JA-4,_Drawings_(6.21.18).pdf
PDF 19 MB Posted
- Attached to
- F-35 Repair Arctic Utilidor CHPP Federal contract opportunity
- Solicitation number
- FA500418BA002
About this file
Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| JA-4_Drawings_(10.31.18.pdf | ||
| JA-2,_Specifications_(11.7.18).pdf | ||
| Solicitation_Amendment_FA500418BA0020004_SF_30.pdf | ||
| JA-3,_Submittal_Register_(11.5.18).pdf | ||
| Solicitation_Amendment_-_FA500418BA0020004.pdf | ||
| Solicitation_Amendment_-_FA500418BA0020003.pdf | ||
| Question_&_Answers_V1_12Oct18.pdf | ||
| Solicitation_Amendment_FA500418BA0020002_SF_30.pdf | ||
| JA-6,_Eielson_ERP_Atlas_2018.pdf | ||
| JA-1,_Synopsis_Rev_1_(10.12.18).doc.pdf | ||
| JA-2_Specs_Rev_1_(07.09.18).pdf | ||
| FA500418BA0020001_SF_30_Solicitation_Amendment.pdf | ||
| JA-3_Submittal_Register_Rev_1_(07.09.18).pdf | ||
| JA-2,_Specifications_(4.18.18).pdf | ||
| JA-1,_Synopsis_(6.26.18).pdf | ||
| JA-5,_Wage_Determination_(8.24.18).pdf | ||
| JA-3,_Submittal_Register.pdf | ||
| Solicitation_-_FA500418BA002.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 View Name 1/8" = 1'-0"A101
GENERAL SYMBOLS
NAME
NUMBER
SHEET LOCATION
SCALE
TRUE NORTH
PLAN NORTH
SEE DISCIPLINES FOR SPECIFIC SYMBOLS
PROJECT TEAM
OWNERS REPRESENTATIVE
EIELSON AIR FORCE BASE
JASON STORMONT
2310 CENTRAL AVENUE, BLDG 2258
907 377-1866
JASON.STORMONT.CTR@US.AF.MIL
LEAD DESIGNER
DESIGN ALASKA
JEFF PUTNAM
601 COLLEGE ROAD
907 452-1241 designalaska.com
VICINITY MAP
PROJECT
LOCATION
PROPOSED STOCKPILE AREA
EIE386 PLANNED STOCKPILE AREA
(ALTERNATE STOCKPILE AREA)
ALASKA MAP
PACIFIC OCEAN
ARCTIC OCEAN
BERING SEA
KODIAK
ARCTIC CIRCLE
SEWARD
SITKA
JUNEAU
HAINES
WHITEHORSE YT
HAINES
JCT
HOMER
ANCHORAGE
EAGLE
CORDOVA
VALDEZ
GLENNALLEN
TOK
NORTH POLE
FAIRBANKS
NENANA
TANANA
CIRCLE
NOME
KOTZEBUE
BARROW
PRUDHOE BAY
U N
IT
ED
S
TA
TE
S
R U
SS
IA U
N
ITED
STATES
C
AN
AD
A
PROJECT
LOCATION
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
21 JUNE 2018
REPAIR ARCTIC
UTILIDOR EIE
SOUTH
021801
AECC511
6/20/2018 11:59:39 AM
RJR
ECW
GENERAL
INFORMATION
G001
REPAIR ARCTIC UTILIDOR EIE SOUTH
EIELSON AIR FORCE BASE, ALASKA
EIELSON AIR FORCE BASE
GENERAL
G001 GENERAL INFORMATION
CIVIL
C100 SITE EXISTING CONDITIONS AND DEMOLITION PLAN
C110 CONTAMINATED SITES PLAN
C111 STOCKPILE SITE PLAN
C200 SITE LAYOUT PLAN
C700 DETAILS
STRUCTURAL
S100 PIPE SUPPORTS AND ANCHORS
S200 UTILIDOR REPAIRS
MECHANICAL
M100 UTILITY DEMOLITION PLAN
M200 UTILITY PLAN
M300 LATERAL DETAILS
M301 LATERAL DETAILS
M302 MECHANICAL DETAILS
M303 MECHANICAL DETAILS
ELECTRICAL
E001 ELECTRICAL DETAILS
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 6
MH523 MH524 MH524-1 MH525
MH526
MH528-1
ASPHALT
PARKING
8' WIDE CONC. SIDEWALK
WITH CURB AND GUTTER
TO REMAIN, SEE NOTE 2
36" CMP SERVICE
LATERAL
EXCAVATION AS REQUIRED TO
ACCESS UTILIDUCT, SEE NOTE 1
EXCAVATION AS REQUIRED TO
ACCESS UTILIDUCT, SEE NOTE 1
SAWCUTTING, PAVEMENT DEMO,
AND EXCAVATION AS REQUIRED
TO ACCESS UTILIDUCT, SEE NOTE 1
MH525-2
FENCE
RAILROAD
TRACKS
EARTHEN BERM
BURIED UTILIDOR
MH528MH527
SURVEY CONTROL
POINT #100
PARTIALLY EXPOSED UTILIDUCT
BETWEEN JUNCTION BOX AND
BLDG 6209, EXCAVATION AS
REQUIRED TO ACCESS UTILIDUCT
EXCAVATION AS REQUIRED
TO INSTALL NEW UTILITIES
TEMPORARY FENCE
AND GATE TO ACCESS
SERVICE LATERAL
HYDRANT TO REMAIN
TOE OF BERM
EXCAVATION AS REQUIRED
TO ACCESS CMP
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 6
DEMOLISH JUNCTION BOX
FENCE
6/21/2018 10:21 AM 021801_C100.DWG
021801
21 JUNE 2018
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR ARCTIC
UTILIDOR EIE
SOUTH
C100
DWB
DWB
SITE EXISTING
CONDITIONS AND
DEMOLITION PLAN
SITE EXISTING CONDITIONS AND DEMOLITION PLAN1
C100 SCALE" 1" = 40'
BRASS CAP IN CONCRETE
FIRE HYDRANT
LIGHT POLE
POWER POLE W/ GUY ANCHOR
TELE. PED.
TREES
OVERHEAD ELECTRIC
OVERHEAD COMM.
CHAIN LINK FENCE
EDGE PAVEMENT
SIGN
BURIED UTILIDOR/UTILIDUCT
LEGENDSURVEY NOTES
1. THE PURPOSE OF THE SURVEY WAS TO LOCATE TOPOGRAPHY AND FEATURES
ALONG INDUSTRIAL DRIVE FOR UTILIDOR REPAIR DESIGN.
2. COORDINATES ARE ALASKA STATE PLANE ZONE 3, NAD83, US FEET; ELEVATIONS
ARE NAVD88 DATUM, FEET. COORDINATES AND ELEVATIONS ARE BASED UPON AN
OPUS SOLUTION AT POINT #100.
3. DATE OF SURVEY: APRIL 12 & 16, 2018.
GENERAL NOTES
1. MAINTAIN EMERGENCY ACCESS TO FRONT DOOR, KNOX BOX, ETC. OF BUILDING
DURING ALL DEMOLITION AND CONSTRUCTION ACTIVITIES.
2. PROTECT EXISTING CONCRETE SIDEWALK, CURB, AND GUTTER AS REQUIRED TO
EXPOSE UTILIDUCT AND INSTALL NEW UTILITIES BENEATH STRUCTURES.
David W. Beiswenger
No. CE13328 21-Jun-2018
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 6
SD022
ST048
ST016
SS031
MY529
SS036
MH523 MH524 MH524-1 MH525
MH526
MH528-1
MH525-2
BURIED UTILIDOR
MH528MH527
6/21/2018 10:22 AM 021801_C110.DWG
021801
21 JUNE 2018
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR ARCTIC
UTILIDOR EIE
SOUTH
C110
RCB
DWB
CONTAMINATED
SITES PLAN
CONTAMINATED SITES PLAN1
C110 SCALE" 1" = 40'
SITE SPECIFIC CONTAMINATED SITES INVENTORY
SITE ID SITE NAME CONTAMINANTS OF CONCERN CURRENT STATUS PROHIBITIONS AND RESTRICTIONS
ST016 OU-2, SER-1,
ST16 SPILL BENZENE ACTIVE ANY CONSTRUCTION MUST GO THROUGH DIG PERMIT PROCESS AND CES/CEV APPROVES PROJECTS ON THIS SITE.
SS036 OU-4, SS36
WASTE OILS, HYDRAULIC FLUID,
DIESEL FUEL, OTHER POLs
STORED AT THE SITE
CLOSED
ADVANCE APPROVAL REQUIRED TO TRANSPORT SOIL OR GROUNDWATER OFF-SITE.
SS031 BLDG 3424 PCBs CLOSED ADVANCE APPROVAL REQUIRED TO TRANSPORT SOIL OR GROUNDWATER OFF-SITE.
MY529 BLDG 2762/6214 POLs, PAINT, SOLVENT, BENZENE, DRO ACTIVE ADDITIONAL COORDINATION WITH ADEC REQUIRED.
ST048 POWER PLANT
SPILL SITE
BENZENE, TOLUENE,
ETHYLBENZENE
GROUNDWATER
CONTROLS AND
GROUNDWATER
MONITORING
1. ANY ACTIVITY THAT MAY RESULT IN THE DISTURBANCE OF SOIL REQUIRES APPROVAL BY INSTALLATION MANAGEMENT (CE/CEI). COMPLETE BASE CIVIL ENGINEERING WORK CLEARANCE (FORM 103) AND OBTAIN APPROVAL PRIOR TO ANY (INTRUSIVE OR OTHERWISE) WORK AT SITE.
2. IN THE EVENT THAT CONTAMINATED SOIL IS REMOVED FROM THE SOURCE AREA, IT WILL BE DISPOSED OF OR TREATED IN ACCORDANCE WITH APPLICABLE STATE AND FEDERAL REGULATIONS.
3. THERE IS A 200-FOOT BUFFER BOUNDARY ON THE SITE UNTIL BETTER DELINEATION IS DEFINED.
SD022
ROAD OILING -
INDUSTRIAL
ROAD
METALS (As, Cr, Mg, Va, Zn, AND Pb), PAHs, PCBs CLOSED
1. ANY ACTIVITY THAT MAY RESULT IN THE DISTURBANCE OF SOIL REQUIRES APPROVAL BY INSTALLATION MANAGEMENT (CE/CEI). COMPLETE BASE CIVIL ENGINEERING WORK CLEARANCE (FORM 103) AND OBTAIN APPROVAL PRIOR TO ANY (INTRUSIVE OR OTHERWISE) WORK AT SITE.
2. IN THE EVENT THAT CONTAMINATED SOIL IS REMOVED FROM THE SOURCE AREA, IT WILL BE DISPOSED OF OR TREATED IN ACCORDANCE WITH APPLICABLE STATE AND FEDERAL REGULATIONS.
3. THERE IS A 200-FOOT BUFFER BOUNDARY ON THE SITE UNTIL BETTER DELINEATION IS DEFINED.
David W. Beiswenger
MH523 MH524 MH524-1 MH525
MH526
MH528-1
ASPHALT
PARKING
MH525-2
RAILROAD
TRACKS
EARTHEN BERM
BURIED UTILIDOR MH528MH527
TOE OF BERM
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 6
JUNCTION BOX
FENCE
RV PARKING
PROPOSED
STOCKPILE
AREA
EIE386 PLANNED
STOCKPILE AREA
(ALTERNATE
STOCKPILE AREA)
6/21/2018 10:23 AM 021801_C111.DWG
021801
21 JUNE 2018
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR ARCTIC
UTILIDOR EIE
SOUTH
C111
DWB
DWB
STOCKPILE SITE
PLAN
STOCKPILE SITE PLAN1
C111 SCALE" 1" = 80'
STOCKPILE NOTES
1. STOCKPILE EXCAVATED SOILS PER THE PROJECT SPECIFICATIONS AND THE
SAMPLING AND ANALYSIS PLAN (SAP).
David W. Beiswenger
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 3
B
LD
G . 6
MH523 MH524 MH524-1 MH525
MH526
MH528-1
36" CMP SERVICE
LATERAL
BACKFILL,
TOPSOIL AND
SEED THIS AREA
BACKFILL, TOPSOIL AND
SEED THIS AREA
REPAIR ASPHALT
PAVEMENT IN
THIS AREA
MH525-2
FENCE
BURIED UTILIDOR
MH528MH527
COVER EXPOSED
UTILIDUCT IN THIS AREA
1&2
C700
RECONSTRUCTED
JUNCTION BOX
PER STRUCTURAL
C700
S200
C700
C700
REPLACE UTILIDUCT
LIDS AS REQUIRED
S100
S200
REPLACE UTILIDUCT
LIDS AS REQUIRED
S200
BACKFILL, TOPSOIL AND
SEED THIS AREA
6/21/2018 10:26 AM 021801_C200.DWG
021801
21 JUNE 2018
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR ARCTIC
UTILIDOR EIE
SOUTH
C200
DWB
DWB
SITE LAYOUT PLANSITE LAYOUT PLAN1
C200 SCALE" 1" = 40'
GENERAL NOTES
1. RESTORE DISTURBED AREAS TO EXISTING OR BETTER CONDITIONS. SITE FEATURES
DISTURBED BY THIS PROJECT SHALL BE REPLACED IN-KIND.
David W. Beiswenger
6/21/2018 10:27 AM 021801_C700.DWG
021801
21 JUNE 2018
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
REPAIR ARCTIC
UTILIDOR EIE
SOUTH
C700
DWB
DWB
DETAILS
12"
NEW ASPHALT PAVEMENT EXISTING
4" CRUSHED AGGREGATE
EXISTING
FILL
EXISTING
ASPHALT
SEE PLANS FOR LOCATION OF
SAWCUT. SAWCUT TO BE
PERPENDICULAR TO EXISTING
PAVEMENT SURFACE.
TACK
COAT
EDGES
2" ASPHALT
PAVEMENT FINISH
GRADE PER PLANS
STRUCTURAL
FILL
DRIVEWAY AND ROAD
CROSSINGS
NON-TRAFFIC
AREAS
2'-6"
MIN
SLOPE SIDES OF TRENCH IN
ACCORDANCE WITH OSHA
REQUIREMENTS, TYP.
3-5% SLOPE, TYP.
1. COMMON FILL SHALL BE
COMPACTED TO MIN 90%
MAX DRY DENSITY.
2. STRUCTURAL FILL SHALL BE
COMPACTED TO 95% MAX
DRY DENSITY.
3. SEE SHEET S200 FOR
UTILIDOR DIMENSIONS AND
CONSTRUCTION DETAILS.
SEE
STRUCTURAL
FILL
C700
BURIED UTILIDUCT EARTHWORK SECTION2
C700 NO SCALE
EXPOSED UTILIDUCT EARTHWORK SECTION3
C700 NO SCALE
2'-6"
MIN
EXCAVATE AS REQUIRED FOR
UTILIDOR IMPROVEMENTS
2:1 SLOPE, TYP.
INSITU SOILINSITU SOIL
UTILIDUCT LID
AND INSULATION
PER STRUCTURAL
COMMON
FILL
UTILIDUCT LID
AND INSULATION
PER STRUCTURAL
EXCAVATE AS REQUIRED FOR
UTILIDOR IMPROVEMENTS
TOPSOIL AND SEED
DISTURBED AREAS
S200
TOPSOIL AND SEED
DISTURBED AREASCOMMON FILL
8" MIN
2% MIN
MATCH
EXISTING
S200
C700
ASPHALT REPAIR DETAIL
NO SCALE
David W. Beiswenger
B-LINE B22SHA OR APPROVED
EQUAL CROSS MEMBERS.
B-LINE B230 ATTACH PER
MANUFACTURER'S INSTRUCTIONS
B-LINE B22SH OR APPROVED EQUAL. EXTEND STRUT
AS NEEDED TO SUPPORT CONDUIT & CABLES.
ANCHOR STRUT WITHIN 3" OF END, SEE ELECTRICAL
EXPANSION ANCHOR 3/8'' X 2'' MIN EMBED TYPE PER GENERAL NOTES
PIPING PER MECHANICAL TYP
B-LINE 3180 STRAP FOR SS TYP
ROLLER GUIDE FOR W, ST, CR TYP
B22SH STRUT
PIPING PER MECHANICAL
1/8'' X 6'' X 6'' PLATE
3/16
TYP 3 SIDES
(4) #12 SELF DRILLING
SCREWS EACH PLATE,
CENTER SCREW OVER CMP
CORRUGATION CREST
SCREW THROUGH STEEL
SHIMS TO LEVEL, MAX
3/8'' SHIMS EACH SIDE
1''X1''X3/16'' MIN BUTYL TAPE
SEALANT OVER CMP AT SCREW
PENETRATION, ENSURE
COMPRESSION OF BUTYL TAPE,
TYP
ANCHOR NOTES:
1. PROVIDE 3/16'' WEEP/DRAIN HOLE ON ALL STEEL MEMBERS THAT HAVE THE
POTENTIAL TO ACCUMULATE STANDING WATER.
2. AT ANCHOR LOCATIONS, PREP SURFACES BY BUSHING AND PLANING
CONCRETE AS NECESSARY TO ENSURE UNIFORM BEARING AND
ALIGNMENT WITH PIPE.
L4X4X1/2 12'' LENGTH
3/16
TYP
3/16
TYP
C10X25
1/4
TYP 3 SIDES
3/8'' PLATES EACH END TYP
S100
TYP
S100
TYP
3/8'' PLATE TYP
(3) 5/8'' X 4'' EMBED
EXPANSION ANCHORS
TYP
GENERAL STRUCTURAL NOTES
1.
A. DESIGN CRITERIA
BUILDING CODE........................................................................................ 2015 IBC (INTERNATIONAL BUILDING CODE) GOVERNING JURISDICTION.................................................................... DEPUTY BASE CIVIL ENGINEER
2. LIVE LOADS
TRAFFIC LOAD ............................................................................. HS-20
3. SNOW LOADS
GROUND SNOW LOAD P g ..................................................... 70 PSF
4. SEISMIC LOADS
SS ............................................................................................... 0.964 S1 ............................................................................................... 0.376 SDS ............................................................................................. 0.716 SD1 ............................................................................................. 0.413 SITE CLASS................................................................................. D
SEISMIC DESIGN CATEGORY................................................... D
IMPORTANCE FACTOR............................................................... 1.5
RESPONSE MODIFICATION FACTOR R P................................... VARIES
AMPLIFICATION FACTOR AP....................................................... 2.5 ANALYSIS PROCEDURE.......................................................... ASCE 7-10 CHAPTER 13 AND 15
1.
A.
B.
C.
D.
2.
A.
B.
C.
D.
3.
A.
a.
b.
B.
C.
D.
B. CONCRETE
GENERAL:
ALL CAST-IN-PLACE CONCRETE SHALL HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH (f'c) OF 4000
PSI.
CONCRETE SHALL MEET ALL REQUIREMENTS OF ACI 318 SPECIFICATION FOR STRUCTURAL CONCRETE
BUILDINGS.
PROVIDE SLEEVES FOR ALL UTILITY OPENINGS.
DIMENSIONS SHOWN ON DRAWING SHALL SUPERCEDE THOSE SHOWN ON GENERAL NOTES.
REINFORCING:
REINFORCING BARS SHALL CONFORM TO ASTM A615 GRADE 60, UNLESS OTHERWISE NOTED, EXCEPT #3
BARS WHICH MAY BE GRADE 40. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185.
DETAIL REINFORCING BARS IN ACCORDANCE WITH THE ACI DETAILING MANUAL AND THE ACI BUILDING
CODE REQUIREMENTS FOR REINFORCED CONCRETE, LATEST EDITION.
PROVIDE ALL ACCESSORIES NECESSARY TO SUPPORT REINFORCING AT POSITIONS SHOWN ON THE
DRAWINGS. PROVIDE SUFFICIENT TIE BARS TO SUPPORT ALL REINFORCING.
UNLESS A REINFORCING SPLICE, CLEAR DISTANCE BETWEEN REINFORCING SHALL NOT BE LESS THAN 1.5
BAR DIAMETERS NOR LESS THAN 1 1/2''
POST-INSTALLED ANCHORS:
EXPANSION ANCHORS:
LESS THAN 18'' ABOVE FLOOR: HILTI KWIK BOLT TZ OR POWER-STUD+ SD4/SD6
(BOTH 316 STAINLESS)
18'' OR MORE ABOVE FLOOR: HILTI KWIK BOLT TZ OR POWER-STUD+ SD4/SD6
INSTALL POST-INSTALLED ANCHORS ONLY AS INDICATED ON THE DRAWINGS OR WITH SPECIFIC WRITTEN
APPROVAL OF THE ENGINEER PRIOR TO INSTALLATION.
THE CONTRACTOR MAY NOT USE SUBSTITUTES FOR THE POST-INSTALLED ANCHORS WITHOUT PRIOR
APPROVAL OF THE ENGINEER.
SEE DRAWINGS FOR ANCHOR TYPE, SIZE, AND EMBEDMENT DEPTHS. INSTALL ANCHORS AS OUTLINED IN MANUFACTURER'S SPECIFICATIONS AND ICC REPORTS. UTILIZE PROPER DRILL TYPE, BIT SIZE, AND HOLE CLEANING, DRIVING OR TIGHTENING TECHNIQUES, UNLESS NOTED OTHERWISE.
1.
2.
3.
4.
5.
6.
7.
C. STRUCTURAL STEEL
ALL STRUCTURAL STEEL WIDE FLANGE MEMBERS AND CHANNELS SHALL BE ASTM A572 - GRADE 50 (Fy = 50 KSI) OR A992.
ANGLES AND PLATES SHALL BE ASTM A36 (Fy = 36 KSI).
ALL STRUCTURAL STEEL SHALL BE DETAILED AND FABRICATED IN ACCORDANCE WITH THE LATEST
EDITION OF THE AISC STEEL CONSTRUCTION MANUAL.
BOLTED CONNECTIONS SHALL BE ACCOMPLISHED WITH HIGH-STRENGTH BOLTS CONFORMING TO
ASTM A325 IN STANDARD HOLES UNLESS NOTED OTHERWISE.
ALL BOLTED CONNECTIONS SHALL BE PRE-TENSIONED UNLESS NOTED OTHERWISE.
WELDING SHALL BE PERFORMED WITH E70XX ELECTRODES. WELDING SHALL BE DONE BY
QUALIFIED WELDERS AND SHALL CONFORM TO THE AWS D1.1 STRUCTURAL WELDING CODE-STEEL, LATEST EDITION. ALL WELDS ARE INTENDED TO BE CONTINUOUS UNLESS NOTED OTHERWISE.
FIELD WELDS NOTED THROUGHOUT THE CONTRACT DOCUMENTS ARE ACCEPTABLE LOCATIONS
FOR FIELD WELDING AT THE CONTRACTOR'S OPTION. FIELD WELDS MAY BE PERFORMED IN THE
SHOP.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
D. GENERAL
CONTRACTOR IS TO FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS TO MATCH NEW CONSTRUCTION
TO EXISTING CONSTRUCTION.
THE STRUCTURAL CONSTRUCTION DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OR SEQUENCE OF CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION.
SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO: BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S MEANS, METHODS, TECHNIQUES, SEQUENCES FOR PROCEDURE OF CONSTRUCTION, OR THE SAFETY PRECAUTIONS AND THE PROGRAMS INCIDENT THERETO (NOR SHALL OBSERVATION
VISITS TO THE SITE INCLUDE INSPECTION OF THESE ITEMS.)
STRUCTURAL DRAWINGS ARE A PORTION OF THE CONTRACT DOCUMENTS AND ARE INTENDED TO BE USED WITH ARCHITECTURAL, CIVIL, MECHANICAL, AND ELECTRICAL DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE REQUIREMENTS FROM THESE DISCIPLINES INTO THEIR SHOP
DRAWINGS AND WORK.
CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND IMPLEMENTATION OF ALL SCAFFOLDING, BRACING AND SHORING.
CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION. LOADS
SHALL NOT EXCEED THE DESIGN LIVE LOAD.
ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL, MECHANICAL, PLUMBING
AND ELECTRICAL WITH THE APPROPRIATE TRADES, DRAWINGS AND SUBCONTRACTORS PRIOR TO
CONSTRUCTION.
NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL STRUCTURAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR
WORK ON THE PROJECT.
DO NOT USE SCALED DIMENSIONS TAKEN FROM STRUCTURAL DRAWINGS. CONTACT STRUCTURAL
ENGINEER IF DIMENSIONAL INFORMATION IS MISSING.
WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL STRUCTURAL NOTES AND
SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL GOVERN.
ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE SEAL
OF A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF ALASKA.
SPECIAL INSPECTIONS
THE FOLLOWING STRUCTURAL ITEMS REQUIRE SPECIAL INSPECTION PER IBC SECTIONS 1704-1707. THESE INSPECTIONS SHALL BE PERFORMED BY A SPECIAL INSPECTOR APPROVED BY THE CONTRACTING OFFICER TO PERFORM THE TYPES OF INSPECTIONS SPECIFIED. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
FOR INSPECTION AND TESTING THAT ARE NOT PART OF SPECIAL INSPECTIONS.
CONCRETE
BOLTS & DOWELS
INSTALLED IN
CONCRETE
REINFORCING STEEL
WELDING
VISUAL INSPECTION OF PLACEMENT OF CONCRETE FOR LIDS (FIRST 20%
CONTINUOUS, 25% BALANCE)
VISUAL INSPECTION OF MECHANICAL ANCHORS INSTALLED IN HARDENED
CONCRETE (INSPECTION FREQUENCY PER MANUFACTURER'S REQUIREMENTS
BUT NOT LESS THAN 10% OF EACH ANCHOR TYPE)
VISUAL INSPECTION OF PLACEMENT OF REINFORCING STEEL
(100% BEFORE CONCRETE PLACEMENT)
WEEKLY VISUAL INSPECTION OF FIELD WELDS AND ASSOCIATED NON-
DESTRUCTIVE TESTING
MECH PIPING
PIPE OR HSS SLEEVE, 1/2'' MAX
TOTAL GAP BETWEEN PIPE AND PIPE
SLEEVE, 1/4'' MIN WALL THICKNESS
VICTAULIC GROOVED COUPLING,
EACH SIDE, 1/4'' MAX GAP TO SLEEVE
1/4
PLATE TO
PIPE, TYP
CHANNEL PER ELEVATION
PLATE PER ELEVATION
MECH PIPING
1/4
PLATE TO
PIPE, TYP
CHANNEL PER ELEVATION
PLATE PER ELEVATION
3/8'' X 8'' X 12''
PLATE TYP
S100
TYP
5/8'' Ø X 4'' MIN EMBED EXPANSION ANCHORS
3/16
3/16
TYP
TYP
8'' EDGE DISTANCE
CMP BEYOND
5"
1-1/2'' TYP
4"
C6X10.5
PIPE SHOE AND ATTACHMENT SIM TO
S100
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
21 JUNE 2018
REPAIR ARCTIC
UTILIDOR EIE
SOUTH
021801
AECC511
6/20/2018 3:36:32 PM
LJA
RGP
PIPE SUPPORTS
AND ANCHORS
S100
NOT TO SCALES100
2 UTILIDOR LATERAL PIPE RACK
NOT TO SCALES100
5 TYPICAL CMP PIPE RACK
NOT TO SCALES100
1 TYPICAL RACK ANCHOR
NOT TO SCALES100
3 WATER AND SEWER ANCHOR
NOT TO SCALES100
4 STEAM AND CONDENSATE ANCHOR
NOT TO SCALES100
6 MH 525 ANCHOR TO CMP
AKAF AL
TS
TA
E O
49 TH
S
Lyle J. Axelarris
CE114159
REGISTERED PROFESSIONAL ENGIN
EE
R
19-JUN-2018
S200
36"
WALL WIDTH
6'' TYP
(E) CMP UTILIDUCT
EQ EQ
ALIGN INSIDE FACES OF UTILIDUCT AND HANDHOLE
CUT AND REMOVE CMP FLUSH
WITH INSIDE FACE OF HANDHOLE
(E) 16'' UTILIDUCT, INSULATE AND
WATERPROOF LID AND FULL
WALL HEIGHT SIM TO 3
S200
#5 @12'' OCEW, PROVIDE
CONTINUOUS BAR AROUND
CORNERS
#5 @ 12'' OCEW
6' ' M
IN
FORM CONCRETE AROUND CMP,
SEAL JOINT WITH HYDROPHYLIC
WATERSTOP
PROVIDE MIN OF (2) #5 BARS OVER OPENINGS
MATCH UTILIDUCT OPENING
CMP UTILIDUCT
REMOVABLE LID SIM
S200
RECESS LID EDGE AT 4 SIDES SIM TO
STRUCTURAL FILL PER CIVIL
CUTBACK AND REPAIR (E) 16'' UTILIDUCT
AS NEEDED, SEAL JOINTS WITH
HYDROPHILIC WATERSTOP
S200
DRILL AND EMBED #4 X 8'' EMBED
EPOXY DOWELS WITH STD HOOKS
AT 8'' OC AT SLAB AND WALLS
HYDROPHYLIC WATERSTOP
TYPICAL AT ALL COLD JOINTS
5' MAX
MATCH UTILIDOR
LIFTING LOOP INSERT WITH
COMBINED SAFE WORKING
LOAD LIMITS EXCEEDING
REMOVABLE LID WEIGHTS.
MIN (2) PER LID.
REMOVABLE LID NOTES:
1. EXISTING LIDS SHALL BE USED WHEN REMOVED AND REPLACED UNDAMAGED
2. LID LENGTH SHALL BE SUCH THAT LIDS WEIGH NO MORE THAN 4,000 LBS.
3. APPLY SHEET WATERPROOFING BENEATH INSULATION
4. UTILIDOR WALL-TO-LID JOINTS SHALL BE SEALED WITH A CONTINUOUS STRIP OF
CONSEAL CS101 BUTYL RUBBER SEALANT.
5. UTILIDOR LID-TO-LID JOINTS SHALL BE SEALED WITH A CONTINUOUS STRIP OF
CONSEAL CS101 BUTYL RUBBER SEALANT.
6. ENSURE LID-TO-LID & LID-TO-WALL JOINTS FORM A CONTINUOUS SEAL
THROUGHOUT LENGTH OF JOINT.
7. TRAFFIC RATED LIDS REQUIRE 1' - 6'' MIN DEPTH BELOW ROAD SURFACE
'' W
H E
R E
T R
A
FF
IC
R
A
TE
D
8" T
Y P
1 1/2"
1- 3/
4" C
O V
E R
1"
SEALANT PER LID NOTES
MATCH WALL WIDTH
BOTTOM BAR, #5 @ 10'' OC
TOP BAR, #4@10'' OC
DEPTH OF
EXCAVATION AT
(E) UTILIDOR
(E) INSULATION
INSULATE LID AND EXTENTS
OF EXCAVATION, MIN 2'' XPS
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
21 JUNE 2018
REPAIR ARCTIC
UTILIDOR EIE
SOUTH
021801
AECC511
6/20/2018 3:36:32 PM
LJA
RGP
UTILIDOR
REPAIRS
S200
NOT TO SCALES200
1 HANDHOLE REPAIR PLAN
NOT TO SCALES200
2 HANDHOLE REPAIR SECTION
NOT TO SCALES200
3 UTILIDOR LID REPLACEMENT
AKAF AL
TS
TA
E O
49 TH
S
Lyle J. Axelarris
CE114159
REGISTERED PROFESSIONAL ENGIN
EE
R
19-JUN-2018
Robin J. Rader
No. ME9386
REGISTERED PROFESSIONAL ENGIN
EE
R
20-JUN-2018
Robin J. Rader
G
NE20-JUN-2018
RE ER
REGISTERED PROFESSIONAL ENGIN
EE
R
20-JUN-2018G
NE20 JUN 2018
Robin J. RaderRE ER
REGISTERED PROFESSIONAL ENGIN
EE
R
20-JUN-2018
Robin J. RaderREG
NE
ER20 JUN 2018
REGISTERED PROFESSIONAL ENGIN
EE
R
20-JUN-2018
Robin J. RaderRERR G
ER20-JUN-2018
REGISTERED PROFESSIONAL ENGIN
EE
R
20-JUN-2018G
NE20 JUN 2018
Robin J. RaderRE ER
REGISTERED PROFESSIONAL ENGIN
EE
R
20-JUN-2018
Robin J. RaderREG
ER20 JUN 2018
MECHANICAL
PIPES
MECHANICAL PIPE RACKS / ANCHORS,
SEE MECHANICAL FOR SPACING (TYPICAL)
ELECTRICAL POWER AND
TELECOMMUNICATION
CABLES (AS APPLICABLE)
TYPICAL, PROVIDE ADDITIONAL CLAMP-BACK CABLE SUPPORTS BETWEEN PIPE
RACK / ANCHORS TO SUPPORT ELECTRICAL AND TELECOMMUNICATION CABLES.
MAXIMUM 3'-0" SPACING UNLESS LARGER SPACING IS ALLOWED PER NEC
(DEPENDENT ON CABLE TYPE). ALL CABLE SUPPORTING MATERIALS SHALL BE
HOT-DIPPED GALVANIZED OR STAINLESS STEEL. BRIDGEPORT, ONE PIECE,
STAINLESS-STEEL CLAMP-BACK STRAP IS THE BASIS OF DESIGN.
E001
1MOUNT POWER AND TELECOMMUNICATIONS RACEWAYS
AND CABLES TO MECHANICAL PIPE RACKING SYSTEM,
SEE DETAIL 2/S100 FOR RACK MATERIALS
POWER AND TELECOMMUNICATIONS
MOUNTING LOCATION(S)
COMPRESSION TYPE STRAP, HOT
DIPPED GALVANIZED (TYPICAL)
UTILIDOR LATERAL
MECHANICAL PIPE
RACKING SYSTEM,
SEE 2/S100
B6209
B3417 B3418 B3419 B3420 B3446
MH523 MH524
MH524-1
MH525-526
MH528-1
NO ELECTRICAL OR
TELECOMMUNICATIONS
IN BLDG 6209 LATERAL
SUMP PUMP & ALARM POWER COPPER TELECOMMUNICATIONS FIBER OPTIC TELECOMMUNICATIONS
& LIFT STATION POWER
FIBER OPTIC TELECOMMUNICATIONS
& COPPER TELECOMMUNICATIONS
EXISTING LIFT STATION
UTILIDOR MAIN OUT OF SCOPE
AKAF AL
TS
TA
E O
49 TH
S
Jeffrey M. Leonelli
EE 107788
REGISTEREDPROFESSIONALENGINE
ER
ISSUE DATE
COMM. NUMBER
DESIGNED BY
DRAWN BY
SCALE 0" 1"
Architects Engineers Surveyors 601 College Road Fairbanks AK 99701
907.452.1241 designalaska.com
21 JUNE 2018
REPAIR ARCTIC
UTILIDOR EIE
SOUTH
021801
AECC511
20-Jun-2018
6/20/2018 5:01:20 PM
MWK
MWK
ELECTRICAL
DETAILS
E001
NOT TO SCALEE001
1 UTILIDOR LATERAL PIPE RACK
SHEET GENERAL NOTES
1. PROVIDE A MINIMUM 3" SEPARATION BETWEEN POWER AND COPPER TELECOMMUNICATION
CABLES, WHERE APPLICABLE.
SHEET SPECIFIC NOTES
1 CONTRACTOR SHALL DETACH AND PROTECT ALL EXISTING POWER & TELECOMMUNICATIONS
CABLES DURING UTILIDOR RENOVATION. CABLES LOCATED WITHIN THE UTILIDOR LATERAL
BETWEEN THE MANHOLE AND BUILDING SHALL BE RE-SUPPORTED/SECURED PER DETAILS 1
AND 2. CABLES SHALL REMAIN IN-SERVICE DURING WORK. FIELD VERIFY LOCATIONS,
QUANTITIES, AND ROUTING OF EXISTING CABLES PRIOR TO BEGINNING WORK. CONTRACTOR
SHALL REPLACE OR REPAIR ANY CABLES DAMAGED DURING WORK, AT NO COST TO THE
GOVERNMENT.
2 SUMP PUMP & ALARM POWER TO BE REMOVED UNDER EIE405 PROJECT FTQW180111. IF CABLE
STILL EXISTS DURING THIS PROJECT, LEAVE CABLE IN PLACE AND DO NOT DISTURB.
NOT TO SCALEE001
2 INTERMEDIATE CABLE SUPPORTS
1" = 50'-0"E001
3 OVERALL PLAN
| G001 |
| C100 |
| C110 |
| C111 |
| C200 |
| C700 |
| S100 |
| S200 |
| M100 |
| M200 |
| M300 |
| M301 |
| M302 |
| M303 |
| E001 |
File details come from the government source that posted it.