This document provides details on a federal contract opportunity to renovate Building 15 at a Veterans Affairs medical center. The solicitation number is 36C25522R0046_1 to renovate Building 15, Project # 657A-18-111, as issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. Bids are due by April 21, 2021 according to the related drawing set file. Renovation services are required to upgrade Building 15 at a Veterans Affairs medical facility.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDEX OF DRAWINGS
# SHT # TITLE
COVER SHEET
1 X-001 COVER SHEET & INDEX OF DRAWINGS
GENERAL INFORMATION
G-001 G-002
GENERAL NOTES, ABBREVIATIONS & SYMBOLS
WALL TYPES & PARTITION DETAILS
LIFE-SAFTY & CODE REVIEW
15-GI101
15-GI102
LIFE-SAFETY & CODE REVIEW PLAN
LIFE-SAFETY & CODE REVIEW
15-1-HA001
15-1-HA101
15-1-HA102
15-1-HA103
GENERAL ASBESTOS ABATEMENT NOTES
LEAD MATERIAL LOCATIONS
ASBESTOS MATERIAL LOCATIONS
TSI LOCATIONS
STRUCTURAL
15-S-001 15-S-101 15-S-101A 15-S-102
STRUCTURAL GENERAL NOTES
FLOOR DEMOLITION AND LEVELING PLANS - BASE BID
FLOOR DEMOLITION AND LEVELING PLANS - DEDUCT ALTERNATE #5
ROOF FRAMING PLAN & DETAILS
ARCHITECTURAL
14 15-AS101 ARCHITECTURAL SITE PLAN - DEMOLITION & RENOVATION
15 15-AD101 FLOOR PLAN - DEMOLITION
16 15-AD102 REFLECTED CEILING PLAN - DEMOLITION
17 15-AD103 ROOF PLANS - DEMOLITION & RENOVATION
18 15-AD201 ELEVATIONS & BUILDING SECTIONS - DEMOLITION
19 15-AD301 WALL SECTIONS - DEMOLITION
20 15-AE101 FLOOR PLAN - RENOVATION
21 15-AE201 ELEVATIONS & BUILDING SECTIONS - RENOVATION
22 15-AE301 WALL SECTIONS - RENOVATION
23 15-AE501 ARCHITECTURAL DETAILS
24 15-AE502 ARCHITECTURAL DETAILS - ROOF & LADDER
25 15-AE503 INTERIOR DETAILS
26 15-AE601 ROOM FINISH SCHEDULE & COLOR SCHEDULE
27 15-AE701 DOOR & FRAME SCHEDULES & DETAILS
28 15-AE702 WINDOW SCHEDULE & DETAILS
29 15-AE901 INTERIOR ELEVATIONS
30 15-AE902 INTERIOR ELEVATIONS
31 15-AC101 REFLECTED CEILING PLAN & DETAILS - RENOVATION
32 15-AF101 FINISH & SIGNAGE PLAN - RENOVATION
33 15-AF601 SIGNAGE SCHEDUILE & DETAILS
34 15-QE101 FURNITURE & EQUIPMENT PLAN - RENOVATION
35 15-QE601 FURNITURE & EQUIPMENT SCHEDULE - RENOVATION
REFERENCE
36 15-RA701 EXISTING EXTERIOR CONDITIONS
37 15-RA702 EXISTING INTERIOR CONDITIONS
38 15-RA703 EXISTING INTERIOR CONDITIONS
FIRE PROTECTION
39 15-FP001 FIRE PROTECTION COVER SHEET
40 15-FD101 FIRST FLOOR PLAN - FIRE PROTECTION DEMOLITION
41 15-FP101 FIRST FLOOR PLAN - FIRE PROTECTION
PLUMBING
42 15-P-001 PLUMBING COVER SHEET
43 15-PD100 FIRST FLOOR PLAN - PLUMBING UNDERFLOOR DEMOLITION
44 15-PD101 FIRST FLOOR PLAN - PLUMBING DEMOLITION
45 15-PD102 ROOF PLAN - PLUMBING DEMOLITION
46 15-PL100 FIRST FLOOR PLAN - PLUMBING UNDERFLOOR
47 15-PL101 FIRST FLOOR PLAN - PLUMBING
48 15-PL102 ROOF PLAN - PLUMBING
HVAC
49 15-M-001 HVAC COVER SHEET
50 15-MD101 FIRST FLOOR PLAN - HVAC DEMOLITION
51 15-MD102 ROOF PLAN - HVAC DEMOLITION
52 15-MH101 FIRST FLOOR PLAN - HVAC
53 15-MH102 ROOF PLAN - HVAC
54 15-MH300 HVAC DETAILS
55 15-MH400 HVAC CONTROLS
56 15-MH500 HVAC SCHEDULES
ELECTRICAL
57 15-E-000 ELECTRICAL COVER SHEET
58 15-E-001 ELECTRICAL COVER SHEET
59 15-ED101 FIRST FLOOR PLAN - ELECTRICAL DEMOLITION
60 15-EL101 FIRST FLOOR PLAN - ELECTRICAL LIGHTING
61 15-EP101 FIRST FLOOR PLAN - ELECTRICAL POWER
62 15-EP102 ROOF PLAN - ELECTRICAL POWER
63 15-ES101 FIRST FLOOR PLAN - ELECTRICAL SYSTEMS
64 15-E-300 ELECTRICAL DETAILS
65 15-E-400 ONE-LINE DIAGRAM
66 15-E-500 ELECTRICAL SCHEDULES
TECHNOLOGY
67 15-T-000 TECHNOLOGY COVER SHEET
68 15-TD101 FIRST FLOOR PLAN - TECHNOLOGY DEMOLITION
69 15-T-101 FIRST FLOOR PLAN - TECHNOLOGY
70 15-T-200 TECHNOLOGY ENLARGEMENTS
71 15-T-300 TECHNOLOGY DETAILS
72 15-T-400 TECHNOLOGY DIAGRAMS
73 15-T-500 TECHNOLOGY SCHEDULES
HAZARDOUS MATERIAL
2401 West Main St., Marion, IL 62959
CONTRACTOR STAGING-
COORDINATE
CONTRACTOR PARKING
PERMITS, BADGING AND
ENTERANCE POINTS W/
COR AND CAMPUS POLICE
BLDG 15 - ENGINEERING
BLDG 14 - BOILER PLANT
BLDG 1 - MAIN HOSPITAL
CAMPUS EAST
ENTRANCE
NOTE:
OBTAIN MOST CURRENT
CAMPUS PLAN FROM COR
PARKING LOT
BLDG 16
BLDG 1
BLDG 14
BLDG 15
MAIN PUBLIC
ENTRANCE
BLDG 16 - WAREHOUSE/
RECEIVING BUILDING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 POC:
AH. INZ
6910 Pacific St #310
Omaha, NE 68106
Phone: 402.553.0234 POC:
IMEG Corp.
2882 106th Street
Des Moines, Iowa
Phone: 515.334.4303
POC:
AMI Enviromental
8802 S 135th Street
Omaha, NE 68138
Phone: 402.397.5001
POC:
BID SET
07/17/2019
Dwg. Of
C
L H
D C
\H o m e \t fi e s e lm a n
\R e v it
M o d e ls \R
-2
B
U
IL
D
IN
G
A lt e rn a te tf ie s e lm a n A
G Y
.r v t
/2
/2
:1
:4
P
M
X-001
COVER SHEET & INDEX OF
DRAWINGS
RENOVATE BUILDING 15
VAHCS MARION, IL
657A5-18-111
7/17/2019 AHT TJF / KRK
1 73
BID SET
CONTRACT NOTES
1 ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS TO DETERMINE THEIR FULL. SCOPE OF WORK. CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
2 COVER AND PROTECT ALL VA EQUIPMENT AND FURNITURE SO THAT THE FUNCTION AND APPEARANCE IS NOT AFFECTED BY CONSTRUCTION, THE CONTRACTOR, THEIR EQUIPMENT, MATERIALS, OR ANY INVOLVED ACTIONS.
FIRE PROOFING GENERAL NOTES
1 MAINTAIN FIRE RATED CONSTRUCTION AT WALL PENETRATIONS AND JOINTS, (CONSTRUCTION TO
CONFORM TO MANUFACTURER'S FIRE RATED/TEST ASSEMBLIES.
2 FIRE CAULK ALL JOINTS, SLEEVES AND PENETRATIONS AT FIRE WALLS/PARTITIONS AND FLOORS.
CONFORM WITH THE TESTED/SUBMITTED FIRE RATED ASSEMBLY. USE RED FIRE CAULK AND
LABEL WALL WITH U.L. DESIGN NUMBER AND ASTM. FIRE RATED WALLS SHOWN ON PLAN.
3 PATCH AND REPAIR ALL EXISTING FIREPROOFING ON EXISTING STRUCTURAL MEMBERS,
INCLUDING THAT WHICH IS UNCOVERED, NEEDING REPAIR AND THAT WHICH IS DISTURBED DURING
CONSTRUCTION.
4 PATCH AND REPAIR ALL EXISTING FIRE CAULKING AT EXISTING RATED WALLS WHICH IS
UNCOVERED, NEEDING REPAIR AND THAT WHICH IS DISTURBED DURING CONSTRUCTION.
RE-LABEL EXISTING WALL IF NECESSARY.
HAZARDOUS MATERIAL
1 IF THE CONTRACTOR ENCOUNTERS MATERIAL THAT COULD BE HAZARDOUS, THE CONTRACTOR SHALL STOP WORK AND NOTIFY
THE OWNER IMMEDIATELY FOR DIRECTION.
MARION VA MEDICAL CENTER
RENOVATE BUILDING 15
PROJECT NUMBER: 657A5-18-111
N.T.S.
INTEGRATED PROJECT TEAM APPROVAL SIGNATURES
CAMPUS PLAN
Revisions: Date:
atast Snapshot
GENERAL ARCHITECTURAL NOTES:
1. THE CONTRACTOR SHALL INSPECT THE SITE AND VERIFY EXISTING CONDITIONS SHOWN PRIOR TO BIDDING. THE CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO ADDITIONAL
EXPENSE TO THE OWNER.
2. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR THE WORK AND BE RESPONSIBLE FOR SAME.
COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED AND MAKE ANY
NECESSARY OFFSETS TO CONCEAL PIPING AND DUCTWORK AND TO CLEAR EQUIPMENT,
STRUCTURAL MEMBERS AND OTHER OBSTRUCTIONS.
3. ALL UTILITIES AND SERVICES SHALL BE KEPT IN CONTINUOUS OPERATION UNLESS WRITTEN
PERMISSION IS OTHERWISE GRANTED BY THE OWNER.
3.1. MINOR SHUTDOWNS OF LESS THAN 48 HOURS REQUIRE 21 DAYS' NOTICE;
3.2. MAJOR SHUTDOWNS OF MORE THAN 48 HOURS REQUIRE 21 DAYS' NOTICE.
3.3. CONTRACTOR MUST CONTACT VA'S COR PRIOR TO ANY SHUTDOWNS.
4. TEMPORARY ALTERATIONS AND CONNECTIONS REQUIRED BY THIS CONTRACT SHALL BE MADE SO THAT ALL BUILDING SERVICES ARE MAINTAINED WITH MINIMUM INTERRUPTION. SCHEDULE ALL
ELECTRICAL/MECHANICAL OUTAGES 21 DAYS IN ADVANCE WITH THE OWNER.
5. PROTECT ALL WORK, MATERIALS AND EQUIPMENT. CAP OR PLUG TEMPORARY OPENINGS. DELIVER
ALL WORK TO THE OWNER CLEAN AND IN GOOD CONDITION.
6. WHEN DEMOLITION IS COMPLETE, NOTIFY ARCHITECT AND OWNER FOR A SCHEDULED MEETING TO
REVIEW EXISTING CONDITIONS AND ANY CONCERNS REGARDING NEW WORK.
7. CUTTING AND PATCHING OF EXISTING WALLS, FLOORS OR CEILINGS REQUIRED BY NEW WORK
SHALL BE INCLUDED AS WORK PROVIDED UNDER THIS CONTRACT.
8. CUTTING SHALL BE DONE WITH CARE SO AS NOT TO DAMAGE EXISTING EQUIPMENT, CONNECTIONS, CONTROLS, ETC.
9. DAMAGE CAUSED BY SUCH CUTTING SHALL BE REPLACED OR REPAIRED TO ORIGINAL CONDITION
BY CONTRACTOR AT NO COST TO THE OWNER, UNLESS UNFORESEEN EXISTING CONDITIONS ARE
DISCOVERED AND OWNER/ARCHITECT ARE NOTIFIED.
10. ALL OCCUPIED WORK AREAS, BUILDING CORRIDORS AND EXTERIOR AREAS SHALL BE KEPT CLEAR
OF DEBRIS.
11. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, OF THE BEST QUALITY AND FREE FROM DEFECTS.
12. MANUFACTURER AND MODEL NUMBERS SPECIFIED ESTABLISH THE TYPE AND QUALITY REQUIRED, UNLESS OTHERWISE NOTED.
13. ALL WORK SHALL COMPLY WITH APPLICABLE REGULATIONS, CODES AND ORDINANCES.
14. THE CONTRACTOR SHALL PERFORM ALL TESTS AS SPECIFIED OR AS NECESSARY TO
DEMONSTRATE A COMPLETE AND SATISFACTORY INSTALLATION.
15. ALL EXPOSED PENETRATIONS MADE THROUGH EXISTING ROOFS, FLOORS, AND WALLS SHALL BE PATCHED WITH LIKE MATERIALS TO MATCH THE SURROUNDING AREAS, AND FILLED AS CLOSE AS
POSSIBLE TO THE NEW PIPING OR DUCTWORK.
15.1. ALL EXPOSED PENETRATIONS MADE THROUGH EXISTING ROOFS ARE TO BE COORDINATED
WITH THE ROOFING WARRANTY CONTRACTOR.
16. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING AND REPLACING ANY DAMAGE TO EXISTING MATERIALS RESULTING FROM WORK UNDER THIS CONTRACT AND SHALL RESTORE SUCH
TO ITS ORIGINAL CONDITION WITH NEW MATERIALS TO MATCH EXISTING.
17. INSTALL THE SPECIFIED FIRE STOPPING (SLEEVES, WRAP, CONDUIT, ETC.) AT RATED
CONSTRUCTION:
A. FIRE STOP ALL PENETRATIONS WHERE NEW DEVICES/LINES RELOCATING EXISTING
DEVICES/LINES PENETRATING FLOORS, CEILINGS AND OTHER RATED BARRIERS.
B. FIRE STOP ALL NEWLY CREATED PENETRATIONS WHERE EXISTING
DEVICES/LINES PENETRATE FLOORS, CEILINGS AND OTHER RATED BARRIERS. USE FIRE
APPROVED CAULKING AND FIRE STOPS (SEE SPECIFICATIONS).
18. ALL METAL STUD AND GYPSUM WALLBOARD PARTITIONS ARE DIMENSIONED TO THE OUTSIDE FACE
OF WALL AND TO THE COLUMN GRID UNLESS OTHERWISE NOTED.
19. ALL GYPSUM BOARD SHALL BE TYPE 'X' FIRE CODE GYPSUM BOARD MOLD AND MOISTURE
RESISTANT AT WALLS AND CEILINGS.
20. PROVIDE WOOD BLOCKING OR 16 GA. SHEET METAL BACKING PLATES IN ALL WALLS TO RECEIVE
WALL HUNG ACCESSORIES, SUCH AS EQUIPMENT, GRAB BARS, MILLWORK, COAT HOOKS, AND
DOOR STOPS, ETC. IF WOOD BLOCKING IS USED, PROVIDE AS FIRE-RESISTANT.
21. ALL ITEMS AND DEVICES, SUCH AS COVER PLATES, SWITCH PLATES, CONVENIENCE OUTLETS, DOOR STOPS, AND OTHER FINISH HARDWARE, ETC. SHALL BE REMOVED AND REINSTALLED AS PART OF
THE REFINISHING OF EXISTING WALLS INDICATED TO REMAIN.
22. THE CONTRACTOR SHALL WORK WITH THE CONDITIONS AS THEY EXIST AT THE SITE. ALL ABOVE CEILING CONDITIONS SHALL BE REVIEWED, AND MODIFICATIONS IDENTIFIED, COORDINATED, AND
INCORPORATED INTO THE SHOP DRAWING PROCESS. COORDINATE ALL ABOVE CEILING WORK TO
ENSURE A COMPLETE AND OPERATIONAL SYSTEM AT NO ADDITIONAL COST TO THE OWNER.
COORDINATION SHALL INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING:
A. THE OWNER'S EQUIPMENT REQUIREMENTS.
B. THE CEILING SUPPORT SYSTEM.
C. THE MECHANICAL DUCTWORK SYSTEM.
D. THE LIGHTING FIXTURES.
E. ELECTRICAL WIRING AND CONDUIT SYSTEMS.
F. THE PLUMBING AND PIPING SYSTEMS.
G. THE COMMUNICATIONS SYSTEMS.
23. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS TO
DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL NOT BE ALLOWED EXTRA COSTS
DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
24. ALL NEW STUD WALLS AND GYPSUM BOARD SHALL EXTEND TO STRUCTURE UNLESS NOTED
OTHERWISE.
25. WHEN ALTERING THE BUILDING, IF STRUCTURAL INTEGRITY APPEARS TO BE IN QUESTION
CONTRACTOR SHALL NOTIFY OWNER AND ARCHITECT IMMEDIATELY.
26. ALL NEW CONSTRUCTION IS INDICATED BOLD OR FULL TONE UNLESS NOTED OTHERWISE.
27. WHEN WALL PARTITIONS OF DIFFERENT FIRE RATING INTERSECT, THE HIGHEST RATED
PARTITION TAKES PRECEDENT. MAINTAIN RATING BEHIND RECESSED AREAS IN WALLS.
28. ALL CORRIDOR WALLS ARE REQUIRED TO BE SMOKE TIGHT, WHETHER THEY ARE FIRE RATED OR
NOT. REPAIR AND EXTEND AT LEAST THE CORRIDOR SIDE OF NON-RATED CORRIDOR WALLS TO
STRUCTURE, UNLESS NOTED OTHERWISE, SEE WALL TYPES.
29. COORDINATE CONSTRUCTION REQUIREMENTS WITH MECHANICAL AND ELECTRICAL
DRAWINGS.
30. REVIEW AREAS OF WORK WITH COR FOR INFECTION CONTROL REQUIREMENTS. AREAS
REQUIRING CLASS I/CLASS II INFECTION CONTROL WILL REQUIRE APPROVAL BY THE COR PRIOR TO BEGINNING WORK. AREAS REQUIRING CLASS III/CLASS IV INFECTION CONTROL REQUIRE PERMITS FROM THE VA. SEE DIVISION 1 SPECIFICATION "SAFETY REQUIREMENTS-INFECTION CONTROL" FOR
DETAILED INFORMATION.
31. CONTRACTOR TO PROVIDE STOCK OF NEW CEILING TILES TO BE INSTALLED, BASED UPON 20% OF
TOTAL AREA OF EACH TYPE OF ACOUSTICAL TILE CEILINGS INDICATED TO BE REMOVED AND
REINSTALLED, TO REPLACE EXISTING DAMAGED ACOUSTICAL CEILING TILE. STOCK OF NEW CEILING
TILES WILL BE RETAINED BY THE MEDICAL CENTER, WITH THE CONTRACTOR DRAWING ON THE
STOCK FOR REPLACEMENT TILES. NEW CEILING TILES NOT INCORPORATED INTO THE WORK SHALL BE RETAINED BY THE OWNER FOR USE BY THE MEDICAL CENTER. SHOULD THE AMOUNT OF TILE
USED FOR REPLACEMENT EXCEED THE QUANTITY OF STOCK PURCHASED FOR AND PROVIDED TO
THE MEDICAL CENTER, THE CONTRACTOR SHALL PROVIDE AND INSTALL ADDITIONAL ACOUSTICAL
CEILING TILE AT AN ESTABLISHED UNIT PRICE PER FULL CASE OF CEILING TILE.
32. CONTRACTOR SHALL TURN OVER TO THE MEDICAL CENTER ALL UNDAMAGED CEILING TILE AND
SUSPENSION GRID THAT HAS REMOVED AND BEEN DETERMINED BY THE MEDICAL CENTER TO BE
SALVAGEABLE FOR FUTURE REPLACEMENT USE AT THE MEDICAL CENTER.
A
AB ANCHOR BOLT, AUGER BORING
ACT ACOUSTIC TILE
ACST ACOUSTIC
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ALC ALCOVE
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ATS AUTOMATIC TRANSFER SWITCH
ABBREVIATIONS - SEE ADDITIONAL FINISH MATERIAL ABBREVIATIONS IN THE ROOM FINISH SCHEDULE MATERIAL LEGEND
B
BD BOARD
BLDG BUILDING
BLK BLOCK
BM BEAM
B BOTTOM
BRG BEARING
BSMT BASEMENT
C
C CELSIUS
CAPTY CAPACITY
CC CENTER TO CENTER
CD CEILING DIFFUSER
CCT CUBICAL CURTAIN TRACK
CEM CEMENT
CG CORNER GUARD
CH CHILLER
CI CAST IRON, COURTYARD INLET
CIP CAST IRON PIPE
CIR CIRCULATING
CJ CONTROL JOINT
CKT CIRCUIT
CENTERLINE
CLN CLEAN
CLG CEILING
CLR CLEAR
CMP CORRUGATED METAL PIPE
CMPA CORRUGATED METAL PIPE ARCH
CMU CONCRETE MASONRY UNITS
CND,C CONDUIT
CNDS CONDENSATE
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
COND CONDUCTOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONV CONVERTER
CP NONREINFORCED CONCRETE PIPE
CR CHAIR OR CRASH RAIL
CS CONCRETE SEALER/SURFACE
CT CERAMIC TILE, CURRENT TRANSFORMER,
COOLING TOWER
CTR CENTER, COOLING TOWER RETURN
CTS COOLING TOWER SUPPLY
CW COLD WATER
CPT CARPET
D
DEFS DIRECT - APPLIED FINISH SYSTEM
DET, DTL DETAIL
DIA DIAMETER
DIM DIMENSION
DMPR DAMPER
DN DOWN
DP DISTRIBUTION PANEL
DS DOWNSPOUT, STORM DRAINAGE STRUCTURE
DW DOMESTIC WATER
DWG DRAWING
E
EA EACH
EF EACH FACE, EXHAUST FAN
EG EXHAUST GRILLE
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
ELEV ELEVATION
ELEC ELECTRIC, ELECTRICAL CLOSET
EMER EMERGENCY
EPDM ROOF MEMBRANE
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION, EXPOSED
EXP JT EXPANSION JOINT
F
FA FIRE ALARM
FD FLOOR DRAIN, FIRE DAMPER
FDN FOUNDATION
FDR FEEDER
FE FIRE EXTENGUISHER
FEC FIRE EXTENGUISHER CABINET
FFE FINISHED FLOOR ELEVATION
FIG FIGURE
FIN FINISH
FL FLOOR, FLASHING, FLOW LINE
FLUOR FLUORESCENT
FR FRAME
FTG FOOTING
FXTR FIXTURE
G
GA GAUGE
GALV GALVANIZED
GFI GROUND FAULT INTERRUPT
GL GLASS
GWB GYPSUM WALL BOARD
GYP GYPSUM
H
HGT,H HEIGHT, HUMIDIFIER
HB HOSE BIBB
HC HANDICAPPED
HDW HARDWARE
HORIZ HORIZONTAL
HR HOUR, HAND RAIL
HSKP HOUSEKEEPING
I
INT INTERIOR
INSUL INSULATION, INSULATED
INV INVERT
J
JB JUNCTION BOX
JC JANITOR CLOSET
JCT JUNCTION
JT JOINT
L
L LOUVER, LENGTH, LENGTH OF CURVE
LT LIGHT
LAV LAVATORY
M
M METER, MEGA
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MET/MTL METAL
MH MANHOLE
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MM,mm MILLIMETER
MOD. BIT. MODIFIED BITUMEN
MTD MOUNTED
MTG MOUNTING
MTL METAL
MMP MEMBRANE WATERPROOFING
MULL MULLION
N
NA NOT APPLICABLE
NEC NATIONAL ELECTRIC CODE
NEG NEGATIVE
NEUT NEUTRAL
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
O
OA OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER
OF OVERFLOW DRAIN
OPNG OPENING
OPP OPPOSITE
OVHD,OH OVERHEAD
P
P PIPE, POLE
PB PULL BOX
PAF POWDER ACTUATED FASTENER
PIV POST INDICATOR VALVE
PL PLATE
PLYWD PLYWOOD
PNL PANEL
PNT PAINT
PRELIM PRELIMINARY
PRIM PRIMARY
PT POINT, POINT OF TANGENT
PTN PARTITION
PVC POINT OF VERTICAL CURVE,
POLY VINYL CHLORIDE
PVMT PAVEMENT
R
R RADIUS, RISER, RUBBER SHEATH
RA RETURN AIR
RAD RADIUS
RB RESILIENT VINYL BASE
RCP REINFORCED CONCRETE PIPE,
REFLECTED CEILING PLAN
RECP RECEPTACLE
REINF REINFORCEMENT
REG REGULATOR, REGISTER
REQD REQUIRED
REV REVISION
RF ROOF, RETURN FAN
RHC REHEAT COIL
RM ROOM
RPM REVOLUTIONS PER MINUTE
RVT RESILIENT VINYL TILE
T
T TILE,TOP,TANGENT
T&B TOP AND BOTTOM
TEL TELEPHONE
TEMP TEMPERATURE, TEMPORARY
TERM TERMINAL
3/C THREE CONDUCTOR
3/P THREE POLE
3 WAY THREE WAY
TO TOP OF
TRANS TRANSITION
TS TOP OF STEEL, TOP OF STONE,
TOP OF SLAB
TV TELEVISION
TYP TYPICAL
U
UH UNIT HEATER
U.N.O. UNLESS NOTED OTHERWISE
V
V VENT,VOLT,VALVE
VA VOLT AMPRE
VAC VACUUM
VCT VINYL COMPOSITION TILE
VENT VENTILATING
VERT VERTICAL
VEST VESTIBULE
VS VENT STACK
VTR VENT THRU ROOF
VWC VINYL WALL COVERING
W
W WIDTH, WASTE, WATER,
WATT, WEST, WIRE,
WATER LINE STRUCTURE
WA WATT
W/ WITH
W/O WITHOUT
WC WATER CLOSET, WHEEL CHAIR
WD WIDTH, WINDOW DIMENSION
WG WALL GUARD
WP WATERPROOF, WEATHERPROOF
WS WASTE STACK, WATER SURFACE,
WATERSTOP
WT WEIGHT
WWF WELDED WIRE FABRIC
S
SAN SANITARY SEWER
SCH SCHEDULE
SD SPLITTER DAMPER, STORM DRAIN
SECT SECTION
SG SUPPLY GRILLE
SH SHEET
SIM SIMILAR
1 PH SINGLE PHASE
SL SLOPE
SP STATIC PRESSURE, SINGLE POLE
SPDT SINGLE POLE, DOUBLE THROW
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SQ SQUARE
SR SUPPLY REGISTER
SS SANITARY SEWER
ST STEAM, SINGLE THROW,
STREET, STAFF
STA STATION
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
SUP SUPPORT
SUSP SUSPENDED
SV SHEET VINYL
SW SWITCH, SIDEWALK
SWBD SWITCHBOARD
SWGR SWITCHGEAR
CL
K
KO KNOCK OUT
KVA KILOVOLT-AMPERE
KW KILOWATT
ARCHITECTURAL SYMBOLS
A101
DETAIL NUMBER
0 COLUMN NUMBER/GRID LINE
SHEET NUMBER
ARCHITECTURAL
WALL SECTION
WINDOW TYPE
1 Ref
R e f
1 Ref
R e f
ARCHITECTURAL
INTERIOR ELEVATIONS
DETAIL NUMBER
SHEET NUMBER
CENTER LINE
DIMENSION LINE
DOOR NUMBER SYMBOL
1"
EXISTING TO REMAIN
NEW CONSTRUCTION
EXISTING TO BE REMOVED
EXISTING TO REMAIN
1i
KEYNOTE - RENOVATION
WALL/ PARTITION TYPE
KEYNOTE - DEMOLITION PLANX
X
X
15-A888 X
SHEET NUMBER
DETAIL NUMBER
ARCHITECTURAL
BUILDING SECTION
DETAIL NUMBER
SHEET NUMBER
ARCHITECTURAL
DETAIL CALLOUT
DETAIL NUMBER
SHEET NUMBER
X
XXXX
X
XXXX
X
XXXX
ARCHITECTURAL
EXTERIOR ELEVATION
MATERIAL LEGEND
CAST-IN-PLACE CONCRETE
EARTH
EXISTING CONSTRUCTION
BRICK
GYPSUM
RIGID INSULATION
STEEL
STATEMENT OF BID ITEM(S)
(FROM PROJECT MANUAL SECTION 01 00 00 – GENERAL REQUIREMENTS)
A. BID ITEM #1 - GENERAL CONSTRUCTION: Provide all labor, material, and supervision for all work shown in the drawings and specifications and complete work within 180 calendar days.
B. DEDUCT ALTERNATES: Following is a list of Deduct Alternates. Provide pricing for deletion of Bid Items in the order shown.
1. BID ITEM #2 – DEDUCT ALTERNATE #1: Provide all work as shown in Bid Item #1, except Remove contingencies for hazardous materials abatement for roofing and removal of lead-based paint for items to be abandoned in place. Complete work within 180 calendar days.
2. BID ITEM #3 – DEDUCT ALTERNATE #2: Provide all work as shown in Bid Item #2, except delete installation of new window shades at all windows; delete low-energy power assist door operators at Doors 100 and 100A. Complete work within 180 calendar days.
3. BID ITEM #4 - DEDUCT ALTERNATE #3: Provide all work as shown in Bid Item #3, except delete work for installation of selected exterior windows in Rooms 109, 111, 120 and 121A;
replace with masonry/DEFS/spray foam insulation infill of exterior openings and light gauge metal framing GWB infill of interior openings. Complete work within 180 calendar days.
4. BID ITEM #5 – DEDUCT ALTERNATE #4: Provide all work as shown in Bid Item #4, except delete installation of normal-weight concrete floor leveling topping. Complete work within 180 calendar days.
5. BID ITEM #6 – DEDUCT ALTERNATE #5: Provide all work as shown in Bid Item #5, except delete installation of partition walls at Rooms 107, 108, 110, 111 and 112, and revise installation of suspended acoustical ceilings, fire protection, mechanical, electrical and telecommunications systems to provide for installation of systems furniture. Complete work within 180 calendar days.
6. BID ITEM #7 - DEDUCT ALTERNATE #6: Provide all work as shown in Bid Item #6, except delete work associated with installation of new domestic water recirculation system. Complete work within 180 calendar days.
7. BID ITEM #8 – DEDUCT ALTERNATE #7: Provide all work show in Bid Item #7, except delete work for connection of building HVAC controls to the campus BACnet system as described in the Construction Documents; Delete work associated with installation of new domestic water recirculation system. Complete work within 180 calendar days.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 POC:
AH. INZ
6910 Pacific St #310
Omaha, NE 68106
Phone: 402.553.0234 POC:
IMEG Corp.
2882 106th Street
Des Moines, Iowa
Phone: 515.334.4303
POC:
AMI Enviromental
8802 S 135th Street
Omaha, NE 68138
Phone: 402.397.5001
POC:
BID SET
07/17/2019
Dwg. Of
C
L H
D C
\H o m e \t fi e s e lm a n
\R e v it
M o d e ls \R
-2
B
U
IL
D
IN
G
A lt e rn a te tf ie s e lm a n A
G Y
.r v t
/2
/2
:1
:4
P
M
G-001
GENERAL NOTES,
ABBREVIATIONS & SYMBOLS
RENOVATE BUILDING 15
VAHCS MARION, IL
657A5-18-111
7/17/2019 AHT KRK / TJF
2 73
BID SET
Revisions: Date:
TRACK - T&B TRACK - T&B TRACK - T&B
TRACK - T&B
STRUCTURE
ABOVE
FIRE RATED SEALANT,
EA. SIDE, T&B
HEAD SLIP
CONNECTOR
FINISHED CEILING
ACOUSTIC BATTS
1 LAYER 5/8" GWB
EA. SIDE
PAF (.145) AT 32" OC
STRUCTURE
ABOVE
FIRE RATED SEALANT,
EA. SIDE, T&B
HEAD SLIP
CONNECTOR
FINISHED CEILING
ACOUSTIC BATTS
1 LAYER 5/8" GWB
EA. SIDE
PAF (.145) AT 32" OC
STRUCTURE
ABOVE
FIRE RATED SEALANT,
EA. SIDE, T&B
HEAD SLIP
CONNECTOR
FINISHED CEILING
ACOUSTIC BATTS
1 LAYER 5/8" GWB
EA. SIDE
PAF (.145) AT 32" OC
TRACK - T&B
6" METAL STUDS
@ (16" O.C.)
3 5/8" METAL STUDS
(16" O.C.)
3 5/8" METAL
STUDS (16" O. C.)
FINISH FLOOR FINISH FLOOR FINISH FLOOR
STRUCTURE
ABOVE
STRUCTURE ABOVE
HEAD SLIP
CONNECTOR
ACOUSTIC SEALANT,
EA. SIDE, T&B
FINISHED CEILING
ACOUSTIC BATTS
1 LAYER 5/8" GWB
(ONE SIDE ONLY)
PAF (.145) AT 32" O. C.
HEAD SLIP
CONNECTOR
ACOUSTIC SEALANT,
T&B
FINISHED
CEILING
ACOUSTIC
BATTS
1 LAYER 5/8" GWB
(ONE SIDE ONLY)
PAF (.145) AT 32" O. C.
3 5/8" METAL STUDS
(16 O. C.)
1 5/8" METAL STUDS
AT 16" O. C.
FINISH FLOOR FINISH FLOOR
SMOKE PARTION/FIRE & SMOKE
30-MIN RATED
SMOKE PARTION/FIRE & SMOKE
30-MIN RATED
1 HOUR FIRE BARRIER
UL 263 DESIGN U419
SBC SBD 1C C A1
STRUCTURE ABOVE
ACOUSTIC SEALANT,
T&B
FINISHED CEILING
1 LAYER 5/8" GWB
(ONE SIDE ONLY)
FINISH FLOOR
F
TRACK - T&B
STRUCTURE ABOVE
HEAD SLIP
CONNECTOR
ACOUSTIC SEALANT,
EA. SIDE, T&B
FINISHED CEILING
1 LAYER 5/8" GWB
(ONE SIDE ONLY)
PAF (.145) AT 32" O. C.
3-5/8" METAL STUDS
AT 16" O. C.
FINISH FLOOR
C1X
SPRAY FOAM INSUL.
EXIST EXTERIOR WALL
FURRED/INSULATED
EXISTING EXTERIOR WALL
FURRED
INTERIOR WALL -
MTL STUDS
FURRED INTERIOR WALL - DWC
OVER MASONRY OR CONC
SEE PLAN
EXIST WALL
EXIST CONC OR
MASONRY WALL
7/8" DWC AT 16" O. C.
VERT. (TYP) W/ PAF
AT 32" O. C. HORIZ. -
ALTERNATE PAF
BETWEEN T&B OF
CHANNEL
7/8" DWC AT
FINISHED CEILING
LEVEL
SHIM DWC AS REQ'D
FOR PLUMB WALL
SURFACE (TYP)
WALL TYPE NOTES:
1. NOT ALL WALL TYPES SHOWN IN THIS SCHEDULE MAY BE USED IN THE
PROJECT. REFER TO FLOOR PLANS FOR WALL TYPES USED. NOT ALL
WALL TYPES ARE SHOWN GRAPHICALLY ON THIS SHEET, SEE THE
SCHEDULE.
2. ALL NEW INTERIOR GWB SHALL BE 5/8" TYPE X MOISTURE AND MOLD
RESISTANT GWB UNLESS OTHERWISE NOTED. USE SOUND BOARD
WHERE INDICATED.
3. ALL NEW INTERIOR GWB ON RESILIENT CHANNELS SHALL BE 5/8" TYPE
C MOISTURE AND MOLD RESISTANT GWB.
4. ALL GWB TO BE SMOOTH FINISH THROUGHOUT, LEVEL 5 FINISH,
UNLESS NOTED OTHERWISE.
5. FIELD VERIFY DETAILED WALL CONSTRUCTION & REVIEW PLAN
LAYOUT WITH EXISTING CONDITIONS IN THE FIELD. WHERE FIELD
CONDITIONS CONFLICT WITH WALL CONSTRUCTION DETAILS, MODIFY
WALL CONSTRUCTION AS PER ARCHITECT'S DIRECTIVE AT NO
ADDITIONAL COST TO THE OWNER.
6. ALL WALL TYPES SHALL HAVE ACOUSTICAL SEALANT AT TOP, BOTTOM,
AND ALONG BOTH SIDES AND AT ALL OTHER CUTOUTS TO PREVENT
SOUND LEAKAGE.
7. CONSTRUCT ALL WALLS TO CONFORM TO THE DETAILED
REQUIREMENTS OF THE MOST-CURRENT EDITION OF UNDERWRITERS
LABORATORIES INC.'S "FIRE RESISTANCE DIRECTORY" AND THE
GYPSUM ASSOCIATION'S "FIRE RESISTIVE DESIGN MANUAL" GA-600,
CURRENT EDITION. APPLY GWB PER LISTED ASSEMBLY TO MEET
DETAILS OF ASSOCIATED UL DESIGN NUMBER.
8. WHERE WALLS ARE INDICATED TO BE FIRE RESISTIVE
CONSTRUCTION, TAPE ALL JOINTS, INCLUDING THOSE JOINTS ABOVE
CEILINGS.
9. ALL RATED WALLS SHALL BE CONTINUOUS WHEN INTERSECTED BY
WALLS OF LESSER OR NO RATING.
10. PROVIDE "MUD ON" CASING, TEAR AWAY, "L", OR "J" BEAD AT FRAMES,
CEILINGS AND OTHER OPENINGS AND TRANSITIONS AS REQUIRED. ALL
BEAD SHALL BE "MUD ON" TYPE UNLESS INDICATED OTHERWISE.
11. ACOUSTIC INSULATION AT 6" STUDS SHALL BE 6" THICK BATTS.
ACOUSTIC INSULATION AT 3-5/8" STUDS SHALL BE 3-1/2" THICK BATTS
MINIMUM.
12. (NOT USED)
13. PROVIDE TILE BACKER BOARD AND WATERPROOF MEMBRANE AT ALL
CERAMIC TILE-FACED WALLS.
14. DIMENSIONS ARE TO FACE OF GWB UNLESS OTHERWISE NOTED.
15. PROVIDE ABUSE-RESISTANT GWB UP TO THE CEILING AT ROOMS
DESIGNATED IN THE ROOM FINISH SCHEDULE, INCLUDING EXTERIOR
WALLS.
16. SEE INTERIOR ELEVATIONS AND FINISH PLANS FOR EXTENTS OF
CERAMIC TILE.
17. PROVIDE MTL STUD WALL BACKING CENTERED AT 3'-0" AFF & WHERE
REQ'D FOR ANCHORAGE OF WALL-MOUNTED ITEMS.
WALL PARTITION GENERAL NOTES:
A. ALL PARTITION FRAMING SHALL EXTEND FROM FLOOR TO FLOOR/ROOF
STRUCTURE ABOVE UNLESS NOTED OTHERWISE. REFER TO INDIVIDUAL
PARTITION TYPES FOR EXTENT OF GYPSUM WALLBOARD AND
ACOUSTICAL TREATMENT.
B. ALL BULKHEAD FRAMING SHALL EXTEND TO UNDERSIDE OF STRUCTURE
ABOVE WITH DIAGONAL METAL STUD BRACING AT 4'-0" ON CENTER
MAXIMUM. PROVIDE MINIMUM TWO BRACES PER BULKHEAD.
C. WHEN A PARTITION IS REQUIRED TO MEET A SPECIFIC FIRE RATED TEST
NUMBER OR STC TEST NUMBER THE SPECIFIC REQUIREMENTS OF THAT
TEST NUMBER SHALL SUPERSEDE ANY CONFLICTING NOTATION ON
THAT PARTICULAR DETAIL OR PARTITION TYPE.
D. ALL PARTITIONS WITH ACOUSTICAL BATT INSULATION SHALL BE
CONSIDERED "SOUND" PARTITIONS. ALL PENETRATIONS SHALL BE
SEALED WITH ACOUSTICAL SEALANT.
A - WALL TYPE PREFIXES - LIFE SAFETY RATING
B - FRAMING SIZES
A 1 5/8" STL STUDS
B 2 1/2" STL STUDS
C 3 5/8" STL STUDS
D 6" STL STUDS
E 6" STL RUNNERS TOP & BOTTOM W/ 2 1/2" STL STUDS EA. SIDE
(STAGGERED)
F 7/8" STL HAT CHANNEL FURRING
G CHASE WALL (SEE DETAIL)
H 2 1/2" C-H SHAFTWALL STL STUDS
C - WALL TYPE SUFFIXES - WALL TYPE MODIFIERS
1 WALL BOARD ON ROOM SIDE ONLY
P PARTIAL-HEIGHT WALL - SEE INT ELEVS/DTLS
R 1/2" STL RESILIENT CHANNEL
T TILE BACKER BOARD W/ CERAMIC TILE FINISH ON ROOM SIDE -
SEE INTERIOR ELEVS & ROOM FINISH PLANS FOR EXTENTS
T2 TILE BACKER BOARD W/ CERAMIC TILE FINISH BOTH SIDES -
SEE INTERIOR ELEVS & ROOM FINISH PLANS FOR EXTENTS
M METAL WRAPPED RIGID INSULATION PANELS
X EXTERIOR WALL CONSTRUCTION
CUT HORIZONTAL FASTENER
FROM METAL STUDS
FASTEN AT BOTH ENDS WITH
MINIMUM 4 SELF-TAPPING
SCREWS
METAL STUDS AT 16" O. C.
ISOMETRIC PLAN VIEW
NOTES:
1. CONTRACTOR SHALL COORDINATE LOCATIONS OF
HORIZONTAL FASTENERS
2. WALL BACKING SHALL BE USED AT ALL GRAB BARS, WALL
CABINETS, BUMPER/CRASH RAILS, ETC. U.N.O.
3. MINIMUIM GAGE FOR WALL BACKING TO BE 16 GA. U.N.O.
NOTES:
1. THIS DETAIL IS APPLICABLE TO ALL PARTITIONS WITH
ACOUSTICAL BATT INSULATION (SOUND PARTITION).
2. REFER TO WALL TYPES FOR ADDITIONAL INFORMATION.
3. REFER TO PARTITION HEAD DETAILS FOR DEFLECTION
CONSIDERATIONS.
ACOUSTIC BATT INSULATION
PER WALL TYPE
WALL FINISH AS SCHEDULED
WALL BASE AS SCHEDULED
CONTINUOUS ACOUSTIC
SEALANT UNDERNEATH
RUNNER AND BOTH SIDES OF
WALL; JAMB LOCATIONS ALSO
FLOOR FINISH AS SCHEDULED
FLOOR LINE
5/ 8"
FINISH FLOOR
STRUCTURE ABOVE
20 GA. LT GA STUD
BRACE TO STRUCTURE
AT 4'-0" O.C. MAX -
ATTACH TO TOP OF WALL
ACOUSTICAL BATT
INSULATION TO MIN 4'-0" FROM PARTITION
FINISHED CEILING
ACOUSTIC BATTS
3 5/8" METAL STUDS (16" O. C.)
1 LAYER 5/8" GWB EA. SIDE
PAF (.145) AT 32" O. C.
TRACK-T&B
CP
7/
8"
NON-RATED PARTIAL-HEIGHT WALL
CONC ROOF DECK
FIRESTOP EA. SIDE
DEFLECTION TRACK
GYP. BD. PER
WALL TYPE
ACOUSTIC BATTS
PER WALL TYPE
HEAD SLIP CONNECTOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 POC:
AH. INZ
6910 Pacific St #310
Omaha, NE 68106
Phone: 402.553.0234 POC:
IMEG Corp.
2882 106th Street
Des Moines, Iowa
Phone: 515.334.4303
POC:
AMI Enviromental
8802 S 135th Street
Omaha, NE 68138
Phone: 402.397.5001
POC:
BID SET
07/17/2019
Dwg. Of
C
L H
D C
\H o m e \t fi e s e lm a n
\R e v it
M o d e ls \R
-2
B
U
IL
D
IN
G
A lt e rn a te tf ie s e lm a n A
G Y
.r v t
/2
/2
:1
:4
P
M
G-002
WALL TYPES & PARTITION
DETAILS
RENOVATE BUILDING 15
VAHCS MARION, IL
657A5-18-111
7/17/2019 AHT KRK / TJF
3 73
BID SET
SCALE: 1" = 1'-0"
B1
WALL TYPES
SCALE: 1 1/2" = 1'-0"
D1
WALL BACKING
SCALE: 3" = 1'-0"
D5
PARTITION BASE DETAIL
REFER TO DTL. F1/15-G-002 FOR NON-RATED PARTIAL HT WALLS
SCALE: 3" = 1'-0"
D4
PARTITION HEAD DETAIL
SCALE: N.T.S.
DN
R e fr ig e ra to r
DN
0 SB 0 SB0 SB 0 SB 0 SB
S
B S
B S
B S
B S
B S
B
S
B S
B S
B S
B S
B S
B
SS SSSS SS SS
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
SB
SS
0 HZ
0 SB
SSSS
S S
S S
S S
S S
S S
S S
A
1 2 3
100 SF
PROJECT
ENGINEER
SUPERVISOR
100 SF/
202 SF
PLAN ROOM
200 SF/
203 SF
BREAK ROOM
318 SF
CONFERENCE
ROOM
300 SF/
41 SF
UNISEX STAFF
TLT
60 SF/
70 SF
UNISEX STAFF
TLT
80 SF/
102 SF
OI&T ROOM
101D
100 SF/
46 SF
HAC
60 SF/
26 SF
ALCOVE
101B
201 SF
MECHANICAL
101C
488 SF/
61 SF
STORAGE
60 SF/ 102 SF
ASST. CHIEF
ENGINEER
100 SF/ 102 SF
CHIEF ENGINEER
100 SF/ 100 SF
FACILITY
PLANNER
100 SF/ 96 SF
ENERGY
MANAGER
100 SF/
60 SF
MENS TOILET
60 SF/ 63 SF
WOMENS TOILET
60 SF/ 95 SF
M&O
SUPERVISOR
100 SF/
12 SF
CLOSET
100 SF
M&O
SUPERVISOR
100 SF/ 99 SF
M&O
SUPERVISOR
100 SF/ 98 SF
M&O
SUPERVISOR
100 SF/
154 SF
CORRIDOR
C01
54 SF
ADMIN OFFICE
ASST
56 SF/
114 SF
CORRIDOR
C01A
124 SF
CORRIDOR
C01B
177 SF
ELECTRICAL
105A
488 SF/
126 SF
CORRIDOR
C02
65 SF
VESTIBULE
17 SF
STEAM TUNNEL
101D
101C
104 105
112 111 110
108107103102
100A
C01CA
101CA
118 SF
PROJECT
ENGINEERS
EGRESS
121B
9 SF
SHOWER
118A
30 SF
VESTIBULE
C01C
105A
C01D
15 SF
STORAGE
C01D
B
169 SF
ENG.
CLERK/TRANS.MGR
101A
175 SF
LOBBY
502 SF
PROJECT
ENGINEERS
WORKSTATIONS
56 SF/
121B
E E
E
36"
36"
101C
3 1
1-50
TRAVEL DIST. TO EXIT = 55'
T R
A V E L
D
IS
T . T
O E
X
IT
9'
TRAVEL DIST. TO EXIT = 66'-4"
T R
A V
E L D
IS
T
. T O
E X
IT
' -7
5' -0
5' -4
/8
1-15
1-15
1 1
1 1
1 2
2 2 1 1
TRAVEL DIST. TO EXIT = 49'
2 2 **
2 *
2 *
2 *
2 *
1 2 *
11'-5 5/8"
5' -0
/8
25' -0
TRAVEL DIST. TO EXIT = 39'
TRAVEL DIST. TO EXIT = 55'
1-50
EXIT SEPARATION = 114'-9 7/8"
FEC
PROJECT
ENGINEERS
WORKSTATIONS
121A
CORRIDOR
C02A
NEW
PARTITION KEY
WALL
RATING DESCRIPTION
NFPA 2018
(EXIST. BUS)
NFPA 2018
(NEW BUS)
RATED UL
ASSEMBLES
OPENINGS
RATING RFRNC.
DAMPERS
TYPE RFRNC.
2 HR
BUILDING SEPARATION:
FIRE BARRIER
NOT
APPLICABLE
NOT
APPLICABLE
UL U412
UL U419
90 MIN
IBC 705.8
TABLE 715.4
FIRE
90 MIN
IBC 705.11
IBC 715.5.1
IBC 716.5.1
1 HR
OCCUPANCY / AREA SEPARATION:
FIRE BARRIER
NFPA 6.1.14
NFPA 8.2.3.1.2
NFPA 6.1.14
NFPA 8.2.3.1.2
45 MIN NFPA 8.2.3.2.3.1 (1)
IBC 706.7
NFPA 8.2.3.2.4.1
IBC 706.10
IBC 716.3.1
IBC 716.5.2
2 HR
OCCUPANCY / AREA SEPARATION:
FIRE BARRIER
NFPA 6.1.14
NFPA 8.2.3.1.2
NFPA 6.1.14
NFPA 8.2.3.1.2
UL U412
UL U419
90 MIN
NFPA 8.2.3.2.3.1 (1)
IBC 706.7
FIRE
90 MIN
NFPA 8.2.3.2.4.1
IBC 706.10
IBC 716.3.1
IBC 716.5.2
2 HR
1 HR
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)
NFPA 39.3.1.1
NFPA 8.2.5.4
NFPA 38.3.1.1
NFPA 8.2.5.4
UL U412
UL U419
UL U415(B)
90 MIN
60 MIN
NFPA 8.2.3.2.3.1
IBC 715.4 / 714.2
NOT
ALLOWED
NFPA 1005.3.4.1
NFPA 1020.12
IBC 715.5.3
IBC 716.5.2
2 HR
1 HR
EXIT PASSAGEWAY (HORIZ)
FIRE BARRIER
NFPA 39.2.2.7
NFPA 7.2.6
NFPA 38.2.2.7
NFPA 7.2.6
90 MIN
60 MIN
NFPA 8.2.3.2.3.1
IBC 715.4 / 714.2
NOT
ALLOWED
NFPA 1005.3.4.1
NFPA 1021.5
1 HR
HAZ / INCIDENTAL USE
FIRE BARRIER
NFPA 38.3.2.1
NFPA 8.4.1.1
NFPA 38.3.2.1
NFPA 8.4.1.1
UL U412
UL U419
45 MIN
NFPA 8.2.3.2.3.1 (2)
IBC 706.7
IBC 715.4
FIRE
90 MIN
IBC 715.3.1
IBC 716.3.1
IBC 715.5.2
IBC 716.5.2
NR-
RESIST
SMK
HAZ / INCIDENTAL USE
SMOKE PARTITIONS (SPRINKLERED)
NFPA 8.4.1.2 NFPA 8.4.1.2
IBC 710.5.3
IBC 715.4.7.3
IBC 508.2.2.1
SEE
NOTE [B]
1 HR
1/2 HR
SUBDIVIDING SPACES
SMOKE BARRIER
NFPA 39.3.7.1 NFPA 38.3.7.1
NFPA 38.3.7.3
NFPA 8.3.4.2 (1)
IBC 709.5
SMOKE
90 MIN
SEE NOTE [A]
UL U412
UL U419
UL U415(A)
20 MIN
NFPA 8.3.5.1
IBC 709.8
IBC 716.5.5
SEE NOTE [C]
NR
SUITE SEPARATION
SMOKE PARTITIONS
NFPA 39.2.5 NFPA 38.2.5
NR SELF
OR AUTO
CLOSING
IBC 710.5.3
IBC 715.4.7.3
SEE
NOTE [B]
HORIZONTAL BUILDING SEPARATION
FIRE BARRIER
NOT
APPLICABLE
NOT
APPLICABLE
IBC 705.8
TABLE 715.4
FIRE
90 MIN
UL U412
UL U419 90 MIN
IBC 705.11
IBC 715.5.1
IBC 716.5.1
2 HR
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
[A] DAMPERS ARE NOT REQUIRED IN DUCT PENETRATIONS OF SMOKE BARRIERS
WHERE HVAC SYSTEMS ARE FULLY DUCTED (39.3.7.3x2).
[B] AIR TRANSFER OPENINGS IN SMOKE PARTITIONS SHALL HAVE DAMPERS
(NFPA 8.2.4.4.3) (IBC 710.7).
[C] SMOKE DAMPERS ARE NOT REQUIRED WHERE OPENINGS IN DUCT ARE
LIMITED TO A SINGLE COMPARTMENT & DUCTS ARE MADE OF STEEL (IBC 716.5.5).
NOTES
SYMBOLS
NR SELF
OR AUTO
CLOSING
NO. OF OCC. EXISTING10
REQ'D. EXIT WIDTH
NO. OF OCC/
NO. OF EXIT
ACTUAL EXIT WIDTH
10/1 2" 34"
5 NO. OCC. EXITING
(SMALLER ROOMS)
AREA
MAXIMUM OCCUPANCY
1:50
OCC. LOAD FACTOR
FE FIRE EXTINGUISHER AND CABINET
FACP FIRE ALARM CONTROL PANEL
FSA FIRE SYSTEM ANNUNCIATOR ALARM
FAAP ANNUNCIATOR PANEL
PROPERTY LINE
STARTING
LOCATION
TRAVEL PATH
TRAVEL
DISTANCE
100'
(50)
EXITING
FE
FIRE EXTINGUISHER AND CABINET
E EXIT
OCCUPANCY LEGEND
BUSINESS - NON-CONCENTRATED USE - 100 SF / PERSON
BUSINESS - CONCENTRATED USE - 50 SF / PERSON
INCIDENTAL USE - 300 SF / PERSON
ASSEMBLY - NON-CONCENTRATED USE - 15 SF / PERSON
A
B
100 SF
FACILITY
PLANNER
100 SF/ 96 SF
ENERGY
MANAGER
100 SF/
63 SF
WOMENS TOILET
60 SF/
95 SF
M&O
SUPERVISOR
100 SF/
100 SF
M&O
SUPERVISOR
100 SF/ 99 SF
M&O
SUPERVISOR
100 SF/ 98 SF
M&O
SUPERVISOR
100 SF/
154 SF
CORRIDOR
C01
54 SF
ADMIN OFFICE
ASST
56 SF/
114 SF
CORRIDOR
C01A
124 SF
CORRIDOR
C01B
C01CA
30 SF
VESTIBULE
C01C
C01D15 SF
STORAGE
C01D
TRAVEL DIST. TO EXIT = 49'
2 *
5' -0
2 * 2 *
2 *
2 *
2 *2 *
OPEN WITH CUBICALS
TRUE
NORTH
PLAN
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 POC:
AH. INZ
6910 Pacific St #310
Omaha, NE 68106
Phone: 402.553.0234 POC:
IMEG Corp.
2882 106th Street
Des Moines, Iowa
Phone: 515.334.4303
POC:
AMI Enviromental
8802 S 135th Street
Omaha, NE 68138
Phone: 402.397.5001
POC:
BID SET
07/17/2019
Dwg. Of
C
L H
D C
\H o m e \a ta s t\
R
-2
B U
IL
D
IN
G
A lt e rn a te a ta s t.
rv t
/1
/2
:0
:5
P
M
15-GI101
LIFE SAFETY & CODE REVIEW
PLAN
RENOVATE BUILDING 15
VAHCS MARION, IL
657A5-18-111
7/17/2019 AHT TJF/KRK
4 73
BID SET
SCALE: 1/4" = 1'-0"
LIFE SAFETY & CODE REVIEW PLAN
SCALE: 1/8" = 1'-0"
LIFE SAFETY & CODE REVIEW PLAN - BUSINESS CONCENTRATED USE-DEDUCT ALTERNATE #5
* SEE PLAN 2/ 15-GI101 FOR DEDUCT ALTERNATE #5
CODE INFORMATION
I. BUILIDNG CONSTRUCTION
A. BUILDING CLASSIFICATION
1. OCCUPANCY CLASSIFICATION:
a. EXISTING BUILDING: B - BUSINESS
b. OCCUPANCY SEPARATION:
1. STORAGE ROOMS OVER 100 SF 1-HOUR
c. COMMON PATH LIMIT: 100FT
d. DEAD END LIMIT: 30FT
e. TRAVEL DISTANCE LIMIT: 200FT
f. FIRE DOOR AND GLAZING IN 1-HR WALL: 45 MIN
g. CORRIDOR WIDTH: 44” CLEAR MINIMUM
h. DOORS REQUIRED TO BE 3’0” WIDE MINIMUM, WITH OPENINGS TO BE SIZED APPROPRIATE TO
ACCOMMODATE ROOM FUNCTIONS.
i. INTERVENING ROOMS NOT PERMITTED, UNLESS THEY ARE ACCESSORY TO THE SPACE
SERVED, I.E. TOILET ROOMS.
j. 1-HOUR HAZARDOUS AREAS: STORAGE OVER 100 SF, 1-HOUR RATED FIRE-SMOKE BARRIER.
k. SUITE WALLS SHALL BE SMOKE PARTITIONS, NO FIRE RATING.
B. CONSTRUCTION TYPE
1. CONSTRUCTION TYP:
a. EXISTING, TYPE IA (332), REFERENCE NFPA 101.39.1.6.1 - RESERVED
(1B FIRE-SPRINKLED) (FOR REFERENCE)
1. HEIGHT - ALLOWABLE: UNLIMITED IBC TABLE 503
2. HEIGHT - ACTUAL: 1 STORY = 19'-0"
3. AREA - ALLOWABLE: UNLIMITED IBC TABLE 504
4. AREA - ACTUAL: 5,264 GSF
5. PROJECT AREA: 5,264 SF
C. FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS -
TYPE IA (332): (IBC TABLE 601 PAGE 119, NFPA TABLE A.8.2.1.2 PAGE 404)
1. STRUCTURAL FRAME: CONCRETE 3-HR IBC TABLE 601 PAGE 119 & NFPA 101.A.8.2.1.2
(INCLUDING COLUMNS, TRUSSES, GIRDERS)
2. BEARING WALLS EXTERIOR: MASONRY 3-HR IBC TABLE 601 & NFPA 101.A.8.2.1.2
3. BEARING WALLS INTERIOR; (SUPPORT MORE THAN 1 FLR, COLUMNS, OR OTHER BEARING WALLS)
MASONRY 3-HR IBC TABLE 601 & NFPA 101.A.8.2.1.2
4. NON-BEARING WALLS - EXTERIOR (IBC TABLE 602)
LESS THAN 30' SEPARATION 1-HR IBC TABLE 602 & NFPA 101.A.8.2.1.2
GREATER THAN 30' SEPARATIN NON-RATED IBC TABLE 602 & NFPA 101.A.8.2.1.2
BUILDING SEPARATION - CLOSEST BUILDING IS APPROXIMATELY 33 FT TO THE WEST.
5. NON-BEARING WALLS & PARTITIONS - INTERIOR
NON-COMBUSTIBLE 0-HR IBC TABLE 601, NFPA 101.A.8.2.1.1.
6. NOT USED
7. ROOF CONSTRUCTION (INCLUDING SUPPORTING BEAMS & JOISTS):
1 1/2-HR IBC TABLE 601 & NFPA 101.A.8.2.1.2
8. SHAFT ENCLOSURE: 1-HR (<4 STORIES) IBC TABLE 601 & NFPA 101.18.3.1
9. CORRIDORS:
CORRIDOR RESISTIVE RATING 0-HR IBC TABLE 1017.1
LIMIT THE TRANSFER OF SMOKE. EXISTING BUSINESS OCCUPANCIES - NO REQUIREMENTS FOR
CORRIDORS - PAGE 339 - NFPA 101.39.3.6.
10. OCCUPANCY SEPARATION (FIRE BARRIER): 2-HR NFPA 101.6.1.14.4.1(B)
11. INTERIOR FINISHES RATING CLASS 'B' IBC TABLE 803.4
12. PER 39.2.2.12.2 NFPA-EXISTING BUSINESS OCCUPANCIES AREAS OF REFUGE- IN BUILDINGS PROTECTED BY AN
APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM, IN ACCORDANCE WITH 101.9.7.1.1(1), TWO ROOMS OR SPACES SEPARATED FROM EACH OTHER BY SMOKE RESISTANT PARTITIONS IN ACCORDANCE WITH THE
DEFINITION OF AREA OF REFUGE IN 101.3.3.22 SHALL NOT BE REQUIRED.
D. EGRESS DISTANCES (MAXIMUM):
1. EXIT TRAVEL DISTANCE 200 FEET IBC TABLE 1016.1
ACTUAL MAX DISTANCE 111 FEET TO PRIMARY EXIT.
2. DEAD END CORRIDOR LENGTH 50 FEET IBC TABLE 601
ACTUAL DEAD END LENGTH 22 FEET
E. DOORS:
1. CORRIDORS/ SUITES: WD/HM FRAME RESIST THE PASSAGE OF SMOKE
NO REQUIREMENTS NFPA 101.39.3.6.
2. SMOKE PARTITIONS: WD/HM FRAME 20 MINUTE NFPA 101.8.3.4.2
TABLE 101.8.3.3.12.
3. SMOKE BARRIERS, 1 HOUR: WD/HM FRAME 20 MINUTE NFPA 101.8.3.4.2
4. FIRE BARRIERS, 1 HOUR: WD/HM FRAME 45 MINUTE NFPA 101.8.3.4.2
5. FIRE BARRIERS, 2 HOUR: WD/HM FRAME 90 MINUTE NFPA 101.8.3.4.2
F. OCCUPANT LOAD FACTORS WITH CALCULATIONS:
BASE BID W/ PRIVATE OFFICES
1. OCCUPANT LOAD FACTORS (NFPA TABLE 7.3.1.2
A. BUSINESS - CONCENTRATED USE (OPEN OFFICES): 50 SF / OCC.
1006 SF / 50 SF = 21 PEOPLE
B. ASSEMBLY - LESS CONCENTRATED USE: 15 SF / OCC.
517 SF / 15 SF / OCC. = 36 PEOPLE
C. BUSINESS - NON-CONCENTRATED USE: 100SF / OCC.
2,561 SF / 100 SF /OCC. = 26 PEOPLE
D. INCIDENTAL USE - MECHANICAL, HAC & OI&T ROOMS: 300SF / OCC.
522 SF / 300 SF / OCC. = 6 PEOPLE*
2. TOTAL OCCUPANCY AFTER RENOVATION: = 89 PEOPLE
*INCIDENTAL USE INCLUDES MECHANICAL ROOM (1 PERSON), OI&T ROOM (1 PERSON),
HAC CLOSET (1 PERSON) + 2 CLOSETS (2 PEOPLE)
DEDUCT ALTERNATE #5 W/ OPEN OFFICE AREA
1. OCCUPANT LOAD FACTOR (NFPA TABLE 7.3.1.2
A. BUSINESS - CONCENTRATION USE (OPEN OFFICES): 50 SF/ OCC.
2031 SF / 50 SF / OCC. = 41 PEOPLE
B. ASSEMBLY - LESS CONCENTRATED USE: 15 SF / OCC.
517 SF / 15 SF / OCC. = 36 PEOPLE
C. BUSINESS - NON-CONCENTRATED USE: 100 SF / OCC.
1,707 SF / 100 SF / OCC. = 18 PEOPLE
D. INCIDENTAL USE - MECHANICAL, HAC & OI&T ROOMS: 300 SF / OCC.
507 SF / 300 SF / OCC. = 5 PEOPLE
2. TOTAL OCCUPANCY AFTER RENOVATION = 100 PEOPLE
*INCIDENTAL USE INCLUDES MECHANICAL ROOM (1 PERSON), OI&T ROOM (1 PERSON),
HAC CLOSET (1 PERSON) + 1 CLOSET (1 PERSON)
G. SEISMIC DESIGN:
a. RENOVATION PROJECT MAY REQUIRE SEISMIC DESIGN CONSIDERATIONS FOR INSTALLATION OF NEW
SUSPENDED ACOUSTICAL CEILINGS AND FMEPT ITEMS.
b. CAMPUS IS LOCATED IN AN AREA THAT FALLS UNDER SEISMIC DESIGN CATEGORY ‘D’ (SS = 1.124G, S1 =
0.311G). NEED TO REVIEW WITH VA MARION ENGINEERING FOR CURRENT METHODS USED IN RENOVATIONS.
c. STATEMENT OF WORK DID NOT INCLUDE RETROFITTING OF PROJECT FOR STRUCTURAL SEISMIC UPGRADES.
NONE ARE BEING PURSUED AT THIS TIME.
H. BUILDING ENVELOPE/ OPAQUE THERMAL REQUIREMENTS:
a. ASHRAE 90.1-2013, ZONE 4 (TABLE 5.5-4):
1) ROOF: ATTIC R-30 CI.
2) EXTERIOR WALLS: MASS R-9.5 CI.
3) WALL BELOW GRADE: R-7.5 CI.
4) UNHEATED SLABS: R-15 FOR 24 IN.
5) HEATED SLABS: R-20 FOR 24 IN.
6) OPAQUE DOORS:
SWINGING U-0.500
NON-SWINGING U-0.500.
7) FENESTRATION/ VERTICAL GLAZING, 0% - 40% OF WALL:
I. METAL FRAMING, FIXED: U-0.42
II. METAL FRAMING, OPERABLE: U-0.50
III. METAL FRAMING, ENTRANCE DOOR: U-0.77
IV. SHGC: N-0.40
V. ASSEMBLY MINIMUM VT/SHGC: 1.10
b. IECC 2015: ZONE 4 (TABLES C402.1.3 (OPAQUE THERMAL ENVELOPE INSULATION COMPONENT MINIMUM REQUIREMENTS, R-FACTOR), C402.4 (BUILDING ENVELOPE FENESTRATION MAXIMUM U-FACTOR AND SHGC
REQUIREMENTS))
1) ROOF: ATTIC R-30CI.
2) EXTERIOR WALLS: MASS R-11.4CI.
3) WALL BELOW GRADE: R-10.0CI.
4) UNHEATED/HEATED SLABS: R-20 FOR 48”.
5) OPAQUE DOORS:
SWINGING U-0.450
NON-SWINGING U-0.450
6) FENESTRATION/ VERTICAL GLAZING, 0% - 40% OF WALL:
I. METAL FRAMING, FIXED: U-0.38
II. METAL FRAMING, OPERABLE: U-0.45
III. METAL FRAMING, ENTRANCE DOORS: U-0.77
IV. SHGC (PF < 0.2): SEW-0.40, N-0.53
V. SHGC (02.< PF < 0.5): SEW-0.48, N-0.58
VI. ASSEMBLY MINIMUM VT/SHGC: 1.10
APPLICABLE CODES & DESIGN STANDARDS
A. BUILDING CODES AND REGULATIONS (LATEST EDITIONS)
1. GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
a. MASTER CONSTRUCTION SPECIFICATIONS, PROGRAM GUIDE, PG-18-1
b. DESIGN AND CONSTRUCTION PROCEDURES, PG-18-3
c. STANDARD DETAILS, PG-18-4
d. EQUIPMENT GUIDE LIST, PG-18-5
e. EQUIPMENT REFERENCE MANUAL, PG-18-6
f. DESIGN MANUALS FOR APPLICABLE DISCIPLINES, PG-18-10
g. DESIGN GUIDES FOR SPACES AND GRAPHICS, PG-18-12
h. BARRIER FREE DESIGN GUIDE, PG-18-13 (SEE ITEM A.11 BELOW)
i. ENVIRONMENTAL COMPLIANCE MANUAL, PG-18-17
j. VA SUSTAINABLE DESIGN GUIDE
k. VA DIRECTIVES, DESIGN MANUALS AND DESIGN GUIDES
1) VA DESIGN ALERTS
2) VA QUALITY ALERTS
3) VA NATIONAL CAD STANDARD APPLICATION GUIDE AND BIM GUIDE
4) VA DRAWING TITLE BOX LAYOUT
5) VA AE DESIGN SUBMISSION REQUIREMENTS
6) VA DESIGN REVIEW CHECKLISTS
7) MINIMUM REQUIREMENTS FOR A/E SUBMISSIONS FOR MINOR AND MINOR MISCELLANEOUS PROJECTS, HANDBOOK H-18-15 VOLUME C
8) OFFICE OF CONSTRUCTION & FACILITIES MANAGEMENT DESIGN MANUAL, ARCHITECTURAL DESIGN MANUAL
9) VA MEDICAL CENTER MEMORANDUMS (MCM) (REQUEST FROM COR)
10) MANUAL FOR PREPARATION AND ISSUANCE OF CONSTRUCTION SOLICITATION AND CONTRACT DOCUMENTS
11) TECHNICAL SUMMARIES
12) ASBESTOS ABATEMENT DESIGN MANUAL
13) ELECTRICAL DESIGN MANUAL FOR HOSPITAL PROJECTS
14) FIRE PROTECTION DESIGN MANUAL
15) SEISMIC REQUIREMENTS
16) ESTIMATING MANUAL
17) VA FORM 10-6238 ESTIMATE WORKSHEET.
l. NATIONAL CODES AND STANDARDS (NFPA, NEC, NATL. PLUMBING CODE, EPA, OSHA, ETC.)
m. UNIFORM ACCESSIBILITY STANDARDS
2. NFPA AND VA FIRE PROJECTION MANUAL FOR FIRE PROTECTION.
3. NFPA 101 LIFE SAFETY CODE: ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES.
a. INTERNATIONAL BUILDING CODE (IBC): ITEMS NOT ADDRESSED IN NFPA 101, INCLUDING STRUCTURAL STRENGTH, SEISMIC
STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION.
4. NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900
5. OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
6. JOINT COMMISSION ON ACCREDITATION OF HEALTHCARE ORGANIZATIONS (JCAHO) REQUIREMENTS.
7. NATIONAL ELECTRICAL CODE (NEC)
8. INTERNATIONAL PLUMBING CODE (IPC)
9. ASME BOILER AND PRESSURE VESSEL CODE
10. ASME CODE FOR PRESSURE PIPING
11. AMERICAN WITH DISABILITIES ACT (ADA), ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA
SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)
12. STATE OF ILLINOIS DEPARTMENT OF NATURAL RESOURCES’ STATE HISTORIC PRESERVATION AGENCY (IHPA)
13. U.S. DEPT. OF THE INTERIOR-NATIONAL PARKS SERVICE - THE SECRETARY OF THE INTERIOR’S STANDARDS FOR REHABILITATION & ILLUSTRATED GUIDELINES ON SUSTAINABILITY FOR REHABILITATING HISTORIC BUILDINGS.
14. THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 01010 OF THE
VA MASTER CONSTRUCTION SPECIFICATION.
15. VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1- 2004.
16. SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15 – 2007.
17. AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR-CONDITIONING ENGINEERS (ASHRAE) STANDARD 90.1-2010, EXCEPT WHERE 90.1-2004 OR 90.1-2007 ARE REFERENCED OR ADOPTED BY SPECIFIC VETERANS AFFAIRS DESIGN AND CONSTRUCTION
PROCEDURES.
18. ENERGY POLICY ACT OF 2005 (EPACT) AND AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR-CONDITIONING
ENGINEERS (ASHRAE) STANDARD 90.1-2004 APPENDIX G.
19. EXTENDED INDUSTRY- STANDARD ARCHITECTURE (EISA) 2007 FOR NEW FACILITY FOSSIL FUEL GENERATED ENERGY
CONSUMPTION REDUCTION.
20. VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ). VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE
ENFORCEMENT PROCEDURES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 POC:
AH. INZ
6910 Pacific St #310
Omaha, NE 68106
Phone: 402.553.0234 POC:
IMEG Corp.
2882 106th Street
Des Moines, Iowa
Phone: 515.334.4303
POC:
AMI Enviromental
8802 S 135th Street
Omaha, NE 68138
Phone: 402.397.5001
POC:
BID SET
07/17/2019
Dwg. Of
C
L H
D C
\H o m e \a ta s t\
R
-2
B U
IL
D
IN
G
A lt e rn a te a ta s t.
rv t
/1
/2
:0
:5
P
M
15-GI102
LIFE SAFETY & CODE REVIEW RENOVATE BUILDING 15
VAHCS MARION, IL
657A5-18-111
7/17/2019 AHT KRK / TJF
5 73
BID SET
TABLE 2 - SUMMARY OF ASBESTOS MATERIALS TO BE ABATED
SHEET NO. DESCRIPTION FRIABLE EST. QTY. OF
ABATEMENT
15-1-HA102 FLOORING + MASTIC NO 510 SF
15-1-HA102 STUCCO SURFACING NO 570 SF
15-1-HA103 THERMAL SYSTEM INSULATION (TSI) YES 710 LF
15-1-HA103 TSI FITTINGS YES 60 EA.
TABLE 1 - SUMMARY OF LEAD-CONTAINING MATERIALS TO BE POTENTIALLY
IMPACTED
SHEET NO. DESCRIPTION PEELING OR
DELAMINATING EST. QTY.
15-1-HA101 STRUCTURAL STEEL NO NOT QUANTIFIED
15-1-HA101 PAINTED BLOCK WALLS NO 10,800 SF (BOTH SIDES)
15-1-HA101 PAINTED BRICK WALLS (EXTERIOR) NO 5,700 SF (INTERIOR SIDE
ONLY
15-1-HA101 STEAM PIPES NO 500 LF
15-1-HA101 ELECTRICAL CONDUIT NO 450 LF
15-1-HA101 DOWNSPOUTS NO 30 LF
15-1-HA101 ELECTRICAL BOXES NO 3 EA
15-1HA101 DOOR SILL PLATE NO 3 LF
GENERAL NOTES:
1. THESE DRAWINGS ARE DIAGRAMMATIC AND FOR GENERAL IDENTIFICATION OF ASBESTOS-CONTAINING MATERIALS (ACM) AND LEAD-BASED PAINT (LBP) SUBJECT TO REMOVAL OR DISTURBANCE. THEIR ACCURACY IS NOT GUARANTEED. LOCATIONS AND QUANTITIES SHOWN OF ACM AND LBP TO BE REMOVED ARE REPRESENTATIVE BASED ON RECENT AND PREEXISTING SITE SURVEY INFORMATION. THE ABATEMENT CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL MATERIAL LOCATIONS AND REMOVAL QUANTITIES, AND EXISTING SITE CONDITIONS. NO CONTRACT MODIFICATIONS WILL BE CONSIDERED FOR UNEXPECTED SITE CONDITIONS OR ABATEMENT QUANTITIES. BY BIDDING THE PROJECT, THE ABATEMENT CONTRACTOR ACKNOWLEDGES AND ACCEPTS ALL RISKS ASSOCIATED WITH SITE CONDITIONS AND
CONCEALED ACMS.
2. ASBESTOS REMOVAL IS BEING PERFORMED PURSUANT TO RENOVATION OF THE PROJECT AREAS. REMOVE AND DISPOSE OF ALL ACM IN ACCORDANCE WITH APPLICABLE REGULATIONS, PROJECT SPECIFICATIONS, AND THE APPROVED ASBESTOS HAZARD ABATEMENT PLAN (AHAP). IF SUSPECT ACMS ARE ENCOUNTERED DURING CONSTRUCTION AND DEMOLITION THAT ARE NOT IDENTIFIED ON THE ASBESTOS ABATEMENT DRAWINGS, STOP WORK AND CONTACT THE PROJECT MANAGER AND VPIH.
3. ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL REGULATIONS; PROJECT SPECIFICATIONS, THE APPROVED WORK PLAN, AND ACCEPTED INDUSTRY PRACTICE.
WHEN REQUIREMENTS OVERLAP OR CONFLICT, THE MOST STRINGENT REQUIREMENT SHALL APPLY.
4. DEMOLITION OF NON-ACM BUILDING MATERIALS MAY BE REQUIRED TO ACCESS REGULATED MATERIALS, INCLUDING, BUT NOT LIMITED TO, CABINETS, RAISED FLOORING, GYPSUM WALLBOARD, EXPANDED METAL OR WOOD LATH AND PLASTER WALLS AND CEILINGS, WALL FRAMING, CARPET, CERAMIC AND VINYL FLOOR COVERINGS, WOOD, ETC. THE ABATEMENT CONTRACTOR SHALL BE RESPONSIBLE FOR DEMOLITION OF
NON-ACM MATERIALS AS NEEDED TO ACCESS REGULATED MATERIALS FOR ABATEMENT, AND FOR
COORDINATING THE LIMITS OF DEMOLITION AND ABATEMENT WITH THE GENERAL CONTRACTOR.
5. ALL COSTS ASSOCIATED WITH EXPLORATORY DEMOLITION AND DEMOLITION OF NON-ACM MATERIALS NEEDED TO ACCOMPLISH ABATEMENT SHALL BE INCLUDED IN THE ABATEMENT CONTRACTOR'S LUMP SUM PRICE FOR THE PROJECT. NO ADDITIONAL COMPENSATION SHALL BE CONSIDERED FOR THIS WORK.
ASBESTOS NOTES:
1. THE PROJECT AREA WAS RECENTLY SURVEYED FOR ACM. REFER TO THE HAZARDOUS BUILDING MATERIALS INSPECTION REPORT BY AMI ENVIRONMENTAL, DATED DECEMBER 17, 2018, FOR MORE INFORMATION ABOUT ACMS IDENTIFIED IN THE PROJECT AREA. AMI REPORT INCLUDES A COPY OF A PREVIOUS ASBESTOS SURVEY.
2. CONCEALED ACM PIPE INSULATION (TSI) MAY EXIST WITHIN WALLS AND CHASES AND ABOVE RIGID CEILINGS.
COORDINATE ACCESS WITH DEMOLITION DRAWINGS AND THE GENERAL CONTRACTOR. SOME EXPLORATORY DEMOLITION MAY BE REQUIRED TO DETERMINE IF CONCEALED ACM IS PRESENT. CONCEALED WINDOWS MAY
EXIST AND MAY CONTAIN ACM WINDOW GLAZING OR LEAD-BASED PAINT.
3. ESTABLISH REGULATED AREAS (RA) AND NEGATIVE PRESSURE ENCLOSURES (NPE) AND PERFORM REMOVAL IN ACCORDANCE WITH APPLICABLE SPECIFICATION SECTIONS: SEC 02 82 13.13, GLOVEBAG ASBESTOS ABATEMENT; SEC 02 82 11, TRADITIONAL ASBESTOS ABATEMENT; SEC 02 82 13.19, ASBESTOS FLOOR TILE AND MASTIC ABATEMENT; 02 82 13.31 ASBESTOS TRANSITE AND CLASS II ABATEMENT. FINALIZE LIMITS OF REGULATED AREAS, LOCATIONS OF NEGATIVE AIR MACHINES (NAM), PERSONAL DECONTAMINATION FACILITIES (PDF), AND WASTE DECONTAMINATION FACILITIES (WDF) BASED ON SITE CONDITIONS, BEST
PRACTICES AND PHASING REQUIREMENTS.
4. ASSUME 50% EFFICIENCY WHEN CALCULATING NAM REQUIREMENTS FOR ACHIEVING FOUR (4) AIR CHANGES PER HOUR AND PROVIDED GREATER THAN -0.02” WCG PRESSURE. CONFIGURE AND PLACE NAMS AS NEEDED TO MAXIMIZE AIR MOVEMENT AND PREVENT DEAD AIR SPACE. COORDINATE NEGATIVE AIR DISCHARGE
LOCATIONS WITH GENERAL CONTRACTOR, OWNER'S REPRESENTATIVE, AND VPIH, IF NEEDED.
5. TSI ABATEMENT FROM SECTIONS OF PIPE AND FITTINGS TO BE DEMOLISHED MAY BE PERFORMED USING GLOVEBAGS TO ACCOMPLISH WRAP AND CUT METHODS IF APPROVED BY THE GENERAL CONTACTOR.
COORDINATE WITH MECHANICAL DEMOLITION DRAWINGS AND THE MECHANICAL CONTRACTOR.
6. ROOF MAY CONTAIN ACM INSULATION OR FLASHING. SAMPLE PRIOR TO REMOVAL OR ASSUME AS ACM.
7. FIRE RATED DOORS MAY CONTAIN ASBESTOS. SAMPLE PRIOR TO REMOVAL OF ASSUME AS ACM.
PAINT CONTAINING LEAD:
1. LEAD-BASED PAINT (LBP) ARE PAINTS THAT CONTAIN LEAD ≥1.0 mg/m² or ≥ 0.5 PERCENT BY WEIGHT.