QUESTIONS AND ANSWERS

N4019220R7093 MECHANICAL SERVICES (36 CES)

Q1: For the Commercial Range Hoods can we know the location and access to the exhaust fans? We need to incorporate any additional equipment needed for them.

A1: Refer to attachment J‐0200000‐08 for the Facility Number. Most facilities have roof access ladders. If a ladder is not attached to the facility an extension ladder will be sufficient to access the roof top. Some areas may require access coordination upon service.

Q2: Reviewing the J-0200000-08 Mechanical Services Inventory page, can you furnish answers for the following? Facility Number 817002 Fire Station 1; how many

Commercial Range Hood does this facility have?

A2: Fire Station 1 is Facility Number B17002 and has one (1) hood and duct system.

Q3: Reviewing the J-0200000-08 Mechanical Services Inventory page, can you furnish answers for the following? Facility Number 89509 Bamboo Willies; how many

Commercial Range Hoods does this location have?

A3: B9509, Bamboo Willies has one (1) hood and duct system.

Q4: Is Andersen AFB requesting for a Cooling Water Treatment Program for B25014 and B32? This includes the chemicals, conductivity controller, chemical feed pumps, bleed off solenoid valves, and water analysis.

A4: Yes, this requirement is to provide Cooling Water Treatment Program for B25014 and B32.

Q5: Is Andersen AFB requesting for a Boiler Water Treatment Program for B25010 and

B26006? This includes the chemicals, chemical feed pumps, and water analysis.

A5: Yes, this requirement is to provide Cooling Water Treatment Program for B25010 and B26006

Q6: If you are requesting a water treatment program for these facilities can the request be reworded as "Cooling Water Treatment Program" and "Boiler Water Treatment Program" so as not to be confused into just servicing the "Water Softeners" and "Boilers" themselves?

A6: ELINS A006/007, B006/007 and C006/007 shall now read Provide Preventative

Maintenance on Boiler Water Treatment System and Preventative Maintenance on

Closed Loop Water Treatment System. The word treatment shall strictly refer to the treatment side of the system.

Q7: If you are requesting a water treatment program for these facilities can the request be so as not to be confused into just servicing the "Water Softeners" and "Boilers" themselves?

A7: ELINS A006/007, B006/007 and C006/007 shall now read Provide Preventative

Maintenance on Boiler Water Treatment System and Preventative Maintenance on

Revised Jun 2017

Closed Loop Water treatment system. The word treatment shall strictly refer to the

Q8: If you are requesting a water treatment program for these facilities can the request be so as not to be confused into just servicing the "Water Softeners" and "Boilers" themselves?

A8: ELINS A006/007, B006/007 and C006/007 shall now read Provide Preventative

Maintenance on Boiler Water Treatment System and Preventative Maintenance on

Closed Loop Water treatment system. The word treatment shall strictly refer to the