COMMUNICATION SQUADRON HEADQUARTERS
BUILDING 314
GRAND FORKS AIR FORCE BASE
JOHN L.
PRESCHER
DATE
TASK JFSD200143A: CONSTRUCT MAIN ENTRY FOR B314
TASK JFSD200143B: REPAIR COMMUNICATION SQUADRON B314
TASK JFSD949951A: ADD PARKING LOT/LIGHTS
TASK JFSD949951B: REPAIR PARKING LOT/LIGHTS
TASK JFSD949951C: LANDSCAPE PARKING LOT
"ISSUE FOR BID/CONSTRUCTION"
TIL
M
IBO
RI
MM
Y
OC
NA
D
IBO
RI
MM
Y
OC
Finished Floor Elev. 895.44
319th Communications Squadron Building 314
(371 Steen Blvd)
Building 313
TIL
M
IBO
RI
MM
Y
OC
Building 314
(371 Steen Blvd)
Building 313
TIL
M
IBO
RI
MM
Y
OC
Building 314
(371 Steen Blvd)
Building 313
TIL
M
IBO
RI
MM
Y
OC
Building 314
(371 Steen Blvd)
Building 313
TIL
M
IBO
RI
MM
Y
OC
NA
D
POINT DISTANCE NORTHING EASTING
ID (FEET) (Y) (X) PC PI PT DELTA R L T
PI-1 S 3°01'50" E 111.89 361173.13 2733319.70 0+00.00
PI-2 S 49°48'55" E 137.70 361061.40 2733325.62 0+62.57 1+55.66 46°47'05" -114.00 93.09 49.31 PI-3 S 40°11'05" W 101.30 360972.55 2733430.82 1+99.05 2+69.74 90°00'00" 45.00 70.69 45.00 PI-4 S 87°41'15" W 63.54 360895.16 2733365.46 2+97.87 3+50.93 47°30'10" 64.00 53.06 28.16
PI-5 360892.60 2733301.97 3+86.31
BEARING
ENTRANCE ROAD - CONTROL LINE DATA
LINE
NO.
LENGTH
(FT)
BEARING
L3 55.77 N 2°18'45" W 360926.64 2733302.39 L4 39.14 S 87°03'24" W 360982.27 2733300.14 L5 9.09 N 87°49'56" E 360939.90 2733113.83 L6 107.83 S 2°18'45" E 360894.21 2733172.59 L7 131.00 N 87°41'15" E 360786.47 2733176.94 L8 67.00 N 2°18'45" W 360791.75 2733307.84 L10 27.18 S 40°22'03" E 360862.16 2733370.59 L11 14.50 S 49°37'57" W 360834.40 2733387.62 L12 211.00 S 40°22'03" E 360825.01 2733376.58 L13 115.00 N 49°37'57" E 360664.25 2733513.24 L14 211.00 N 40°22'03" W 360738.73 2733600.86 L15 62.50 S 49°37'57" W 360899.50 2733464.20 L16 22.02 N 40°22'03" W 360859.59 2733409.53 L20 29.00 S 2°18'45" E 360936.49 2733199.41 L21 29.00 N 2°18'45" W 360907.92 2733210.57 L22 29.00 S 2°18'45" E 360939.08 2733263.36 L23 29.00 N 2°18'45" W 360910.50 2733274.52 L24 29.00 S 2°18'45" E 360869.55 2733202.11 L25 29.00 N 2°18'45" W 360840.98 2733213.27 L26 29.00 S 2°18'45" E 360872.13 2733266.06 L27 29.00 N 2°18'45" W 360843.56 2733277.22 L30 29.00 S 49°37'57" W 360856.41 2733457.51 L31 29.00 N 49°37'57" E 360830.01 2733441.89 L32 29.00 S 49°37'57" W 360746.69 2733550.78 L33 29.00 N 49°37'57" E 360720.29 2733535.16
LINE TABLE
BEGINNING POINT
(NORTH, EAST)
NO. RADIUS
(FT) DELTA LENGTH
(FT)
C1 40.00 90°00'00" 62.83 360966.13 2733354.73 C4 48.00 89°51'19" 75.28 360892.27 2733124.63 C6 50.00 51°56'42" 45.33 360829.78 2733332.49 C7 5.00 90°00'00" 7.85 360838.21 2733384.39 C8 5.00 90°00'00" 7.85 360862.83 2733413.34 C9 25.00 80°33'08" 35.15 360892.56 2733414.31 C10 50.00 90°00'00" 78.54 360968.27 2733380.09 C20 5.00 180°00'00" 15.71 360936.70 2733204.40 C21 5.00 180°00'00" 15.71 360907.72 2733205.58 C22 5.00 180°00'00" 15.71 360939.28 2733268.35 C23 5.00 180°00'00" 15.71 360910.30 2733269.52 C24 5.00 180°00'00" 15.71 360869.75 2733207.11 C25 5.00 180°00'00" 15.71 360840.77 2733208.28 C26 5.00 180°00'00" 15.71 360872.33 2733271.06 C27 5.00 180°00'00" 15.71 360843.36 2733272.23 C30 5.00 180°00'00" 15.71 360852.60 2733460.75 C31 5.00 180°00'00" 15.71 360833.82 2733438.66 C32 5.00 180°00'00" 15.71 360742.88 2733554.02 C33 5.00 180°00'00" 15.71 360724.10 2733531.92
CURVE TABLE
RADIUS POINT
(NORTH, EAST)
Building 314
(371 Steen Blvd)
Building 313
TIL
M
IBO
RI
MM
Y
OC
Building 314
(371 Steen Blvd)
Building 313
TIL
M
IBO
RI
MM
Y
OC
Building 314
(371 Steen Blvd)
Building 313
TIL
M
IBO
RI
MM
Y
OC
IBO
RI
MM
Y
OC
NA
D
NORTH EAST
MH-1 361029.09 2733402.62 90° 90° 6.60 48" ID D-722-5 MANHOLE D-722-5 C.I. RING & COVER 893.40 886.80 MH-2 0.95 886.40 12" PVC 41 MH-2 361055.28 2733371.61 145° 6.80 48" ID D-722-5 MANHOLE D-722-5 C.I. RING & COVER 893.10 886.30 MH-3 1.06 885.70 15" PVC 65 MH-3 361117.86 2733354.48 105° 88° 6.70 48" ID D-722-5 MANHOLE D-722-5 C.I. RING & COVER 892.30 885.60 J-1 29.80 881.13 24" PVC 16 J-1 361133.59 2733353.85 90° -- -- SEE DETAIL SPECIAL N/A N/A -- 881.13 -- -- -- -- -- DIRECT CONNECTION TO EXISTING 66" RCP
CB-5 360931.40 2733320.10 3.40 30" ID D-722-1A INLET - CATCH BASIN D-722-1A TYPE A 893.90 890.50 MH-1 2.82 887.00 12" PVC 128 CB-6 361117.77 2733309.20 2.47 30" ID D-722-1B INLET - SPECIAL D-722-1 TYPE I-V 891.07 888.60 CB-7 1.85 888.10 12" PVC 27 CB-7 361117.87 2733336.06 180° 3.03 48" ID D-722-1B INLET - SPECIAL D-722-1 TYPE I-V 891.03 888.00 MH-3 2.78 887.50 12" PVC 18 FES-1 360650.90 2733525.15 1.50 -- D-714-01 FLARED END SECTION N/A N/A 892.00 890.50 WETLAND -- -- 18" RCP 6
CASTING STD.
DWG. (NDDOT)
DEPTH
(FEET)
CASTING
TOP EL.
STORM DRAIN SCHEDULE
COORDINATES
DRAINAGE
STRUCTURE REMARKS% GRADE INLET OR
INV. ELEV.
PIPE SIZE
& TYPE
LENGTH
(FEET)
OUTLET
ELEV.
DRAINS TO
DESCRIPTIONSTRUCTURELOCATION
ANGLE (°) DIMENSION
STRUCTURE
STD. DWG.
(NDDOT)
CASTING TYPE
IBO
RI
MM
Y
OC
NA
D
NO.
SW1 360771.26 2733236.11
SW2 360743.00 2733242.56
SW3 360721.01 2733243.46
SW4 360730.82 2733289.31
SW5 360773.20 2733296.56
SW6 360708.19 2733288.46
SW7 360666.01 2733320.08
SW8 360640.45 2733318.78
SW9 360646.85 2733344.98
SW10 360658.16 2733448.45
SW11 360678.65 2733480.00
SW12 360811.64 2733370.51
SW13 360786.61 2733315.82
SIDEWALK POINT TABLE
RADIUS POINT
(NORTH, EAST)
IBO
RI
MM
Y
OC
IBO
RI
MM
Y
OC
IBO
RI
MM
Y
OC
IBO
RI
MM
Y
OC
12 SIPR
20 Training
22 Conference Room
23 Classroom
50 Mail Room
100 Command Support Staff
108 Command Conference Room
200 Plans and Requirements
209 SCXP Conference Room
300 HFGCS Control Center
307 HFGCS Administration
321 COMSEC
400 Knowledge Ops
500 Airfield Systems
600 ITAM
700 MSG / EIM
800 PWCS
SCOT
319 Communications Squadron
DIRECTORY
ROOM NUMBER ROOM NAME WALLS FLOORING BASE CEILING CEILING HEIGHT NOTES
1 Entry Alum Storefront PT-1 PT-2 ACT3 10'-6" Embedded walk-off mat 2 Lobby See A-401, 402 RT-1, RT-2, RT-3 V ACT3 10'-0" 3 Corridor (N-S) PT RT-1, RT-2 V ACT2 8'-0"
5 Corridor (E-W) PT RT-1 V ACT2 8'-0" 6 Corridor (N-S) PT RT-1, RT-2 V ACT2 8'-0" 7 Corridor (E-W) PT RT-1 V ACT2 8'-0" 8 Corridor (E-W) PT RT-1 V ACT2 8'-0"
9-11
12 SIPR PT RT-1 V GB 8'-0"
13 Comm Closet PT RT-1 V EXP, PT 13' (verify) 16 Mens Toilet CT-1, CT-2 PT-1 PT-2 GB 8'-6" 17 Womens Toilet CT-1, CT-3 PT-1 PT-2 GB 8'-6" 18 Vestibule PT PT-3 PT-2 GB 8'-0" 19 Mechanical Rm ~ ~ ~ ~ 20 Training Rm PT CPT V ACT1 9'-0" 21 Vestibule PT PT-3 PT-2 GB 8'-0"
22 Conference Rm VWC & PT CPT V ACT1 9'-0" Perimeter dropped soffit, VWC below chair rail 23 Classroom PT CPT V ACT1 9'-0" 24 Mens Toilet CT-1, CT-2 PT-1 PT-2 GB 8'-6" 25 Womens Toilet CT-1, CT-3 PT-1 PT-2 GB 8'-6" 26 Roof Access ~ ~ ~ ~ ~ 27 Utility Rm ~ ~ ~ ~ ~ 28 Mechanical Rm ~ ~ ~ ~ ~ 29 Mechanical Rm ~ ~ ~ ~ ~ 30 Vehicle Bay PT Urethane ~ EXP, PT 20' (verify) 31 ~ ~ ~ ~ ~ ~ 32 Corridor PT RT-1 V ACT2 8'-0" 33 Mens Toilet ~ ~ ~ ~ ~ 34 Womens Toilet ~ ~ ~ ~ ~ 35 Vestibule ~ ~ ~ ~ ~ 36 Storage ~ ~ ~ ~ ~ 37 Mechanical Rm ~ ~ ~ ~ ~ 38 Records ~ ~ ~ ~ ~ 39 Vestibule PT PT-3 PT-2 ACT-1 8'-0" 40 Office PT CPT V ACT1 8'-0"
41-49 50 Mail PT RSF-1 V EXP, PT 13' (verify) 51 Secure Storage PT RSF-1 V GB 8'-0"
52-59 60 ACC High Bay ~ ~ ~ ~ ~ 61 ~ ~ ~ ~ ~
62 ACC ~ ~ ~ ~ ~
63 ACC ~ ~ ~ ~ ~
64 ACC ~ ~ ~ ~ ~
65 ACC ~ ~ ~ ~ ~
67-99 100 Reception VWC & PT CPT V ACT1 9'-0" 101 Commander VWC & PT CPT V ACT1 9'-0"
101A Closet PT CPT V ACT1 8'-0" 102 Executive Officer VWC & PT CPT V ACT1 8'-6" VWC ON NORTH AND EAST WALLS 103 1stSGT PT CPT V ACT1 8'-0"
104 CEM OFF PT CPT V ACT1 8'-0"
105 Admin PT CPT V ACT1 8'-0" 106 Work Rm PT CPT V ACT1 8'-0" 107 Storage PT RT-1 V ACT1 8'-0"
108 Conference Rm VWC & PT CPT V ACT1 9'-0" Perimeter dropped soffit, VWC WEST
WALL
109-199
200 SCXP VWC & PT CPT V ACT1 9'-0"
201 Flt Chief VWC & PT CPT V ACT1 8'-6" 202 Flt Sup PT CPT V ACT1 8'-0" 203 Office PT CPT V ACT1 8'-0" 204 Reception PT CPT V ACT1 8'-0" 205 Unit Res Adv PT CPT V ACT1 8'-0" 206 Work Rm PT RT-3 V ACT1 8'-0" 207 Break Rm PT RT-3 V ACT1 8'-0" 208 UDM Office PT CPT V ACT1 8'-6"
209 Conference Rm VWC & PT CPT V ACT1 9'-0" Perimeter dropped soffit, VWC below chair rail, North and South walls
210 CAD PT CPT V ACT2 10'-0"
211 Storage PT RT-1 V EXP, PT 13' (verify)
212-299 300 HFGCS Control Ctr PT ~ ~ ~ ~ NOTE 4
300A Control PT RT-1 V GB 8'-0" 301 Control PT RT-1 V GB 8'-0" 302 HFGCS Equip. ~ ~ ~ ~ ~ 303 Training Rm PT CPT V ACT1 8'-0" 304 Break Area PT RT-3 V ACT1 8'-0"
304A Vestibule PT RT-1 V ACT1 8'-0" 305 Mens Toilet CT-1, CT-2 PT-3 PT-2 GB 8'-0" 306 Womens Toilet CT-1, CT-3 PT-3 PT-2 GB 8'-0" 307 HFGCS Admin PT CPT V ACT1 9'-0"
308 OIC PT CPT V ACT1 8'-0"
309 NCOIC PT CPT V ACT1 8'-0"
310 Office PT CPT V ACT1 8'-0" 311 Control PT CPT V GB 8'-0" 312 Storage PT RT-3 V ACT1 8'-0"
313-319 320 Control PT RT-1 V ACT1 8'-0" 321 Comm Sec PT CPT V ACT1 9'-0"
322 NCOIC PT CPT V ACT1 8'-0"
323 Equipment PT CPT V ACT1 ~ Existing clg remains
324-399
400 SCXK PT CPT V ACT1 9'-0"
401 Admin Office PT CPT V ACT1 8'-0" 402 Record Mgmt PT CPT V ACT1 8'-0" 403 Storage PT CPT V ACT1 8'-0"
404-499 500 Radar Maint. PT Urethane V EXP, PT 13' (verify) 501 Office PT CPT V ACT1 8'-0" 502 Storage PT CPT V ACT1 8'-0" 503 SCOA Storage PT RT-1 V EXP, PT 13' (verify) 504 Office PT CPT V ACT1 8'-0"
505-599
600 SCOS PT RSF-1 V ACT2 10'-0"
601 Office PT CPT V ACT1 8'-0"
602-699
700 QA PT CPT V ACT1 9'-0"
701 NCOIC PT CPT V ACT1 8'-0"
702-799
800 PWCS PT CPT V ACT1 8'-0"
801 Office PT CPT V ACT1 8'-0" 802 PWCS Trunk Rm PT CPT V ACT1 8'-0" 803 Storage PT CPT V ACT1 8'-0"
CPT = CARPET
VCT = VINYL COMPOSITION TILE NUMBERS INDICATE COLOR/PATTERN - SEE SPECIFICATIONS
ACT = ACOUSTICAL CEILING TILE
GB = GYPSUM BOARD
EXP = EXPOSED TO STRUCTURE
CT = CERAMIC TILE
RT = RESILIENT TILE
V = VINYL BASE
PT=PAINT
LIN = LINOLEUM
PT=PORCELAIN TILE
ROOM SCHEDULE
not used not used not used not used not used not used not used
ROOM DESIGNATION FINISHES
not used not used not used not used not used
DOOR NUMBER SIZE TYPE MATERIAL GLASS TYPE MATERIAL DETAIL FIRE RATING HARDWARE SECURITY NOTES 5 72x84 D HM ~ B4 HM SH, SJ smoke 13 Smoke Seals
10 72x84 A ALUM LA Storefront ALUM 1a Center mullion, one leaf power-operated 11 72x84 A ALUM LHS Storefront ALUM 1b Center mullion 12 36x84 B HM A4 HM AH, AJ 2 Keypad Lockset 13 36x84 B HM A2 HM BJ 2 Keypad Lockset 16 36x84 B WD A4 HM GJ 6 17 36x84 B WD A4 HM GJ 6
18A 36x84 C HM 1/4" Clr A4 HM HH, HJ 7 Thermally-broken frame 18B 36x84 C HM 1/4" Clr A4 HM AH, AJ 8
19 72x84 D HM B4 HM IH, IJ 9 Louvers and removable mullion 20 36x84 C WD 1/4" Clr A2 HM BJ 10
21A 72x84 ~ ~ ~ ~ ~ ~ ~ Existing Door & Frame, Paint
21B 72x84 ~ ~ ~ ~ ~ ~ ~ Existing Door & Frame, Paint 22A 36x84 C WD 1/4" Clr A2 HM BJ 10 Acoustical Gasket 22B 36x84 C WD 1/4" Clr A2 HM BJ 10 Acoustical Gasket 23 36x84 C WD 1/4" Clr A2 HM BJ 10 24 36x84 B WD A4 HM JH, JJ 6 25 36x84 B WD A4 HM JH, JJ 6 26 36x84 B HM A4 HM JH, JJ 12 39 72x84 F HM LHS A2 HM LH, LJ 16 Thermally-broken frame 50 40x84 C WD 1/4" Clr A2 HM BJ 3 51 36x84 B HM A2 HM BJ 2 Keypad Lockset
100 36x84 E WD 1/4" Clr, Lam A4 HM CH, CJ 3 101 36x84 C WD 1/4" Clr A2 HM FJ 10 Acoustical Gasket
101A 36x84 B WD A2 HM FJ 18 102 36x84 C WD 1/4" Clr A2 HM FJ 10 103 36x84 C WD 1/4" Clr A2 HM FJ 10 104 36x84 C WD 1/4" Clr A2 HM FJ 10 105 36x84 C WD 1/4" Clr A2 HM FJ 10 106 36x84 ~ ~ ~ A2 HM PJ ~ Cased Opening 107 36x84 B HM A4 HM AH, AJ 10
108A 36x84 C WD 1/4" Clr A4 HM CH, CJ 3 Acoustical Gasket 108B 36x84 C WD 1/4" Clr A2 HM FJ 10 Acoustical Gasket 108C 48x84 D WD B2 HM EJ 5 200 36x84 E WD 1/4" Clr, Lam A4 HM CH, CJ 3 201 36x84 C WD 1/4" Clr A2 HM FJ 10 202 36x84 C WD 1/4" Clr A2 HM FJ 10 203 36x84 C WD 1/4" Clr A2 HM FJ 10 204 36x84 C WD 1/4" Clr A2 HM FJ 10 205 36x84 C WD 1/4" Clr A2 HM FJ 10 206 36x84 C WD 1/4" Clr A2 HM FJ 18 207 36x84 C WD 1/4" Clr A2 HM FJ 18 208 36x84 C WD 1/4" Clr A4 HM CH, CJ 3
209A 36x84 C WD 1/4" Clr A4 HM CH, CJ 3 209B 36x84 C WD 1/4" Clr A2 HM FJ 10 210 36x84 C HM A4 HM 21 211 36x84 B HM A2 HM BJ 10
300A 36x84 BS HM ~ A2 HM FJ 26
Security Door Combination Lock
Keypad Lockset
300B 72x84 DS HM ~ B4 HM NH, NJ 23
Security Door Thermally-broken frame, Center mullion, No exterior trim
300C 42x84 ~ ~ ~ A2 HM PJ 25 Cased Opening
301 72x84 DS HM ~ A4 HM OH, OJ 28
Security Door Combination Lock
Keypad Lockset Removable mullion
302 72x84 DS HM ~ A2 HM FJ 27
Security Door Keypad Lockset
Acoustical Gasket Removable mullion
303 36x84 C WD 1/4" Clr A2 HM FJ 18 304 60x84 ~ ~ ~ B2 HM PJ ~ Cased Opening
304A 96x84 ~ ~ ~ B2 HM UJ ~ Cased Opening 305 36x84 B WD ~ A2 HM FJ 6 306 36x84 B WD ~ A2 HM FJ 6 308 36x84 C WD 1/4" Clr A2 HM FJ 10 309 36x84 C WD 1/4" Clr A2 HM FJ 10 310 36x84 C WD 1/4" Clr A2 HM FJ 10 311 36x84 B WD ~ A2 HM BJ 3 312 36x84 B WD ~ A2 HM FJ 18
320 36x84 BS HM ~ A4 HM VJ, VH 26
Security Door Combination Lock
Keypad Lockset
321 36x84 BS HM ~ A2 HM BJ 25
Security Door Keypad Lockset
Acoustical Gasket 322 36x84 C WD 1/4" Clr A2 HM FJ 10
323 36x84 BS HM ~ A4 HM NH, NJ 20
Security Door Thermally broken frame, No exterior trim 400 36x84 C WD 1/4" Clr C2 HM BJ 3 Side Light 401 36x84 C WD 1/4" Clr A2 HM FJ 10 402 36x84 C WD 1/4" Clr A2 HM FJ 10 403 36x84 B WD A2 HM FJ 18
500A 36x84 C WD 1/4" Clr C2 HM BJ 3 500B 72x84 D HM ~ B4 MH QH, QJ smoke 22 Smoke Seals 501 36x84 C WD 1/4" Clr A2 HM FJ 10 502 36x84 C WD 1/4" Clr A2 HM FJ 18 503 36x84 B HM ~ A4 HM JH, JJ 10 504 36x84 C WD 1/4" Clr A2 HM FJ 10
600A 36x84 C HM 1/4" Clr A4 HM RH, RJ smoke 15 Smoke Seals 600B 80x84 D HM ~ B4 HM RH, RJ smoke 24 Smoke Seals 601 36x84 C WD 1/4" Clr A2 HM FJ 10 700 36x84 C HM 1/4" Clr A4 HM Existing 3 701 36x84 C WD 1/4" Clr A2 HM FJ 10 800 72x84 D HM ~ B4 HM Existing 19 Thermally broken frame
HM = HOLLOW METAL
ALUM = ALUMINUM
STL = STEEL
WD = WOOD
LA = Type LA Insulating Glass LHS = Type LHS Insulating Glass Center mullions to be removable unless noted otherwise
DOOR SCHEDULE
Door Openings, 22A, 22B, 101, 108A, 108B, 302 and 321 shall perform acoustically to a STC rating of 45 or better.
DOOR FRAME
Commander Support Staff
Command Conference Room
Storage
SIPR
Plans And Requirements
SCXP
Conference Room
Unit Deployment Manager
Storage
Comm Closet
Training Room
HFGCS
Administration
HFGCS
Control Center
Training Room
COMSEC
Knowledge Ops
Conference Room
Classroom
Mail Room
ITAM
MSG/EIM Suite
PWCS
SCOA Storage
Stair Access to Roof
CS/CSS
CS/SCXP CS/SCXX
CS/SCP CS/SCP
CS/SCXS
CS/SCXK
SC/SCOA
Airfield Systems
SC/SCOS SC/SCOS
EXIT ACCESSIBLE
EXIT MEN WOMEN
MEN WOMEN
XX
XXXXX
XX
XXXXX
XX
XXXXX
XX
XXXXX
XX
XXXXX
12 SIPR
20 Training
22 Conference Room
23 Classroom
50 Mail Room
100 Command Support Staff
108 Command Conference Room
200 Plans and Requirements
209 SCXP Conference Room
300 HFGCS Control Center
307 HFGCS Administration
321 COMSEC
400 Knowledge Ops
500 Airfield Systems
600 ITAM
700 MSG / EIM
800 PWCS
SCOT
319 Communications Squadron
DIRECTORY
PLUMBING FIXTURE SCHEDULE
LAV-1 LAVATORY 1 1/4 1 1/4 1/2 1/2 (2)
LAV-2 LAVATORY 1 1/4 1 1/4 1/2 1/2 (3)
SH-1 SHOWER 2 1 1/2 1/2 1/2 -
WC-1 WATER CLOSET 2 1 1/2 1 - -
WC-2 WATER CLOSET 2 1 1/2 1 - (1)
EWC-1 ELECTRIC WATER COOLER 1 1/4 1 1/4 1 - (4)
UR-1 URINAL 1 1/2 1 1/2 1/2 - (2)
NOTES:
(1) ADA COMPLIANT
(2) WALL-MOUNTED
(3) COUNTER-MOUNTED
(4) PROVIDE WATER BOTTLE FILLER AS SPECIFIED
NOTE(S)HW (IN)CW (IN)
PLAN
DESIGNATION TYPE
WASTE
(IN) VENT (IN)
LOUVER DIMENSIONS THROAT DIMENSIONS
LENGTH
(IN) WIDTH (IN) LENGTH
(IN)
WIDTH
(IN)
LVR-1 ROOF HP-9 INTAKE STATIONARY RUSKIN PH811 175 500 1.0 0.10 10 28 28 12 12 1 (1) LVR-2 ROOF HP-10 INTAKE STATIONARY RUSKIN PH811 210 500 1.0 0.10 10 28 28 12 12 1 (1) LVR-3 ROOF HP-11 INTAKE STATIONARY RUSKIN PH811 200 500 1.0 0.10 10 28 28 12 12 1 (1) LVR-4 ROOF HP-12 INTAKE STATIONARY RUSKIN PH811 200 500 1.0 0.10 10 28 28 12 12 1 (1) LVR-5 ROOF HP-13 INTAKE STATIONARY RUSKIN PH811 250 500 1.0 0.10 10 28 28 12 12 1 (1)
NOTES:
(1) PROVIDE BIRD SCREEN
LOCATION MODE BASIS OF DESIGN
MANUFACTURERTYPESERVICE
LOUVER (LVR) SCHEDULE
HEIGHT
(IN) NOTESQTY.BASIS OF
DESIGN MODEL
FLOW RATE
(CFM)
MAXIMUM FREE
AREA VELOCITY
(FPM)
MINIMUM FREE
AREA (ft2)
MAXIMUM PRESSURE
DROP (in. w.g.)
PLAN
DESIGNATION
PLAN
DESIGNATION
SERVICE LOCATION BASIS OF DESIGN
MANUFACTURER
BASIS OF
DESIGN MODEL
STORAGE
CAPACITY (GAL.)
UPPER
ELEMENT (KW)
VOLTS/HZ
/PHASE
FLOW RATE (GPM) @
TEMPERATURE RISE (°F)
NOTES
WH-1 16/17 17 EEMAX EX012240TML - 11.5 240/60/3 1.5 GPM @ 55°F
WH-2 305/306 306 EEMAX EX95TML - 9.5 240/60/3 1 GPM @ 55°F
NOTES:
INSTANTANEOUS ELECTRIC WATER HEATER (WH) SCHEDULE
PLAN
DESIGNATION SERVICE LOCATION
BASIS OF
DESIGN
MANUFACTURER
BASIS OF
DESIGN
MODEL
CATALOG
NUMBER SIZE FINS/FT TIERS
TUBE
SIZE
(IN)
HEIGHT
(IN)
AVG
WATER
TEMP
BTU/HR/FT NOTES
FT-1 HEATING SYSTEM 10 STERLING VB-PM C3/4-435 4-1/4" X 3-5/8" 50 2-W 3/4 10.75 180 1904 (1)(2)
NOTES:
(1) PEDESTAL MOUNTED SYSTEM.
(2) INSTALL PER MANUFACTURER RECOMMENDATIONS.
FINTUBE (FT) SCHEDULEGRILLE, REGISTER, AND DIFFUSER SCHEDULE
SD-1 SUPPLY DIFFUSER TITUS TMS 30 0 240 6" DIA LAY IN STEEL (1)
SD-2 SUPPLY DIFFUSER TITUS TMS 30 240 350 8" DIA LAY IN STEEL (1)
SD-3 SUPPLY DIFFUSER TITUS TMS 30 350 540 10" DIA LAY IN STEEL (1)
SD-4 LINEAR DIFFUSER TITUS ML-39 30 70/FT 70/FT 2 SLOTS, 1" WIDE, 4' LENGTH LAY IN ALUMINUM (5) (6)
RG-1 RETURN EGGCRATE TITUS 50F 30 0 350 12"x 6" LAY IN ALUMINUM (1) (4) RG-2 RETURN EGGCRATE TITUS 50F 30 350 750 12"x 12" LAY IN ALUMINUM (1) (4) RG-3 RETURN EGGCRATE TITUS 50F 30 750 1,000 22"x 10" LAY IN ALUMINUM (1) (4)
EG-1 EXHAUST GRILLE TITUS 350 RL 30 0 200 6"x 6" SURFACE STEEL (1) (3) EG-2 EXHAUST GRILLE TITUS 350 RL 30 200 600 12"x 12" SURFACE STEEL (1) (3)
NOTES:
(1) WHITE FINISH
(2) CONCEALED MOUNTING
(3) 35° BLADES 3/4" SPACING
(4) 1/2"x1/2"x1/2" GRID CORE
(5) PROVIDE OPPOSED BLADE DAMPER
(6) PROVIDE ANODIZED FINISH TO MATCH CEILING SYSTEM
NOTES
MINIMUM
FLOW RATE
(CFM)
MAXIMUM
FLOW RATE
(CFM)
MAXIMUM
NC LEVEL
PLAN
DESIGNATIO
N
TYPE
BASIS OF
DESIGN
MANUFACTURER
BASIS
OF
DESIGN
MODEL
NECK SIZE MOUNTING/
CONSTRUCTION
0-33.5 3/4" 0-3.5 33.6-67 1" 3.6-7.0 67-124 1-1/4" 7.1-13.0
125-209 1-1/2" 13.1-19.0 210-428 2" 19.1-45.0 429-665 2-1/2" 45.1-70.0 666-1235 3" 71-130
1236-2565 4" 131-270 2566-4750 5" 271-500 4751-7600 6" 501-800 7601-15675 8" 801-1650
NOTES:
(1) BASED ON TYPE L COPPER PIPE
(2) 20 DEG TEMPERATURE DROP
HOT WATER SIZING SCHEDULE
MBH SUPPLY AND
RETURN GPM
H-14 HP-14 ARMSTRONG EHU-701 CM 14 2,900 15 79/22 79/50 16 26 D-2 24 2 208/60/3 14 1 (1) (2) (3)
NOTES:
(1) HUMIDISTAT DUCT-MOUNTED
(2) INSTALL PER MANUFACTURERS RECOMMENDATIONS
(3) HIGH LIMIT HUMIDISTAT
ELECTRICAL
(NOM AMP
RATING)
DUCT HUMIDIFIER (H) SCHEDULE
NOTESQTY.BASIS OF DESIGN MODEL FLOW RATE
(CFM) LBS/HR VAPOR TRAIL
(FT)
MANIFOLD
LENGTH (IN)
EAT (F)/RELATIVE
HUMIDITY
ELECTRICAL
(V/HZ/PH)MANIFOLD MODEL #PLAN
DESIGNATION SERVES BASIS OF DESIGN
MANUFACTURER
LAT (F)/RELATIVE
HUMIDITY DUCT HEIGHT DUCT WIDTH
FAN (EF, RF, PRE) SCHEDULE
PLAN
DESIGNATION TYPE SERVICE BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL
FLOW
RATE
(CFM)
EXTERNAL
STATIC
PRESSURE (in.
w.g.)
RPM DRIVE
BRAKE
POWER
(hp)
MOTOR
POWER
(hp)
ELECTRICAL
(V/Hz/PHASE) QTY. ACCESSORIES Disconnect by
MC or EC
Starter by MC or
EC
VFD or
ATL NOTES
EF-75 DOWNBLAST POWERED ROOF EXHASUT FAN ROOM 306/307 TWIN CITY FAN DCRD070BE 230 0.25 1,500 DIRECT 0.02 0.25 120/60/1 1 A,B,C,D,E EC EC ATL (1) EF-80 DOWNBLAST POWERED ROOF EXHASUT FAN ROOM 16/17 TWIN CITY FAN DCRD085BE 420 0.25 1,350 DIRECT 0.06 0.25 120/60/1 1 A,B,C,D,E EC EC ATL (1)
ACCESSORIES:
A PROVIDE UNIT MOUNTED DISCONNECT SWITCH
B PROVIDE GRAVITY BACK DRAFT DAMPER
C PROVIDE ROOF CURB WITH FLASHING SUITABLE FOR ROOF CONSTRUCTION SHOWN ON DRAWINGS
D PROVIDE BIRD SCREEN
E PROVIDE HINGED BASE
NOTES:
(1) DIRECT DRIVE
REHEAT COIL
HEATING
FLOW
RATE (CFM)
COIL AREA
(ft2)
FACE VELOCITY
(FPM)
MINIMUM
ROWS
EAT
(°F)
LAT (°F)
FLOW
RATE
(GPM)
EWT
(°F)
LWT
(°F)
MBH COIL ACV TOTAL
VAV-6 18 102 HP-14 130 80 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3,5 VAV-9 100 CORRIDOR HP-14 465 285 150 8 0.5 150 0.4 375 1 60.0 115 0.9 180 160 9.0 5.0 5.0 10.0 1,2,4,5 VAV-10 14 107 HP-14 100 80 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3,5 VAV-11 105 105 HP-14 250 155 80 6 0.5 80 0.2 400 1 60.0 100 0.5 180 160 3.5 5.0 5.0 10.0 1,2,3,5 VAV-12 104 103/104 HP-14 375 230 115 6 0.5 115 0.2 575 1 60.0 105 0.6 180 160 5.6 5.0 5.0 10.0 1,2,3,5 VAV-13 100 100 HP-14 305 190 110 6 0.5 110 0.2 550 1 60.0 105 0.5 180 160 5.4 5.0 5.0 10.0 1,2,3,5 VAV-14 14 106/12 HP-14 340 210 115 6 0.5 115 0.4 288 1 60.0 100 0.5 180 160 5.0 5.0 5.0 10.0 1,2,3,5 VAV-32 101 101 HP-14 720 445 220 8 0.5 220 0.4 550 1 60.0 100 1.0 180 160 9.5 5.0 5.0 10.0 1,2,4,5
VAV-17A 321 321/322 HP-2 810 525 250 8 0.5 250 0.4 625 1 60.0 115 1.5 180 160 14.9 5.0 5.0 10.0 1,2,4,5 VAV-19 307 304 HP-2 220 145 90 8 0.5 90 0.4 225 1 60.0 90 0.5 180 160 2.9 5.0 5.0 10.0 1,2,4,5 VAV-20 307 305/306 HP-2 220 145 90 6 0.5 90 0.2 450 1 60.0 90 0.5 180 160 2.9 5.0 5.0 10.0 1,2,3,5 VAV-21 11 307 HP-2 780 505 235 8 0.5 235 0.3 783 1 60.0 115 1.4 180 160 14.0 5.0 5.0 10.0 1,2,4,5 VAV-22 2 11 HP-2 1290 835 290 10 0.5 290 0.4 725 1 60.0 95 1.1 180 160 11.0 5.0 5.0 10.0 1,2,4,5 VAV-23 303 303 HP-2 675 435 205 8 0.5 205 0.3 683 1 60.0 90 0.7 180 160 6.7 5.0 5.0 10.0 1,2,3,5 VAV-25 CORR 06 209/504 HP-2 205 135 80 6 0.5 80 0.2 400 1 60.0 100 0.5 180 160 3.5 5.0 5.0 10.0 1,2,3,5 VAV-27 CORR 06 308/309 HP-2 200 130 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3,5 VAV-28 CORR 06 20 HP-2 1100 710 330 8 0.5 330 0.4 825 1 60.0 90 1.1 180 160 10.7 5.0 5.0 10.0 1,2,4,5 VAV-29 CORR 06 310/311/312 HP-2 320 205 100 6 0.5 100 0.2 500 1 60.0 105 0.5 180 160 4.9 5.0 5.0 10.0 1,2,3 VAV-31 CORR 06 CORRIDOR HP-2 345 225 145 8 0.5 145 0.3 483 1 60.0 100 0.6 180 160 6.3 5.0 5.0 10.0 1,2,3 VAV-33 CORR 06 40 HP-2 100 80 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3
VAV-34 CORR 06 500 HP-3 1405 820 425 12 0.5 425 0.8 531 1 60.0 105 2.1 180 160 20.8 5.0 5.0 10.0 1,2,4 VAV-35 50 51 HP-3 570 330 175 8 0.5 175 0.2 875 1 60.0 110 0.9 180 160 9.5 5.0 5.0 10.0 1,2,3 VAV-36 CORR 06 502 HP-3 100 80 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3 VAV-37 CORR 06 8 HP-3 795 465 240 8 0.5 240 0.8 300 3 60.0 110 1.3 180 160 13.0 5.0 5.0 10.0 1,2,3 VAV-38 CORR 06 129 HP-3 210 245 80 6 0.5 80 0.2 400 1 60.0 105 0.5 180 160 3.9 5.0 5.0 10.0 1,2,3 VAV-39 CORR 06 122 HP-3 635 370 190 8 0.5 190 0.4 475 1 60.0 115 1.1 180 160 11.3 5.0 5.0 10.0 1,2,4 VAV-41 CORR 120 503/125 HP-3 325 190 100 8 0.5 100 0.3 333 1 60.0 110 0.5 180 160 5.4 5.0 5.0 10.0 1,2,3 VAV-42 51 400 HP-3 700 405 200 8 0.5 200 0.3 667 1 60.0 110 1.1 180 160 10.9 5.0 5.0 10.0 1,2,3 VAV-43 25 25/26 HP-3 495 290 149 6 0.5 149 0.3 495 1 60.0 100 0.6 180 160 6.4 5.0 5.0 10.0 1,2,3 VAV-46 50 401,402,403,COORD HP-3 995 580 300 10 0.5 300 0.6 500 1 60.0 105 1.5 180 160 14.6 5.0 5.0 10.0 1,2,4 VAV-47 CORR 06 501 HP-3 100 80 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3 VAV-51 CORR 08 24 HP-3 425 245 130 6 0.5 130 0.2 650 1 60.0 90 0.5 180 160 4.2 5.0 5.0 10.0 1,2,3
VAV-48 700 700 HP-4 380 280 115 6 0.5 115 0.2 575 1 60.0 105 0.6 180 160 5.6 5.0 5.0 10.0 1,2,3 VAV-49 700 700 HP-4 380 280 115 6 0.5 115 0.2 575 1 60.0 105 0.6 180 160 5.6 5.0 5.0 10.0 1,2,3 VAV-50 700 701 HP-4 210 155 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3 VAV-16 800 35 HP-4 110 80 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3 VAV-53 800 33/34 HP-4 300 225 90 6 0.5 90 0.2 450 1 60.0 90 0.5 180 160 2.9 5.0 5.0 10.0 1,2,3 VAV-26 801 802 HP-4 210 155 80 8 0.5 80 0.3 267 1 60.0 105 0.5 180 160 3.9 5.0 5.0 10.0 1,2,4 VAV-55 801 801 HP-4 100 80 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3 VAV-56 800 800 HP-4 900 670 350 10 0.5 350 0.9 389 2 60.0 100 1.5 180 160 15.2 5.0 5.0 10.0 1,2,3 VAV-57 800 803 HP-4 360 265 120 10 0.5 120 0.4 300 1 60.0 110 0.7 180 160 6.5 5.0 5.0 10.0 1,2,3 VAV-58 SCOT SCOT OFFICE HP-4 555 410 170 8 0.5 170 0.3 567 1 60.0 95 0.6 180 160 6.5 5.0 5.0 10.0 1,2,3 VAV-59 SCOT SCOT HP-4 555 410 170 8 0.5 170 0.3 567 1 60.0 105 0.8 180 160 8.3 5.0 5.0 10.0 1,2,3 VAV-60 WEST MECH 38 HP-4 760 1040 220 16 0.5 220 1.5 147 1 60.0 110 1.2 180 160 11.9 5.0 5.0 10.0 1,2,4
VAV-1 208 208 HP-1 185 150 80 6 0.5 80 0.3 267 1 60.0 110 0.5 180 160 4.3 5.0 5.0 10.0 1,2,3 VAV-2 202 202/203 HP-1 200 165 90 6 0.5 90 0.2 450 1 60.0 90 0.5 180 160 2.9 5.0 5.0 10.0 1,2,3 VAV-3 201 201 HP-1 140 115 80 6 0.5 80 0.2 400 1 60.0 90 0.5 180 160 2.6 5.0 5.0 10.0 1,2,3 VAV-4 200 205/206 HP-1 230 190 90 6 0.5 90 0.2 450 1 60.0 115 0.5 180 160 5.4 5.0 5.0 10.0 1,2,3 VAV-5 205 204/207 HP-1 260 215 80 6 0.5 80 0.2 400 1 60.0 100 0.5 180 160 3.5 5.0 5.0 10.0 1,2,3 VAV-15 15 16/17 HP-1 380 310 115 6 0.5 115 0.2 575 1 60.0 90 0.5 180 160 3.7 5.0 5.0 10.0 1,2,3 VAV-44 200 200 HP-1 700 575 230 10 0.5 230 0.4 575 1 60.0 110 1.2 180 160 12.5 5.0 5.0 10.0 1,2,3 VAV-52 210 210 HP-1 840 690 300 10 0.5 300 0.4 750 1 60.0 100 1.3 180 160 13.0 5.0 5.0 10.0 1,2,3 VAV-40 210 600 HP-1 1350 1110 555 12 0.5 555 0.7 793 1 60.0 100 2.4 180 160 24.1 5.0 5.0 10.0 1,2,3
NOTES:
(1) SALAVAGED EXISTING UNIT. RELOCATE TO LOCATION LISTED AND SHOWN ON DRAWINGS. BALANCE UNIT TO FLOW RATES SHOWN.
(2) PRESSURE INDEPENDENT VOLUME CONTROL UNIT
(3) 2-WAY VALVE
(4) 3-WAY VALVE
MAXIMUM
FLOW RATE
(CFM)
MINIMUM
FLOW RATE
(CFM)
INLET
CONNECTION
DIAMETER (IN)
PLAN
DESIGNATION
HP-CLG
MINIMUM
FLOW RATE
(CFM)
LOCATION SERVICE SERVED FROM
VARIABLE AIR VOLUME BOX (VAV) WITH WATER REHEAT SCHEDULE
MAXIMUM AIR
PRESSURE DROP
(in. w.g.)
MAXIMUM PRESSURE DROP (ft)
NOTES
WATER SOURCE HEAT PUMP (HP) SCHEDULE
COMPRESSOR
AIRFLOW
(CFM)
MIN. O. A.
(CFM)
E.S.P.
(IN. WG) QUANTITY
MOTOR
POWER
EACH
(HP)
EAT DB
(° F)
EAT WB
(° F)
LAT DB
(° F)
LAT WB
(° F)
EWT
(° F)
MIN. EER @
ACTUAL
CONDITIONS
EAT DB
(° F)
LAT DB
(° F)
EWT
(° F)
MIN. COP @
ACTUAL
CONDITIONS
KW
HP-1 NORTH MECH RM NORTH PERIMETER VERTICAL TRANE AXIOM GEVE15031 4300 900 1.25 1.00 3 80.2 65.0 56.6 54.0 90 11.33 49.0 78.6 30 3.41 9.96 37.5 14.88 EC EC VFD 208/60/3 54.2 (1) (2) (3) (4) (6) HP-2 MECH RM 323 EAST ZONE VERTICAL TRANE AXIOM GEVE18041 6300 800 1.25 1.00 5 79.0 65.1 59.2 56.7 90 10.14 56.0 77.0 30 3.46 12.81 45.0 20.29 EC EC VFD 460/60/3 31.4 (1) (2) (3) (4) (6) HP-3 MECH RM 28 SOUTH ZONE VERTICAL TRANE AXIOM GEVE18041 7000 1800 1.25 1.00 5 80.1 65.7 59.8 57.2 90 10.34 48.2 78.8 30 3.55 12.85 45.0 20.29 EC EC VFD 460/60/3 31.4 (1) (2) (3) (4) (6) HP-4 MECH RM 37 WEST ZONE VERTICAL TRANE AXIOM GEVE18041 5600 880 1.25 1.00 5 79.3 64.7 59.1 56.3 90 9.93 53.2 78.7 30 3.40 12.76 45.0 20.29 EC EC VFD 460/60/3 31.4 (1) (2) (3) (4) (6) HP-5 RM 323 RM 323 HORIZONTAL FHP EC072-4VTC-FBT 2000 0 0.50 1.00 1 80.0 60.0 55.0 54.0 90 10.80 80.0 70.0 30 3.1 17.0 23.30 EC EC VFD 460/60/3 (1) (2) (3) (4) (5) HP-6 RM 302 HFGCS EQUIP HORIZONTAL FHP EC072-4HZC-FBT 2000 0 0.50 1.00 1 80.0 60.0 55.0 54.0 90 10.80 80.0 70.0 30 3.1 17.0 23.30 EC EC VFD 460/60/3 (1) (2) (3) (4) (5)
HP-8 COORD. 05 RM 13 HORIZONTAL TRANE AXIOM GEHE02441 850 0 0.30 1.00 1/3 76.1 60.3 56.0 52.2 90 11.07 67.6 78.0 30 3.22 1.6 5.6 11.65 EC EC VFD 208/60/3 9.2 (1) (2) (3) (4) (7) HP-9 COORD. 03 RM 15 HORIZONTAL TRANE AXIOM GEHE02441 750 175 0.50 1.00 1/3 79.0 65.4 57.8 55.5 90 11.58 54.8 80.0 30 3.55 1.59 5.6 11.65 EC EC VFD 460/60/3 4.6 (1) (2) (3) (4) (7) HP-10 RM 14 RM 14 HORIZONTAL TRANE AXIOM GEHE02441 760 210 0.50 1.00 1/3 78.7 65.6 59.2 56.8 90 11.63 55.3 80.0 30 3.57 1.59 5.6 11.65 EC EC VFD 460/60/3 4.6 (1) (2) (3) (4) (7) HP-11 RM 22 RM 22 HORIZONTAL TRANE AXIOM GEHE02441 760 200 0.50 1.00 1/3 79.1 65.1 56.1 53.9 90 11.56 53.5 80.0 30 3.58 1.59 5.6 11.65 EC EC VFD 460/60/3 4.6 (1) (2) (3) (4) (7) HP-12 RM 23 RM 23 HORIZONTAL TRANE AXIOM GEHE03641 1300 200 0.60 1.00 1/2 77.5 63.3 56.0 53.4 90 14.30 60.2 78.0 30 4.55 1.72 8.4 13.43 EC EC VFD 460/60/3 7.5 (1) (2) (3) (4) (7) HP-13 RM 300 RM 300 HORIZONTAL TRANE AXIOM GEHE12041 3800 250 1.00 1.00 3 77.0 63.1 59.0 55.7 90 10.24 63.9 78.0 30 3.12 7.51 30.0 15.90 EC EC VFD 460/60/3 23.3 (1) (2) (3) (4) (7) HP-14 NORTH MECH RM NORTH PERIMETER VERTICAL TRANE AXIOM GEVE09031 2900 310 1.25 1.00 1 1/2 78.6 65.3 59.0 56.3 90 12.00 56.9 78.9 30 3.54 5.72 22.5 11.65 EC EC VFD 208/60/3 33.1 (1) (2) (3) (4) (6)
NOTES:
(1) EXTERNAL STATIC PRESSURE INCLUDES DUCTWORK, FILTERS, AND COILS NOT IN HP CASING.
(2) PROVIDE UNITS SUITABLE FOR EXTENDED TEMPERATURE USE WITH 20% PROPLEYENE GLYCOL SOLUTION.
(3) PROVIDE UNITS WITH HOSE KITS. HOSE KITS SHALL INCLUDE STAINLESS STEEL BRAID HOSES WITH SWIVEL CONNECTIONS, BALL VALVES, AUTOMATIC FLOW CONTROL VALVE, Y-STRAINER WITH PT TEST PORT, AND HONEYWELL 2 WAY 2 POSITION 24 VOLT VC SERIES CONTROL VALVE.
(4) PROVIDE SINGLE POINT ELECTRICAL CONNECTION TO UNIT.
(5) EXISTING UNIT. SHOWN FOR REFERENCE ONLY.
(6) PROVIDE UNITS WITH HOT GAS BYPASS, ENHANCED SOUND ATTENUATION AND ELECTRICALLY COMMUTATED MOTOR.
(7) PROVIDE UNITS WITH HOT GAS REHEAT, ENHANCED SOUND ATTENUATION AND ELECTRICALLY COMMUTATED MOTOR.
LOCATIONPLAN
DESIGNATION
BASIS OF DESIGN
MANUFACTURER MODEL
COIL
PRESSURE
DROP (FT W.G.)
VOLTS/HZ/P
HASE
Disconnect by MC or
EC
Starter by MC or EC
SERVICE ARRANGEMENT NOTES
HEATING PERFOMANCE
WATER
FLOW RATE
(GPM)
SUPPLY FAN COOLING PERFOMANCE
VFD or ATL TOTAL FLA
Building 314
(371 Steen Blvd)
Building 313
Building 314
(371 Steen Blvd)
Building 314
(371 Steen Blvd)
PANEL 'HE (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSEWESTINGHOUSE
400-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 75 KVA XFMR PANEL LE 150 3 0.0 30 3 HEAT PUMP HP-13 2
3 --- ** * 0.0 ** * --- 4
5 --- ** * 0.0 ** * --- 6
7 HEAT PUMP HP-2 40 3 0.0 20 3 HEAT PUMP HP-5 8
9 --- ** * 0.0 ** * --- 10
11 --- ** * 0.0 ** * --- 12
13 #2 MG SET DISCONNECTED OFF 30 3 0.0 20 1 LTG 141A, 141B 14
15 --- ** * 0.0 20 1 LTG 122 16
17 --- ** * 0.0 20 1 SPARE 18
19 LTG RM 141 20 1 0.0 15 3 OFF #1 MG SET DISCONNECTED 20
21 LTG RM 141 20 1 0.0 ** * --- 22
23 LTG 142, 142, 144 20 1 0.0 ** * --- 24
25 SPARE 100 3 0.0 100 3 RM 143 75KVA XFMR 26
27 --- ** * 0.0 ** * --- 28
29 --- ** * 0.0 ** * --- 30
31 HUMIDIFIER H-2 40 3 0.0 50 3 UNKNOWN 32
33 --- ** * 0.0 ** * --- 34
35 --- ** * 0.0 ** * --- 36
37 HEAT PUMP HP-6 20 3 0.0 20 3 HUMIDIFIER H-6 38
39 --- ** * 0.0 ** * --- 40
41 --- ** * 0.0 ** * --- 42
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LE (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
225-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 WEST POWER POLE 20 1 0.0 SPACE 2
3 WEST POWER POLE 20 1 0.0 SPACE 4
5 WEST POWER POLE 20 1 0.0 SPACE 6
7 GSM-235 OFF 20 3 0.0 30 3 GSM-235 8
9 --- ** * 0.0 ** * --- 10
11 --- ** * 0.0 ** * --- 12
13 GSM-234 OFF 20 3 0.0 20 1 COND PUMP OUTLET 14
15 --- ** * 0.0 20 1 GEN CONTROL PANEL 16
17 --- ** * 0.0 SPACE 18
19 SPACE 0.0 SPACE 20
21 SPACE 0.0 SPACE 22
23 SPACE 0.0 SPACE 24
25 SPACE 0.0 SPACE 26
27 SPACE 0.0 SPACE 28
29 SPACE 0.0 SPACE 30
31 SPACE 0.0 SPACE 32
33 SPACE 0.0 SPACE 34
35 SPACE 0.0 SPACE 36
37 SPACE 0.0 SPACE 38
39 SPACE 0.0 SPACE 40
41 SPACE 0.0 SPACE 42
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN4 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
225-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 REC 20 1 0.0 20 1 REC 2
3 REC 20 1 0.0 20 1 REC 4
5 REC 20 1 0.0 20 1 REC 6
7 REC 20 1 0.0 20 1 REC 8
9 REC 20 1 0.0 20 1 REC 10
11 REC 20 1 0.0 20 1 REC 12
13 REC 20 1 0.0 20 1 REC 14
15 REC 20 1 0.0 100 3 GEN BUILDING 16
17 REC 20 1 0.0 ** * --- 18
19 REC 20 1 0.0 ** * --- 20
21 BLOWER FOR DISINTIGRATOR 20 1 0.0 20 1 RM 303 PROJECTOR 22
23 RECEPTS - RM 321, 322 20 1 0.0 20 1 ENTRY DOOR OPERATOR 24
25 RECEPTS - RM 321, 322 20 1 0.0 20 1 RECEPT - RM 304 26
27 RECEPTS - RM 303, 304 20 1 0.0 20 1 RECEPT - RM 304 28
29 RECEPTS - RM 303, 304 20 1 0.0 SPACE 30
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN7 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD RENAMED FROM "OFFICE PANEL"
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: SIEMENS
200-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 UNKNOWN 20 1 0.0 20 1 UNKNOWN 2
3 UNKNOWN 20 1 0.0 20 1 UNKNOWN 4
5 UNKNOWN 20 1 0.0 20 1 UNKNOWN 6
7 UNKNOWN 20 1 0.0 20 1 UNKNOWN 8
9 UNKNOWN 20 1 0.0 20 1 UNKNOWN 10
11 REC - RM 143 20 1 0.0 20 1 UNKNOWN 12
13 REC - RM 133 20 1 0.0 20 1 UNKNOWN 14
15 UNKNOWN 20 1 0.0 30 1 UNKNOWN 16
17 REC - RM 143 20 1 0.0 30 1 UNKNOWN 18
19 REC - RM 146 20 1 0.0 20 2 UNKNOWN 20
21 REC - RM 144 20 1 0.0 ** * --- 22
23 UNKNOWN 30 1 0.0 20 1 RM 132 LIGHTS 24
25 --- ** * 0.0 SPACE 26
27 UNKNOWN 30 1 0.0 30 2 UNKNOWN 28
29 SPACE 0.0 ** * --- 30
31 UNKNOWN 30 1 0.0 SPACE 32
33 --- ** * 0.0 SPACE 34
35 UNKNOWN 20 2 0.0 SPACE 36
37 --- ** * 0.0 SPACE 38
39 SPACE 0.0 SPACE 40
41 SAPCE 0.0 SPACE 42
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN9 SECT1 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD RENAMED FROM PANEL "B" AREA A
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: SHALLBETTER INDUSTRIES
225-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 EF - M&R 30 3 0.0 20 1 POWER OUTLET 2
3 --- ** * 0.0 20 2 ICE MACHINE 4
5 --- ** * 0.0 ** * --- 6
7 M&R AREA - CENTER 20 3 0.0 20 1 DOOR OPERATORS 8
9 --- ** * 0.0 20 1 DOOR OPERATORS 10
11 --- ** * 0.0 20 1 DOOR OPERATORS 12
13 UH-12, 14 20 1 0.0 20 1 SPARE 14
15 UH-7 20 1 0.0 20 1 SPARE 16
17 UH-8, 9, 10 20 1 0.0 20 1 EF - AGE STORE 18
19 SPARE 20 1 0.0 20 1 DOOR OPERATORS 20
21 SPARE 20 1 0.0 20 1 DOOR OPERATORS 22
23 SPARE 20 1 0.0 20 1 DOOR OPERATORS 24
25 SPARE 20 1 0.0 20 1 DOOR OPERATORS 26
27 WATER COOLER 20 1 0.0 20 1 LIGHTING BAY 28
29 TEMP CONTROL PANEL 20 1 0.0 20 1 SPARE 30
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN9 SECT2 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD RENAMED FROM PANEL "A" AREA A
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: SHALLBETTER INDUSTRIES
225-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 M&R AREA - CENTER 20 1 0.0 20 1 M&R AREA - ENDS 2
3 M&R AREA - CENTER 20 1 0.0 20 1 M&R AREA - ENDS 4
5 M&R AREA - CENTER 20 1 0.0 20 1 M&R AREA - ENDS 6
7 M&R AREA - CENTER 20 1 0.0 20 1 BENCHES - EAST WALL 8
9 M&R AREA - CENTER 20 1 0.0 20 1 BENCHES - EAST WALL 10
11 M&R AREA - CENTER 20 1 0.0 20 1 SMOKE DAMPERS 12
13 SPARE 20 1 0.0 20 1 AGE STORAGE 14
15 SPARE 20 1 0.0 20 1 AGE STORAGE 16
17 UNIT HEATERS 11, 13 20 1 0.0 20 1 OUTSIDE 18
19 AGE STORAGE M&R 20 1 0.0 20 1 OUTSIDE 20
21 BOILER 20 1 0.0 20 1 MECH ROOM 22
23 AGE STORAGE M&R 20 1 0.0 20 1 UNIT HEATERS 1, 2 24
25 AGE STORAGE M&R 20 1 0.0 20 1 M&R 26
27 OUTLETS EMT SUPPLY 20 1 0.0 20 1 M&R 28
29 SPACE 0.0 20 1 M&R MECH ROOM 30
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'C (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: GE
225-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 LIGHTING 20 1 0.0 20 1 LIGHTING 2
3 LIGHTING 20 1 0.0 20 1 LIGHTING 4
5 LIGHTING 20 1 0.0 20 1 LIGHTING 6
7 REC 20 1 0.0 20 1 REC 8
9 REC 20 1 0.0 20 1 REC 10
11 REC 20 1 0.0 20 1 REC 12
13 PUMP P-1 1/3HP 15 1 0.0 30 3 WATER HEATER 14
15 PUMP P-2 1/3HP 15 1 0.0 ** * --- 16
17 SOUTH POLE LIGHTS 20 1 0.0 ** * --- 18
19 UECB AIR CONDITIONER 20 2 0.0 50 3 OFF HV-1 20
21 --- ** * 0.0 ** * --- 22
23 SPACE 0.0 ** * --- 24
25 UNKNOWN 90 3 0.0 90 3 UNKNOWN 26
27 --- ** * 0.0 ** * --- 28
29 --- ** * 0.0 ** * --- 30
31 SPECIAL OUTLET OFF 60 3 0.0 20 1 MICROWAVE 32
33 --- ** * 0.0 20 1 SNACK BAR 34
35 --- ** * 0.0 20 1 LIGHTS 36
37 LIGHTING 20 1 0.0 20 1 LIGHTING 38
39 LIGHTING 20 1 0.0 20 1 LIGHTING 40
41 LIGHTING 20 1 0.0 20 1 LIGHTING 42
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN10 ' NOTES: NEW COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER:
225-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 LIGHTING 20 1 0.0 20 1 LIGHTING 2
3 LIGHTING 20 1 0.0 20 1 LIGHTING 4
5 LIGHTING 20 1 0.0 20 1 LIGHTING 6
7 REC 20 1 0.0 20 1 REC 8
9 REC 20 1 0.0 20 1 REC 10
11 REC 20 1 0.0 20 1 REC 12
13 PUMP P-1 1/3HP 15 1 0.0 30 3 WATER HEATER 14
15 PUMP P-2 1/3HP 15 1 0.0 ** * --- 16
17 SOUTH POLE LIGHTS 20 1 0.0 ** * --- 18
19 UECB AIR CONDITIONER 20 2 0.0 50 3 OFF HV-1 20
21 --- ** * 0.0 ** * --- 22
23 SPACE 0.0 ** * --- 24
25 UNKNOWN 90 3 0.0 90 3 UNKNOWN 26
27 --- ** * 0.0 ** * --- 28
29 --- ** * 0.0 ** * --- 30
31 SPECIAL OUTLET OFF 60 3 0.0 20 1 MICROWAVE 32
33 --- ** * 0.0 20 1 SNACK BAR 34
35 --- ** * 0.0 20 1 LIGHTS 36
37 LIGHTING 20 1 0.0 20 1 LIGHTING 38
39 LIGHTING 20 1 0.0 20 1 LIGHTING 40
41 LIGHTING 20 1 0.0 20 1 LIGHTING 42
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'ELN1 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD RENAMED FROM "UPSTAIRS PANEL"
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: SQUARE D
600-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 UPS C - RM 150A 125 2 0.0 125 2 UPS A - RM 150A 2
3 --- ** * 0.0 --- 4
5 UPS B - RM 150A 125 2 0.0 40 3 CRAC UNIT - RM 150A 6
7 --- ** * 0.0 ** * --- 8
9 PANEL ELN3 100 3 0.0 ** * --- 10
11 --- ** * 0.0 20 1 COMSEC CONDENSING UNIT 12
13 --- ** * 0.0 20 3 HEAT PUMP - 150A 14
15 UPS - RM 150A 125 2 0.0 ** * --- 16
17 --- ** * 0.0 ** * --- 18
19 OUTSIDE CONDENSER 40 3 0.0 60 3 TVSS 20
21 --- ** * 0.0 ** * --- 22
23 --- ** * 0.0 ** * --- 24
25 HUMIDIFIER 30 3 0.0 100 3 CIRCUIT BKR PNL - NODE RM 26
27 --- ** * 0.0 ** * --- 28
29 --- ** * 0.0 ** * --- 30
31 0.0 32
33 0.0 34
35 0.0 36
37 UPS RM 150 GEN PANEL 225 3 0.0 38
39 --- ** * 0.0 40
41 --- ** * 0.0 42
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'ELN2 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD RENAMED FROM PANEL "UPS"
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
225-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 RACK OUTLETS 20 1 0.0 20 3 LIGHTS & EM LIGHTS RM 150A 2
3 RACK OUTLETS 20 1 0.0 ** * --- 4
5 RACK OUTLETS 20 1 0.0 ** * --- 6
7 RACK OUTLETS 20 1 0.0 20 1 SEC PANEL POWER 8
9 IT NODE RM 165 30 2 0.0 30 2 IT NODE RM 10
11 --- ** * 0.0 ** * --- 12
13 IT NODE RM 165 20 1 0.0 40 3 OUTSIDE COND UNIT 14
15 IT NODE RM 165 30 1 0.0 ** * --- 16
17 SPACE 0.0 ** * --- 18
19 SPACE 0.0 SPACE 20
21 SPACE 0.0 SPACE 22
23 SPACE 0.0 SPACE 24
25 SPACE 0.0 SPACE 26
27 SPACE 0.0 SPACE 28
29 SPACE 0.0 SPACE 30
31 SPACE 0.0 SPACE 32
33 SPACE 0.0 SPACE 34
35 SPACE 0.0 SPACE 36
37 SPACE 0.0 SPACE 38
39 SPACE 0.0 SPACE 40
41 SPACE 0.0 SPACE 42
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'ELN3' NOTES: NEW COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER:
225-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 RECEPTS. COMM CLOSET 13 20 1 0.0 20 1 RECEPT. SIPR 12 2
3 RECEPTS. COMM CLOSET 13 20 1 0.0 20 1 RECEPT. SIPR 12 4
5 RECEPTS. COMM CLOSET 13 20 1 0.0 20 1 RECEPT. SIPR 12 6
7 RECEPTS. COMM CLOSET 13 20 1 0.0 20 1 RECEPT. SIPR 12 8
9 SPARE 20 1 0.0 20 1 COMMUNICATIONS RACK 10
11 SPARE 20 1 0.0 20 1 COMMUNICATIONS RACK 12
13 SPARE 20 1 0.0 20 1 COMMUNICATIONS RACK 14
15 SPARE 20 1 0.0 20 1 COMMUNICATIONS RACK 16
17 SPARE 20 1 0.0 20 1 COMMUNICATIONS RACK 18
19 SPARE 20 1 0.0 20 1 COMMUNICATIONS RACK 20
21 COMMUNICATIONS RACK 20 1 0.0 20 1 COMMUNICATIONS RACK 22
23 COMMUNICATIONS RACK 20 1 0.0 20 1 COMMUNICATIONS RACK 24
25 COMMUNICATIONS RACK 20 1 0.0 20 1 SPARE 26
27 COMMUNICATIONS RACK 20 1 0.0 20 1 COMMUNICATIONS RACK 28
29 COMMUNICATIONS RACK 20 1 0.0 20 1 COMMUNICATIONS RACK 30
31 COMMUNICATIONS RACK 20 1 0.0 20 1 COMMUNICATIONS RACK 32
33 COMMUNICATIONS RACK 20 1 0.0 20 1 COMMUNICATIONS RACK 34
35 COMMUNICATIONS RACK 20 1 0.0 20 1 COMMUNICATIONS RACK 36
37 HEAT PUMP HP-8 20 3 0.0 20 1 COMMUNICATIONS RACK 38
39 --- ** * 0.0 20 1 COMMUNICATIONS RACK 40
41 --- ** * 0.0 20 1 COMMUNICATIONS RACK 42
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN6 SECT 1' NOTES: NEW COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER:
400-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 RECEPTS - 18, 101, 102 20 1 0.0 20 1 RECEPTS - 100, 101, 102 2
3 RECEPTS.- 100, 103, 104, 105 20 1 0.0 20 1 RECEPTS.- 103, 104, 105, 108 4
5 RECEPTS. - 200, 201, 202,203, 20 1 0.0 20 1 RECEPTS. - 200, 201, 202,203, 6
7 RECEPTS. - 02, 107, 108 20 1 0.0 20 1 RECEPTS. - 106, 108 8
9 RECEPTS. - 200, 204, BRK RM 20 1 0.0 20 1 RECEPTS. - 200,204,205,206, BRK 10
11 RECEPT. BRK RM 20 1 0.0 20 1 RECEPTS. - 204, 206, 209 12
13 RECEPT. BRK RM 20 1 0.0 20 1 RECEPTS. - 208, 211, 504 14
15 RECEPTS. - 206, 208, 209 20 1 0.0 20 1 RECEPTS. - 20, 40 16
17 RECEPTS. - REST RM 16, 17 20 1 0.0 20 1 RECEPTS. - 308, 309, 310, 312 18
19 RECEPTS. - 20, 40, 504 20 1 0.0 20 1 RECEPTS. - 305, 307 20
21 RECEPTS. - 308, 309, 310, 312 20 1 0.0 20 1 RECEPTS. - 306, 307 22
23 BUILDING DIRECTORY 20 1 0.0 20 1 LOBBY 02 WATER COOLER 24
25 SPARE 20 1 0.0 20 1 RM 108 PROJECTOR 26
27 SPARE 20 1 0.0 20 1 RM 209 PROJECTOR 28
29 SPARE 20 1 0.0 20 1 RM 20 PROJECTOR 30
31 HEAT PUMP H-14 20 3 0.0 20 1 HFGCS 307 WATER COOLER 32
33 --- ** * 0.0 20 1 SPARE 34
35 --- ** * 0.0 20 1 SPARE 36
37 HUMIDIFIER HP-1 70 3 0.0 50 3 HEAT PUMP HP-14 38
39 --- ** * 0.0 ** * --- 40
41 --- ** * 0.0 ** * --- 42
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN6 SECT 2' NOTES: NEW COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER:
400-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
43 RM 100 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 LOBBY TRACK LTG 44
45 RM 100 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 LOBBY TRACK LTG 46
47 RM 200 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 SKYLIGHT LTG 48
49 RM 200 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 SKYLIGHT LTG 50
51 RM 307 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 EXTERIOR LIGHTING CONTACTOR 52
53 RM 307 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 EXHAUST FAN EF-75 54
55 SPARE 20 1 0.0 20 1 EXHAUST FAN EF-80 56
57 SPARE 20 1 0.0 20 1 SPARE 58
59 SPARE 20 1 0.0 20 1 SPARE 60
61 SPARE 20 1 0.0 20 1 SPARE 62
63 SPARE 20 1 0.0 20 1 SPARE 64
65 SPARE 20 1 0.0 20 1 SPARE 66
67 SPARE 20 1 0.0 20 1 SPARE 68
69 SPARE 20 1 0.0 20 1 SPARE 70
71 SPARE 20 1 0.0 20 1 SPARE 72
73 SPARE 20 1 0.0 20 1 SPARE 74
75 SPARE 20 1 0.0 20 1 SPARE 76
77 SPARE 20 1 0.0 20 1 SPARE 78
79 SPARE 20 1 0.0 20 1 SPARE 80
81 SPARE 20 1 0.0 20 1 SPARE 82
83 SPARE 20 1 0.0 20 1 SPARE 84
PANEL 'HN1 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
200-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 LN1 (VIA T1) 50 3 0.0 20 1 LTG. 147,149,151 2
3 --- ** * 0.0 20 1 LTG. 135,138,145,179 4
5 --- ** * 0.0 20 1 LTG. 102,133,134,139 6
7 EGRESS LTG. 20 1 0.0 15 3 EF 11 (RM 131) 8
9 SPACE 0.0 ** * --- 10
11 SPACE 0.0 ** * --- 12
13 WATER HEATER WH-1 20 3 0.0 15 3 HEAT PUMP HP-11 14
15 --- ** * 0.0 ** * --- 16
17 --- ** * 0.0 ** * --- 18
19 WATER HEATER WH-2 20 3 0.0 15 3 HEAT PUMP HP-9 20
21 --- ** * 0.0 ** * --- 22
23 --- ** * 0.0 ** * --- 24
25 HEAT PUMP HP-10 15 3 0.0 SPACE 26
27 --- ** * 0.0 SPACE 28
29 --- ** * 0.0 SPACE 30
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'HN2 SECT1 (EXST) ' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
600-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 EXTERIOR SITE BOLLARD LTG. 20 1 0.0 20 1 PARKING LOT LIGHTING 2
3 RM 126 TEST BENCH 60 3 0.0 20 1 PARKING LOT/ROADWAY LTG 4
5 --- ** * 0.0 15 3 HEAT PUMP HP-12 6
7 --- ** * 0.0 ** * --- 8
9 E.F. 8,9 15 3 0.0 ** * --- 10
11 --- ** * 0.0 15 3 AHU-2 12
13 --- ** * 0.0 ** * --- 14
15 LTG. 124, 164 20 1 0.0 ** * --- 16
17 LTG. 126, 165, 166 20 1 0.0 60 3 PUMP 6 18
19 PUMP 5 60 3 0.0 ** * --- 20
21 --- ** * 0.0 ** * --- 22
23 --- ** * 0.0 20 1 EGRESS LTG 24
25 HEAT PUMP HP-3 40 3 0.0 50 3 WH-2 26
27 --- ** * 0.0 ** * --- 28
29 --- ** * 0.0 ** * --- 30
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'HN2 SECT2 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
100-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 SPACE 0.0 SPACE 2
3 SPACE 0.0 SPACE 4
5 AC-1 15 3 0.0 60 3 PUMP 7 6
7 --- ** * 0.0 ** * --- 8
9 --- ** * 0.0 ** * --- 10
11 AC-2 15 3 0.0 40 3 HUMIDIFIER H-3 12
13 --- ** * 0.0 ** * --- 14
15 --- ** * 0.0 ** * --- 16
17 LTG 116, 118, 126, 160, 162 20 1 0.0 20 1 LTG 106, 109, 112, 130 18
19 LTG 119, 120, 122, 123 20 1 0.0 20 1 LTG 103, 105, 108, 113, 115 20
21 LTG 127, 129 20 1 0.0 20 1 LTG 131, 132, 150, 152 22
23 CHILLER TEST BENCH 80 3 0.0 50 3 D-1,2,3,4 24
25 --- ** * 0.0 ** * --- 26
27 --- ** * 0.0 ** * --- 28
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN1 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
100-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 REC 131, 151 20 1 0.0 20 1 REC 148, 149 2
3 REC 149, 151 20 1 0.0 20 1 REC 148, 149 4
5 REC 148, 149 20 1 0.0 20 1 REC 149 6
7 REC 136, 147 20 1 0.0 20 1 REC 134, 139 8
9 REC 137, 138, 145 20 1 0.0 20 1 REC 135 10
11 REC 179 20 1 0.0 20 1 REC 136, 139, 140 12
13 REC 101, 102, 133 20 1 0.0 20 1 QUAD REC 133 14
15 QUAD REC 133 20 1 0.0 20 1 QUAD REC 133 16
17 QUAD REC 133 20 1 0.0 20 1 QUAD REC 133 18
19 QUAD REC 133 20 1 0.0 20 1 QUAD REC FLOOR 133 20
21 HONEYWELL EF 11 20 1 0.0 20 1 QUAD REC FLOOR 133 22
23 HVAC CONTROL PANEL 147 20 1 0.0 20 1 EF-12, UH-25 24
25 OUTLET STRIP 20 1 0.0 20 1 OUTLET STRIP 26
27 REC 147 20 1 0.0 20 1 REC 147 28
29 OUTLETS 20 1 0.0 20 1 OUTLETS 30
31 OUTLETS 20 1 0.0 20 1 OUTLETS 32
33 OUTLETS 20 1 0.0 20 1 OUTLETS 34
35 OUTLETS 20 1 0.0 20 1 30A TWIST LOCK 36
PROJECT #JFSD200113E-Panel Schedules 1 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSE
800-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 #1 ENGINE HEATER RESETS 50 3 0.0 50 3 AIR COMP OUTLET 2
3 #7 ENGINE HEATER RESETS 60 3 0.0 60 3 #20 ENGINE HEATER 4
5 SPARE 70 3 0.0 60 3 #26 ENGINE HEATER 6
7 SPARE 60 3 0.0 70 3 SPARE 8
9 #31 ENGINE HEATER RESETS 70 3 0.0 70 3 #14 ENGINE HEATER 10
11 #25 ENGINE HEATER RESETS 60 3 0.0 100 3 SPARE 12
13 SPARE 150 3 0.0 100 3 SPARE 14
PROJECT #JFSD200113E-Panel Schedules PANEL TOTALS: 0 0 0 0% DIFFERENCE 05/15/13
PANEL 'LN5 ' NOTES: NEW COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
208Y/120-VOLT, 3-PHASE, 4-WIRE MANUFACTURER:
400-AMP, MAIN CIRCUIT BREAKER MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 RECEPTS. - 501, 502 20 1 0.0 50 3 AIR COMP OUTLET 2
3 RECEPTS. - 501, 502 20 1 0.0 ** * --- 4
5 RECEPTS. - 22, 400 20 1 0.0 ** * --- 6
7 RECEPTS. - 400, 401 20 1 0.0 20 1 RECEPTS. - 501, 502 8
9 RECEPTS. - 400, 402 20 1 0.0 20 1 RECEPTS. - 27, 50 10
11 RECEPTS. - 50, 51 20 1 0.0 20 1 RECEPTS. - 24, 25 12
13 RM 400 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 RM 22 PROJECTOR 14
15 RM 400 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 RM 23 PROJECTOR 16
17 RM 400 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 SKYLIGHT LTG 18
19 RM 400 SYSTEMS FURN RECEPTS. 20 1 0.0 20 1 SPARE 20
21 RECEPTS. - 22, 23 20 1 0.0 20 1 SPARE 22
23 SPARE 20 1 0.0 20 1 SPARE 24
25 SPARE 20 1 0.0 20 1 SPARE 26
27 SPARE 20 1 0.0 20 1 SPARE 28
29 SPACE 0.0 SPACE 30
31 SPACE 0.0 SPACE 32
33 SPACE 0.0 SPACE 34
35 SPACE 0.0 SPACE 36
37 SPACE 0.0 SPACE 38
39 SPACE 0.0 SPACE 40
41 SPACE 0.0 SPACE 42
PANEL 'HN3 (EXST)' NOTES: EXISTING COMMERCIAL BOLT-ON CIRCUIT BREAKER PANELBOARD.
480Y/277-VOLT, 3-PHASE, 4-WIRE MANUFACTURER: WESTINGHOUSEWESTINGHOUSE
400-AMP, MAIN LUGS ONLY MOUNTING: SURFACE
CKT LOAD REF BRKR LOAD BREAKER LOAD PHASE AMPS LOAD BREAKER LOAD BRKR REF LOAD CKT NO DESCRIPTION NO TYPE AMPS AMP P TYPE A B C TYPE AMP P AMPS TYPE NO DESCRIPTION NO
1 WH-4 50 3 0.0 30 3 AHU-1 2
3 --- ** * 0.0 ** * --- 4
5 --- ** * 0.0 ** * --- 6
7 HUMIDIFIER H-4 100 3 0.0 40 3 HEAT PUMP HP-4 8
9 --- ** * 0.0 ** * --- 10
11 --- ** * 0.0…