Date: June 15, 2021
Tech:
Safe-Tech Inc. Phone:
Address
Phone
Manufacturer
FM-200 HALON CO2 Inergen Dry Chem Water Load Test
24V 12V 110V Pneumatic Cable Battery
Start 1:30 PM Restore 2:00 PM Operator ID
VIA VIA
Size 4" Supply PSI 60 PSI Seat PSI 44 Air Solenoid NA Comments:
Zone Air PSI NA LoAir 20 PSI System Loc.
Size AC On PSI 25 AC Off PSI 44 Comments:
Zone Supervisory Type Lo Air Serial No NA Sensativity OK GA NA Comments:
Zone Supervisory Type Tamper Serial No NA Sensativity 2 Turns Comments:
Zone Alarm Type Pressure Serial No NA Sensativity OK GA NA Comments:
DateCustomer Signature 6/15/2021
Printed Name
Signing Below will constitute acceptance of the Inspection & Fire Services Noted:
Comments: The spread between cut-in and cut-out is 20 PSI, as adjusted last year - OK
James J. Peters VA Medical Center
SYSTEM TRIPS AT 20 PSI +/-
Boiler Room
Direct to Class "E" panel - OK
Direct to Class "E" panel - OK
Reliable Battery Backup
Fire Suppression Inspection Report
Dry Pipe Sprinkler Mechanical Information
Boiler Room
Comments:
Building FACP NA
130 W. Kingsbridge
Detection Information
Customer
Contact
System Type
Notifications Central Station
Shutdowns NA
City, State, Zip Bronx, NY 10468
Protected Area
Control Panel
Heater Blade Exchange Room
NA - Dry System
Direct to Class "E" panel - OK
Supply @ 44 PSI
LOCAL AIR COMPRESSOR
System Location
Agent
Date: June 15, 2021
Tech:
Safe-Tech Inc. Phone:
Address
Phone
Manufacturer
FM-200 HALON CO2 Inergen Dry Chem Water Load Test
24V 12V 110V Pneumatic Cable Battery
Start 11:30 AM Restore 12:00 PM Operator ID
VIA VIA
Size 4" Supply PSI 105 PSI Seat PSI 40 PSI Air Solenoid NA Comments:
Zone Air PSI 38 PSI NA LoAir NA System Loc.
Size AC On PSI 30 PSI AC Off PSI 40 PSI Comments:
Zone Supervisory Type Lo Air Serial No Sensativity GA NA Comments:
Zone Supervisory Tamper OK
Zone ALARM Type Pressure Serial No NA Sensativity OK GA NA Comments:
Comments:
Comments:
Comments:
Comments:
DateCustomer Signature 6/15/2021
Printed Name
Reliable
Fire Suppression Inspection Report
Dry Pipe Sprinkler Mechanical Information
Signing Below will constitute acceptance of the Inspection & Fire Services Noted:
Comments: The New low air pressure switch, needs to be monitored by Class "E" system directly. If the system pressure goes below 28 PSI, you need to know it. The new drum drip was opened to test the air compressor points of operation
- and significant amounts of rust water was drained out - to the point of air only. This should be done just before the cold weather.
James J. Peters VA Medical Center
Valve is in service Cage by pallet wrap
Battery Backup
INSTALLED BUT NOT TIED IN
Direct to Class "E" panel - OK
NA
Locked Cage by pallet wrap
Comments:
COMPRESSOR SET UP FOR 110 VAC OPERATION - OK
Building FACP NA
NA - Dry System
130 W. Kingsbridge
Detection Information
Customer
Contact
System Type
Notifications Central Station
Shutdowns
Gast Compressor
Direct to Class "E" panel - OK
Inspectors Test Valve @ Dock by tank storage cages in ceiling
System Location
Agent
City, State, Zip Bronx, NY 10468
Protected Area
Control Panel
Warehouse/Loading Dock