Confidential and Proprietary Information Contract # 5
JEFF - 180194 26 56 00-1
081314 Revised 09/12/14 EXTERIOR LIGHTING
SECTION 26 56 00 – EXTERIOR LIGHTING
GENERAL PART 1
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes
1. Exterior luminaires with associated light sources and electric components.
2. Poles and accessories
B. Related Sections
1. Division 26 Sections
2. Division 26 09 43 Networked Lighting Controls
1.3 DEFINITIONS
A. Luminaire: Complete lighting fixture, including housings, drivers, ballasts where required
B. Pole: Luminaire support structure provided by designated lighting product’s manufacturer
C. CCT: Correlated Color Temperature
D. CRI: Color Rendering Index
E. LER: Luminaire Efficacy Rating
F. LED: Light Emitting Diode
G. HID: High-Intensity Discharge
H. Lamp: Source within luminaire producing visible light (may be fluorescent, HID, or LED)
1.4 LIGHTING CONSULTANT
A. There is an independent lighting consultant and designer for this project, Randy Burkett Lighting Design, Inc., St. Louis, Missouri.
B. The consultant or contracting officer will review all final light fixture shop drawings.
JEFF - 180194 26 56 00-2
1.5 ACTION SUBMITTALS
A. Product Data: For each luminaire, lamp, pole, and support component, arranged in order of lighting unit designation as indicated on E-300 Lighting Fixture Schedule and herein, submit prior to order and installation. Include data on features, accessories, finishes, and the following:
1. Physical description of luminaire, including materials, dimensions, effective projected area, and verification of indicated parameters.
2. Details of attaching luminaires and accessories.
3. Details of installation and construction.
4. Luminaire materials.
5. Photometric data based on laboratory tests of each luminaire type, complete with indicated lamp, driver or ballast, and accessories as specified.
a. Testing Agent Certified Data: For indicated luminaires, photometric data shall be certified by a qualified independent testing agency. Photometric data for remaining luminaires shall be certified by manufacturer.
b. Manufacturer Certified Data: Photometric data shall be certified by manufacturer’s laboratory with a current accreditation under the National Voluntary Laboratory Accreditation Program for Energy Efficient Lighting Products.
6. Drivers, including energy-efficiency data.
7. Lamp including rated life, output, CCT, CRI, lumen output, center beam candlepower and beam angle where indicated, and energy-efficiency data.
8. Materials, dimensions, and finishes of poles and their mounting hardware.
9. Means of attaching luminaires to supports, and indication that attachment is suitable for components involved.
10. Base plates and anchor bolts for poles.
B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work.
1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
2. Anchor-bolt templates keyed to specific poles and structurally certified by manufacturer.
3. Where indicated, provide scaled composite drawing indicating pole, luminaire, pole base, and any other specified components such as receptacles.
4. For any luminaire utilizing a pole, manufacturer shall provide anchor bolt size, embedment length, and embedment calculations for each foundation type (see S111) required on project.
5. Wiring diagrams: for power, signal, and control wiring.
C. Mock-Ups: For products that are designated for mock-up sample review within the lighting fixture schedule and submittal schedule for Contract 5:
1. Contractor shall prepare and conduct an exterior nighttime lighting mock-up temporary in set-up, and available for viewing by the Contracting Owner for up to five (5) consecutive business days. Scope of work includes procurement and temporary installation of
JEFF - 180194 26 56 00-3
specified equipment as well as all ancillary materials necessary for a complete mockup of luminaire, exactly as specified.
2. Contractor shall coordinate mockup with landscape architecture details to provide accurate mounting and installation condition.
3. Contractor shall make modifications in mock-up installation as deemed necessary by Contracting Owner, to asses possible alterations in final mounting disposition.
1.6 INFORMATIONAL SUBMITTALS
A. Where indicated provide source quality-control test reports.
B. Where indicated provide field quality-control test reports.
1.7 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For luminaires and their various components and accessories, to include in emergency, operation, and maintenance manuals.
1. Manufacturers recommended installation and maintenance documents.
2. Any quality-control test results.
3. Copy of returned final, approved shop drawings.
4. Field condition wiring diagrams of control system.
5. Warranty documents, including certification of commencement date
6. List of manufacturer contact addresses and telephone numbers for each specified fixture.
1.8 COORDINATION
A. Coordinate exterior luminaires and their mounting with all applicable Contract Document details.
B. Refer to drawings for dimensions and details. Check and verify dimensions before proceeding with the Work. Clarify any discrepancies with the Contracting Officer. Should it appear that the Work intended to be described, is not sufficiently detailed or explained on the drawings or in these specifications, refer to Contracting Officer for further explanations.
C. Fixture locations as indicated on the electrical drawings are generalized and approximate.
Carefully verify locations with Contracting Officer plans and details and other reference data prior to installation.
D. Check for adequacy of headroom and non-interference with other equipment, such as pipes, conduit, or openings.
E. Bring non-standard modifications necessary to comply with the Contract Documents, and construction conflicts, to Contracting Officer’s attention before proceeding with Work.
F. Coordinate with other exterior trades with regard to mounting fixtures on project structures and bring any variance to Contracting Officer’s attention before proceeding with Work.
JEFF - 180194 26 56 00-4
1.9 DELIVERY, STORAGE, AND HANDLING
A. Package aluminum poles for shipping according to ASTM B 660.
B. Poles shall be supported to prevent any distortion.
C. Store all luminaires on decay-resistant-treated skids at least 12 inches above grade and vegetation.
D. Arrange to provide free air circulation ensuring fixtures are not stored in conditions outside of manufacturer’s recommendations.
1.10 WARRANTY
A. Special Warranty: Manufacturer’s standard form, which manufacturer agrees to repair or replace luminaire and or components of luminaires and lamps that fail in materials or workmanship;
corrode; or fade, stain, or chalk due to effects of weather or solar radiation within specified warranty period. Manufacturer may exclude lightning damage, hail damage, vandalism, abuse, or unauthorized repairs or alterations from special warrant coverage.
1. Warranty period for Luminaires: Three years from date of Substantial Completion
a. Warranty Period for Metal Corrosion: Five years from date of Substantial Completion
b. Warranty Period for Color Retention: Five years from date of Substantial Completion
c. Warranty Period for Poles: Repair or replace lighting poles and standards that fail in finish, materials, and workmanship within manufacturer’s standard warranty period, but not less than three years from date of Substantial completion.
d. Warranty Period for Lamps:
1) Replace any non-LED lamp and fuses that fail within 12 months from date of Substantial Completion; furnish replacement lamps and fuses that fail within the second 12 months from date of Substantial Completion.
2) Replace any LED lamp and its associated driver and electrical components that fail within five years from Substantial Completion.
3) Luminaires shall not be operated, other than to confirm operation for a period not to exceed 96 hours, prior to substantial completion point without acceptance from Owner.
2. Contractor responsible for notifying manufacturer of following:
a. Installation date
b. Date energized
c. Agree date of Substantial Completion with Owner.
PRODUCTS PART 2
2.1 GENERAL
JEFF - 180194 26 56 00-5
A. Luminaires must be the type designated as drawings and specifications herein indicate. Fixtures of the same type must be provided by one manufacturer.
B. Luminaire must be of the types and manufacturers described in the REQUIREMENTS FOR LUMINAIRES below, with light source, wattage, and voltage as indicated. With approval from the Contracting Officer, other manufacturers may be supplied if the submitted product meets or exceeds the specifications.
C. Substitution Limitations:
1. Listed equal manufacturers must provide a product that nominally matches physical dimensions while maintaining industrial design and equaling or bettering all performance aspects of luminaire specified including, but not limited to:
a. Distribution
b. Intensity
c. Efficacy
d. Color Rendering Index
e. CCT
f. Controllability attributes
2.2 REQUIREMENTS FOR LUMINAIRES
A. Luminaires shall comply with UL 1598 and be listed and labeled for installation in wet locations by an NRTL acceptable to authorities having jurisdiction.
1. All associated components of the fixture, including but not limited to drivers and remote power supplies, required for the operation of the luminaire shall be UL listed for its intended use.
B. Light Distribution Patterns: Comply with IESNA RP-8 for parameters of light distribution patterns indicated for luminaires, unless otherwise noted or specified for specific luminaire.
C. Metal Parts: free of burrs and sharp corners and edges.
D. Sheet Metal Components: Corrosion-resistant aluminum unless otherwise indicated. Form and support to prevent warping and sagging.
E. Housings: Rigidly formed, weather- and light-tight enclosures that will not warp, sag, or deform in use. Provide filter/breather for enclosed luminaires.
F. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under operation conditions, and designed to permit access to purpose with use of tamper-resistant hardware. Designed to prevent doors, frames, lenses, diffusers, and other components from falling accidentally during relamping and when secured in operating position. Doors shall be removable for cleaning or replacing lenses. Designed to disconnect ballast/driver when door opens.
G. Exposed Hardware Material: Stainless steel fasteners with matching stainless steel receiver to avoid galvanic corrosion.
JEFF - 180194 26 56 00-6
H. Plastic Parts: High resistance to yellowing and other changes due to aging, exposure to heat, and UV radiation.
1. Where used in optical elements, plastic shall be UV stabilized and pure acrylics.
I. Reflecting surfaces shall have minimum reflectance as follows unless otherwise indicated:
1. White: 85 percent
2. Specular: 83 percent
3. Diffusing Specular: 75 percent
J. Lens and Refractor Gaskets: Use single piece heat- and aging-resistant gaskets to seal and cushion lenses and refractors in luminaire doors.
K. Luminaire finish: Manufacturer’s standard paint applied to factory assembled and tested luminaire before shipping. Where indicated, match finish process and color of pole or support materials
L. Factory-Applied Finish for Aluminum Luminaires: Comply with NAAMM’s “Metal Finishes Manual for Contracting Officer and Metal Products” for recommendations for applying and designating finishes.
1. Finish designations prefixed by AA comply with the system established by the Aluminum Association for designating aluminum finishes.
2. Natural Satin Finish: Provide fine, directional, medium satin polish (AA-M32); buff complying with AA-M20; and seal aluminum surfaces with clear, hard-coat wax.
M. Factory-Applied Labels: Comply with UL 1598. Include recommended lamps and drivers/ballasts. Labels shall be located where they will be readily visible to service personnel, but not seen from normal viewing angles when lamps are in place.
1. Label shall include the following characteristics:
a. “USES ONLY” and include specific lamp type.
b. Lamp type, wattage, color temperature
1) For LEDs: provide unique identifier used to track diode manufacturer, chip style, efficacy, and manufacture date.
2) CCT and CRI for all luminaires.
N. All recessed fixtures shall be provided with appropriate housing for its mounting condition.
Check the fixture types against the approved Contracting Officer detail prior to submittal of Action Submittals.
O. Where light fixtures are specified to be furnished with aimable, adjustable or directional components, the exact location shall be obtained from the Contracting Officer/Engineer in writing prior to roughing in.
P. 80% of luminaire material by weight shall be recyclable at end of life.
Q. LED sources must be integrally designed elements to the luminaire meeting the following requirements:
JEFF - 180194 26 56 00-7
1. Rated for operation within luminaire between -40°C to +35°C
2. Where indicated in fixture specifications, CCT values shall meet the following criteria:
a. 3000K (3045 ± 175)
b. 4000K (3985 ± 275)
3. CRI shall be greater than 75
4. Where indicated or for any substitution, luminaire manufacturer must submit reliability reports from the manufacturer of the LED (chip, diode, or package) has performed JEDEC (Joint Electron Devices Engineering Council) tests of the following aspects:
a. High Temperature Operating Life
b. Room Temperature Operating Life
c. Low Temperature Operating Life
d. Powered Temperature Cycle
e. Non-Operating Thermal Shock
f. Variable Vibration Frequency
R. Driver Requirements
1. Minimum efficiency: 85%
2. Must be rated to operate between -40°C to +35°C
3. Input Voltage: 277V unless indicated
4. Operating frequency must be 50/60 Hz
5. Power Factor of: ≥0.90
6. Total Harmonic Distortion (THD): ≤20%
7. Comply with FCC 47 CFR part 15 Non-Consumer RFI/EMI standards
2.3 GENERAL REQUIREMENTS FOR POLES AND SUPPORT COMPONENTS
A. Structural Characteristics: Comply with AASHTO LTS-4-M
1. Wind-Load Strength of Poles: Adequate at indicated heights above grade without failure, permanent deflection, or whipping with a wind speed zone of 90 MPH.
B. Luminaire Attachment Provisions: Comply with luminaire manufacturers’ mounting requirements. Use stainless-steel fasteners and mounting bolts that match manufacturer’s recommendations, unless otherwise indicated.
C. Mounting, Fasteners, and Appurtenances for Pole: Corrosion-resistant items compatible with support components:
1. Materials: Shall not cause galvanic action at contact points.
2. Anchor bolts, Leveling Nuts, Bolt Caps, and Washers: Hot-dip galvanized after fabrication unless otherwise indicated.
3. Anchor-Bolt Template: Plywood or steel
JEFF - 180194 26 56 00-8
D. Handhole: Cast aluminum oval-shaped reinforcement frame, with minimum clear opening of 2- 1/2 by 4 inches, with cover secured by stainless-steel captive screws.
2.4 POLE ACCESSORIES
A. Base Covers: Manufacturers’ standard metal units, arranged to cover pole’s mounting bolts and nuts. Finish same as pole.
B. Collar: Provide where specified and detailed in cutsheets or shop drawings.
2.5 FIXTURES
A. F1 – Glass globe with guard for general illumination located within equipment vaults. (Contractor Procured and Installed)
1. Construction: Luminaire shall be designed to support a LED source as a wet location listed fixture. Housing shall be a non-metallic body supporting a glass globe with a guard.
All elements shall be enclosed within luminaire guard and globe with molded ‘U-channel’ silicone gaskets as required.
2. Electrical: Provide with driver rated for a minimum of 50,000 hours operation at 277V.
15 watt maximum.
3. Certification: Listed for wet locations per 2.2.A.
4. Mounting: Provide installation details and equipment to match electrical details 5/E201 and 6/E201.
5. Source and Optics: Minimum of 40 lumens/watt at 80 CRI or better. Provide at 4000K.
6. Distribution: N/A
7. Light Source Rating: LM70/B50 of 60,000
8. Minimum Dimensions
a. H: 8.5”
b. DIA: 5.0”
9. Product:
a. Lithonia Lighting OLVTCM-4000K-MVOLT-Grey
b. Hubbell Lighting VNGL-1
c. DAC D8012-LED8-277-MG-WET
B. SA – Single head, pole mounted full cutoff pedestrian LED area light for use in illumination of pathways and plazas. (Following fixture will be provided by the Government, FOB Job Site)
1. Construction: Luminaire shall be designed as an integral design element within same shape and profile as pole. Housing shall be fabricated from aluminum with no visible welds. Wall thickness shall be no less than 3/16” treated to produce a T6 temper. Provide with flush hand-hole and include tamper-resistant locking device. All hardware shall be stainless steel with matching inserts to prevent galvanizing components. Two piece fabricated aluminum base cover. Luminaire design shall be in the shape of inverted ‘L’ with the projecting arm to be installed perpendicular to the path.
JEFF - 180194 26 56 00-9
2. Electrical: Provide with driver rated for a minimum of 50,000 hours operation capable of supporting DALI control protocol. Luminaire shall operate as a single device within control loop. 60 watt maximum.
3. Certification: Listed for wet locations per 2.2.A.
4. Mounting: Provide wood anchor bolt template. Anchor bolts shall be sized by manufacturer to meet necessary requirements of pole design and structural foundation details on drawing S111. Anchor bolt plate shall be no larger than 11.81” square with a nominal bolt circle of 7.87”. Anchor bolts shall be at 90° increments located in corners of bolt plate. Two piece fabricated aluminum base cover to encapsulate anchor bolt plate with minimal spacing possible.
5. Source and Optics: Minimum of 40 system lumens/watt at 75 CRI or better. Provide with 4000K field replaceable aluminum core LED module. Prismatic lens shall be of molded optical quality US stabilized acrylic single piece prismatic lens.
6. Distribution: ANSI Type III
7. Light Source Life Rating: LM70/B50 of 60,000
8. Dimensions:
a. H: 177.6”
b. L: 43.7”
c. W: 7.5”
d. D: 4.1”
9. Product:
a. Hess America LN450/2LV-2/N-ME-UNVMOD/A/15SRA/xx(FINISH)
C. SA-R – Single head, pole mounted full cutoff pedestrian LED area light for use in illumination of pathways and plazas with integral convenience receptacle. Fixtures identified per E300 lighting fixture schedule; only responsible for quantity within contract boundary per L100 layout series and E100 series drawings. (Following fixture will be provided by the Government, FOB Job Site)
1. Construction: Luminaire shall be designed as an integral design element within same shape and profile as pole. Housing shall be fabricated from aluminum with no visible welds. Wall thickness shall be no less than 3/16” treated to produce a T6 temper. Provide with flush hand-hole and include tamper-resistant locking device. All hardware shall be stainless steel with matching inserts to prevent galvanizing components. Two piece fabricated aluminum base cover. Luminaire design shall be in the shape of inverted ‘L’ with the projecting arm to be installed perpendicular to the path.
2. Electrical: Provide with driver rated for a minimum of 50,000 hours operation capable of supporting DALI control protocol. Luminaire shall operate as a single device within control loop. 60 watt maximum. Provide with integral 120V duplex convenience receptacle.
3. Certification: Listed for wet locations per 2.2.A.
4. Mounting: Provide wood anchor bolt template. Anchor bolts shall be sized by manufacturer to meet necessary requirements of pole design and structural foundation details on drawing S111. Anchor bolt plate shall be no larger than 11.81” square with a nominal bolt circle of 7.87”. Anchor bolts shall be at 90° increments located in corners of
JEFF - 180194 26 56 00-10
bolt plate. Two piece fabricated aluminum base cover to encapsulate anchor bolt plate with minimal spacing possible.
5. Source and Optics: Minimum of 40 system lumens/watt at 75 CRI or better. Provide with 4000K field replaceable aluminum core LED module. Prismatic lens shall be of molded optical quality US stabilized acrylic single piece prismatic lens.
6. Distribution: ANSI Type III
7. Light Source Life Rating: LM70/B50 of 60,000
8. Dimensions:
a. H: 177.6”
b. L: 43.7”
c. W: 7.5”
d. D: 4.1”
9. Product:
a. Hess America LN450/2LV-2/N-ME-UNVMOD/A/15SRA/xx(FINISH)/MODREC
D. SB-1 – Adjustable accent light with precision optic system with field interchangeable distribution lenses. Luminaire shall allow for vertical surface mounting and surface conduit power feeds.
(Contractor Procured and Installed)
1. Construction:
a. Fixture – Main exterior components including housing, hinge, cover, and mounting bracket shall be corrosion-resistant, cast aluminum with a two layer powder-coat finish selected from manufacturer’s standard finishes or a RAL color during submittals. Hinge shall provide 130° tilt at a minimum with a stainless steel graduated disc. Cover glass shall be optically clear safety glass and cover shall be secured by screw without spill light. All hardware shall be stainless steel with matching inserts to prevent galvanizing components. Finish shall be selected from manufacturer’s standard finishes or a RAL color during submittals. Any louver or snoot specified or indicated within fixture construction shall be integral to luminaire.
2. Electrical: Luminaire shall be supplied with driver operating at 277V and support through-wiring. All wiring shall be internal to the luminaire – no visible wiring. Total wattage per luminaire shall be no more than 50W.
3. Certification:
a. Fixture - Listed for wet locations per 2.2.A. Minimum IP65 rating.
b. Pole – wind load report for support of specified fixture
4. Mounting:
a. Fixtures - Luminaire shall be provided with mounting sleeve of same construction and finish as luminaire designed for purpose and detailed as integral element.
Mounting sleeve shall allow for 360° of rotation by luminaire. Contractor shall utilize spacer to allow surface mounted conduit to extend beyond fixtures mounting plate. Spacer and fixture shall be mounted to vertical face with M10 threaded rod per manufacturers’ installation recommendations and architectural details within drawing set. Install fixture and associated components per manufacturer’s installation instructions using tamper-proof screws were possible.
JEFF - 180194 26 56 00-11
5. Source and Optics: Minimum of 90 lumens/watt at 4000K with a CRI of 80 or better.
Diodes shall be mounted to metal-core PCB with surge protection. Luminaire shall utilize a projection based optical system including collimating and separate distribution lenses made of optical polymer. Distribution lens shall be installed recessed within luminaire housing from outer safety glass in such a manner to allow 360° rotation and be field interchangeable.
6. Distribution: Spot, 16°; Centerbeam Candlepower minimum of 35,000 candela
7. Light Source Life Rating: LM70/B10 of 50,000
8. Dimensions (Fixture):
a. H: 13.25”
b. L: 13.75”
c. DIA: 8.75”
d. Weight: 32.0lbs maximum
e. EPA maximum: 1.0ft²
9. Product:
a. Fixture
1) ERCO 34413.099/34991.099
2) ERCO 34503.099/34990.099
3) Lumenpulse LBL-277-40K-NF-CC-NO-MOD/Bracket//LBL-SN-CC-BK
E. SB-2 – Adjustable accent light with precision optic system with field interchangeable distribution lenses. Luminaire shall allow for pole mounting using manufacturer provided integral pole adaptor rated as UL wiring device matching fixture base and finish. (Contractor Procured and Installed)
1. Construction:
a. Fixture – Main exterior components including housing, hinge, cover, and mounting bracket shall be corrosion-resistant, cast aluminum with a two layer powder-coat finish selected from manufacturer’s standard finishes or a RAL color during submittals. Hinge shall provide 130° tilt at a minimum with a stainless steel graduated disc. Cover glass shall be optically clear safety glass and cover shall be secured by screw without spill light. All hardware shall be stainless steel with matching inserts to prevent galvanizing components. Finish shall be selected from manufacturer’s standard finishes or a RAL color during submittals. Any louver or snoot specified or indicated within fixture construction shall be integral to luminaire.
2. Electrical: Luminaire shall be supplied with driver operating at 277V and support through-wiring. All wiring shall be internal to the luminaire – no visible wiring. Total wattage per luminaire shall be no more than 50W.
3. Certification:
a. Fixture - Listed for wet locations per 2.2.A. Minimum IP65 rating.
b. Pole – wind load report for support of specified fixture
4. Mounting:
a. Fixtures - Luminaire shall be provided with mounting sleeve of same construction and finish as luminaire designed for purpose and detailed as integral element.
JEFF - 180194 26 56 00-12
Mounting sleeve shall allow for 360° of rotation by luminaire. Install fixture to sleeve and sleeve to pole per manufacturer’s installation instructions using tamper-proof screws were possible.
5. Source and Optics: Minimum of 90 lumens/watt at 4000K with a CRI of 80 or better.
Diodes shall be mounted to metal-core PCB with surge protection. Luminaire shall utilize a projection based optical system including collimating and separate distribution lenses made of optical polymer. Distribution lens shall be installed recessed within luminaire housing from outer safety glass in such a manner to allow 360° rotation and be field interchangeable.
6. Distribution: Spot, 16°; Centerbeam Candlepower minimum of 35,000 candela
7. Light Source Life Rating: LM70/B10 of 50,000
8. Dimensions (Fixture):
a. H: 13.25”
b. L: 13.75”
c. DIA: 8.75”
d. Weight: 32.0lbs maximum
e. EPA maximum: 1.0ft²
9. Product:
a. Fixture
1) ERCO 34463.099/34961.099
2) ERCO 34544.099/34961.099
3) Lumenpulse LBL-277-40K-NF-CC-NO-MOD/Bracket//LBL-SN-CC-BK
F. SB – Direct-burial, adjustable LED accent floodlight for uplight illumination of flag with slip reduction lens treatment installed to be flush at lens in architectural pre-cast plinth.
1. Construction: Single piece, water tight housing of both optical assembly and driver;
external drivers will not be acceptable. Housing shall allow for adjustment of optic assembly to provide both rotation and tilt to light beam. Interior of housing and components shall be finished matte black to reduce glare and fixture brightness; LED fixtures utilizing a reflector shall not be accepted. Fixtures locating the optical assembly within top 1/3rd of fixture housing shall include honeycomb louver to reduce surface brightness. Housing and safety glass shall be installed such that the fixture is flush with finished architectural surface. Trim ring shall be corrosion resistant stainless steel, secured to housing with tamper-proof, captive screws. Fasteners shall be such that they prevent galvanizing to either housing or rim ring. Safety glass shall be treated to reduce slip without distorting optical distribution by more than 10%. Maximum cover glass temperature shall be 100°F.
2. Electrical: Luminaire shall be supplied with a driver operating at 277V and minimum 30” AWG14, factory installed leader cable allowing for external connection to electrical service. Fixtures will not be accepted that utilize interior wiring chambers. Contractor shall be responsible for providing and ensuring electrical connection outside fixture in waterproof. Total wattage of fixture shall no exceed 45W.
3. Certification: Listed for wet locations per 2.2.A. Minimum IP67 rating.
JEFF - 180194 26 56 00-13
4. Mounting: Fixture shall be installed in concrete plinth according to project details and within manufacturer guidelines. Utilize standard factory recessed, concrete pour housing where necessary to ensure proper installation.
5. Source and Optics: Minimum of 90 lumens/watt at 4000K with a CRI of 80 or better.
Diodes shall be mounted to metal-core PCB with surge protection. Luminaire shall utilize a projection based optical system including collimating and separate distribution lenses made of optical polymer. Distribution lens shall be installed recessed within luminaire housing from outer safety glass in such a manner to allow 360° rotation and field adjustment of tilt up to 20°. Optical cut-off shall be 40° from horizontal.
6. Distribution: Spot, 15°; Centerbeam Candlepower minimum of 16,000 candela
7. Light Source Life Rating: L70/B10 50,000 minimum
8. Dimensions (product only):
a. D: 9-3/4” nominal
b. DIA: 11-1/2” maximum at surface including trim ring
9. Product:
a. ERCO 33640.099/33968.000/SRLens
b. Kim LTV81SS/SP/36L/4K/UV/SR/HL/RCA81/MOD
c. Hydrel M9720/SS/18LED/WHT30K/MVOLT/MFL/FLC20SR/MOD/IHL
G. SG – Straight aluminum pole with mounting collar for attachment of (3) adjustable LED floodlights. (Following fixture will be provided by the Government, FOB Job Site)
1. Construction:
a. Fixture – Main exterior components including housing, hinge, cover, and mounting bracket shall be corrosion-resistant, cast aluminum with a two layer powder-coat finish selected from manufacturer’s standard finishes or a RAL color during submittals. Hinge shall provide 130° tilt at a minimum with a stainless steel graduated disc. Cover glass shall be optically clear safety glass and cover shall be secured by screw without spill light. All hardware shall be stainless steel with matching inserts to prevent galvanizing components. Finish shall be selected from manufacturer’s standard finishes or a RAL color during submittals.
b. Pole – Shaft shall be 5” in diameter, extruded from seamless aluminum and heat treated to a T6 tamper. Anchor base shall be cast from aluminum and welded to shaft with similar heat treatment to T6 temper. Provide with flush hand-hole and include tamper-resistant locking device. Luminaire collar shall be of same material and construction as shaft, 7” in diameter and 8” tall secured by weld prior to finishing allowing. Provide 4” from top of collar to top of pole. Anchor base shall be cast aluminum and welded to shaft. Collar shall be spun aluminum no larger than 11” in diameter and 5” tall. Finish shall be selected from manufacturer’s standard finishes or a RAL color during submittals to match fixture finish. Pole manufacturer shall be responsible for coordinating final collar and fixture fit prior to delivery.
2. Electrical: Luminaire shall be supplied with driver operating at 277V and support through-wiring. All wiring shall be internal to the luminaire – no visible wiring.
3. Certification:
a. Fixture - Listed for wet locations per 2.2.A. Minimum IP65 rating.
JEFF - 180194 26 56 00-14
4. Mounting:
a. Fixtures - (3) luminaires to be mounted at 90° of each other on pole collar.
Luminaires shall be provided with mounting sleeve of same construction and finish as luminaire designed for purpose and detailed as integral element. Mounting sleeve shall allow for 360° of rotation by luminaire.
b. Pole: Provide wood anchor bolt template. Anchor bolts shall be sized by manufacturer to meet necessary requirements of pole design and structural foundation details on drawing S111. Anchor bolt plate shall be triangular in shape allowing nominal bolt circle of 7-3/8” minimum and 8-1/2” maximum. Anchor bolts shall be at 120° increments. Two piece fabricated aluminum base cover to encapsulate anchor bolt plate with minimal spacing possible.
5. Source and Optics: Minimum of 90 lumens/watt at 4000K with a CRI of 80 or better.
Diodes shall be mounted to metal-core PCB with surge protection. Luminaire shall utilize a projection based optical system including collimating and separate distribution lenses made of optical polymer. Distribution lens shall be installed recessed within luminaire housing from outer safety glass in such a manner to allow 360° rotation and be field interchangeable. In addition to base specification, luminaire shall be provided with following distribution lenses: Wide Flood, Oval Flood.
6. Distribution: Flood, 29°; Center Beam Candlepower minimum of 2800 candela.
7. Light Source Life Rating: LM70/B10 of 50,000
8. Dimensions (Fixture):
a. H: 7.6”
b. L: 8.3”
c. DIA: 5.3”
d. Weight: 8.5lbs maximum
e. EPA maximum: 0.4ft²
9. Dimensions (Pole):
a. H: 144.0”
b. DIA: 5.0”
c. Collar DIA: 7.0”
d. Collar H: 8.0”
10. Product:
a. Fixture
1) ERCO 34475.099/34957.023 (.099-provide FL, WF and OF lenses)
b. Pole
1) Valmont 1000-50-50-5-S-3-MODCollar-xx(FINISH)
EXECUTION PART 3
3.1 LUMINAIRE INSTALLATION
A. Fasten luminaire to indicated structural supports.
JEFF - 180194 26 56 00-15
1. Use fastening methods and materials selected to resist seismic forces defined for the application and approved for by manufacturer.
B. Where Work of this section is to be flush or concealed, install so that it does not project beyond the finished lines of the surface into which the fixture is installed, unless otherwise designated.
C. Where indicated for fixtures installed recessed flush within wall construction, Contractor shall verify and supply all necessary mounting and installation hardware required to ensure a safe, secure, code compliant application.
1. If necessary, Contractor shall pre-order back boxes for fixture to be installed prior to arrival of optical/lamp assembly, in order to avoid compromises in schedule or damage to finished luminaire surfaces.
D. Lenses, Louvers, and Reflectors:
1. Wear special gloves, as approved by the fixture manufacturer, to preclude smudging or damaging the reflector surface when installing fixtures and lamps in fixtures with specular reflector material.
2. Install louvers and glare shields in place after the project is complete and dust free or provide with protective cover over louvers, UL listed for temporary lighting. Upon completion of Work, remove cover with special gloves indicated above.
E. Accessibility
1. Install equipment such as junction and pull boxes, fixture housing, transformers, ballasts, drivers, controls, and other apparatus that requires occasional maintenance, to be accessible and appropriate for mounting.
3.2 POLE INSTALLATION
A. Alignment: Align pole foundations and poles for optimum directional alignment of luminaires and their mounting provisions of the pole.
1. See Landscape Detail Drawings for additional direction and guidance.
B. Foundation-Mounted Poles: Mount pole with leveling nuts, and tighten top nuts to torque level recommended by pole manufacturer.
1. Use anchor bolts and nut selected to resist seismic forces defined for the application and approved by manufacturer.
2. Grout void between pole base and foundation. Use no-shrink or expanding concrete grout firmly packed to fill space.
3. Install base covers unless otherwise indicated.
4. Use a short length of ½ inch-diameter pipe to make a drain hole through grout. Arrange to drain condensation from interior of pole.
5. Refer to structural drawings for specifications for further installation requirements.
3.3 CORROSION PREVENTION
JEFF - 180194 26 56 00-16
A. Aluminum: Do not use in contact with earth or concrete. When in direct contact with a dissimilar metal or material, protect aluminum by insulation fittings or treatment.
B. Steel Conduits: Comply with applicable Division 26 section. In concrete foundations, wrap conduit with 0.010 inch thick, pipe wrapping plastic tape applied with a 50 percent overlap.
3.4 GROUNDING
A. Ground metal poles and support structures according to applicable Division 26 Section.
1. Install grounding electrode for each pole unless otherwise indicated.
2. Install grounding conductor pigtail in the base for connecting luminaire to grounding system.
B. Ground nonmetallic poles and support structures according to applicable Division 26 Section.
1. Install grounding electrode for each pole.
2. Install grounding conductor and conductor protector.
3. Ground metallic components of pole accessories and foundations.
3.5 FIELD QUALITY CONTROL
A. Execution requirements: Testing, Adjusting, and Focusing: refer to Projects General Conditions and Lighting Fixture Schedule.
B. Inspect each installed fixture for damage. Replace damaged fixtures and components to the satisfaction of the Contracting Officer.
C. Operate each luminaire after installation and connection for a period not to exceed 96 hours.
Inspect connections after operation.
D. If luminaires are believed to be underperforming in early life, the Site Owner may choose to take field measurements between 2,000 and 3,000 operating hours of the completion of installation to confirm that lighting levels are in accordance with the projected levels. If average light levels are more than 15% below the Day 1 submittal, and the luminaire locations in the field are as designed, the luminaire manufacturer must provide replacement luminaires for those tested.
3.6 AIMING AND FOCUSING
A. Contractor shall be responsible for final targeting/focusing of adjustable light fixtures under the observation of, and according to, the recommendations of the Contracting Officer or Lighting Designer. Aiming shall take place after dark at a mutually agreed upon time, after all relevant amenities’ have been installed.
B. All necessary equipment to complete aiming and focusing work including ladders, lifts, and personnel shall be supplied by the Contractor.
JEFF - 180194 26 56 00-17
C. Where made necessary by site conditions, Contractor shall provide surface protection for surrounding materials to protect from potential damage caused by the use of any lifts and related equipment used during the final lighting adjustments.
3.7 CLEANING
A. Execution Requirements: Final Cleaning (Refer to Project’s General Conditions)
B. Remove dirt and debris from enclosures.
3.8 PROTECTION OF FINISHED WORK
A. Execution Requirements: Protecting Finished Work (Refer to Project’s General Conditions).
END OF SECTION