DHQCAP17MP60014__QA__ROUND_2.pdf
PDF 190 KB Posted
- Attached to
- DISA Ogden High Density (HD) Computer Room Air Handler (CRAH) & Power Distribution Units (PDU) Install
- Solicitation number
- HC1028-17-R-0186
- Issued by
-
Defense Information Systems Agency
About this file
QA_ Round 2
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 17R0186__AMD0005.docx | DOCX document | |
| 17R0186__AMD0006.docx | DOCX document | |
| 17R0186__AMD0004.docx | DOCX document | |
| DHQCAP17MP60014__QA.pdf | ||
| 17R0186__AMD0003.docx | DOCX document | |
| 17R0186_AMD0002.docx | DOCX document | |
| 17R0186__AMD0001.docx | DOCX document | |
| Attachment_1__QASP.docx | DOCX document | |
| Attachment_2__Pricing_sheet.xlsx | XLSX spreadsheet | |
| HC1028-17-R-0186__RFP.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question Government Response
Plumbing;
a. We need the specifications for the new humidifier based on 6.2.2.3
b. Provide specifications for the existing humidifier to be relocated based on 6.2.5.3
a. New humidifier shall be of the same or similar to
Dristeem VM-34. b. Contractor shall validate on-site.
2. Access flooring;
a. HC1028-17-R-0186_RFP 5.4.1 replace the raised floor in room 146
- 6.3.11 Raised floor modifications is required to install the new equipment. Provide specifications of existing access floor system.
Answer provided in 2b.
- Based on appendix L, r, Installation & Leveling. This access floor system to be installed needs to be laser leveled, to do so we need a complete empty room.
Which is the opposed to what 6.5.1.3 requires.
The majority of the room is free and clear. This requirements holds, however for the localized areas where there are existing racks, the Government will accept matching the height with the surrounding new floor that is laser leveled.
- 6.5.1.3 what is the size and weight of the ten (10) IT racks that will require temporary structural support.
These racks must be lifted at least 24” to be able to replace the raised access floor system, can this be done?
The average weight for an IT rack is between 300 and 2500 pounds. Previous floor replacements were accomplished with the racks being lifted only 3 inches.
- 6.5.1.10 Provide specifications for the vinyl base
In 6.5.1.10, there is a typo. Please read as "Install new vinyl cove base...". Match the existing height of the vinyl cove in
Room 145.
Question & Answer, Round 2
b. For all rooms 145, 146, 147, 216, and 234 where
CRAH, PDU, & humidifier work will be done, the access floor system will be removed and some replaced.
Provide specifications and manufacturer for the access floor system.
The existing raised floor in Rooms 145, 146, 147 and 234 is
Tate 1500. The existing raised floor in Room 216 is Tate
2500.