National Fire Protection Association (NFPA) Kitchen Fire Protection System Form 1 of 3
Report of Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Kitchen Systems
Inspector: SEMI-ANNUAL Inspection Date: December 28, 2022 Service Ticket #: 184334
Site: System Inspected: Area: Site Contact:
James J Peters VA Medical Center 130 West Kingsbridge Road, Bronx, NY, 10468
System # 66-079006 Type: Kitchen Panel:
Kitchen/Hood 1 Floor: Ground Building:
NOT_DISPLAY
Location of Kitchen Shunt Switch KPGEA breaker#4 by double doors
Date Fusible Links Replaced 12/28/2022 (2)360*. (1)Mechanical Pull Station
Renovation N/A
Recharge N/A
Fuel Shutdown
NO SHUNT TRIP SYSTEM INSTALLED
Electric YES
Gas YES
Last Hydro Test Date
How many tanks
Size of Tank 1 3 gallon
COOKING APPLIANCE LOCATIONS FROM LEFT TO RIGHT:
Stove Microwave. Conveyor toaster
Fryer N/A
Griddle N/A
All appliances properly covered w/ proper nozzles YES
Duct & plenum covered w/ correct nozzles YES
Check positioning of all nozzles YES
System installed in accordance w/mfg. UL listing YES
Hood.duct penetration sealed w/weld/UL device YES
Check if seals intact, evidence of tampering YES
Report of Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Kitchen Systems
Inspector: SEMI-ANNUAL Inspection Date: December 28, 2022 Service Ticket #: 184334
Site: System Inspected: Area: Site Contact:
James J Peters VA Medical Center 130 West Kingsbridge Road, Bronx, NY, 10468
System # 66-079007 Type: Kitchen Panel:
Kitchen/Hood 2 Floor: Ground Building:
NOT_DISPLAY
Location of Kitchen Shunt Switch KPGEA breaker #4 by double doors
Date Fusible Links Replaced 12/28/2022 (3)360. (1)Mechanical Pull Station
Renovation N/A
Recharge N/A
Fuel Shutdown N/A
Electric YES
Gas YES
Last Hydro Test Date
How many tanks
Size of Tank 1 3 gallon
COOKING APPLIANCE LOCATIONS FROM LEFT TO RIGHT:
Stove N/A
Fryer N/A
Griddle N/A
All appliances properly covered w/ proper nozzles YES
Duct & plenum covered w/ correct nozzles YES
Check positioning of all nozzles YES
System installed in accordance w/mfg. UL listing YES
Hood.duct penetration sealed w/weld/UL device YES
Check if seals intact, evidence of tampering YES
Report of Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Kitchen Systems
Inspector: SEMI-ANNUAL Inspection Date: December 28, 2022 Service Ticket #: 184334
Site: System Inspected: Area: Site Contact:
James J Peters VA Medical Center 130 West Kingsbridge Road, Bronx, NY, 10468
System # 66-079008 Type: Kitchen Panel:
Kitchen/Hood 3 Floor: Ground Building:
NOT_DISPLAY
Location of Kitchen Shunt Switch KPGEA breaker #4 by double doors
Date Fusible Links Replaced 12/28/2022 (3)360. (1)Mechanical Pull Station.
Renovation N/A
Recharge N/A
Fuel Shutdown
Electric YES
Gas YES
Last Hydro Test Date
How many tanks 4 (3)gallon
COOKING APPLIANCE LOCATIONS FROM LEFT TO RIGHT:
Stove Burner, Stove top
All appliances properly covered w/ proper nozzles YES
Duct & plenum covered w/ correct nozzles YES
Check positioning of all nozzles YES
System installed in accordance w/mfg. UL listing YES
Hood.duct penetration sealed w/weld/UL device YES
Check if seals intact, evidence of tampering YES
If system has been discharge, report same YES
Pressure gauge in proper range (if gauged) N/A
Check cartridge weight (if applicable) YES
Hydrostatic test date YES
6 years maintenance date YES
UNITED FIRE PROTECTION CORP.
Work Ticket Delivery Date: December 28, 2022 Ticket #: 184334.12282022
Account #: 66-07900
PO#
Scheduled by:
Site Name: James J Peters VA Medical Center
Address: 130 West Kingsbridge Road, Bronx, NY, 10468 Building
Site Contact:
Type of Call: Inspection
Work Tickets Notes: Call
Point of contact:
Scope of Work: Perform Semi Annual Kitchen inspection.
TO BE PERFORMED:
Site Act # Frequency Ctrl Panl
System Area Building Str# Str Fl City St
66-079006 Semi Annual
Kitchen Kitchen/ Hood 1
130 West Kingsbridge Road
Ground Bronx NY
66-079007 Semi Annual
Kitchen Kitchen/ Hood 2
130 West Kingsbridge Road
Ground Bronx NY
66-079008 Semi Annual
Kitchen Kitchen/ Hood 3
130 West Kingsbridge Road
Ground Bronx NY
Description of Work Performed:
Performed Semi-Annual Inspection and Maintenance of (3) Kitchen Systems Protecting Ground Level Kitchen Prep.
All Systems Left Normal and in Full Service.
Follow-up Required:
Kitchen Kitchen/Hood2 -Between 1st and 2nd Link Housing, conduit needs to be supported.
Kitchen Kitchen/Hood3 -Discharge Nozzle are not aligned with appliances.
Material Used:
Qty Make Model Description
NA
Technicians Actual Time for the Job: