Questions-Responses_May_2015.doc

DOC document 28 KB Posted

Attached to
Repair Roofs Bldg 821 and Bldg 617
Solicitation number
FA6633-15-B0006
Issued by

About this file

Questions-Responses

View the file

Other files

File Type Posted
Questions-Responses_May_2015.doc DOC document
Technical_Specifications-BOTH_PROJECTS.pdf PDF
Drawings_B617.pdf PDF
Wage_Determination_MN36.doc DOC document
Amendment_0003.doc DOC document
Drawings_B821.pdf PDF
Amendment_0002.doc DOC document
Amendment_0001.doc DOC document
REV_Technical_Drawings_05May15.pdf PDF
B617_ADDENDUM__1.pdf PDF
SV_Attendance_Roster_29Apr15.pdf PDF
Site_Visit_Minutes_23Apr15.pdf PDF
Bldg_617_-_QJKL_14-0020_-_Drawings.pdf PDF
SF_24_Bid_Bond_Form.pdf PDF
Wage_Determination_MN36.doc DOC document
Bldg_821_-_QJKL_14-0014_-_Drawings.pdf PDF
Financial_Responsibility_Sheet.doc DOC document
Technical_Specs_-_Both_Projects.pdf PDF
FA6633-15-B0006 _IFB.doc DOC document
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sol #FA6633-15-B0006

Site Visit Questions & Responses April 2015

FA6633-15-B-0006/QJKL 14-0014 & QJKL 14-0020

Repair Roofs, Building 821 & Building 617

1. QUESTION: BLDG 617: Per plans and specs, 16 gauge is specified for gutter. Is 24 gauge okay? 24 gauge is in industry standard.

RESPONSE: Yes, it should read 24 gauge, the drawings mistakenly indicate 16G. This will be corrected in a forthcoming Amendment.

2. QUESTION: BLDG 617: The plans shows two layers of 2” ISO but that is only R 25. You are requesting an R value of 33. Do you want 3 layers of ISO, or are you icluding the planking and hard board in the R value?

RESPONSE: The R value for the roof should be a total of 33, the drawings mistakenly indicate an R value of 33 for each layer. The layers of insulation should be: two layers of ISO, one layer of planking and one layer of fiber board, totaling 33. This will be corrected in a forthcoming Amendment.

3. QUESTION: BLDG 821: Can 60 mil EPDM be used instead of the vinyl roofing specified in the plans?

RESPONSE: No, bid according to the specifications provided for this building.

MAY 2015 (SEE Amendment 0001)