SECTION TABLE OF CONTENTS
DIVISION 32 - EXTERIOR IMPROVEMENTS
SECTION 32 31 13.53
HIGH-SECURITY CHAIN LINK FENCES AND GATES
04/08
PART 1 GENERAL
| 1.1 | REFERENCES |
| 1.2 | SUBMITTALS |
| 1.3 | QUALITY ASSURANCE |
| 1.3.1 | Required Report Data |
| 1.3.2 | Assembly and Installation Drawings |
| 1.4 | DELIVERY, STORAGE, AND HANDLING |
PART 2 PRODUCTS
| 2.1 | FENCE FABRIC |
| 2.1.1 | General |
| 2.1.2 | Approval Of Polyvinyl Chloride-Coated Fence Materials |
| 2.2 | POSTS |
| 2.2.1 | Metal Posts for Chain Link Fence |
| 2.2.2 | Accessories |
| 2.3 | BRACES AND RAILS |
| 2.4 | WIRE |
| 2.4.1 | Wire Ties |
| 2.4.2 | Barbed Wire |
| 2.4.3 | Tension Wire |
| 2.5 | BARBED TAPE (RAZOR WIRE) |
| 2.6 | CONCRETE |
| 2.7 | GATES |
| 2.7.1 | Gate Assembly |
| 2.7.2 | Gate Leaves |
| 2.7.3 | Gate Hardware and Accessories |
| 2.8 | TURNSTILES |
| 2.9 | PADLOCKS |
| 2.10 | GATE OPERATOR |
| 2.11 | ELECTRO-MECHANICAL LOCKS |
PART 3 EXECUTION
| 3.1 | FENCE INSTALLATION |
| 3.1.1 | Line and Grade |
| 3.1.2 | Excavation |
| 3.1.3 | Concrete Slabs and Walls |
| 3.2 | POST INSTALLATION |
| 3.2.1 | Earth and Bedrock |
| 3.2.2 | Concrete Slabs and Walls |
| 3.3 | RAILS |
| 3.4 | FABRIC INSTALLATION |
| 3.5 | SUPPORTING ARMS |
| 3.6 | BARBED TAPE (RAZOR WIRE) INSTALLATION |
| 3.7 | GATE INSTALLATION |
| 3.8 | GROUNDING |
| 3.9 | SECURITY |
| 3.10 | CLEANUP |
-- End of Section Table of Contents --
SECTION 32 31 13.53
Page
SECTION 32 31 13.53
HIGH-SECURITY CHAIN LINK FENCES AND GATES
04/08
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A116 (2011) Standard Specification for Metallic-Coated, Steel Woven Wire Fence Fabric
ASTM A121 (2007) Standard Specification for Metallic-Coated Carbon Steel Barbed Wire
ASTM A153/A153M (2009) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A176 (1999; R 2009) Standard Specification for Stainless and Heat-Resisting Chromium Steel Plate, Sheet, and Strip
ASTM A392 (2011a) Standard Specification for Zinc-Coated Steel Chain-Link Fence Fabric
ASTM A478 (1997; R 2008) Standard Specification for Chromium-Nickel Stainless Steel Weaving and Knitting Wire
ASTM A491 (2011) Standard Specification for Aluminum-Coated Steel Chain-Link Fence Fabric
ASTM A666 (2010) Standard Specification for Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate and Flat Bar
ASTM A702 (1989; R 2006) Standard Specification for Steel Fence Posts and Assemblies, Hot Wrought
ASTM A780/A780M (2009) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A824 (2001; R 2007) Standard Specification for Metallic-Coated Steel Marcelled Tension Wire for Use With Chain Link Fence
ASTM B117 (2011) Standard Practice for Operating Salt Spray (Fog) Apparatus
ASTM C94/C94M (2012) Standard Specification for Ready-Mixed Concrete
ASTM F1043 (2011a) Strength and Protective Coatings on Metal Industrial Chain-Link Fence Framework
ASTM F1083 (2010) Standard Specification for Pipe, Steel, Hot-Dipped Zinc Coated (Galvanized) Welded, for Fence Structures
ASTM F1184 (2005; R 2010) Industrial and Commercial Horizontal Slide Gates
ASTM F567 (2011a) Standard Practice for Installation of Chain Link Fence
ASTM F626 (2008) Standard Specification for Fence Fittings
ASTM F668 (2011) Poly(Vinyl Chloride) (PVC) and other Organic Polymer-Coated Steel Chain-Link Fence Fabric
ASTM F883 (2009) Padlocks
ASTM F900 (2011) Industrial and Commercial Swing Gates
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FS RR-F-191 (Rev K) Fencing, Wire and Post Metal (and Gates, Chain-Link Fence Fabric, and Accessories)
FS RR-F-191/1 (Rev F) Fencing, Wire and Post, Metal (Chain-Link Fence Fabric)
FS RR-F-191/2 (Rev E) Fencing, Wire and Post, Metal (Chain-Link Fence Gates)
FS RR-F-191/3 (Rev E; Am 1) Fencing, Wire and Post, Metal (Chain-Link Fence Posts, Top Rails and Braces)
FS RR-F-191/4 (Rev F) Fencing, Wire and Post, Metal (Chain-Link Fence Accessories)
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fence Installation Installation Drawings Location of Gate, Corner, End, and Pull Posts Gate Assembly Turnstiles Gate Hardware and Accessories
SD-03 Product Data
Fence Installation Gate Assembly Gate Hardware and Accessories
SD-04 Samples
Fabric Posts Post Caps Braces Line Posts Sleeves Top Rail Bottom Rail Tension Wire Barbed Wire Barbed Wire Supporting Arms Barbed Tape Stretcher Bars Gate Posts Gate Hardware and Accessories Turnstiles Padlocks Wire Ties SD-06 Test Reports Zinc Coating PVC Coating Aluminum Alloy Coating
SD-07 Certificates
Chain Link Fence Reports Zinc Coating PVC Coating Aluminum Alloy Coating Fabric Barbed Wire Stretcher Bars Gate Hardware and Accessories Concrete Gate Operator
SD-08 Manufacturer's Instructions
Fence Installation Gate Assembly Hardware Assembly Accessories
SD-10 Operation and Maintenance Data
Electro-Mechanical Locks Gate Operator Operating and Maintenance Instructions
1.3 QUALITY ASSURANCE
1.3.1 Required Report Data
Submit reports, signed by an official authorized to certify on behalf of the manufacturer, of chain-link fencing listing and accessories regarding weight in ounces for zinc coating, thickness of PVC coating, and chemical composition and thickness of aluminum alloy coating. Submit reports demonstrating full compliance with the following standards: FS RR-F-191, FS RR-F-191/1, FS RR-F-191/2, FS RR-F-191/3, and FS RR-F-191/4.
1.3.2 Assembly and Installation Drawings
Submit Manufacturer's instructions and complete Fence Installation Drawings for review and approval by the Contracting Officer prior to shipment. Drawing details shall include, but are not limited to: Fence Installation, Location of gate, corner, end, and pull posts, Gate Assembly, Turnstiles, and Gate Hardware and Accessories.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver materials to site in an undamaged condition. Store materials off the ground to provide protection against oxidation caused by ground contact.
PART 2 PRODUCTS
2.1 FENCE FABRIC
2.1.1 General
Provide ASTM A392, Class 2, zinc-coated steel wire with minimum coating weight of 2.0 ounces of zinc per square foot of coated surface, or ASTM A491, Type I, aluminum-coated steel wire. Fabricate fence fabric of 9 gauge wire woven in 2 inch mesh conforming to ASTM A116. Set fabric height as stated in each individual task order Statement of Work. Fabric shall be twisted and barbed on the top and bottom selvages. Secure fabric to posts using stretcher bars or ties spaced 15 inches on center, or by integrally weaving to integral fastening loops of end, corner, pull, and gate posts for full length of each post. Install fabric on opposite side of posts from area being secured.
2.2 POSTS
2.2.1 Metal Posts for Chain Link Fence
Provide posts conforming to ASTM F1083, zinc-coated. Group IA, with external coating Type A steel pipe. Group IC steel pipe, zinc-coated with external coating Type A or Type B and Group II, roll-formed steel sections, meeting the strength and coating requirements of ASTM F1043 and ASTM A702. Group III, ASTM F1043 steel H-section may be used for line posts in lieu of line post shapes specified for the other classes. Post shall be either Group IA steel pipe, Group IC, Group II, roll-formed steel sections, or Group III steel H-sections and be zinc coated (Type A) and conforming to the requirements of ASTM F1043. Provide sizes as shown on the drawings. Line posts and terminal (corner, gate, and pull) posts selected shall be of the same designation throughout the fence. Provide gate post for the gate type specified subject to the limitation specified in ASTM F900 and/or ASTM F1184. Post spacing shall conform to the recommended guidelines as set forth in the CLFMI "Wind Load Guide for the Selection of Line Post Spacing and Size" unless specified to exceed those guidelines. FS RR-F-191/3 line posts; Class 1, steel pipe, Grade A. End, corner, and pull posts; Class 1, steel pipe, Grade A.
2.2.2 Accessories
a. Provide accessories conforming to ASTM F626. Ferrous accessories shall be zinc coated.
b. Furnish truss rods for each terminal post. Provide truss rods with turnbuckles or other equivalent provisions for adjustment.
c. Provide Barbed wire supporting arms, as directed in each individual task Statement of Work, of the single 45 degree outward angle 3-strand or the V 6-strand arm type and of the design required for the post furnished. Secure arms by top tension wire.
d. Furnish post caps in accordance with manufacturer's standard accessories.
e. Provide 9 gauge steel tie wire for attaching fabric to rails, braces, and posts and match the coating of the fence fabric. Tie wires for attaching fabric to tension wire on high security fences shall be 16 gage stainless steel. Provide double loop tie wires 6.5 inches in length. Miscellaneous hardware coatings shall conform to ASTM A153/A153M unless modified.
2.3 BRACES AND RAILS
ASTM F1083, zinc-coated, Group IA, steel pipe, size NPS 1-1/4. Group IC steel pipe, zinc-coated, shall meet the strength and coating requirements of ASTM F1043. Braces and rails shall be Group IA or Group IC, steel pipe, size NPS 1-1/4 or Group II, formed steel sections, size 1-21/32 inch and be zinc coated (Type A) and conforming to the requirements of ASTM F1043. Group II, formed steel sections, size 1-21/32 inch, conforming to ASTM F1043, may be used as braces and rails if Group II line posts are furnished.
Braces; Class 1, steel pipe, Grade A, in minimum sizes listed in FS RR-F-191/3 for Class 1 and Grade A.
2.4 WIRE
2.4.1 Wire Ties
Submit samples as specified. FS RR-F-191/4. Provide wire ties constructed of the same material as the fencing fabric.
2.4.2 Barbed Wire
Provide barbed wire conforming to ASTM A121 zinc-coated, Type Z, Class 3, with 12.5 gauge wire and 14 gauge, round, 4-point barbs spaced no more than 5 inches apart.
2.4.3 Tension Wire
Provide Type I or Type II tension wire, Class 4 coating, in accordance with ASTM A824. Provide 7 gauge coil spring wire for top wire.
2.5 BARBED TAPE (RAZOR WIRE)
Provide reinforced barbed tape, single coil, for fence toppings fabricated from 430 series stainless steel with a hardness range of Rockwell (30N) 37-45 conforming to the requirements of ASTM A176. Provide stainless steel strip 0.025 inch thick by 1 inch wide before fabrication. Each barb shall be a minimum of 1.2 inch in length, in groups of 4, spaced on 4 inch centers. The stainless steel core wire shall have a 0.098 inch diameter with a minimum tensile strength of 140 psi and be in accordance with ASTM A478. Use sixteen gauge stainless steel twistable wire ties for attaching the barbed tape to the barbed wire.
2.6 CONCRETE
ASTM C94/C94M, using 3/4 inch maximum size aggregate, and having minimum compressive strength of 3000 psi at 28 days. Grout shall consist of one part portland cement to three parts clean, well-graded sand and the minimum amount of water to produce a workable mix.
2.7 GATES
2.7.1 Gate Assembly
Provide gate assembly conforming to ASTM F900 and/or ASTM F1184 of the type and swing shown. Provide gate frames conforming to strength and coating requirements of ASTM F1083 for Group IA, steel pipe, with external coating Type A, nominal pipe size (NPS) 1-1/2. Provide gate frames conforming to strength and coating requirements of ASTM F1043, for Group IC, steel pipe with external coating Type A, nominal pipe size (NPS) 1-1/2. Gate fabric shall be as specified for chain link fabric.
2.7.2 Gate Leaves
For gate leaves, more than 8 feet wide, provide either intermediate members and diagonal truss rods or tubular members as necessary to provide rigid construction, free from sag or twist. Gate leaves less than 8 feet wide shall have truss rods or intermediate braces. Provide intermediate braces on all gate frames with an electro-mechanical lock. Attach fabric to the gate frame by method standard with the manufacturer except that welding will not be permitted.
2.7.3 Gate Hardware and Accessories
Submit manufacturer's catalog data. Furnish and install latches, hinges, stops, keepers, rollers, and other hardware items as required for the operation of the gate. Arrange latches for padlocking so that the padlock will be accessible from both sides of the gate. Provide stops for holding the gates in the open position. For high security applications, each end member of gate frames shall be extended sufficiently above the top member to carry three strands of barbed wire in horizontal alignment with barbed wire strands on the fence.
2.8 TURNSTILES
Provide galvanized steel, three wing turnstile consisting of a rotor, cage, ceiling plate, and bottom bearing plate. Provide electronic opening and closing by card key. Provide one way continuous turn motion.
2.9 PADLOCKS
Provide padlocks conforming to ASTM F883, Type P01 (key operated), Option B (cylinder is removable), Grade 6 (environmentally resistant). Size 1-3/4 inch. Key all padlocks into master key system as specified in Base Facility Design Standards.
2.10 GATE OPERATOR
Provide electric gate operators for sliding gates as follows: Electrical gate operators shall have a right angle gearhead instantly reversing motor with magnetic drum-type brake, friction disc clutch, reversing starter with thermal overload protection, and a chain-driven geared rotary-type automatic limit switch. Gears shall consist of a hardened steel machine cut worm and mating bronze gear. All gears and bearings shall operate in a bath of oil. Gate operators with V-belt pulleys are not allowed. Equip gate operators with an emergency release to allow the gate to be operated manually. The emergency release mechanism shall be capable of being locked in the engaged or disengaged position. Provide positive stops on the gate tracks as a backup to the limit switches.
2.11 ELECTRO-MECHANICAL LOCKS
Electro-mechanical locking devices for sliding gates and personnel gates shall be solenoid actuated such that the deadbolt retracts when the solenoid is energized and remains electrically retracted until the gate is closed. Provide continuous duty type solenoid, rated for 120V ac, 60Hz operation. The locking device shall be lockable by key and keyed on both sides. Status of the electro-mechanical lock shall be monitored by two limit switches (integral to the locking device) wired in series. One switch shall monitor the deadlock lever and the other monitor the locking tongue.
PART 3 EXECUTION
3.1 FENCE INSTALLATION
Perform complete installation conforming to ASTM F567.
3.1.1 Line and Grade
Install fence to the lines and grades indicated. Clear the area on either side of the fence line to the extent indicated. Space line posts equidistant at intervals not exceeding 10 feet. Terminal (corner, gate, and pull) posts shall be set at abrupt changes in vertical and horizontal alignment. Provide fabric continuous between terminal posts; however, runs between terminal posts shall not exceed 500 feet. Repair any damage to galvanized surfaces, including welding, with paint containing zinc dust in accordance with ASTM A780/A780M.
3.1.2 Excavation
Clear all post holes of loose material. Spread waste material where directed. Eliminate ground surface irregularities along the fence line to the extent necessary to maintain a 1 inch clearance between the bottom of the fabric and finish grade.
3.1.3 Concrete Slabs and Walls
Set posts into zinc-coated sleeves, set in concrete slab or wall, to a minimum depth of 12 inches. Fill sleeve joint with non-shrink grout. Set posts for support of removable fence sections into sleeves that provide a tight sliding joint and hold posts aligned and plumb without use of a setting material.
3.2 POST INSTALLATION
For fences over 6 feet tall, post hole diameters shall be 16 inches for terminal posts and 12 inches for line posts.
3.2.1 Earth and Bedrock
a. Set posts plumb and in alignment. Except where solid rock is encountered, set posts in concrete to the depth indicated on the drawings. Where solid rock is encountered with no overburden, set posts to a minimum depth of 18 inches in rock. Where solid rock is covered with an overburden of soil or loose rock, set posts to the minimum depth indicated on the drawing unless a penetration of 18 inches in solid rock is achieved before reaching the indicated depth, in which case terminate depth of penetration. Grout all portions of posts set in rock.
b. Portions of posts not set in rock shall be set in concrete from the rock to ground level. Posts set in concrete shall be set in holes not less than the diameter shown on the drawings. Make diameters of holes in solid rock at least 1 inch greater than the largest cross section of the post. Thoroughly consolidate concrete and grout around each post, free of voids and finished to form a dome. Allow concrete and grout to cure for 72 hours prior to attachment of any item to the posts. Group II line posts may be mechanically driven, for temporary fence construction only, if rock is not encountered. Set driven posts to a minimum depth of 3 feet and protect with drive caps when setting.
c. Test fence post rigidity by applying a 50 pound force on the post, perpendicular to the fabric, at 5 feet above ground. Post movement measured at the point where the force is applied shall be less than or equal to 3/4 inch from the relaxed position. Test every tenth post for rigidity. When a post fails this test, make further tests on the next four posts on either side of the failed post. All failed posts shall be removed, replaced, and retested at the Contractor's expense.
3.2.2 Concrete Slabs and Walls
Set posts into zinc-coated sleeves, set in concrete slab or wall, to a minimum depth of 12 inches. Fill sleeve joint with non-shrink grout. Set posts for support of removable fence sections into sleeves that provide a tight sliding joint and hold posts aligned and plumb without use of a setting material.
3.3 RAILS
Bolt bottom rail to double rail ends and securely fasten double rail ends to the posts. Peen bolts to prevent easy removal. Install bottom rail before chain link fabric. Provide 3/8" diameter eye hook anchored into concrete footing at midpoint.
3.4 FABRIC INSTALLATION
a. Install chain link fabric on the side of the post indicated. Attach fabric to terminal posts with stretcher bars and tension bands. Space bands at approximately 15 inch intervals. Install fabric and pull taut to provide a smooth and uniform appearance free from sag, without permanently distorting the fabric diamond or reducing the fabric height. Fasten fabric to line posts at approximately 15 inch intervals and fastened to all rails and tension wires at approximately 12 inch intervals.
b. Cut fabric by untwisting and removing pickets. Accomplish splicing by weaving a single picket into the ends of the rolls to be joined. The bottom of the installed fabric shall be 1 plus or minus 1/2 inch above the ground.
c. After the fabric installation is complete, exercise the fabric by applying a 50 pound push-pull force at the center of the fabric between posts; the use of a 30 pound pull at the center of the panel shall cause fabric deflection of not more than 2.5 inches when pulling fabric from the post side of the fence; every second fence panel shall meet this requirement; re-secure and retest all failed panels at the Contractor's expense.
3.5 SUPPORTING ARMS
Install barbed wire supporting arms and barbed wire as indicated on the drawings and as recommended by the manufacturer. Anchor supporting arms with 3/8 inch diameter plain pin rivets or, at the Contractor's option, with studs driven by low-velocity explosive-actuated tools for steel, wrought iron, ductile iron, or malleable iron. Studs driven by an explosive-actuated tool shall not be used with gray iron or other material that can be fractured. Use a minimum of two studs per support arm. Pull barbed wire taut and attach to the arms with clips or other means that will prevent easy removal.
3.6 BARBED TAPE (RAZOR WIRE) INSTALLATION
Install stainless steel reinforced barbed tape as detailed on the drawings. Stretch out barbed tape to its manufacturer's recommended length, set on top of the barbed wire and "V" shaped support arms, then secure it to the barbed wire. Secure the barbed tape to the barbed wire at the two points and at every spiral turn of both coils as shown on the drawings.
3.7 GATE INSTALLATION
a. Install gates at the locations shown. Mount gates to swing as indicated. Install latches, stops, and keepers as required. Install Slide and Lift gates as recommended by the manufacturer.
b. Attach padlocks to gates or gate posts with chains. Weld or otherwise secure hinge pins, and hardware assembly to prevent removal.
c. Submit 2 copies of operating and maintenance instructions, a minimum of 2 weeks prior to field training. Operating instructions shall outline the step-by-step procedures required for system startup, operation, and shutdown. Include the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Include in the maintenance instructions routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guide. Also include the general gate layout, equipment layout and simplified wiring and control diagrams of the system as installed.
3.8 GROUNDING
a. Ground fencing as indicated on drawings and specified.
b. Ground fences crossed by overhead power lines in excess of 600 volts. Electrical equipment attached to the fence shall be grounded.
c. Ground fences on each side of all gates, at each corner, at the closest approach to each building located within 50 feet of the fence, and where the fence alignment changes more than 15 degrees. Grounding locations shall not exceed 650 feet. Bond each gate panel with a flexible bond strap to its gate post. Ground fences crossed by power lines of 600 volts or more at or near the point of crossing and at distances not exceeding 150 feet on each side of crossing.
d. Provide ground conductor consisting of No. 8 AWG solid copper wire. Grounding electrodes shall be 3/4 inch by 10 foot long copper-clad steel rod. Drive electrodes into the earth so that the top of the electrode is at least 6 inches below the grade. Where driving is impracticable, electrodes shall be buried a minimum of 12 inches deep and radially from the fence. The top of the electrode shall not be less than 2 feet or more than 8 feet from the fence. Clamp ground conductor to the fence and electrodes with bronze grounding clamps to create electrical continuity between fence posts, fence fabric, and ground rods. Total resistance of the fence to ground shall not be greater than 25 ohms.
3.9 SECURITY
Install new security fencing, remove existing security fencing, and perform related work to provide continuous security for facility. Schedule and fully coordinate work with Contracting Officer and cognizant Security Officer.
3.10 CLEANUP
Remove waste fencing materials and other debris from the work site each workday.
-- End of Section --