Date: June 15, 2021
Tech:
NICET # 134121
FDNY # 87563169
Safe-Tech Inc. Phone:
Fax:
Address
Phone
Manufacturer
FM-200 HALON CO2 Inergen Dry Chem Water 2 x 12v 7 AH Load Test
24V 12V 110V Pneumatic Cable Battery
Start 10:00 AM Restore 11:30 AM Operator ID
VIA VIA
Fill: 75#
Hydro: Sep-17
Fill: 75#
Hydro: Sep-17
Fill: 75#
Hydro: Sep-17
Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments:
Zone 2 Type Photo Sm Sensativity 2.20% Activated Yes Comments:
Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments:
Zone 2 Type Photo Sm Sensativity 2.40% Activated Yes Comments:
Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments:
Zone 2 Type Photo Sm Sensativity 2.40% Activated Yes Comments:
Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments: Data Center Control Room underfloor
Zone 2 Type Photo Sm Sensativity 2.40% Activated Yes Comments: Data Center Control Room underfloor
Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments: Data Center Storage underfloor
Zone 2 Type Photo Sm Sensativity 2.40% Activated Yes Comments: Data Center Storage underfloor
Zone 3 Type MPS Serial No NA Sensativity NA Activated Yes Comments:
Zone 4 Type Abort Activated Yes Comments:
Zone ? Type Pressure Sw Serial No NA Sensativity NA Activated Yes Comments:
NAC Alarm 1 Bell 1st Alarm Comments:
Alarm 2 Horn/Strobe
3 Solenoid Comments:
Comments:
Comments:
Comments:
Date
Closet by IT Computer RmSystem Location
Agent
City, State, Zip Bronx, NY 10468
Protected Area
Control Panel
Ground Floor IT Computer Room
Aegis 2.0
130 W. Kingsbridge
Detection Information
Customer
Contact
System Type
Notifications Central Station
Shutdowns NA
Data Center underfloor
Data Center underfloor - near hallway side near corner
Comments:
Building FACP NA
Left 13.8 VDC/Mhos 112: Right 13.9 VDC/Mhos 70 NOT OK
Battery Backup
OK - 2 devices in separate dishcharge circuits
Alarm ONLY to Class "E" Panel
2 Installed - 10 Second Delay
Direct to building Class E - Trips Pre-Action System
SYSTEM TROUBLE is TIED IN TO "E"
Kidde
Fire Suppression Inspection Report
Signing Below will constitute acceptance of the Inspection & Fire Services Noted:
Comments: New Aegis 2.0 panel is properly installed, circuited and programmed operationally. CO2 pressure switch does activate the Pre-Action system.
Detector coverage is NOW APPROPRIATE considering contents. AC units MUST shut down (according to NFPA 13) on or prior to discharge.
Replace batteries ASAP.
James J. Peters VA Medical Center
2 Installed, provide timer hold & timer reset on release
Pn: Kidde 75# CO2
Data Center underfloor - near hallway side far corner
Sn: WF-005167 AB Empty: 148# Gross: Listed 223# Actual 223# - right cylinderLLI: NA
Customer Signature 6/15/2021
Printed Name
LLI: NA
Zone: 1 IT FLOOR
Sn: WF-005373 AB
Pressure: NA
Adjacent closetZone: 1 IT FLOOR Pressure: NA DOT: 3AA2300 Cylinder Location:
Pressure: NA
Pn: Kidde 75# CO2 Gross: Listed 221# Actual 220#
Adjacent closet
Gross: Listed 216# Actual 220# - left cylinder
Adjacent closet
LLI: NA
Cylinder Location:
Pn: Kidde 75# CO2
Zone: 1 IT FLOOR Cylinder Location:
System Sensor i3-2W
System Sensor i3-2W
System Sensor i3-2W
System Sensor i3-2W
CO2 Cylinder Information
6" Bells & Horn/Strobes are properly circuited and supervised
Empty: 145#
DOT: 3AA2300
Empty: 141#
DOT: 3AA2300
Sn: WF-005352 AB
Data Center underfloor
Data Center underfloor
Data Center underfloor
Pulsed on 2nd Alarm & Steady on Discharge
System Sensor i3-2W
System Sensor i3-2W
System Sensor i3-2W
System Sensor i3-2W
System Sensor i3-2W
System Sensor i3-2W