Updated_Specifications.pdf

PDF 148 KB Posted

Attached to
Repair Bldg 314 Federal contract opportunity
Solicitation number
FA4659-14-R-0011
Issued by
Department of the Air Force Air Mobility Command

About this file

Updated Specifications 05 50 13 09 06 90 09 72 00 10 10 00 27 10 00 32 93 00 28 July 2014

View the file

Other files for this federal contract opportunity

Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Repair Communications Squadron Building 314 and Parking Lot Grand Forks Air Force Base

SECTION TABLE OF CONTENTS

DIVISION 05 - METALS

SECTION 05 50 13

MISCELLANEOUS METAL FABRICATIONS

05/10

PART 1 GENERAL

1.1 REFERENCES

1.2 SUBMITTALS

1.3 DELIVERY, STORAGE, AND PROTECTION

PART 2 PRODUCTS

2.1 MATERIALS

2.1.1 Structural Carbon Steel

2.1.2 Structural Tubing

2.1.3 Steel Pipe

2.1.4 Fittings for Steel Pipe

2.1.5 Gratings

2.1.6 Floor Plates, Patterned

2.1.7 Anchor Bolts

2.1.7.1 Bolts, Nuts, Studs and Rivets

2.1.7.2 Washers

2.1.8 Aluminum

2.1.9 Wire Fabric (Generator Enclosure Roof)

2.1.10 Wire Fabric Frame

2.2 FABRICATION FINISHES

2.2.1 Galvanizing

2.2.2 Galvanize

2.2.3 Repair of Zinc-Coated Surfaces

2.2.4 Shop Cleaning and Painting

2.2.4.1 Surface Preparation

2.2.4.2 Pretreatment, Priming and Painting

2.2.5 Nonferrous Metal Surfaces

2.2.6 Aluminum Surfaces

2.2.6.1 Surface Condition

2.2.6.2 Aluminum Finishes

2.3 2.4 2.5 2.6 2.7 2.8

ACCESS DOORS AND PANELS

MISCELLANEOUS PLATES AND SHAPES

SAFETY CHAINS

FENCE SECURITY BARRIER

TRASH GUARDS

GUY CABLES

ENCLOSURES

PART 3 EXECUTION

3.1 3.2 3.3 3.4

GENERAL INSTALLATION REQUIREMENTS

WORKMANSHIP

ANCHORAGE, FASTENINGS, AND CONNECTIONS

BUILT-IN WORK

mn142 SECTION 05 50 13 Page 1

2.9

1396325833C Line

3.6 FINISHES

3.6.1 Dissimilar Materials

3.6.2 Field Preparation

3.6.3 Environmental Conditions

3.7 MOUNTING OF SAFETY CHAINS

-- End of Section Table of Contents --mn142 SECTION 05 50 13 Page 2

WELDING 3.5 3

SECTION 05 50 13

MISCELLANEOUS METAL FABRICATIONS

05/10

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ALUMINUM ASSOCIATION (AA)

AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes

AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

AISC 303 (2010) Code of Standard Practice for Steel Buildings and Bridges

AMERICAN WELDING SOCIETY (AWS)

AWS D1.1/D1.1M (2010; Errata 2010) Structural Welding Code - Steel

ASME INTERNATIONAL (ASME)

ASME B18.2.2 (2010) Standard for Square and Hex Nuts

ASME B18.21.1 (2009) Washers: Helical Spring-Lock, Tooth Lock, and Plain Washers (Inch Series)

ASTM INTERNATIONAL (ASTM)

ASTM A123/A123M (2009) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products

ASTM A153/A153M (2009) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware

ASTM A307 (2010) Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength

ASTM A36/A36M (2008) Standard Specification for Carbon Structural Steel

ASTM A467/A467M (2007) Standard Specification for Machine Coil Chain

ASTM A47/A47M (1999; R 2009) Standard Specification for Ferritic Malleable Iron Castings mn142 SECTION 05 50 13 Page 3

ASTM A475 (2003; R 2009e1) Standard Specification for Zinc-Coated Steel Wire Strand

ASTM A48/A48M (2003; R 2008) Standard Specification for Gray Iron Castings

ASTM A500/A500M (2010a) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes

ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless

ASTM A653/A653M (2011) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM A767/A767M (2009) Standard Specification for Zinc-Coated (Galvanized) Steel Bars for Concrete Reinforcement

ASTM A780/A780M (2009) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings

ASTM A786/A786M (2005; R 2009) Standard Specification for Hot-Rolled Carbon, Low-Alloy, High-Strength Low-Alloy, and Alloy Steel Floor Plates

ASTM A924/A924M (2010a) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process

ASTM B209 (2010) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate

ASTM B221 (2012) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

ASTM D1187/D1187M (1997; R 2011e1) Asphalt-Base Emulsions for Use as Protective Coatings for Metal

MASTER PAINTERS INSTITUTE (MPI)

MPI 79 (Oct 2009) Alkyd Anti-Corrosive Metal Primer

NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)

NAAMM MBG 532 (2009) Heavy Duty Metal Bar Grating Manual mn142 SECTION 05 50 13 Page 4

THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)

SSPC SP 3 (1982; E 2004) Power Tool Cleaning

SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning

U.S. GENERAL SERVICES ADMINISTRATION (GSA)

FS RR-F-191/3 (Rev E; Am 1) Fencing, Wire and Post, Metal (Chain-Link Fence Posts, Top Rails and Braces)

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01000 TECHNICAL PROVISIONS:

SD-02 Shop Drawings

Fabrication and installation drawings of miscellaneous metal; G, STR

Including but not limited to gates, pickets, wire fabric roof of generator and dumpster enclosures.

Embedded angles and plates, installation drawings; G, STR

Submit fabrication drawings showing layout(s), connections to structural system, and anchoring details as specified in AISC 303.

Submit templates, erection and installation drawings indicating thickness, type, grade, class of metal, and dimensions. Show construction details, reinforcement, anchorage, and installation with relation to the building construction.

1.3 DELIVERY, STORAGE, AND PROTECTION

Protect from corrosion, deformation, and other types of damage. Store items in an enclosed area free from contact with soil and weather. Remove and replace damaged items with new items.

PART 2 PRODUCTS

2.1 MATERIALS

2.1.1 Structural Carbon Steel

ASTM A36/A36M.

2.1.2 Structural Tubing

ASTM A500/A500M.

2.1.3 Steel Pipe

ASTM A53/A53M, Type E or S, Grade B.

mn142 SECTION 05 50 13 Page 5

2.1.4 Fittings for Steel Pipe

Standard malleable iron fittings ASTM A47/A47M.

2.1.5 Gratings

a. Gray cast iron ASTM A48/A48M, Class 40.

b. Metal plank grating, non-slip requirement, aluminum ASTM B209, 6061-T6;

steel ASTM A653/A653M, G90.

c. Metal bar type grating NAAMM MBG 532.

2.1.6 Floor Plates, Patterned

Floor plate ASTM A786/A786M. Steel plate shall not be less than 14 gage.

2.1.7 Anchor Bolts

ASTM A307. Where exposed, shall be of the same material, color, and finish as the metal to which applied.

2.1.7.1 Bolts, Nuts, Studs and Rivets

ASME B18.2.2 or ASTM A307.

2.1.7.2 Washers

Provide plain washers to conform to ASME B18.21.1. Provide beveled washers for American Standard beams and channels, square or rectangular, tapered in thickness, and smooth. Provide lock washers to conform to ASME B18.21.1.

2.1.8 Aluminum

Conform to ASTM B209 for plate and ASTM B221 for extrusions. Extrusions and plate shall be a minimum thickness of 1/8 inch unless noted otherwise.

Pickets and aluminum plate for generator enclosure to be dark bronze anodized.

2.1.9 Wire Fabric (Generator Enclosure Roof)

PVC-coated, welded wire cloth, 10 gauge wire in both directions, rectangular pattern, approximate 2 inch x 3 inch spacing. PVC coating, dark color to approximate metal roofing panels.

2.1.10 Wire Fabric Frame

SS40, hot-dipped galvanized and chromate by total immersion with clear organic coating, meeting FS RR-F-191/3D for chain link fence posts, braces and top rails.

2.2 FABRICATION FINISHES

2.2.1 Galvanizing

Hot-dip galvanize items specified to be zinc-coated, after fabrication where practicable. Galvanizing: ASTM A123/A123M, ASTM A153/A153M, mn142 SECTION 05 50 13 Page 6

ASTM A653/A653M or ASTM A924/A924M, G90, as applicable.

2.2.2 Galvanize

Anchor bolts, grating fasteners, washers, and parts or devices necessary for proper installation, unless indicated otherwise.

2.2.3 Repair of Zinc-Coated Surfaces

Repair damaged surfaces with galvanizing repair method and paint conforming to ASTM A780/A780M or by application of stick or thick paste material specifically designed for repair of galvanizing, as approved by Contracting Officer. Clean areas to be repaired and remove slag from welds. Heat surfaces to which stick or paste material is applied, with a torch to a temperature sufficient to melt the metallics in stick or paste; spread molten material uniformly over surfaces to be coated and wipe off excess material.

2.2.4 Shop Cleaning and Painting

2.2.4.1 Surface Preparation

Blast clean surfaces in accordance with SSPC SP 6/NACE No.3. Surfaces that will be exposed in spaces above ceiling or in attic spaces, crawl spaces, furred spaces, and chases may be cleaned in accordance with SSPC SP 3 in lieu of being blast cleaned. Wash cleaned surfaces which become contaminated with rust, dirt, oil, grease, or other contaminants with solvents until thoroughly clean. Steel to be embedded in concrete shall be free of dirt and grease. Do not paint or galvanize bearing surfaces, including contact surfaces within slip critical joints, but coat with rust preventative applied in the shop.

2.2.4.2 Pretreatment, Priming and Painting

Apply pretreatment, primer, and paint in accordance with manufacturer's printed instructions. On surfaces concealed in the finished construction or not accessible for finish painting, apply an additional prime coat to a minimum dry film thickness of 1.0 mil. Tint additional prime coat with a small amount of tinting pigment.

2.2.5 Nonferrous Metal Surfaces

Protect by plating, anodic, or organic coatings.

2.2.6 Aluminum Surfaces

2.2.6.1 Surface Condition

Before finishes are applied, remove roll marks, scratches, rolled-in scratches, kinks, stains, pits, orange peel, die marks, structural streaks, and other defects which will affect uniform appearance of finished surfaces.

2.2.6.2 Aluminum Finishes

Unexposed sheet, plate and extrusions may have mill finish as fabricated.

Sandblast castings' finish, medium, AA DAF45. Unless otherwise specified, provide all other aluminum items with a standard mill finish. Provide a coating thickness not less than that specified for protective and decorative type finishes for items used in interior locations or mn142 SECTION 05 50 13 Page 7 architectural Class I type finish for items used in exterior locations in AA DAF45. Provide a polished satin finish on items to be anodized.

2.4 MISCELLANEOUS PLATES AND SHAPES

Provide for items that do not form a part of the structural steel framework, such as lintels, sill angles, miscellaneous mountings and frames. Provide lintels fabricated from structural steel shapes over openings in masonry walls and partitions as required to support wall loads over openings. Provide with connections and fasteners. Construct to have at least 8 inches bearing on masonry at each end.

Provide angles and plates, ASTM A36/A36M, for embedment as indicated.

Galvanize embedded items exposed to the elements according to

ASTM A123/A123M.

2.5 SAFETY CHAINS

Construct safety chains of galvanized steel, straight link type, 3/16 inch diameter, with at least twelve links per foot, and with snap hooks on each end. Test safety chain in accordance with ASTM A467/A467M, Class CS.

Provide snap hooks of boat type. Provide galvanized 3/8 inch bolt with 3/4 inch eye diameter for attachment of chain, anchored as indicated. Supply two chains, 4 inches longer than the anchorage spacing, for each guarded area. Locate safety chain where indicated. Mount the top chain feet 6 inches above the ground and mount the lower chain 2 feet above the ground.

2.6 FENCE SECURITY BARRIER

Fabricate fence security barrier as shown on the drawings. Use galvanized steel bars and angles in accordance with ASTM A123/A123M (flat steel bars and angles) and ASTM A767/A767M for steel reinforcing bars.

2.7 TRASH GUARDS

Fabricate flared end section trash guards as shown on the drawings. Use galvanized steel bars meeting ASTM A767/A767M requirements.

2.8 GUY CABLES

Guy cables shall be prestretched, galvanized wire rope of the sizes indicated. Wire rope shall conform to ASTM A475, high strength grade with Class A coating. Guys shall have a factory attached clevis top-end fitting; a factory attached open-bridge strand socket bottom-end fitting;

and be complete with oval eye, threaded anchor rods. Fittings and accessories shall be hot-dip galvanized.

mn142 SECTION 05 50 13 Page 8

2.3 ACCESS DOORS AND PANELS

Provide flush type access doors and panels unless otherwise indicated.

Fabricate frames for access doors of steel not lighter than 14 gage with welded joints and anchorage for securing into construction. Provide access doors with a minimum of 24 by 24 inches and of not lighter than 14 gage steel, with stiffened edges and welded attachments. Provide access doors hinged to frame and with a flush-face, turn-screw-operated latch.

Provide exposed metal surfaces with a shop applied prime coat.

PART 3 EXECUTION

3.1 GENERAL INSTALLATION REQUIREMENTS

Install items at locations indicated, according to manufacturer's instructions. Verify all measurements and take all field measurements necessary before fabrication. Exposed fastenings shall be compatible materials, shall generally match in color and finish, and harmonize with the material to which fastenings are applied. Include materials and parts necessary to complete each item, even though such work is not definitely shown or specified. Poor matching of holes for fasteners shall be cause for rejection. Conceal fastenings where practicable. Thickness of metal and details of assembly and supports shall provide strength and stiffness.

Form joints exposed to the weather shall be formed to exclude water. Items listed below require additional procedures.

3.2 WORKMANSHIP

Provide miscellaneous metalwork that is well formed to shape and size, with sharp lines and angles and true curves. Drilling and punching shall produce clean true lines and surfaces. Provide continuous welding along the entire area of contact except where tack welding is permitted. Do not tack weld exposed connections of work in place and ground smooth. Provide a smooth finish on exposed surfaces of work in place and unless otherwise approved, flush exposed riveting. Mill joints where tight fits are required. Corner joints shall be coped or mitered, well formed, and in true alignment. Accurately set work to established lines and elevations and securely fastened in place. Install in accordance with manufacturer's installation instructions and approved drawings, cuts, and details.

3.3 ANCHORAGE, FASTENINGS, AND CONNECTIONS

Provide anchorage where necessary for fastening miscellaneous metal items securely in place. Include for anchorage not otherwise specified or indicated slotted inserts, expansion shields, and powder-driven fasteners, when approved for concrete; toggle bolts and through bolts for masonry;

machine and carriage bolts for steel; through bolts, lag bolts, and screws for wood. Do not use wood plugs in any material. Provide non-ferrous attachments for non-ferrous metal. Make exposed fastenings of compatible materials, generally matching in color and finish, to which fastenings are applied. Conceal fastenings where practicable.

3.4 BUILT-IN WORK

Form for anchorage metal work built-in with concrete or masonry, or provide with suitable anchoring devices as indicated or as required. Furnish metal work in ample time for securing in place as the work progresses.

mn142 SECTION 05 50 13 Page 9

2.9 ENCLOSURES

Fabricate aluminum picket assemblies, panels and gates, as shown on drawings for generator enclosure. Separate aluminum components from other dissimilar metals as indicated on drawings. Fabricate roof or cap cover over generator enclosure. Fabricate gate assembly for dumpster enclosure.

Assemblies shall be designed such that, while enclosures are closed and secured, all gaps between individual components or between components and larger assemblies or building faces, etc., shall be less than 4 inches to prohibit the placement of objects larger than 4 inches within the enclosure.

Where dissimilar metals are in contact, protect surfaces with a coat conforming to MPI 79 to prevent galvanic or corrosive action. Where aluminum is in contact with concrete, plaster, mortar, masonry, wood, or absorptive materials subject to wetting, protect with ASTM D1187/D1187M, asphalt-base emulsion.

3.6.2 Field Preparation

Remove rust preventive coating just prior to field erection, using a remover approved by the rust preventive manufacturer. Surfaces, when assembled, shall be free of rust, grease, dirt and other foreign matter.

3.6.3 Environmental Conditions

Do not clean or paint surface when damp or exposed to foggy or rainy weather, when metallic surface temperature is less than 5 degrees F above the dew point of the surrounding air, or when surface temperature is below 45 degrees F or over 95 degrees F, unless approved by the Contracting Officer.

3.7 MOUNTING OF SAFETY CHAINS

Mount safety chains 3 feet 6 inches and 2 feet above the floor.

-- End of Section --mn142 SECTION 05 50 13 Page 10

3.6 FINISHES

3.6.1 Dissimilar Materials

3.5 WELDING

Perform welding, welding inspection, and corrective welding, in accordance with AWS D1.1/D1.1M. Use continuous welds on all exposed connections.

Grind visible welds smooth in the finished installation.

SECTION TABLE OF CONTENTS

DIVISION 09 - FINISHES

SECTION 09 06 90

COLOR SCHEDULE

05/09

PART 1 GENERAL

1.1 SYSTEM DESCRIPTION

1.2 SUBMITTALS

PART 2 PRODUCTS

2.1 REFERENCE TO MANUFACTURER'S COLOR

2.2 COLOR SCHEDULE

2.2.1 Exterior Walls

2.2.1.1 Brick:

2.2.1.2 Mortar:

2.2.1.3 Concrete Masonry Units (Burnished):

2.2.1.4 Paint:

2.2.1.5 Composite Wall Panels:

2.2.1.6 Glass and Glazing:

2.2.1.7 Metal Wall Panels:

2.2.1.8 Metal Louvers:

2.2.2 Exterior Trim

2.2.2.1 Steel Doors and Door Frames:

2.2.2.2 Aluminum Doors and Door Frames:

2.2.2.3 Aluminum Windows (mullion, muntin, sash, trim, and sill):

2.2.2.4 Metal Panel Fascia/Horizontal Metal Band:

2.2.2.5 Soffits:

2.2.2.6 Exterior Overhang Ceiling:

2.2.2.7 Downspouts, Gutters, Louvers, and Flashings:

2.2.2.8 Coping:

2.2.2.9 Precast Concrete Caps:

2.2.2.10 Caulking and Sealants:

2.2.2.11 Control Joints:

2.2.2.12 Aluminum Cover Plates:

2.2.3 Exterior Metal Roof

2.2.3.1 Metal:

2.2.3.2 Penetrations (Metal Roof):

2.2.3.3 Flat Roof Fan Shrouds and Metal Ducts, Exposed to View from

Grade:

2.2.4 Interior Floor Finishes

2.2.4.1 Carpet Tile:

2.2.4.2 Resilient Tile/Vinyl Composition Tile:

2.2.4.3 Porcelain Tile:

2.2.4.4 Resilient Sheet Flooring:

2.2.4.5 Grout:

2.2.4.6 Urethane Topcoat:

2.2.4.7 Entrance Walk-Off Mat

2.2.4.7.1 Room 01:

2.2.4.7.2 Room 18:

mn142 SECTION 09 06 90 Page 1

2.2.5 Interior Base Finishes

2.2.5.1 Resilient Base and Moldings:

2.2.5.2 Porcelain Tile:

2.2.5.3 Grout:

2.2.6 Interior Wall Finishes

2.2.6.1 Paint:

2.2.6.2 Vinyl Wall Covering:

2.2.6.3 Acoustical Fabric Wall Covering:

2.2.6.4 Ceramic Tile:

2.2.6.5 Ceramic Tile Grout:

2.2.6.6 Brick:

2.2.6.7 Mortar:

2.2.6.8 Modular Wall Panel System:

2.2.6.9 Concrete Masonry Units (Burnished):

2.2.7 Interior Ceiling Finishes

2.2.7.1 Ceiling Tile and Grid:

2.2.7.2 Paint:

2.2.7.3 Metal Deck:

2.2.7.4 Structural Framing:

2.2.8 Interior Trim

2.2.8.1 Steel Doors:

2.2.8.2 Steel Door Frames:

2.2.8.3 Aluminum Doors and Door Frames:

2.2.8.4 Aluminum Windows:

2.2.8.5 Wood Doors:

2.2.8.6 Wood Stain:

2.2.8.7 Window Stools:

2.2.8.8 Fire Extinguisher Cabinets:

2.2.8.9 Ladders:

2.2.8.10 Exposed Ductwork:

2.2.8.11 Closet Shelving:

2.2.9 Interior Miscellaneous

2.2.9.1 Toilet Partitions and Urinal Screens:

2.2.9.2 Plastic Laminate:

2.2.9.3 Solid Surfacing Material:

2.2.9.4 Casework (Lobby Display Case):

2.2.9.5 Signage Message Color:

2.2.9.6 Signage Background Color:

2.2.9.7 Corner Guards:

2.2.9.8 Chair Rail:

2.2.9.9 Shower Curtain:

2.2.9.10 Shower Wall Kits, Trim and Shower Pan:

PART 3 EXECUTION (Not Applicable)

-- End of Section Table of Contents --mn142 SECTION 09 06 90 Page 2 mn142 Section 09 06 90 Page 3

SECTION 09 06 90

COLOR SCHEDULE

05/09

PART 1 GENERAL

1.1 SYSTEM DESCRIPTION

This section covers only the color of the exterior and interior materials and products that are exposed to view in the finished construction. The word "color", as used herein, includes surface color and pattern.

Requirements for quality and method of installation are covered in other appropriate sections of the specifications. Specific locations where the various materials are required are shown on the drawings. Items not designated for color in this section may be specified in other sections.

When color is not designated for items, propose a color for approval.

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01000 TECHNICAL PROVISIONS:

SD-04 Samples

Color Schedule; G

PART 2 PRODUCTS

2.1 REFERENCE TO MANUFACTURER'S COLOR

Where color is shown as being specific to one manufacturer, an equivalent color by another manufacturer may be submitted for approval. Manufacturers and materials specified are not intended to limit the selection of equal colors from other manufacturers.

2.2 COLOR SCHEDULE

The color schedule lists the colors, patterns and textures required for exterior and interior finishes, including both factory applied and field applied colors. Submit 1 set of color boards, no more than 60 days after the Contractor is given Notice to proceed, complying with the following requirements:

a. Color boards shall reflect all actual finish textures, patterns, and colors required for this contract.

b. Materials shall be labeled with the finish type, manufacturer's name, pattern, and color reference.

c. Samples shall be on size 8-1/2 by 11 inch boards with a maximum spread of size 25-1/2 by 33 inches for foldouts.

mn142 Section 09 06 90 Page 4

d. Samples for this color board are required in addition to samples requested in other specification sections.

2.2.1 Exterior Walls

Exterior wall colors shall apply to exterior wall surfaces including recesses at entrances and projecting vestibules. Conduit shall be painted to closely match the adjacent surface color. Wall color shall be provided to match the colors listed below.

2.2.1.1 Brick:

Crimson Creek Ironspot, Smooth - Modular, Hebron.

2.2.1.2 Mortar:

Natural.

2.2.1.3 Concrete Masonry Units (Burnished):

Structural Block Inc., St. Paul Limestone.

2.2.1.4 Paint:

Existing CMU: Match existing CMU.

2.2.1.5 Composite Wall Panels:

Laminator: Sierra Tan.

2.2.1.6 Glass and Glazing:

Clear, low-emissivity insulated glass.

2.2.1.7 Metal Wall Panels:

Centria Prismatic Series 154 - Dark Bronze.

2.2.1.8 Metal Louvers:

Dark Bronze.

2.2.2 Exterior Trim

Exterior trim shall be provided to match the colors listed below.

2.2.2.1 Steel Doors and Door Frames:

2.2.2.2 Aluminum Doors and Door Frames:

Dark Bronze, anodized.

2.2.2.3 Aluminum Windows (mullion, muntin, sash, trim, and sill):

Dark Bronze, anodized.

mn142 Section 09 06 90 Page 5

2.2.2.4 Metal Panel Fascia/Horizontal Metal Band:

2.2.2.5 Soffits:

Centria Prismatic Series 154 - Dark Bronze.

2.2.2.6 Exterior Overhang Ceiling:

Centria Prismatic Series 9911 - Pebble.

2.2.2.7 Downspouts, Gutters, Louvers, and Flashings:

2.2.2.8 Coping:

2.2.2.9 Precast Concrete Caps:

Precast Stoneworks, Old Kasota #269.

2.2.2.10 Caulking and Sealants:

Match color of penetrating item. Match masonry unit color in masonry joints.

2.2.2.11 Control Joints:

Match masonry unit color in masonry joints.

2.2.2.12 Aluminum Cover Plates:

Powder coat to match adjacent masonry units.

2.2.3 Exterior Metal Roof

Roof color shall apply to exterior roof surfaces including sheet metal flashings and copings, mechanical units, roof trim, pipes, conduits, electrical appurtenances, and similar items. Provide roof color to match the colors listed below.

2.2.3.1 Metal:

Midnight Bronze.

2.2.3.2 Penetrations (Metal Roof):

Match roof in color.

2.2.3.3 Flat Roof Fan Shrouds and Metal Ducts, Exposed to View from Grade:

Paint Dark Bronze to match metal roofing.

mn142 Section 09 06 90 Page 6

2.2.4 Interior Floor Finishes

Provide flooring materials to match the colors listed below.

2.2.4.1 Carpet Tile:

CPT-1 Mannington, Benchmark III; color: 1403 Chinchilla.

2.2.4.2 Resilient Tile/Vinyl Composition Tile:

RT-1 Mannington, Solid Point, 337 Toasted Sesame.

RT-2 Mannington, Solid Point, 345 Silver Leaf.

RT-3 Mannington, Brushworks Brights, 727 Deep Ochre.

2.2.4.3 Porcelain Tile:

PT-1: American Olean, Amber Valley, Bowling Green, AM88, 13 by 13.

PT-2: American Olean, Amber Valley, Bowling Green, AM88, 3 by 12.

PT-3: American Olean, Amber Valley, Bowling Green, AM88, 3 by 3.

2.2.4.4 Resilient Sheet Flooring:

LIN: Mannington, Relay, Color, 23014 Corrugated.

2.2.4.5 Grout:

GR-1 MAPEI: #11 Sahara Beige. Use with PT-1, PT-2, PT-3.

2.2.4.6 Urethane Topcoat:

Canada Gray, 100: Room 30, Vehicle Bay.

Sandy Beige: Room 500, Radar Maintenance.

2.2.4.7 Entrance Walk-Off Mat

2.2.4.7.1 Room 01:

C-S; Peditred G4; Frame Finish: Anodized clear Tread Inserts: Carpet 9322 Slate

2.2.4.7.2 Room 18:

Interface: K-12, Entry Level, Black.

2.2.5 Interior Base Finishes

Provide base materials to match the colors listed below.

2.2.5.1 Resilient Base and Moldings:

BASE-1: Roppe, Pinnacle Rubber Base, 632 Flax.

2.2.5.2 Porcelain Tile:

PT-2: Unglazed Ceramic Mozaic, Bowling Green, AM88, 3 by 12.

mn142 Section 09 06 90 Page 7

2.2.5.3 Grout:

GR-1 MAPEI: #11 Sahara Beige. Use with CT-1a.

2.2.6 Interior Wall Finishes

Interior wall color shall apply to the entire wall surface, including reveals, vertical furred spaces, grilles, diffusers, electrical and access panels, and piping and conduit adjacent to wall surfaces unless otherwise specified. Items not specified in other paragraphs shall be painted to match adjacent wall surface. Provide wall materials to match the colors listed below.

2.2.6.1 Paint:

Match Sherwin Williams, SW6098 Pacer White.

2.2.6.2 Vinyl Wall Covering:

VWC-1: Bolta, Sailor's Net, Shark, BB-NS-18

2.2.6.3 Not Used

2.2.6.4 Ceramic Tile:

CT-1: Unglazed Ceramic Mozaic, Cocoa, A89, 2 x 2 CT-2: Unglazed Ceramic Mozaic, Artichoke, A63, 2 x 2 CT-3: Unglazed Ceramic Mozaic, Cappucino, A78

2.2.6.5 Ceramic Tile Grout:

GR-2 MAPEI: #16 Malta. Use with CT-1, CT-2.

2.2.6.6 Brick:

Crimson Creek Ironspot, smooth-modular Hebron

2.2.6.7 Mortar:

Natural

2.2.6.8 Modular Wall Panel System:

Panels: Marlite Map System, Wood Veneer, 8107, Quartered Cherry Mounting Rails: Clear Satin, 1/2 inch reveal

2.2.6.9 Concrete Masonry Units (Burnished):

Masterblock, St. Paul Limestone

2.2.7 Interior Ceiling Finishes

Ceiling colors shall apply to ceiling surfaces including soffits, furred down areas, grilles, diffusers, registers, and access panels. Ceiling color shall also apply to joist, underside of roof deck, and conduit and piping where joists and deck are exposed and required to be painted. Provide ceiling materials to match the colors listed below.

mn142 Section 09 06 90 Page 8

2.2.7.1 Ceiling Tile and Grid:

ACT-1, ACT-2: Match existing ACT-3: Perforated Metal Panels, Silver Satin

2.2.7.2 Paint:

Sherwin Williams, Ceiling White, Semi-Gloss, Dry-Fall Acrylic.

2.2.7.3 Metal Deck:

2.2.7.4 Structural Framing:

2.2.8 Interior Trim

Provide interior trim to match the colors listed below.

2.2.8.1 Steel Doors:

Match Sherwin Williams 6160 Best Bronze

2.2.8.2 Steel Door Frames:

Match Sherwin Williams 6160 Best Bronze

2.2.8.3 Aluminum Doors and Door Frames:

Dark Bronze

2.2.8.4 Aluminum Windows:

(mullion, muntin, sash, trim, and sill) Dark Bronze

2.2.8.5 Wood Doors:

Match Marshfield, White Birch, Autumn 32-95

2.2.8.6 Wood Stain:

Match Marshfield, White Birch, Autumn 32-95

2.2.8.7 Window Stools:

Corian: "Moss".

2.2.8.8 Fire Extinguisher Cabinets:

Brushed Stainless.

2.2.8.9 Ladders:

Roof Access Ladder: Safety Yellow mn142 Section 09 06 90 Page 9

2.2.8.10 Exposed Ductwork:

White to match ceiling.

2.2.8.11 Closet Shelving:

PL-1: Nevamar, Basic, S2110T

2.2.9 Interior Miscellaneous

Provide miscellaneous items to match the colors listed below.

2.2.9.1 Toilet Partitions and Urinal Screens:

Mens: General Partitions, Mission Sage Womens: General Partitions Natural Tigris

2.2.9.2 Plastic Laminate:

PL-1, Nevamar, Basic, S2110T PL-2, Nevamar, House Rock, RK4001T

2.2.9.3 Solid Surfacing Material:

Window Stools: Corian "Moss" Lavatory Countertops: Corian "Canvas"

2.2.9.4 Casework (Lobby Display Case):

PL-3, Nevmar, Chinchilla textured, S6018T

2.2.9.5 Signage Message Color:

290 Sign System, Color: Oyster 232 (exclusive of ADA requirements)

2.2.9.6 Signage Background Color:

290 Sign Systems, Color: Bronze 156 (exclusive of ADA requirements)

2.2.9.7 Corner Guards:

Brushed Stainless Steel

2.2.9.8 Chair Rail:

C/S Acrovyn FRW-270N, 307 Sienna

2.2.9.9 Shower Curtain:

White

2.2.9.10 Shower Wall Kits, Trim and Shower Pan:

As selected by Owner from manufacturer's standard palette of colors.

mn142 Section 09 06 90 Page 10

PART 3 EXECUTION (NOT APPLICABLE)

-- End of Section --

SECTION TABLE OF CONTENTS

DIVISION 09 - FINISHES

SECTION 09 72 00

WALLCOVERINGS

11/12

PART 1 GENERAL

1.1 REFERENCES

1.2 SUBMITTALS

1.3 DELIVERY, STORAGE, AND HANDLING

1.4 ENVIRONMENTAL REQUIREMENTS

1.5 WARRANTY

1.6 EXTRA MATERIALS

PART 2 PRODUCTS

2.1 WALLCOVERINGS AND ACCESSORIES

2.1.1 Product Data

2.1.2 Samples

2.1.3 Certificates

2.1.4 Manufacturer's Instructions

2.1.5 Operations and Maintenance Data

2.2 VINYL WALLCOVERING (VWC1, VWC2)

2.3 ACOUSTICAL WALLCOVERING (AWC1)

2.4 PRIMER AND ADHESIVE

2.5 COLOR, TEXTURE, AND PATTERN

PART 3 EXECUTION

3.1 EXAMINATION

3.2 SURFACE PREPARATION

3.3 INSTALLATION

3.3.1 Wallcovering

3.4 CLEAN-UP

-- End of Section Table of Contents --mn142 SECTION 09 72 00 Page 1 mn142 Section 09 72 00 Page 2

SECTION 09 72 00

WALLCOVERINGS

11/12

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM C423 (2009a) Sound Absorption and Sound Absorption

Coefficients by the Reverberation Room Method

ASTM E84 (2012) Standard Test Method for Surface

Burning Characteristics of Building Materials

CHEMICAL FABRICS & FILM ASSOCIATION (CFFA)

CFFA-W-101-D (2002) Vinyl Coated Fabric Wallcovering

GYPSUM ASSOCIATION (GA)

GA 214 (2010) Recommended Levels of Gypsum Board

Finish

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 286 (2011) Standard Methods of Fire Tests for

Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth

UNDERWRITERS LABORATORIES (UL)

UL 723 (2008; Reprint Sep 2010) Test for Surface

Burning Characteristics of Building Materials

1.2 SUBMITTALS

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01000 TECHNICAL PROVISIONS:

SD-03 Product Data

Wallcoverings Primer and Adhesive

SD-04 Samples

Wallcoverings; G mn142 Section 09 72 00 Page 3

SD-07 Certificates

SD-08 Manufacturer's Instructions

SD-10 Operation and Maintenance Data

1.3 DELIVERY, STORAGE, AND HANDLING

Deliver the material to the site in manufacturer's original wrappings and packages and clearly label with the manufacturer's name, brand name, pattern and color name and number, dye lot number, size, and other related information. Store in a safe, dry, clean, and well-ventilated area at temperatures not less than 50 degrees F and within a relative humidity range of 30 to 60 percent. Store wallcovering material in a flat position and protected from damage, soiling, and moisture. Do not open containers until needed for installation, unless verification inspection is required.

1.4 ENVIRONMENTAL REQUIREMENTS

Comply with wallcovering manufacturer's printed installation instructions for minimum temperature of area to receive requirements for conditioning adhesive and wallcovering. Provide a minimum 50 degrees F area temperature, 72 hours prior to installation, during installation, and until the adhesive dries. Observe ventilation and safety procedures.

1.5 WARRANTY

Provide manufacturer's standard performance guarantees or warranties that extend beyond a one-year period.

1.6 EXTRA MATERIALS

Provide one linear foot of full-width wallcovering of each pattern and color for each 100 linear feet of wallcovering installed, excluding presentation dry erase wallcovering. Provide the same manufacturer, type, pattern, color, and lot number of extra stock as the installed wallcovering. Provide full rolls, packed for storage and marked with content, manufacturer's name, pattern and color name and number and dye lot number. Leave extra stock at the site at a location as directed by the Contracting Officer.

2.1 WALLCOVERINGS AND ACCESSORIES

Provide wall coverings and accessories material designed specifically for the specified use. Furnish vinyl wallcovering and borders with a mercury, cadmium, lead, and chromium free base. Protect wallcoverings with bactericides and mildew inhibitors against microbiological and mildew growth.

mn142 Section 09 72 00 Page 4

2.1.1 Product Data

a. Wallcovering: Submit manufacturer's descriptive data, documenting physical characteristics, flame resistance, mildew and germicidal characteristics for wallcovering.

b. Primer and Adhesive: Submit manufacturer's descriptive data, documenting physical characteristics, mildew and germicidal characteristics.

2.1.2 Samples

a. Wallcovering: Submit three samples of each indicated type, pattern, and color of wallcovering. Provide minimum 5 by 7 inch samples of wallcovering to show pattern repeat of sufficient size.

2.1.3 Certificates

Submit manufacturer's statement attesting that the product furnished meets or exceeds specification requirements. Date the statement after the award of the contract, state Contractor's name and address, name the project and location, and list the requirements being certified. Include these certificates:

(1) Certified laboratory test reports of the physical properties for vinyl wallcovering, as specified.

(2) Certificates of Compliance for UL fire hazard classification listing, as specified.

(3) Certificates of Compliance for contact adhesive.

2.1.4 Manufacturer's Instructions

Submit preprinted installation instructions for wallcovering and accessories, adhesives and primers. Include substrate preparation and material application in the instructions.

2.1.5 Operations and Maintenance Data

Submit manufacturer's maintenance instructions for each type of vinyl wallcovering and accessory describing recommended type of cleaning equipment and materials, spotting and cleaning methods, and cleaning cycles.

Instructions to also include preventative maintenance, recommended cleaning materials and precautions in the use of cleaning materials that may be detrimental to the wallcovering surface and accessories when improperly applied.

2.2 VINYL WALLCOVERING (VWC)

Provide a vinyl coated woven or nonwoven wallcovering fabric. Conform to CFFA-W-101-D for vinyl wallcovering, Type II (Medium Duty) with a minimum total weight of 13 ounces/square yard and 20 ounces/linear yard. Test vinyl wallcovering in accordance with NFPA 286 or meet the requirements of Class A when tested in accordance with ASTM E84 or UL 723.

mn142 Section 09 72 00 Page 5

2.3 NOT USED

2.4 PRIMER AND ADHESIVE

Provide a type primer and adhesive recommended by the wallcovering manufacturer, containing a non-mercury based mildewcide, and complying with local indoor air quality standards. Primer shall permit removal of the wallcovering and protect the wall surface during removal. Do not damage gypsum wallboard facing paper during removal of wallcovering. Provide a strippable type adhesive. When substrate color variations show through vinyl wallcovering, provide a white pigmented primer as recommended by the wallcovering manufacturer used to conceal the variations.

2.5 COLOR, TEXTURE, AND PATTERN

Provide color as specified in Section 09 06 90 COLOR SCHEDULE.

PART 3 EXECUTION

3.1 EXAMINATION

Inspect all areas and conditions under which wallcoverings are to be installed. Notify the Contracting Officer, in writing, of any conditions detrimental to the proper and timely completion of the installation. Work will proceed only when conditions have been corrected and accepted by the installer.

3.2 SURFACE PREPARATION

Do not apply wallcovering to surfaces that are rough, that contain stains which will bleed through the wallcovering, or that are otherwise unsuitable for proper installation. Fill cracks and holes; sand rough spots smooth.

Finish walls to receive presentation dry erase wallcovering to a Level 4 gypsum wallboard finish in accordance with GA 214 unless Level 5 is recommended by the wallcovering manufacturer. Thoroughly dry surfaces at least 30 days prior to installation of vinyl wallcovering. Provide interior surfaces of new and existing gypsum wallboard with a wallcovering primer in accordance with the manufacturer's printed instructions. As required, use white primer when substrate color variations are visible through thin or light color wallcovering. Seal interior surfaces of exterior masonry walls to prevent moisture penetration, then prime with a wallcovering primer in accordance with the manufacturer's printed instructions. Provide masonry walls with flush joints. Test moisture content of plaster, concrete, and masonry with an electric moisture meter of a maximum five percent reading.

Apply a thin coat of joint compound or cement plaster, as recommended by the wallcovering manufacturer, to the concrete and masonry walls as a substrate preparation. To promote adequate adhesion of wall lining over masonry walls, prime the walls as recommended by the wall lining manufacturer.

Prime the surfaces of walls as required by the manufacturer's printed instructions to permit ultimate removal of wallcovering from the wall surfaces. Allow primer to completely dry before adhesive application.

3.3 INSTALLATION

3.3.1 Wallcovering

mn142 Section 09 72 00 Page 6

Install wallcovering in accordance with the manufacturer's printed installation instructions. Remove glue and adhesive spillage from wallcovering face and seams with a remover recommended by the manufacturer.

3.4 CLEAN-UP

Upon completion of the work, clean wallcovering free of dirt, soiling, stain, or residual film. Remove and clean surplus materials, rubbish, and debris resulting from the wallcovering installation.

-- End of Section --

SECTION TABLE OF CONTENTS

DIVISION 10 - SPECIALTIES

SECTION 10 10 00

VISUAL COMMUNICATIONS SPECIALTIES

06/14

PART 1 GENERAL

1.1 SUBMITTALS

1.2 DELIVERY, STORAGE, AND HANDLING

1.3 WARRANTY

PART 2 PRODUCTS

2.1 2.2

CEILING PROJECTOR MOUNT

MARKERBOARD

PROJECTION SCREEN

PART 3 EXECUTION

3.1 INSTALLATION

-- End of Section Table of Contents --mn142 SECTION 10 10 00 Page 1

2.3

SECTION 10 10 00

VISUAL COMMUNICATIONS SPECIALTIES

06/14

PART 1 GENERAL

1.1 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01000 TECHNICAL PROVISIONS:

SD-03 Product Data

Ceiling Projector Mount

1.2 DELIVERY, STORAGE, AND HANDLING

Deliver materials to the building site in the manufacturer's original unopened containers and store them in a clean dry area.

1.3 WARRANTY

Provide manufacturer's standard performance guarantees or warranties.

PART 2 PRODUCTS

2.1 CEILING PROJECTOR MOUNT

Provide 24 inch by 24 inch suspended ceiling tile replacement kit equal to Model CmA455 as manufactured by Chief Manufacturing. Provide cable, brackets, turnbuckles, and anchors supplied by manufacturer to secure the tile replacement to the structure above the ceiling. Color: White.

2.2 MARKERBOARD

Markerboard shall have a porcelain enamel writing surface and a chalktray.

Markerboard shall be a factory assembled unit complete in one piece, without joints whenever possible. When markerboard dimensions require delivery in separate sections, components shall be prefit at the factory, disassembled for delivery and jointed at the site. Frame shall be aluminum. Chalktray shall be the same material as the frame and extend the full length of the markerboard. The markerboard shall have a map rail.

The map rail with a tackable insert shall extend the full length of the markerboard, and shall have map hooks with clips for holding sheets of paper. Two map hooks shall be provided for each 4 foot of map rail. Dry erase markings shall be removable with a felt eraser or dry cloth without ghosting. Each unit shall come complete with an eraser and four different color compatible dry erase markers. The size shall be as shown in the drawings.

mn142 SECTION 10 10 00 Page 2

PART 3 EXECUTION

3.1 INSTALLATION

Perform installation and assembly in accordance with manufacturer's printed instructions.

-- End of Section --mn142 SECTION 10 10 00 Page 3

Ceiling mounted motorized projection screen shall have 120V motor that is lubricated for life, quick reversal type, has overload protector, integral gears, and preset accessible limit switches. Recessed mount projection screens shall have an operable closure door and access panel. Screen shall be flame retardant, mildew resistant, and white matte with black masking borders . Bottom of screen fabric shall be weighted with metal rod. Roller shall be a rigid metal at least 3 inches in diameter mounted onsound absorbing supports. Motor will be end mounted or motor-in-roller design.

Screen shall have a 3 position control switch to stop or reverse screen at any point.

The switch shall be installed in a flush electrical box with cover plate, location(s) as shown on the electrical drawings. All conduit and wiring from the control switch to the projection screen shall be furnished and installed by the Contractor. Ceiling recessed case shall be extruded aluminum. Screen shall be UL listed. Provide drop fabric at top of screen so that bottom of screen is 48 inched above finish floor in the full down position. Proportion screen height to width for HDTV format ratio. The size shall be as shown below.

a. Room 108: 11 feet wide.

PROJECTION SCREEN2.3

mn142 Section 27 10 00 Page 1

SECTION 27 10 00

BUILDING TELECOMMUNICATIONS CABLING SYSTEM

08/11

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM D709 (2001; R 2007) Laminated Thermosetting

Materials

ELECTRONIC COMPONENTS ASSOCIATION (ECA)

ECA EIA/ECA 310 (2005) Cabinets, Racks, Panels, and

Associated Equipment

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms

INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)

ICEA S-83-596 (2011) Indoor Optical Fiber Cables

ICEA S-90-661 (2008) Category 3, 5, & 5e Individually

Unshielded Twisted Pair Indoor Cables for Use in General Purpose and LAN Communications Wiring Systems Technical Requirements

NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION (NECA)

NECA/BICSI 568 (2006) Standard for Installing Building

Telecommunications Cabling

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

ANSI/NEMA WC 66 (2001; Errata 2003) Performance Standard for

Category 6 and Category 7 100 Ohm Shielded and Unshielded Twisted Pairs

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2011; Errata 2 2012) National Electrical

Code mn142 Section 27 10 00 Page 2

TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)

TIA J-STD-607 (2002a) Commercial Building Grounding

(Earthing) and Bonding Requirements for Telecommunications

TIA-1152 (2009) Requirements for Field Test

Instruments and Measurements for Balanced Twisted-Pair Cabling

TIA-526-14 (2010b) OFSTP-14A Optical Power Loss

Measurements of Installed Multimode Fiber Cable Plant

TIA-526-7 (2002; R 2008) OFSTP-7 Measurement of Optical

Power Loss of Installed Single-Mode Fiber Cable Plant

TIA-568-C.0 (2009; Add 1 2010) Generic Telecommunications

Cabling for Customer Premises

TIA-568-C.1 (2009; Add 2 2011; Add 1 2012) Commercial

Building Telecommunications Cabling Standard

TIA-568-C.2 (2009; Errata 2010) Balanced Twisted-Pair

Telecommunications Cabling and Components Standards

TIA-568-C.3 (2008; Corrections 2008) Optical Fiber

Cabling Components Standard

TIA-569 (2012c) Commercial Building Standard for

Telecommunications Pathways and Spaces

TIA/EIA-598 (2005c) Optical Fiber Cable Color Coding

TIA/EIA-606 (2002a; Errata 2007; R 2007; Adm 1 2008)

Administration Standard for the Telecommunications Infrastructure

U.S. FEDERAL COMMUNICATIONS COMMISSION (FCC)

FCC Part 68 Connection of Terminal Equipment to the

Telephone Network (47 CFR 68)

UNDERWRITERS LABORATORIES (UL)

UL 1286 (2008; Reprint Sep 2011) Office Furnishings

UL 1666 (2007; Reprint May 2011) Test for Flame

Propagation Height of Electrical and Optical- Fiber Cables Installed Vertically in Shafts

UL 1863 (2004; Reprint Aug 2008) Communication

Circuit Accessories mn142 Section 27 10 00 Page 3

UL 444 (2008; Reprint Apr 2010) Communications Cables

UL 467 (2007) Grounding and Bonding Equipment

UL 50 (2007; Reprint Apr 2012) Enclosures for

Electrical Equipment, Non-environmental Considerations

UL 514C (1996; Reprint Novy 2011) Nonmetallic Outlet

Boxes, Flush-Device Boxes, and Covers

UL 723 (2008; Reprint Sep 2010) Test for Surface

Burning Characteristics of Building Materials

UL 969 (1995; Reprint Nov 2008) Standard for Marking and Labeling Systems

1.2 RELATED REQUIREMENTS

Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM applies to this section with additions and modifications specified herein.

1.3 DEFINITIONS

Unless otherwise specified or indicated, electrical and electronics terms used in this specification shall be as defined in TIA-568-C.1, TIA-568-C.2, TIA-568-C.3, TIA-569, TIA/EIA-606 and IEEE 100 and herein.

1.3.1 Campus Distributor (CD)

A distributor from which the campus backbone cabling emanates.

(International expression for main cross-connect (MC).)

1.3.2 Building Distributor (BD)

A distributor in which the building backbone cables terminate and at which connections to the campus backbone cables may be made. (International expression for intermediate cross-connect (IC).)

1.3.3 Floor Distributor (FD)

A distributor used to connect horizontal cable and cabling subsystems or equipment. (International expression for horizontal cross-connect (HC).)

1.3.4 Telecommunications Room (TR)

An enclosed space for housing telecommunications equipment, cable, terminations, and cross-connects. The room is the recognized cross-connect between the backbone cable and the horizontal cabling.

1.3.5 Entrance Facility (EF) (Telecommunications)

An entrance to the building for both private and public network service cables (including wireless) including the entrance point at the building wall and continuing to the equipment room.

mn142 Section 27 10 00 Page 4

1.3.6 Equipment Room (ER) (Telecommunications)

An environmentally controlled centralized space for telecommunications equipment that serves the occupants of a building. Equipment housed therein is considered distinct from a telecommunications room because of the nature of its complexity.

1.3.7 Open Cable

Cabling that is not run in a raceway as defined by NFPA 70. This refers to cabling that is "open" to the space in which the cable has been installed and is therefore exposed to the environmental conditions associated with that space.

1.3.8 Open Office

A floor space division provided by furniture, moveable partitions, or other means instead of by building walls.

1.3.9 Pathway

A physical infrastructure utilized for the placement and routing of telecommunications cable.

1.4 SYSTEM DESCRIPTION

The building telecommunications cabling and pathway system shall include permanently installed backbone and horizontal cabling, horizontal and backbone pathways, service entrance facilities, work area pathways, telecommunications outlet assemblies, conduit, raceway, and hardware for splicing, terminating, and interconnecting cabling necessary to transport telephone and data (including LAN) between equipment items in a building.

The horizontal system shall be wired in a star topology from the telecommunications work area to the floor distributor or campus distributor at the center or hub of the star. The backbone cabling and pathway system includes intrabuilding and interbuilding interconnecting cabling, pathway, and terminal hardware. The intrabuilding backbone provides connectivity from the floor distributors to the building distributors or to the campus distributor and from the building distributors to the campus distributor as required. The backbone system shall be wired in a star topology with the campus distributor at the center or hub of the star. Provide telecommunications pathway systems referenced herein as specified in Section

26 20 00 INTERIOR DISTRIBUTION SYSTEM.

1.5 SUBMITTALS

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01000 TECHNICAL PROVISIONS:

SD-02 Shop Drawings

Telecommunications drawings; G

Telecommunications Space Drawings; G mn142 Section 27 10 00 Page 5

In addition to Section 01000 TECHNICAL PROVISIONS, provide shop drawings in accordance with paragraph SHOP DRAWINGS.

SD-03 Product Data

Telecommunications cabling (backbone and horizontal); G

Patch panels; G

Telecommunications outlet/connector assemblies; G

Equipment support frame; G

Connector blocks; G

Spare Parts; G

Submittals shall include the manufacturer's name, trade name, place of manufacture, and catalog model or number. Include performance and characteristic curves. Submittals shall also include applicable federal, military, industry, and technical society publication references. Should manufacturer's data require supplemental information for clarification, the supplemental information shall be submitted as specified in paragraph REGULATORY REQUIREMENTS and as required in Section 01000 TECHNICAL PROVISIONS.

SD-06 Test Reports

Telecommunications cabling testing; G

SD-07 Certificates

Telecommunications Contractor Qualifications; G

Key Personnel Qualifications; G

Manufacturer Qualifications; G

Test plan; G

SD-09 Manufacturer's…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .