Questions and Responses.pdf

PDF 78 KB Posted

Attached to
WPAFB Construction - Replace Steam Lines, Project 04-0052
Solicitation number
FA8601-08-R-0034
Issued by

About this file

Questions Responses

View the file

Other files

File Type Posted
Wage Dec OH080002 Mod 8.pdf PDF
Amendment 0006.doc DOC document
Amendment 0005.doc DOC document
Amendment 0004.doc DOC document
Amendment 0003.doc DOC document
Addendum 2.doc DOC document
Site Visit Attendance.pdf PDF
Conformed Solicitation.doc DOC document
Amendment 0002.doc DOC document
Amendment 0001.doc DOC document
Wage Dec OH080002 Mod 7.pdf PDF
Addendum 1.doc DOC document
Solicitation.doc DOC document
Specs 04-0052.pdf PDF
Drawings 05-0013.pdf PDF
Specs 05-0013.pdf PDF
Wage Decision OH080029 4 Jul 08 Mod 6.docx DOCX document
Drawings 04-0052.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Responses for FA8601-08-R-0034, Project 04-0052, Replace Steam Lines, WPAFB

Q1. Please provide a pavement detail for the parking apron shown on Sheet CME-6 that we are to cut through between stations 4+50 and 10+50.

R1: THE DETAIL TO USE IS SHOWN ON SHT. M-10.

Q2: On Sheet CME-6, Note 3 states to provide a 2” HPR direct-buried pipe between vaults S-299 and S-300, but the vault details on Sheets M-14 and M-15 do not show this 2” pipe. Please clarify.

R2: DELETE CODED NOTE #3 SHOWN ON THE PLAN VIEW INBETWEEN MANHOLES S-299 & S-300.

THIS WILL BE STATED ON ADDENDUM #2. SHEETS M-14 & M-15 ARE CORRECT; NO 2" HPR IS TO

BE INSTALLED BETWEEN MANHOLES S-299 & S-300.