B617_ADDENDUM__1.pdf

PDF 37 KB Posted

Attached to
Repair Roofs Bldg 821 and Bldg 617
Solicitation number
FA6633-15-B0006
Issued by

About this file

Addendum 01 - 05May15

View the file

Other files

File Type Posted
Questions-Responses_May_2015.doc DOC document
Technical_Specifications-BOTH_PROJECTS.pdf PDF
Drawings_B617.pdf PDF
Wage_Determination_MN36.doc DOC document
Amendment_0003.doc DOC document
Drawings_B821.pdf PDF
Amendment_0002.doc DOC document
Amendment_0001.doc DOC document
REV_Technical_Drawings_05May15.pdf PDF
SV_Attendance_Roster_29Apr15.pdf PDF
Questions-Responses_May_2015.doc DOC document
Site_Visit_Minutes_23Apr15.pdf PDF
Bldg_617_-_QJKL_14-0020_-_Drawings.pdf PDF
SF_24_Bid_Bond_Form.pdf PDF
Wage_Determination_MN36.doc DOC document
Bldg_821_-_QJKL_14-0014_-_Drawings.pdf PDF
Financial_Responsibility_Sheet.doc DOC document
Technical_Specs_-_Both_Projects.pdf PDF
FA6633-15-B0006 _IFB.doc DOC document
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA6633-15-B0006

Amendment 0001 05 May 2015

ADDENDUM #1

FA6633-15-B0006, Repair Roofs Bldg 617

Project QJKL 14-0020

Reference Drawing T-01

Add the following notes:

CORRECTIONS: (5 MAY, 2015)

ALL GALVANIZED STEEL SHOULD BE 24 GA.

THE TOTAL R-VALUE FOR ALL

LAYERS OF INSULATION SHOULD EQUAL 33.

Revised 5 May, 2015 By Kyle Turner, Engineering Technician for the 934th Civil Engineering

Reference Drawing A-01

Change the following note:

6/A-01|A-01 FURNISH AND INSTALL NEW PREFIN. METAL D.S. SET IN 14 GA STL

LINER. CONT. SEAL & RODSTOCK AT PERIMETER

To:

6/A-01|A-01 FURNISH AND INSTALL NEW PREFIN. METAL D.S. SET IN 24 GA STL

LINER. CONT. SEAL & RODSTOCK AT PERIMETER

Reference Drawings A-02

Add the following note:

1, 2, 3, 4/A-02|A-01 THE TOTAL R-VALUE FOR ALL LAYERS SHOULD EQUAL 33.

1 & 2/A-02|A-01 FURNISH AND INSTALL NEW 12 GA. GLV. STL. GUTTERS @ N. & S.

WALLS; DRAIN TO PILASTERS; RETURN EDGE FOR SEAL @ PVC FLASHING (TYP.)

To:

1 & 2/A-02|A-01 FURNISH AND INSTALL NEW 24 GA. GLV. STL. GUTTERS @ N. & S.

WALLS; DRAIN TO PILASTERS; RETURN EDGE FOR SEAL @ PVC FLASHING (TYP.)

3 & 4/A-02|A-01 CONT. GALV. KEEPER 20 GA. MIN. VERIFY

To:

3 & 4/A-02|A-01 CONT. GALV. KEEPER 24 GA. MIN. VERIFY

1, 2, 3, & 4/A-02|A-01 FURNISH AND INSTALL NEW 2” POLYISOCYANURATE INSUL

FA6633-15-B0006

Amendment 0001 05 May 2015

R-VALUE 33

U-VALUE 0.03

1, 2, 3, & 4/A-02|A-01 FURNISH AND INSTALL NEW 2” POLYISOCYANURATE INSUL

Reference Drawing A-03

1/A-03|A-03 CONT. KEEPER 20 GA. MIN VERIFY & COORD.

1/A-03|A-03 CONT. KEEPER 24 GA. MIN VERIFY & COORD.

1/A-03|A-03 FURNISH AND INSTALL NEW 2” POLYISOCYANURATE INSUL

R-VALUE 33

U-VALUE 0.03

1/A-03|A-03 FURNISH AND INSTALL NEW 2” POLYISOCYANURATE INSUL

1/A-03|A-03 THE TOTAL R-VALUE FOR ALL LAYERS SHOULD EQUAL 33.

Reference Drawing A-04

5/A-04|A-01 FURNISH AND INSTALL NEW 2” POLYISOCYANURATE INSUL

R-VALUE 33

U-VALUE 0.03

5/A-04|A-01 FURNISH AND INSTALL NEW 2” POLYISOCYANURATE INSUL

5/A-04|A-01 THE TOTAL R-VALUE FOR ALL LAYERS SHOULD EQUAL 33.