CO2 System Insp_Redacted.pdf

PDF 14 KB Posted

Attached to
H312--Fire Suppression and Sprinkler Services Federal contract opportunity
Solicitation number
36C24223Q0714
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

View the file

Other files for this federal contract opportunity

Other files attached to H312--Fire Suppression and Sprinkler Services, newest first.
File Type Posted
Ground Floor Kitchen_Redacted.pdf PDF
First Floor Kitchen_Redacted.pdf PDF
Dry Pipe Systems_Redacted.pdf PDF
Dry Chem Sys in Radioactive Storage_Redacted.pdf PDF
36C24223Q0714.docx DOCX document
WD 2015-4187 Rev. 24.pdf PDF
Pre Action Systems_Redacted.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date: June 15, 2021

Tech:

NICET # 134121

FDNY # 87563169

Safe-Tech Inc. Phone:

Fax:

Address

Phone

Manufacturer

FM-200 HALON CO2 Inergen Dry Chem Water 2 x 12v 7 AH Load Test

24V 12V 110V Pneumatic Cable Battery

Start 10:00 AM Restore 11:30 AM Operator ID

VIA VIA

Fill: 75#

Hydro: Sep-17

Fill: 75#

Hydro: Sep-17

Fill: 75#

Hydro: Sep-17

Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments:

Zone 2 Type Photo Sm Sensativity 2.20% Activated Yes Comments:

Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments:

Zone 2 Type Photo Sm Sensativity 2.40% Activated Yes Comments:

Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments:

Zone 2 Type Photo Sm Sensativity 2.40% Activated Yes Comments:

Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments: Data Center Control Room underfloor

Zone 2 Type Photo Sm Sensativity 2.40% Activated Yes Comments: Data Center Control Room underfloor

Zone 1 Type Photo Sm Sensativity 2.40% Activated Yes Comments: Data Center Storage underfloor

Zone 2 Type Photo Sm Sensativity 2.40% Activated Yes Comments: Data Center Storage underfloor

Zone 3 Type MPS Serial No NA Sensativity NA Activated Yes Comments:

Zone 4 Type Abort Activated Yes Comments:

Zone ? Type Pressure Sw Serial No NA Sensativity NA Activated Yes Comments:

NAC Alarm 1 Bell 1st Alarm Comments:

Alarm 2 Horn/Strobe

3 Solenoid Comments:

Comments:

Comments:

Comments:

Date

Closet by IT Computer RmSystem Location

Agent

City, State, Zip Bronx, NY 10468

Protected Area

Control Panel

Ground Floor IT Computer Room

Aegis 2.0

130 W. Kingsbridge

Detection Information

Customer

Contact

System Type

Notifications Central Station

Shutdowns NA

Data Center underfloor

Data Center underfloor - near hallway side near corner

Comments:

Building FACP NA

Left 13.8 VDC/Mhos 112: Right 13.9 VDC/Mhos 70 NOT OK

Battery Backup

OK - 2 devices in separate dishcharge circuits

Alarm ONLY to Class "E" Panel

2 Installed - 10 Second Delay

Direct to building Class E - Trips Pre-Action System

SYSTEM TROUBLE is TIED IN TO "E"

Kidde

Fire Suppression Inspection Report

Signing Below will constitute acceptance of the Inspection & Fire Services Noted:

Comments: New Aegis 2.0 panel is properly installed, circuited and programmed operationally. CO2 pressure switch does activate the Pre-Action system.

Detector coverage is NOW APPROPRIATE considering contents. AC units MUST shut down (according to NFPA 13) on or prior to discharge.

Replace batteries ASAP.

James J. Peters VA Medical Center

2 Installed, provide timer hold & timer reset on release

Pn: Kidde 75# CO2

Data Center underfloor - near hallway side far corner

Sn: WF-005167 AB Empty: 148# Gross: Listed 223# Actual 223# - right cylinderLLI: NA

Customer Signature 6/15/2021

Printed Name

LLI: NA

Zone: 1 IT FLOOR

Sn: WF-005373 AB

Pressure: NA

Adjacent closetZone: 1 IT FLOOR Pressure: NA DOT: 3AA2300 Cylinder Location:

Pressure: NA

Pn: Kidde 75# CO2 Gross: Listed 221# Actual 220#

Adjacent closet

Gross: Listed 216# Actual 220# - left cylinder

Adjacent closet

LLI: NA

Cylinder Location:

Pn: Kidde 75# CO2

Zone: 1 IT FLOOR Cylinder Location:

System Sensor i3-2W

System Sensor i3-2W

System Sensor i3-2W

System Sensor i3-2W

CO2 Cylinder Information

6" Bells & Horn/Strobes are properly circuited and supervised

Empty: 145#

DOT: 3AA2300

Empty: 141#

DOT: 3AA2300

Sn: WF-005352 AB

Data Center underfloor

Data Center underfloor

Data Center underfloor

Pulsed on 2nd Alarm & Steady on Discharge

System Sensor i3-2W

System Sensor i3-2W

System Sensor i3-2W

System Sensor i3-2W

System Sensor i3-2W

System Sensor i3-2W