MILITARY SEALIFT COMMAND

N32205-18-R-4152

QUESTIONS AND ANSWERS #3

The following are answers to questions received from potential offerors. The answers provide clarification only and do not constitute an amendment to the solicitation.

1. Work Item 102 – paragraph/section 7.8, calls for an insert in the deck of the Port Jet Equipment Room between frames 79 and 80, however those frames are located in the Aft Peak Void. Please provide location and size of the insert.

ANSWER: Frames should have stated 78 and 79. Port Jet Equipment Room is the location. For estimating purposes assume the minimum ABS size insert 12 inches by 12 inches. All locations shall be cropped out to replace areas of corrosions. Locations are approximate estimates; contractor shall verify exact dimensions of repair required. WI 102 has been modified. WI 102 will be provided via AMRDEC Safe.

2. Work Item 104 – paragraph/section 3.1, lists spaces with square feet (e.g. main engine room bilge at 4350 square feet each). However, paragraphs 3.2.1, 3.2.2 and 3.2.4 lists square footage in each location as well and doubles it (e.g. main engine room bilge at 8700 square feet each). Do we estimate the square footage in 3.1 or 3.2?

ANSWER: Paragraph 3.2.1 is referencing two locations 5-52-1 and 5-52-2 for a total 8700 sqft. Paragraph 3.2.2 is referencing two locations 5-16-1 and 5-16-2 for a total of 1100 sqft. Paragraph 3.2.3 is referencing two locations 3-16-1 and 3-16-2 for a total of 500 sqft. The below chart shows the individual space listing with the individual sqft.

Main Engine Rooms

Description
Location
Paint Quantity (Total)
Area

(sqft)

Port
5-52-2
32 Gal
4350
Starboard
5-51-1
32 Gal
4350

Pump Rooms 1 and 2

Description
Location
Paint Quantity
Area

(sqft)

Port 2nd Platform
3-16-2
2 Gal
250
Starboard 2nd Platform
3-16-1
2 Gal
250
Port
5-16-2
4 Gal
550
Starboard
5-16-1
4 Gal
550

3. Work Item 107 – Please define the locations and amount of plate to be replaced in FW Fuel Storage Tank and STBD Pump Room 1.

ANSWER: Paragraph 7.2.8 and 7.2.9 are applicable. For bidding purposes estimate Fuel Tank BHD to be 18 inches by 121 inches. Inboard shell section shall be 12 inches by 36 inches. For bidding purposes Pump Room 1 deck insert shall be 30 inches by 36 inches. All locations shall be cropped out to replace areas of corrosions. Locations are approximate estimates; contractor shall verify exact dimensions of repair required.