Equipment_List_FTQW131503_June2015.xlsx

XLSX spreadsheet 24 KB Posted

Attached to
Replace Motors & Install VFDs Federal contract opportunity
Solicitation number
FA5004-15-B-C008
Issued by
Department of the Air Force Pacific Air Forces

About this file

Revised equipment list

View the file

Other files for this federal contract opportunity

Other files attached to Replace Motors & Install VFDs, newest first.
File Type Posted
Equipment_List_FTQW1315_23_June2015.pdf PDF
FA5004-15-B-C008-0007.pdf PDF
Site_Visit_Attendance_Sheet_19_June_15.pdf PDF
FA5004-15-B-C008-0006.pdf PDF
FA5004-15-B-C008-0005.pdf PDF
SOW_18_June_15.pdf PDF
Q A__2.pdf PDF
Eielson_AFB_HVAC_Standards_June_2015.pdf PDF
FA5004-15-B-C008-0004.pdf PDF
FA5004-15-B-C008-0003_Extension.pdf PDF
Site_Visit_Attendance_Sheet.pdf PDF
JA-2_Tab_1_Motor_Replacement_List_FTQW131503_28May2015.xlsx XLSX spreadsheet
Answers_to_Questions__1.pdf PDF
JA-6_Tab_5_Eielson_AFB_HVAC_Standards_May_2015.pdf PDF
JA-1_FTQW131503_Statement_of_Work_28May2015.pdf PDF
FA5004-15-B-C008-0002.pdf PDF
FA5004-15-B-C008-0001.pdf PDF
JA-13_Wage_Determination.pdf PDF
JA-9_AF_Form_103.pdf PDF
JA-8_Tab_7_FTQW131503_AF_Form_66.pdf PDF
JA-7_Tab_6_Supplemental_Mech_Guide_Specs.pdf PDF
JA-10_AF_Form_3000.pdf PDF
JA-2_Tab_1_Motor_Replacement_List_FTQW131503.pdf PDF
JA-1_FTQW131503_Statement_of_Work.pdf PDF
JA-3_Tab_2_Specification_01030_-_SAFETY _ENVIRONMENTAL_PROTECTION_16Mar2015.pdf PDF
JA-6_Tab_5_Eielson_AFB_HVAC_Standards_Apr_2013.pdf PDF
JA-11_AF_Form_3064.pdf PDF
JA-12_AF_Form_3065.pdf PDF
JA-4_Tab_3_Specification_01300-Submittals.pdf PDF
FA5004-15-B-C008.pdf PDF
JA-5_Tab_4_Specification_15035_Testing _Adjusting _and_Balancing_for_HVAC.pdf PDF
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet2

Data is for bidding purposes only. Must be field verified before start of workMotor Data for existing motors to be replacedPump Data for existing pumps to be replaced
BldgLocationEquipment TypeModelEff#HPVoltagePhaseAmpRPMEnclosure TypeFrameMax Effdelta effReplacement CostkWh savMMBtu savYrly Cost savTot Rpl CostSimple PbckSIRPump DataPump GPMPump Head (Ft)Pump modelPump MfctrFan Design CFMVFDs
1183Mech RmLarge loop duplex pump #1Century E-29486.513.020839.1-8.8/4.41725DPY182JM89.5$781.41Replace Pump19334Series 80 3x3x7BB&G--
1183Mech RmLarge loop duplex pump #2Baldor JMM 3221T82.513.020838.4/1.151725OPSB182JM89.5$781.4127279.3$511.00ERROR:#REF!ERROR:#REF!2.4Replace Pump19334Series 80 3x3x7BB&G--
1209Mech RmHeatEx PumpReliance Electric 01MAP6428686.515.046036.10/1.151750TEFC184JM88.53.0$1,120.8822447.7$420.00$1,902.004.533Replace Pumps12060Cat # 16-25953-730111-1682Paco--
1209Mech RmHeatEx PumpBaldor Reliance VJMM3218T86.515.046037/1.151740ODTF184JM89.53.0$1,120.8822447.7$420.00$1,902.004.533Replace Pumps12060Cat # 16-25991-7301x1 A04-1Paco--
1336Mech RmHHW PumpBaldor Reliance VJMM3157T78.512.0208-230/46036.8-6.4/3.21725ODTF145JM86.5$640.50Replace Pump105432.5x7B&G--
1336Mech RmHHW PumpUS Electric Motors80.012.0208-230/46036.4-6.6/3.31735DP145JM86.5$640.50Replace Pump105432.5x7B&G--
1337Life support rmREF-2-17.52083500-----14,841-
1337Mech RmAHU 2AO Smith84.1115.0208342.201750DPS254T-----14,841-
1340Fan room access through hangarP-1A and P-1B25.0208315.3/1.15172518481.5------VFDs on Pumps
1341Eject Seat LabGlycol PumpsMagnatek Centurey86.527.5230/460 200/208319/9.5 22-213460M184JM91.04.5$1,441.13Replace Pumps88118Model 80 5.625B&G--
1341Mech RmAHU-1-91.0115.04603102493.02.0$2,209.73-----10,942-
1347Mech RmHHW PumpCentury87.515.0230/460 200/400312.8/6.4 15/71800TEFC184JM89.52.0$1,120.88Replace Pump139.2763x3x10 4380 BFArmstrong--
1347Mech RmHHW PumpMarathon86.515.0230/460 200/400312.8/6.4 15/71750TEFC184JM89.53.0$1,120.8815545.3$291.00$2,242.007.701.8Replace Pump139.2763x3x10 4380 BFArmstrong--
1348MER RmHHW Pumps Inline (CP2-1/2)Marathon81.523.046034.5/1.151730-182M89.5781.41Replace Pumps230303D 4380 BFArmstrong--
1348MER RmCP1-1 HHW PumpMarathon SVA89.5110.0460313.2/1.151760-215T91.72.2$1,825.43-------
1348MER RmCP1-2 HHW PumpMarathon EVC 215TTDBA4026A86.5110.0460313.3/1.151745-215T91.75.2$1,825.43-------
1353Mech rmGlycol supply CP-1 and CP-2Baldor EM3218789.525.046036.4/1.151750184T------VFDs on Pumps
1353Mech rmAHU-117.546039.6/1.151760S213T88.82.2$1,825.43-----8,350VFD with bypass on fans
1353Fan room access thru work bayAHU-2Magnatek Centurey89.5110.0460313.4/1.151745DPS215T2.5$1,441.13-----10,000VFD with bypass on fans
2196Mech rmGlycol supply CP-1A and CP-1BBaldor27.5208322.5/1.151760213T2.0$2,209.73------VFDs on Pumps
2200Mech rmGlycol supply CP-1A and CP-1BBaldor27.5208321.9/1.151760213T2.0$2,209.731152339.3$2,158.00$8,327.003.8615.8------VFDs on Pumps
2207Mech RmGlycol Supply Duplex Pump SmallLPUnimount80.021.046032.1/1.251725143JP89.5$576.45648622.1$1,215.00$3,138.002.585.3Replace Pumps3334VL1507 61Taco--
2207Mech RmGlycol Supply med LP (P-3 P-4)Unimount82.525.046036.5/1.251745184Y89.57.0$1,120.88Replace Pumps11552VL25087.4Taco--
2225Meeting Room Fan DecksAHU-1Centure Gould88.517.520839.6/1.151760254T91.02.5$1,441.13396713.5$743.00$2,658.003.583.8-----8,360-
2225Meeting Room Fan DecksAHU-2Centure Gould88.517.520839.6/1.151760254T-----8,280-
2225Mech RmGlycol circ pumps PMP-1 and PMP-2Baldor Reliance EM3311T91.727.5230319.2/1.151770OPSB213T2.5$1,441.13Replace pumps400304AC 6.25BFB&G-VFDs on pumps
2225Mech RmGlycol circ pumps PMP-3 and PMP-4Marathon M9907721.0208-230/46033.5-3.6/1.81725DP56CZ-702.5$1,441.13Replace Pumps65302A 5.57BFB&G-VFDs on Pumps
2268Liebert RmGlycol PumpsMarathon #CVE182TTDR4108AP85.545.0208-230/460313.4-12/63475182TC86.54.0$813.44Replace Pumps17553P02-001AFlowserv--
3309Mech/fan rmGlycol PumpsReliance Duty Master88.525.0208389.51.0$1,120.886102.1$114.00$1,121.009.831.4-------
3310Mech RoomAir Handler AHU-3Baldor M2531T91.7125.0230/460362/311760OPSB284T-----26,500-
3343Basement Mech rmBasement Exhaust FanReliant P18S305085.515.0208314.6/1.151745184T87.5-------
3343Mech RmGlycol supply P-2Baldor Reliance M2515T91.7120.0460324/1.151760OPSB256T2.0$2,209.73608920.8$1,140.00$5,092.004.473.1Replace Pumps60090SN-CO36715-01B&G-VFDs on Pumps
3343Mech RmGlycol supply P-1Marathon 256TTDB4026AA91115.0460310.8/1.151750DP213TReplace Pumps60090SN-CO36715-02B&G-VFDs on Pumps
3426Mech RmP1-A and P1-BUnimount B071A/Dayton23.046034.5/1.251750182JMReplace pumps158402.5AB6.25 1510B&G--
3426Mech RmP2-A and P2-BUnimount B075A/Century AC23.046033.1/1.751725145JMReplace pumps123351510 2ACB&G-VFDs on Pumps
3426Mech RmP3-A and P3-BUnimount B075A25.046036.65/1.251745184JMReplace pumps1675015102BCB&G--
3426Mech RmP4-A and P4-BUnimount B075A25.046036.8/1.251745184JMReplace pumps121501510 2BC7.375B&G--
3426Mech RmP5-A and P5-BUnimount FHS23.046033.1/1.251745145JMReplace pumps119401510 2A6.75BFB&G--
3426Mech RmP6-A and P6-BBaldor Reliant JMM3211T23.046034.1/1.251750182JMReplace pumps120452AC7BFB&G-VFDs on Pumps
3426Mezzanine over officesAHU-1115.0460318.8/1.151750254T90.2-----25,200-
3426North mezzanineAHU-3115.0460318.8/1.151750254T90.2-----25,200-
3426North mezzanineAHU-4115.0460318.9/1.151770S264T93.0-----24,000-
3426South mezzanineAHU-5120.0460324/1.151760S256T-----28,800-
3426South mezzanineAHU-6110.0460312.2/1.151750215T-----17,500-
3426North mezzanineHRU-115.046036.2/1.151745184T86.5-----8,000-
3426North mezzanineHRU-215.046036.2/1.151745A184T86.5-----8,000-
3446Mech rmHHW Pumps for AHUsMarathon88.527.5208320.4/1.151770OPSB213T91.02.5$1,441.13-------
3460Garage MezzEF1 motorMarathon UVN215TTDR7359BP86.5110.0208391.75.2$1,825.43-----17,100-
3460Garage MezzSF1 motorMarathon W254TTDR5033AA86.5115.0208393.06.5$2,209.731055436$1,977.00$5,252.002.665.2-----18,000-
5182Mech RmP-32A and P-32BUnimount25.0208316.6/1.251745184JM85.5Replace Pumps30037V1307E2JAN626DTaco-VFDs on Pumps
5182Mech RmP-7A and P-7BBaldor21.520835.0/1.151725Replace Pumps56471919CINJTaco-VFDs on Pumps