspected: Area: Site Contact:
James J Peters VA Medical Center 130 West Kingsbridge Road, Bronx, NY, 10468
System # 66-0790 Type: Dry Chemical Panel:
Radioactive Storage Shed Floor:
Building:
If ALL items on the form are marked "OK" or "N/A", the inspection has found no deficiencies.
Any items that are marked "NO" are discrepancies. Describe these in more detail for each item. Some discrepancies could be resolved immediately (such as moving boxes that obstruct access to a manual pull station). If any discrepancies remain unresolved CONTACT UNITED FIRE PROTECTION CORPORATION FOR SERVICE AND REPAIR 24 HOURS / 7 DAYS = 908-688-0300
RELEVANT HAZARD MODIFICATIONS TO NOTE DURING MONTHLY INSPECTION
Look for any of the following items that have changed since the last inspection:
-Have new walls been erected or demolished, that make the hazard different from before?
-Have penetrations been made in any of the walls that would allow clean agent gas to leak out of the hazard?
-Have there been changes to the HVAC system (such as a new air conditioner installed in the wall)?
The following items would NOT be considered relevant changes to note:
-Movement of furniture (desks, racks, etc.).
-Erection or demolition of cubicle walls that do not extend to near the ceiling.
-Painting of walls.
-Additional equipment, similar to that already within the hazard (as long as clean agent equipment is not obstructed).
TYPE OF SUPRESSION SYSTEM(S)
TYPE OF SUPRESSION SYSTEM(S) 1) ABC Dry Chem System 2) 3)
TYPE OF ACTUATION (fill in quantity of each)
SLC Wiring / Class Mechanical - heat link
Manual Release 1 - mechanical
Photo Smoke
Ion Smoke
Heat Detector
Cross Zone None
(Explain) No cross zoning - mechanical system
Other
(4) - 212 deg links
Waterflow
Supervisory (tampers)
CONTROL PANEL
Quantity
Model Kidde Industrial Dry Chem Control Head
Manufacturer Kidde
Software Version
Graphic
Manufacturer
AGENT STORAGE CONTAINERS
Quantity
Agent Type Dry Chem
Manufacturer Kidde
PREACTION INFORMATION
Valve Size
Model
Manufacturer
COMPRESSOR INFORMATION
Manufacturer
Model
HP
Volts
INSPECTION
Were all personnel and authorities notified? YES
Are all devices securely mounted and unobstructed? YES
Is there a 24-hour call for service sticker on the control panel? YES
Is area free of any changes that might affect protection? YES
Is area free of unsealed penetrations? N/A
Do doors operate properly? YES
Are doors vapor tight? N/A
Are all ceiling tiles in place? N/A
If required, was area checked for volume? N/A
Were all tanks checked for hydrostatic date? YES
Were all tanks checked for weight and recorded? YES
Is there an adequate amount of agent for area? YES
Is net weight the same as last inspection? Weight lbs 45 LBS main tank 21 LBS second tank
YES
Is cylinder bracketing secure? YES
Are nozzles secure and unobstructed? YES
Are nozzles located to give maximum protection? YES
Is all piping secure and free of corrosion? YES
Is main reserve capability operational and readily accessible? N/A
Is there a riser diagram by the control panel? For NYC only, is the riser diagram 11" x 17" per the 2008 NYC city fire code?
N/A
Is there a sequence of operation by control panel (NYC)? N/A
Does control panel have a sign describing the type of agent supression system (NYC)? N/A
DETECTION (see Individual Detector Report below)
Were all detectors checked for operation per manufacturer's recommendation? N/A
Did they function properly? N/A
Were all settings recorded? N/A
Were all detectors cleaned where needed? N/A
Were they replaced as needed? N/A
MANUAL RELEASES
Are all manual releases properly labeled? YES
Did they all function properly? YES
Are they easily accessible in case of fire? YES
Will manual release override abort? N/A
ABORTS
Were all aborts tested? N/A
Did they function properly? N/A
TIME DELAY
Did delay and/or investigation timer operate as intended? N/A
Delay in seconds
NA
Investigation in seconds
NA
GRAPHIC ANNUNCIATOR
Was annunciator checked? N/A
Did all the lights work properly? N/A
CONTROL
Were all operating functions checked & functioning properly? YES
Were batteries functioning properly? N/A
Were all supervisory functions checked & function properly? N/A
Were batteries tested per manufacture's recommendations? N/A
Amps in Stand-by
NA
Amps in Alarm
NA
Battery Size Volts
NA
AH
NA
Were all batteries replaced as needed? Date Installed
NA
N/A
Was alarm verification checked? N/A
Was ground fault protection tested? N/A
Is there a fuse cut out / fuse disconnect, and is it labeled properly?Location
NA
N/A
Is there a circuit breaker # and location on the control panel?Location of breaker
NA
N/A
Breaker #
NA
Panel #
NA
AUDIBLE(S)
Do all indicating devices operate as per NFPA and/or Local AHJ? YES
Do all indicating devices have signs to show purpose? N/A
Are warning signs provided? N/A
Class / Style Wiring
NA
EXPLOSIVE RELEASE DEVICES
Were they replaced with bulbs and fired? N/A
Are they within replacement date?
NA
N/A
SOLENOID RELEASE DEVICE
Solenoid and/or Control Head(s) removed from Cylinder and/or Valve and activated? N/A
PREACTION VALVE
First Valve Location
NA
Was preaction valve tripped? N/A
Was waterflow test valve checked? N/A
Priming water pressure PSI
NA
Building water pressure PSI
NA
Residual water pressure PSI
NA
Was tamper valve checked and working properly? N/A
Was air pressure checked and working properly? N/A
Normal Air Pressure PSI or Oz
NA
Compressor On Pressure PSI or Oz
NA
Low Air Pressure PSI or Oz
NA
High Air Pressure PSI or Oz
NA
INTERLOCKS AND AUXILIARY FUNCTIONS TESTING
Remote Station Monitoring Local bell only 1/13/22
N/A
Account Number
NA
Equipment Shutdown N/A
Description of Equipment Shutdown
NA
Building Tie-in N/A
Description of Building Tie-in There is no indication of Building Fire Alarm tie in
Self air conditioning system N/A
Description of self air conditioning system
Building air conditioning N/A
Description of building air conditioning
NA
Dampers? (If E.T.L.'s remove and test with bulb) N/A
Description of Dampers
NA
Door releases N/A
Description of door releases
NA
Fans N/A
Description of fans
NA
Purge N/A
Description of Purge
NA
Other Local Bell Wheelock 6"
Were all tested? YES
Did they function properly? YES
Was annual room pressurization test performed? N/A
Date room pressurization last tested?
NA
If interlocks cannot be tested, or there is not adequate interlocks or if deficiencies exist, explain in detail below:
NA
Agent Type Dry Chem - Kidde
INDIVIDUAL DEVICE REPORT 4 Devices (uploaded files will be emailed/stored with Inspection Report)
Location Manufacturer Serial # Model # Sens.
Setting Graphic
Conn.
Comments
Shed-A
Globe NA ML 212 Deg NA
NA
Shed-A
Globe NA ML 212 Deg NA
NA
Shed-B
Globe NA ML 212 Deg NA
NA
Shed-B
Globe NA ML 212 Deg NA
AGENT STORAGE CONTAINER REPORT
ACS # Gross Weight lbs.
Agent Weight lbs.
Pressure P.S.I Hydro Test Date
Liquid Levels Inches
Location Area Protecting
1 TAR051214 21lbs 360 04/2017 NA Exterior of waste shed Waste Shed
2 P14335TC 45lbs 360 04/2017 NA Exterior of waste shed Waste Shed
3 87-20043-001 237grams 2-2018 NA Nitrogen cartridge
UNITED FIRE PROTECTION CORP.
Work Ticket Delivery Date: January 09, 2023 Ticket #: 184336.01092023
Account #: 66-0790
PO#
Site Name: James J Peters VA Medical Center
Address: 130 West Kingsbridge Road, Bronx, NY, 10468 Building
Site Contact:
Type of Call: Inspection
Work Tickets Notes: Call
Associate Radiation Safety Officer
Scope of Work: Perform Semi Annual Dry Chemical inspection.
TO BE PERFORMED:
Site Act # Frequency Ctrl Panl
System Area Building Str# Str Fl City St
66-0790 Semi Annual
Dry Chemical
Radioactive Storage Shed
130 West Kingsbridge Road
Bronx NY
Description of Work Performed:
Performed Semi Annual Dry Chemical inspection. Replaced all (4) 212* fusible links.
Note:
System is Local only. Bell on side of enclosure.
There is no connection to the building Simplex Fire Alarm.
All systems have been restored to normal operations upon completion of inspection.
Material Used:
Qty Make Model Description
4 Globe ML 212* Fusable Links
Technicians Actual Time for the Job:
Date Technician Disp Arr Dep Trvl Frm Site
Total Trvl
HRPC TOJ Lunch
01/09/2023 08:00 09:00 12:00 00:00 00:00 R 03:00 00:00
01/09/2023 08:00 09:00 12:00 00:00 00:00 R 15:00 00:00
System Left: In Normal Operation Is Call or Insp Complete? Yes Need to Reschedule? No