MQ-008.pdf
PDF 199 KB Posted
- Attached to
- Expand and Upgrade Building 42 for Laboratory
- Solicitation number
- 36C25520R0073-0007
About this file
This document contains mechanical drawings and specifications for an air handling unit to be installed as part of the Expand and Upgrade Building 42 for Laboratory project. Key details include mechanical equipment such as air handling units, fans, coils, dampers and controls to provide temperature regulation, humidity control, air filtration and smoke detection for the facility. Specific equipment includes variable speed motor controllers, modulating control valves, temperature and humidity sensors throughout the air distribution system. The air handling unit will provide temperature conditioned supply air to terminal box units with reheat coils for further temperature control at the room level.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| MC-101.pdf | ||
| 36C25520R0073 0007.docx | DOCX document | |
| FINAL QUESTIONS AND ANSWERS 657-502.docx | DOCX document | |
| MQ-011.pdf | ||
| MQ-009.pdf | ||
| 233600 - Air Terminal Units R1.doc | DOC document | |
| 074213.23 SF - METAL COMPOSITE MATERIAL WALL PANELS.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS:
42-AdditionApproved: Associate Director
Approved: Chief of Staff
Approved: Chief Engineer
Approved: Infection Control
Approved: Safety Officer
Approved: Chief, Police & Security o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
1 Memorial Dr. STE 1800 Saint Louis, MO 63102 Tel
Fax
314.621.4343 314.621.0261
220 N College Ave Indianapolis, IN 46202 Tel
Fax
317.464.9090 317.464.9393
Office of Facilities
ManagementMcComas Engineers 1717 E 116th Street Carmel, IN 46032 Tel
Fax
317.580.0402 317.582.0766
Structural Asaturian Eaton & Assoc.
1440 Old West Main Carbondale, IL 62901 Tel
Fax
618.529.3414 618.529.3423
Civil John A Jurgiel & Assoc.
123 N. Main Street St. Charles, MO 63301 Tel
Fax
636.757.3060 636.757.3064
Industrial Hygenist Holcomb Foundation 393 Wood Road Carbondale, IL 62901 Tel
Fax
618.529.5262 618.457.8991
Geotechnical
SHEET UPDATED PER ADDENDUM 08-06-20
ENGINEER
S
T
A
T
E
O
F
I
L
L
N
O
I
S
E
R
A
W
L
U
O
B E
D
A
W
L
R
A
E
I
062-044274
REGISTERED
PROFESSIONAL
Expand & Upgrade Building 42 for Laboratory
657-502
Marion, IL
11-07-2019
Bid Document
DH BZ
MECHANICAL DETAILS
MQ-008
F
LEGEND AHU SEQUENCE OF OPERATION
CONTROL SCHEMATIC AHU-1
VAV REHEAT OR CONSTANT VOLUME
TYPE "F" AIR TERMINAL UNIT CONTROL DIAGRAM
FSD-2 SUPPLY AIR FIRE/SMOKE DAMPER
CLOSES WHEN UNIT IS SHUT
OFF OR WHENEVER SMOKE
IS DETECTED BY F SD.
RETURN AIR FIRE/SMOKE DAMPERFSD-1
BY F SD.
OR WHENEVER SMOKE IS DETECTED
CLOSES WHEN UNIT IS SHUT OFF
SUPPLY AIR HUMIDITY SENSORH-2
CONTROL AND INDICATION
AIR HUMIDITY TO DCP FOR
SENSES AND TRANSMITS SUPPLY
H-1 RETURN AIR HUMIDITY SENSOR
CONTROL AND INDICATION
AIR HUMIDITY TO DCP FOR
SENSES AND TRANSMITS RETURN
G FILTER CONDITION INDICATORPRESSURE GAUGE
DUCT SMOKE DETECTORS
(FURNISHED AND WIRED TO
FIRE ALARM PANEL BY ELECTRICAL)
SENSES AND TRANSMITS SMOKE
CONDITIONSD
ECC ENGINEERING CONTROL CENTER FOR MONITORING OF
SYSTEM OPERATIONS.
D-2 RETURN AIR DAMPER MODULATING
DCP DISTRIBUTED CONTROL PANEL
CONTROLS OPERATION OF AIR
WITH THE SEQUENCE OF OPERATION.
HANDLING UNIT IN ACCORDANCE
P DIFFERENTIAL PRESSURE SENSOR
TRANSMITS DIFFERENTIAL PRESSURE
CONDITIONS AND STATUS OF FANS.
TO DCP TO INDICATE FILTER
AFM AIR FLOW MEASURING DEVICE
MONITORS AIR FLOW RATE
FOR TRANSMITTAL TO DCP.
PROVIDES VELOCITY PRESSURE
PROPORTIONS FLOW OF
RETURN AIR IN RESPONSE
TO DCP.
STATIC PRESSURE SENSOR
(SEE FLOOR PLANS FOR
LOCATION)
SPS-1 SENSES AND TRANSMIT DUCT
STATIC PRESSURE TO DCP.
SENSOR
HIGH LIMIT STATIC PRESSURE SENSES AND TRANSMITS DUCT
STATIC PRESSURE NEAR AHU TO
DCP.
SPS-2
SUPPLY AIR TEMPERATURE
SENSOR
SENSES AND TRANSMITS SUPPLY
AIR DRY BULB TEMPERATURE TO
DCP FOR CONTROL AND INDICATION.
OUTSIDE AIR TEMPERATURE
SENSOR
SENSES AND TRANSMITS OUTSIDE
AIR DRY BULB TEMPERATURE TO
DCP FOR CONTROL AND INDICATION.
T-1
T-2
AIR TEMPERATURE SENSOR
(FREEZE PROTECTION)
LEAVING PREHEAT COIL AIR
DCP FOR CONTROL AND INDICATION.
AIR DRY BULB TEMPERATURE TO
SENSES AND TRANSMITS PREHEAT
T-3
T-4
T-5
T-6
V-1
V-2
RETURN AIR
TEMPERATURE SENSOR
SENSES AND TRANSMITS RETURN
AIR DRY BULB TEMPERATURE TO
DCP FOR INDICATION ONLY.
DCP FOR INDICATION ONLY.
AIR DRY BULB TEMPERATURE TO
SENSES AND TRANSMITS MIXED
SENSOR
MIXED AIR TEMPERATURE
SENSOR
AIR TEMPERATURE
LEAVING COOLING COIL
DCP FOR INDICATION ONLY.
COIL DRY BULB TEMPERATURE TO
SENSES AND TRANSMITS COOLING
COIL IN RESPONSE TO DCP.
CHILLED WATER TO COOLING
PROPORTIONS FLOW OFCHILLED WATER CONTROL VALVE
TYPE
TWO WAY MODULATING
STEAM CONTROL VALVE
MODULATING TWO WAY
PROPORTIONS FLOW OF
HEATING WATER TO PREHEAT COIL
IN RESPONSE TO DCP.
TO HUMIDIFIER IN RESPONSE TO DCP.
PROPORTIONS FLOW OF STEAM
MODULATING HUMIDIFIER
HEATING WATER CONTROL VALVE
V-3
SENSES AND TRANSMITS
VELOCITY PRESSURE TO DCP.
RETURN FANS MOTOR SPEED
IN RESPONSE TO DCP.
CONTROLS SUPPLY AND
CONTROLLER WITH MOTOR
VARIABLE SPEED MOTOR
STARTER
VPS
VSMC
VELOCITY PRESSURE SENSOR
UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT
THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION.
"HAND" AND "OFF" SHALL BE USED ONLY FOR MAINTENANCE. WHEN UNIT
IS "OFF" D-1, FSD-1 AND FSD-2 SHALL BE FULLY CLOSED. WHEN
UNIT IS "ON" FSD-1 AND FSD-2 SHALL BE FULLY OPEN. D-1 AND D-2
SHALL MODULATE IN ACCORDANCE WITH THE FOLLOWING SEQUENCE:
THE SUPPLY AIR TEMPERATURE, SENSED BY T-1, SHALL BE MAINTAINED
AT SETPOINT BY DCP MODULATING V-1 OR D-1, D-2 AND V-2
IN SEQUENCE.
THE DCP USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS SHALL
RESET THE RETURN FAN VSMC TO MAINTAIN A CONSTANT CFM DIFFERENCE
BETWEEN THE CFM FOR THE SUPPLY FAN AND THE CFM FOR THE RETURN
FAN.
3. AIR FLOW CONTROL
2.4
2.3
2.1
2.2
1.1
2.
1. GENERAL
TEMPERATURE CONTROL
3.1
THE DCP USING HIGH PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY
FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER
THREE INCHES OF STATIC PRESSURE. IF STATIC PRESSURE AT SPS-2
EXCEEDS THREE INCHES SUPPLY FAN SHALL SHUT "OFF".
FREEZE PROTECTION
IF THE AIR TEMPERATURE AS SENSED BY T-3 FALLS BELOW 45°F, AN
ALARM SIGNAL SHALL BE INDICATED AT THE DCP AND ECC. IF THIS
TEMPERATURE FALLS BELOW 40°F, THE UNIT SUPPLY AND RETURN FANS
SHALL SHUT "OFF" AND A CRITICAL ALARM SHALL BE INDICATED AT THE
DCP AND ECC.
AUTOMATIC SHUTDOWN/RESTART
EMERGENCY CONSTANT SPEED OPERATION
ON ALL VSMC FANS IN VAV SYSTEMS UPON FAILURE OF THE VSMC THE
FANS SHALL BE STARTED/STOPPED MANUALLY AT THE DCP OR THE ECC
THROUGH THE BY-PASS STARTER. FANS SHALL THEN BE OPERATED AT
CONSTANT DESIGN SPEED.
4.
5.
6.
4.1
5.1
6.1
T- 2 5
C
M
D
P
6 7
D-1
P R
E -F
IL
T
E R
T-5 T-3PR
EH
EA
T
CO
IL
CO
IL
CO
OL
IN
G
CH
W
R
G
V-1
T-6
P
VSMC
H
T-1
E
P
AF
TE
R
FI
LT
ER
SPS-2 F
J
M
FSD-2
SD
H-2
SPS-1
SUPPLY AIR TO
TERMINAL UNITS
MB
D-2
SUPPLY
FAN
T-4
4 3
H-1 M
A
F
SD
FSD-1
LOCATE OUTSIDE
UNDER SHIELD
1 2 3 4 5 6 7 8 9 10 11 12 13 14
A B C D E F G H J K
INPUT
DCP
OUTPUT
(DDC)
M
DDC FLOW
CONTROLLER
T-7
UNIT
TERMINAL
HWH
HWHR
REHEAT COIL
V-4
VPS
AF
M
AIR
OUTSIDE
VPS
2-WAY CONTROL
VALVE UNLESS
OTHERWISE
INDICATED
OUTSIDE AIR DAMPER (MODULATING)D-1
RESPONCE TO DCP.
AIR IN ECONOMISER MODE IN
PROPORTIONS FLOW OF OUTSIDE
2-WAY CONTROL
VALVE UNLESS
OTHERWISE INDICATED
ROOM THERMOSTAT T-7 SHALL CONTROL OPERATOR FOR VARIABLE AIR
VOLUME ON CONSTANT VOLUME REHEAT BOX AND REHEAT COIL VALVE
V-4. ON A DROP IN ROOM TEMPERATURE TO THE SET POINT ROOM
THERMOSTAT T-7, THRU OPERATOR, SHALL REDUCE AIR FLOW TO THE ROOM
TO THE BOXES MINIMUM SETTING. ON A FURTHER DROP IN ROOM
TEMPERATURE BELOW THE SET POINT ROOM THERMOSTAT T-7 SHALL MODULATE
VALVE V-4 AND INCREASE AIR FLOW TO THE BOXES SCHEDULED REHEAT COIL
CFM TO MAINTAIN THE REQUIRED TEMPERATURE.
T-7
SENSES AND TRANSMITS SPACE
TEMPERATURE TO TERMINAL BOX
FLOW CONTROLLER.
SPACE AIR TEMPERATURE SENSOR
3.4
SD
INLET PROBES
FAN VOLUME
THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DCP MODULATING
SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO MAINTAIN
THE DUCT STATIC PRESSURE SETPOINT (SET AT 0.75 INCHES STATIC
PRESSURE) AS SENSED BY SPS STATIC PRESSURE SENSOR (SEE PLANS
FOR LOCATION).
WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY T-2, IS BELOW
THE SUPPLY AIR TEMPERATURE, SENSED BY T-1, THEN DAMPERS D-1M
SHALL BE FULLY OPEN, DAMPERS D-1 AND D-2 SHALL MODULATE
TO MAINTAIN THE SCHEDULED SUPPLY AIR TEMPERATURE. IF D-2 IS
OPEN, D-1 AND D-3 ARE CLOSED THEN V-2 SHALL MODULATE OPEN TO
MAINTAIN THE SUPPLY AIR TEMPERATURE. SET POINT AS SENSED BY T-1.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY T-2, IS
BETWEEN 65°F AND THE SUPPLY AIR TEMPERATURE SETPOINT T-1, DAMPER
D-2 SHALL BE FULLY CLOSED AND D-1, D-1M SHALL BE FULLY
OPENED (MAXIMUM OUTSIDE AIR POSITION). THE DCP SHALL MODULATE
V-1 TO MAINTAIN THE SUPPLY AIR TEMPERATURE, SENSED BY T-1.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY T-2, IS ABOVE
65°F, THE DCP SHALL OPEN D-1M TO MINIMUM POSITION, D-2 SHALL BE
FULLY OPEN, D-1 SHALL BE CLOSED. THE DCP SHALL MODULATE
V-1 TO MAINTAIN THESUPPLY AIR TEMPERATURE, SENSED BY T-1.
NO SCALE 3.2
3.3
OUTSIDE AIR FLOW SHALL BE MEASURED BY AN AIR FLOW MEASURING
STATION LOCATED IN THE MINIMUM OUTSIDE AIR DUCT.
WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTORS F SD SHOWN
ABOVE, THE SUPPLY AND RETURN FANS SHALL SHUT "OFF" AND AN ALARM
SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. FOR ALARM
PURPOSES ONLY ALL FIRE/SMOKE DAMPERS IN THE SUPPLY AND RETURN
DUCTS SHALL CLOSE. EXHAUST FANS SERVING SPACE OF SUPPLY FAN
SHALL CONTINUE TO RUN. SUPPLY AND RETURN FANS SHALL RESTART AND
FIRE/SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM CIRCUIT IS RESET.
C
MQ008
A
MQ008
HW
R
F
V-2
HW
S
RETURN AIRVPS
AF
M
K
V-3
LP
S
HUMIDIFIER
H-3
SUPPLY AIR HUMIDITY SENSORH-3
CONTROL AND INDICATION
AIR HUMIDITY TO DCP FOR
SENSES AND TRANSMITS SUPPLY
HEATING WATER CONTROL VALVES
TO TERMINAL UNIT
PROPORTIONS FLOW OF HEATING WATER
MODULATING TWO WAYV-4
RI
VPS
AF
M
SOAI
HW
18 19
W F 18
WFMD-1A
CH
W
S W
F 19
WFMD-1B
SENSE AND TRANSMITS GPMHEATING WATER FLOW METERWFMD-1A
SENSE AND TRANSMITS GPMCHILLED WATER FLOW METERWFMD-1B