National Fire Protection Association (NFPA) Kitchen Fire Protection System Form 1 of 3
Report of Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Kitchen Systems
Inspector: SEMI-ANNUAL Inspection Date: December 28, 2022 Service Ticket #: 184110
Site: System Inspected: Area: Site Contact:
James J Peters VA Medical Center 130 West Kingsbridge Road, Bronx, NY, 10468
System # 66-079001 Type: Kitchen Panel:
Kitchen/Hood 1 Floor: 1 Building:
NOT_DISPLAY
Location of Kitchen Shunt Switch Panel C by front serving line
Date Fusible Links Replaced 12/28/22 (6) 360degree. (1)Mechanical Pull Station
Renovation N/A
Recharge N/A
Fuel Shutdown yes
Electric YES
Gas YES
Last Hydro Test Date 2016 refilled after a system release-Tank manufactured in 2010
How many tanks
Size of Tank 1 3 gal
Size of Tank 2 3 gal
Size of Tank 3
NA
COOKING APPLIANCE LOCATIONS FROM LEFT TO RIGHT:
Stove Appliance
Fryer
NA
Griddle
NA
All appliances properly covered w/ proper nozzles
(2) New Pressure Cooker are NOT properly protected, (4)Discharge Nozzles need to be reconfigured to protected appliances.
NO
Duct & plenum covered w/ correct nozzles YES
Check positioning of all nozzles YES
System installed in accordance w/mfg. UL listing YES
Hood.duct penetration sealed w/weld/UL device YES
Check if seals intact, evidence of tampering YES
If system has been discharge, report same N/A
Pressure gauge in proper range (if gauged) N/A
Check cartridge weight (if applicable) YES
Hydrostatic test date YES
6 years maintenance date YES
Inspect cylinders and mount YES
Operate system from terminal link YES
Test for proper operation from remote YES
Check operation from micro switch YES
Check operation of gas valve YES
Clean nozzles YES
Proper nozzle covers in place YES
Check Fuse Links and clean YES
Replace fuse links YES
Check travel of cable nut/s hooks YES
Piping & Conduit securely bracketed YES
Proper separation between fryers & flame YES
Proper clearance flame to filters YES
Exhaust fan in operating order YES
All filters replaced N/A
Fuel shut-off in on position YES
Manual & remote set seals in place YES
Replace system covers N/A
System operational & seals in place YES
Slave system operational YES
Clean cylinder and mount YES
Fan warning sign on hood YES
Personnel instructed in manual operation YES
20 BC Extinguisher mounted YES
Portable extinguishers properly serviced YES
Service & Certification tag on system YES
Comments
Report of Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Kitchen Systems
Inspector: SEMI-ANNUAL Inspection Date: December 28, 2022 Service Ticket #: 184110
Site: System Inspected: Area: Site Contact:
James J Peters VA Medical Center 130 West Kingsbridge Road, Bronx, NY, 10468
System # 66-079002 Type: Kitchen Panel:
Kitchen/Hood 2 Floor: 1 Building:
NOT_DISPLAY
Location of Kitchen Shunt Switch Panel C by front serving line
Date Fusible Links Replaced 12/28/2022 (2)360degree. (1)Mechanical Pull Station
Renovation N/A
Recharge N/A
Fuel Shutdown gas shut down reset push buttons at system control panel
Electric YES
Gas YES
Last Hydro Test Date 2016 refilled after a system release-Tank manufactured in 2010
How many tanks
Size of Tank 1 3gal
Size of Tank 2 3gal
Size of Tank 3
NA
COOKING APPLIANCE LOCATIONS FROM LEFT TO RIGHT:
Stove Yes
Fryer
NA
Griddle
NA
All appliances properly covered w/ proper nozzles YES
System installed in accordance w/mfg. UL listing YES
Hood.duct penetration sealed w/weld/UL device YES
Check if seals intact, evidence of tampering YES
If system has been discharge, report same N/A
Pressure gauge in proper range (if gauged) N/A
Check cartridge weight (if applicable) YES
Hydrostatic test date YES
6 years maintenance date YES
Inspect cylinders and mount YES
Operate system from terminal link YES
Test for proper operation from remote YES
Check operation from micro switch YES
Check operation of gas valve YES
Clean nozzles YES
Proper nozzle covers in place YES
Check Fuse Links and clean YES
Replace fuse links YES
Check travel of cable nut/s hooks YES
Piping & Conduit securely bracketed YES
Proper separation between fryers & flame YES
Proper clearance flame to filters YES
Exhaust fan in operating order YES
All filters replaced N/A
Fuel shut-off in on position YES
Manual & remote set seals in place YES
Replace system covers N/A
System operational & seals in place YES
Slave system operational YES
Clean cylinder and mount YES
Fan warning sign on hood YES
Personnel instructed in manual operation YES
20 BC Extinguisher mounted YES
Portable extinguishers properly serviced YES
Report of Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Kitchen Systems
Inspector: SEMI-ANNUAL Inspection Date: December 28, 2022 Service Ticket #: 184110
Site: System Inspected: Area: Site Contact:
James J Peters VA Medical Center 130 West Kingsbridge Road, Bronx, NY, 10468
System # 66-079003 Type: Kitchen Panel:
Serving Line/Hood 3 Floor: 1 Building:
NOT_DISPLAY
Location of Kitchen Shunt Switch Panel C by front serving line
Date Fusible Links Replaced 12/28/2022 (4)360degree. (1)Mechanical Pull Station
Renovation N/A
Recharge N/A
Fuel Shutdown Gas shut off via pressure line piston reset location behind flat top stove
Electric YES
Gas YES
Last Hydro Test Date 2016 refilled after a system release-Tank manufactured in 2010
How many tanks
Size of Tank 1
3 GAL
Size of Tank 2
NA
Size of Tank 3
NA
COOKING APPLIANCE LOCATIONS FROM LEFT TO RIGHT:
Stove
NA
Fryer Yes
Griddle Yes
Hood.duct penetration sealed w/weld/UL device YES
Check if seals intact, evidence of tampering YES
If system has been discharge, report same N/A
Pressure gauge in proper range (if gauged) N/A
Check cartridge weight (if applicable) YES
Hydrostatic test date YES
6 years maintenance date YES
Inspect cylinders and mount YES
Operate system from terminal link YES
Test for proper operation from remote YES
Check operation from micro switch YES
Check operation of gas valve YES
Clean nozzles YES
Proper nozzle covers in place YES
Check Fuse Links and clean YES
Replace fuse links YES
Check travel of cable nut/s hooks YES
Piping & Conduit securely bracketed YES
Proper separation between fryers & flame YES
Proper clearance flame to filters YES
Exhaust fan in operating order YES
All filters replaced N/A
Fuel shut-off in on position YES
Manual & remote set seals in place YES
Replace system covers N/A
System operational & seals in place YES
Slave system operational YES
Clean cylinder and mount YES
Fan warning sign on hood YES
Personnel instructed in manual operation YES
20 BC Extinguisher mounted YES
Portable extinguishers properly serviced YES
Report of Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Kitchen Systems
Inspector: SEMI-ANNUAL Inspection Date: December 28, 2022 Service Ticket #: 184110
Site: System Inspected: Area: Site Contact:
James J Peters VA Medical Center 130 West Kingsbridge Road, Bronx, NY, 10468
System # 66-079004 Type: Kitchen Panel:
Serving Line/Hood 4 Floor: 1 Building:
NOT_DISPLAY
Location of Kitchen Shunt Switch Panel C by front serving line
Date Fusible Links Replaced 12/28/2022 (1)360degree. (1)Mechanical Pull Station
Renovation N/A
Recharge N/A
Fuel Shutdown
YES
Electric YES
Gas YES
Last Hydro Test Date 2016 refilled after a system release-Tank manufactured in 2010
How many tanks
Size of Tank 1
3 GAL
Size of Tank 2
NA
Size of Tank 3
NA
COOKING APPLIANCE LOCATIONS FROM LEFT TO RIGHT:
Stove Oven
Fryer
NA
Griddle
NA
Hood.duct penetration sealed w/weld/UL device YES
Check if seals intact, evidence of tampering YES
If system has been discharge, report same N/A
Pressure gauge in proper range (if gauged) N/A
Check cartridge weight (if applicable) YES
Hydrostatic test date YES
6 years maintenance date YES
Inspect cylinders and mount YES
Operate system from terminal link YES
Test for proper operation from remote YES
Check operation from micro switch YES
Check operation of gas valve YES
Clean nozzles YES
Proper nozzle covers in place YES
Check Fuse Links and clean YES
Replace fuse links YES
Check travel of cable nut/s hooks YES
Piping & Conduit securely bracketed YES
Proper separation between fryers & flame YES
Proper clearance flame to filters YES
Exhaust fan in operating order YES
All filters replaced N/A
Fuel shut-off in on position YES
Manual & remote set seals in place YES
Replace system covers N/A
System operational & seals in place YES
Slave system operational YES
Clean cylinder and mount YES
Fan warning sign on hood YES
Personnel instructed in manual operation YES
20 BC Extinguisher mounted YES
Portable extinguishers properly serviced YES
Report of Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Kitchen Systems
Inspector: SEMI-ANNUAL Inspection Date: December 28, 2022 Service Ticket #: 184110
Site: System Inspected: Area: Site Contact:
James J Peters VA Medical Center 130 West Kingsbridge Road, Bronx, NY, 10468
System # 66-079005 Type: Kitchen Panel:
Serving Line/Hood 5 Floor: 1 Building:
NOT_DISPLAY
Location of Kitchen Shunt Switch Panel C by front serving line
Date Fusible Links Replaced 12/28/2022 (1)360degree. (1)Mechanical Pull Station
Renovation N/A
Recharge N/A
Fuel Shutdown
YES
Electric YES
Gas YES
Last Hydro Test Date 2016 refilled after a system release-Tank manufactured in 2010
How many tanks
Size of Tank 1
3 GAL
Size of Tank 2
NA
Size of Tank 3
NA
COOKING APPLIANCE LOCATIONS FROM LEFT TO RIGHT:
Stove
NA
Fryer
NA
Griddle Yes
Hood.duct penetration sealed w/weld/UL device YES
Check if seals intact, evidence of tampering YES
If system has been discharge, report same N/A
Pressure gauge in proper range (if gauged) N/A
Check cartridge weight (if applicable) YES
Hydrostatic test date YES
6 years maintenance date YES
Inspect cylinders and mount YES
Operate system from terminal link YES
Test for proper operation from remote YES
Check operation from micro switch YES
Check operation of gas valve YES
Clean nozzles YES
Proper nozzle covers in place YES
Check Fuse Links and clean YES
Replace fuse links YES
Check travel of cable nut/s hooks YES
Piping & Conduit securely bracketed YES
Proper separation between fryers & flame YES
Proper clearance flame to filters YES
Exhaust fan in operating order YES
All filters replaced N/A
Fuel shut-off in on position YES
Manual & remote set seals in place YES
Replace system covers N/A
System operational & seals in place YES
Slave system operational YES
Clean cylinder and mount YES
Fan warning sign on hood YES
Personnel instructed in manual operation YES
20 BC Extinguisher mounted YES
Portable extinguishers properly serviced YES
UNITED FIRE PROTECTION CORP.
Work Ticket Delivery Date: December 28, 2022 Ticket #: 184110.12282022
Account #: 66-07900
PO#
Scheduled by:
Site Name: James J Peters VA Medical Center
Address: 130 West Kingsbridge Road, Bronx, NY, 10468 Building
Site Contact:
Type of Call: Inspection
Work Tickets Notes:
Scope of Work: Perform Semi Annual Kitchen inspection.
TO BE PERFORMED:
Site Act # Frequency Ctrl Panl
System Area Building Str# Str Fl City St
66-079001 Semi Annual Kitchen Kitchen/ Hood 1
130 West Kingsbridge Road
1 Bronx NY
66-079002 Semi Annual Kitchen Kitchen/ Hood 2
130 West Kingsbridge Road
1 Bronx NY
66-079003 Semi Annual Kitchen Serving Line/ Hood 3
130 West Kingsbridge Road
1 Bronx NY
66-079004 Semi Annual Kitchen Serving Line/ Hood 4
130 West Kingsbridge Road
1 Bronx NY
66-079005 Semi Annual Kitchen Serving Line/ Hood 5
130 West Kingsbridge Road
1 Bronx NY
Description of Work Performed:
Performed Annual Inspection and Maintenance of (5)Kitchen Systems Protection 1Flr Kitchen Prep. Area.
System Left Normal and in Full Service.
Follow-up Required:
Kitchen Hood Serving Line 2.
(2) New Pressure Cooker are NOT properly protected, (4)Discharge Nozzles need to be reconfigured to protected appliances.
Material Used:
Qty Make Model Description
NA