Addendum 01 - Attachment 3 - Specification 08 14 00 - Wood Doors.pdf

PDF 17 KB Posted

Attached to
B2190 Construct Munitions Load/Unload Facilities Building
Solicitation number
FA441823R0011
Issued by

View the file

Other files

File Type Posted
Solicitation Amendment FA441823R00110001 SF 30.pdf PDF
Solicitation Amendment FA441823R00110001 SF 30.pdf PDF
Addendum 01 - Attachment 1 - Specification 03 45 00 - Precast Architectural Concrete.pdf PDF
FA441823R0011 - Addendum 01 - Construct HAZMAT Load-Unload Facility B2190.pdf PDF
Addendum 01 - Attachment 2 - Specification 07 42 13 - Metal Wal Panels.pdf PDF
Questions and Answers - B2190.pdf PDF
Addendum 01 - Attachment 4 - Specification 31 31 16.19 - Termite Control Barriers.pdf PDF
B2190 - 20230217 - 16.jpg JPG image
B2190 - 20230217 - 18.jpg JPG image
B2190 - 20230217 - 10.jpg JPG image
B2190 - 20230217 - 3.jpg JPG image
B2190 - 20230217 - 7.jpg JPG image
B2190 - 20230217 - 14.jpg JPG image
B2190 - 20230217 - 9.jpg JPG image
B2190 - 20230217 - 5.jpg JPG image
B2190 - 20230217 - 12.jpg JPG image
B2190 - 20230217 - 15.jpg JPG image
B2190 - 20230217 - 17.jpg JPG image
B2190 - 20230217 - 11.jpg JPG image
B2190 - 20230217 - 2.jpg JPG image
B2190 - 20230217 - 8.jpg JPG image
B2190 - 20230217 - 1.jpg JPG image
B2190 - 20230217 - 6.jpg JPG image
B2190 - 20230217 - 13.jpg JPG image
B2190 - 20230217 - 4.jpg JPG image
FA441823R0011 - B2190 - Site Visit Sign In Sheet.pdf PDF
B2190 Site Visit List 13FEB23.pdf PDF
Davis-Bacon Act WD SC20230023 Mod 0 06JAN23.pdf PDF
JB Charleston - Question and Answer Form - B2190.xlsx XLSX spreadsheet
Solicitation - FA441823R0011.pdf PDF
Site Visit Burger King Map.png PNG image
15a - Submittal Register B2190.pdf PDF
17b - Specifications B2190.pdf PDF
17a - Drawings B2190.pdf PDF
15 - Submittal Register B2190.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Construct HAZMAT Load-Unload Facility, B.2190 Addendum No. 2 JBC No. DKFX 1051228 March 1, 2023

SECTION 08 14 00

WOOD DOORS

08/ 16, CHG 1: 08/ 18

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.

WINDOW AND DOOR MANUFACTURERS ASSOCIATION (WDMA)

ANSI/WDMA I.S.1A (2013) Interior Architectural Wood Flush Doors

ANSI/WDMA I.S.6A (2013) Interior Architectural Stile and Rail Doors

WOODWORK INSTITUTE (WI)

NAAWS 3.1 (2017; 2018 Errata Edition) North American Architectural Woodwork Standards

1.2 SUBMITTALS

Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Doors ; G

Submit drawings or catalog data showing each type of door unit .

Indicate within drawings and data the door types and construction, sizes, thickness, methods of assembly.

SD-03 Product Data

Doors ; G

Sample Warranty

SD-04 Samples

Doors ; G

Prior to the delivery of wood doors, submit a sample section of each type of door which shows the stile, rail, veneer, finish, and core construction.

Door Finish Colors ; G

Submit a minimum of three color selection samples , minimum 3 by 5

SECTION 08 14 00 Page 1 inches in size representing wood stain .

SD-06 Test Reports

Cycle-Slam ; G

Hinge Loading Resistance ; G

Submit cycle-slam test report for doors tested in accordance with ANSI/WDMA I.S.1A , and hinge loading resistance test report for doors tested in accordance with ANSI/WDMA I.S.6A .

SD-07 Certificates

Certificates of Grade ; G

SD-11 Closeout Submittals

Warranty ; G

1.3 CERTIFICATIONS

1.3.1 Certified Wood Grades

Provide certificates of grade from the grading agency.

1.4 DELIVERY, STORAGE, AND HANDLING

Deliver doors to the site in an undamaged condition and protect against damage and dampness. Stack doors flat under cover. Support on blocking, a minimum of 4 inch thick, located at each end and at the midpoint of the door. Store doors in a well-ventilated building so that they will not be exposed to excessive moisture, heat, dryness, direct sunlight, or extreme changes of temperature and humidity. Do not store in a building under construction until concrete, masonry work, and plaster are dry. Replace defective or damaged doors with new ones.

1.5 WARRANTY

Warrant doors free of defects as set forth in the door manufacturer's standard door warranty.

PART 2 PRODUCTS

2.1 DOORS

Provide doors of the types, sizes, and designs indicated free of urea-formaldehyde resins.

2.1.1 Flush Doors

Conform to ANSI/WDMA I.S.1A for flush doors. Provide hollow core doors with lock blocks and 1 inch minimum thickness hinge stile. Hardwood stile edge bands of doors receives a natural finish, compatible with face veneer. Provide mill option for stile edge of doors scheduled to be painted. No visible finger joints will be accepted in stile edge bands.

When used, locate finger-joints under hardware.

SECTION 08 14 00 Page 2

2.1.1.1 Interior Flush Doors

Provide staved lumber core, Type II flush doors conforming to ANSI/WDMA I.S.1A with faces of premium grade natural birch. Hardwood veneers must be rotary cut .

2.2 FABRICATION

2.2.1 Marking

Stamp each door with a brand, stamp, or other identifying mark indicating quality and construction of the door.

2.2.2 Quality and Construction

Identify the standard on which the construction of the door was based and identify doors having a Type I glue bond.

2.2.3 Preservative Treatment

Treat doors scheduled for restrooms, janitor closets and other possible wet locations including exterior doors with a water-repellent preservative treatment and so marketed at the manufacturer's plant.

2.2.4 Adhesives and Bonds

ANSI/WDMA I.S.1A . Use Type I bond for exterior doors and Type II bond for interior doors. Provide a nonstaining adhesive on doors with a natural finish.

2.2.5 Prefitting

Provide factory prefinished factory prefitted doors for the specified hardware, door frame and door-swing indicated. Machine and size doors at the factory by the door manufacturer in accordance with the standards under which the doors are produced and manufactured. The work includes sizing, beveling edges, mortising, and drilling for hardware and providing necessary beaded openings for glass and louvers. Provide the door manufacturer with the necessary hardware samples, and frame and hardware schedules to coordinate the work.

2.2.6 Finishes

2.2.6.1 Factory Finish

Provide doors finished at the factory by the door manufacturer as follows:

NAAWS 3.1 Section 1500, specification for System No. 4 Conversion varnish alkyd urea or System No. 5 Vinyl catalyzed. The coating is NAAWS 3.1 premium, medium rubbed sheen, closed grain effect. Use stain when required to produce the finish specified for color. Seal edges, cutouts, trim, and wood accessories, and apply two coats of finish compatible with the door face finish. Touch-up finishes that are scratched or marred, or where exposed fastener holes are filled, in accordance with the door manufacturer's instructions. Match color and sheen of factory finish using materials compatible for field application.

2.2.6.2 Color

Provide door finish colors as selected from manufacturer's standard colors .

SECTION 08 14 00 Page 3

2.3 SOURCE QUALITY CONTROL

Meet or exceed the following minimum performance criteria:

a. Cycle-slam : Heavy Duty Doors: 500,000 cycles with no loose hinge screws or other visible signs of failure when tested in accordance with the requirements of ANSI/WDMA I.S.1A .

b. Hinge loading resistance : Averages of ten test samples not less than Extra Heavy Duty doors: 550 pounds force when tested for direct screw withdrawal in accordance with ANSI/WDMA I.S.6A using a No. 12, 1-1/4 inch long, steel, fully threaded wood screw. Drill 5/32 inch pilot hole, use 1-1/2 inch opening around screw for bearing surface, and engage screw full, except for last 1/8 inch . Do not use a steel plate to reinforce screw area.

PART 3 EXECUTION

3.1 INSTALLATION

Do not install building construction materials that show visual evidence of biological growth.

Before installation, seal top and bottom edges of doors with the approved water-resistant sealer. Seal cuts made on the job immediately after cutting using approved water-resistant sealer. Fit, trim, and hang doors with a 1/16 inch minimum, 1/8 inch maximum clearance at sides and top, and a 3/16 inch minimum, 1/4 inch maximum clearance over thresholds. Provide 3/8 inch minimum, 7/16 inch maximum clearance at bottom where no threshold occurs. Bevel edges of doors at the rate of 1/8 inch in 2 inch . Door warp must not exceed 1/4 inch when measured in accordance with

ANSI/WDMA I.S.1A .

-- End of Section --