Construct HAZMAT Load-Unload Facility, B.2190 Addendum No. 2 JBC No. DKFX 1051228 March 1, 2023
SECTION 07 42 13
METAL WALL PANELS
05/ 11, CHG 2: 02/ 18
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA ADM (2020) Aluminum Design Manual
AA ASD1 (2017; Errata 2017) Aluminum Standards and Data
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 501.1 (2017) Standard Test Method for Water Penetration of Windows, Curtain Walls and Doors Using Dynamic Pressure
AAMA 800 (2016) Voluntary Specifications and Test Methods for Sealants
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 341 (2016) Seismic Provisions for Structural Steel Buildings
AMERICAN IRON AND STEEL INSTITUTE (AISI)
AISI S100 (2012) North American Specification for the Design of Cold-Formed Steel Structural Members
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7-16 (2017; Errata 2018; Supp 1 2018) Minimum Design Loads and Associated Criteria for Buildings and Other Structures
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2019) Standard Specification for Carbon Structural Steel
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A653/A653M (2022) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by
SECTION 07 42 13 Page 1 the Hot-Dip Process
ASTM A1008/A1008M (2021a) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM B117 (2019) Standard Practice for Operating Salt Spray (Fog) Apparatus
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM C920 (2018) Standard Specification for Elastomeric Joint Sealants
ASTM D522/D522M (2017) Mandrel Bend Test of Attached Organic Coatings
ASTM D523 (2014; R 2018) Standard Test Method for Specular Gloss
ASTM D610 (2008; R 2019) Standard Practice for Evaluating Degree of Rusting on Painted Steel Surfaces
ASTM D714 (2002; R 2017) Standard Test Method for Evaluating Degree of Blistering of Paints
ASTM D822 (2013; R 2018) Filtered Open-Flame Carbon-Arc Exposures of Paint and Related Coatings
ASTM D968 (2017) Standard Test Methods for Abrasion Resistance of Organic Coatings by Falling Abrasive
ASTM D1056 (2020) Standard Specification for Flexible Cellular Materials - Sponge or Expanded Rubber
ASTM D1308 (2002; R 2013) Effect of Household Chemicals on Clear and Pigmented Organic Finishes
ASTM D1654 (2008; R 2016; E 2017) Standard Test Method for Evaluation of Painted or Coated Specimens Subjected to Corrosive Environments
ASTM D1667 (2017) Standard Specification for Flexible Cellular Materials - Poly (Vinyl Chloride) Foam (Closed-Cell)
ASTM D2244 (2016) Standard Practice for Calculation of Color Tolerances and Color Differences from Instrumentally Measured Color Coordinates
SECTION 07 42 13 Page 2
ASTM D2247 (2015) Testing Water Resistance of Coatings in 100% Relative Humidity
ASTM D2794 (1993; R 2019) Standard Test Method for Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact)
ASTM D3359 (2017) Standard Test Methods for Rating Adhesion by Tape Test
ASTM D3363 (2005; E 2011; R 2011; E 2012) Film Hardness by Pencil Test
ASTM D4214 (2007; R 2015) Standard Test Method for Evaluating the Degree of Chalking of Exterior Paint Films
ASTM D4587 (2011; R 2019; E 2019) Standard Practice for Fluorescent UV-Condensation Exposures of Paint and Related Coatings
ASTM D5894 (2016) Standard Practice for Cyclic Salt Fog/UV Exposure of Painted Metal, (Alternating Exposures in a Fog/Dry Cabinet and a UV/Condensation Cabinet)
ASTM E72 (2022) Conducting Strength Tests of Panels for Building Construction
ASTM E84 (2020) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E283 (2019) Standard Test Method for Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
ASTM E331 (2000; R 2016) Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference
ASTM E1592 (2017) Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference
ASTM G152 (2013; R 2021) Standard Practice for Operating Open Flame Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials
ASTM G153 (2013; R 2021) Standard Practice for Operating Enclosed Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials
SECTION 07 42 13 Page 3
METAL BUILDING MANUFACTURERS ASSOCIATION (MBMA)
MBMA MBSM (2018) Metal Building Systems Manual
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM AMP 500 (2006) Metal Finishes Manual
SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION
(SMACNA)
SMACNA 1793 (2012) Architectural Sheet Metal Manual, 7th Edition
1.2 DEFINITIONS
Metal Wall Panel: Metal wall panels, attachment system components and accessories necessary for a complete weather-tight wall system.
1.3 DESCRIPTION OF WALL PANEL SYSTEM
aluminum metal wall panel system with concealed fastening attachment.
Panel profile must be angled box rib .
1.3.1 Metal Wall Panel General Performance
Comply with performance requirements, conforming to AISI S100 , without failure due to defective manufacture, fabrication, installation, or other defects in construction. Wall panels and accessory components must conform to the following standards:
ASTM A1008/A1008M
ASTM A123/A123M
ASTM A36/A36M
1.3.2 Structural Performance
Maximum calculated fiber stress must not exceed the allowable value in the AISI or AA manuals; a one third overstress for wind is allowed. Midspan deflection under maximum design loads is limited to L/180. Contract drawings show the design wind loads and the extent and general assembly details of the metal siding. Contractor must provide design for members and connections not shown on the drawings. Siding panels and accessories must be the products of the same manufacturer.
Provide metal wall panel assemblies complying with the load and stress requirements in accordance with ASTM E1592. Wind Load force due to wind action governs the design for panels.
Wall systems and attachments are to resist the wind loads as determined by ASTM E72 and ASCE 7-16 in the geographic area where the construction will take place, in pounds per square foot. Submit five copies of wind load tests and seismic tests to the Contracting Officer.
Provide metal wall panel assembly for seismic conditions complying with the applicable requirements of AISC 341 .
SECTION 07 42 13 Page 4
1.3.3 Air Infiltration
Air leakage must conform to the limits through the wall assembly area when tested according to ASTM E283.
1.3.4 Water Penetration Under Static Pressure
No water penetration when tested according to ASTM E331.
1.3.5 Water Penetration Under Dynamic Pressure
No evidence of water leakage when tested according to AAMA 501.1 .
1.4 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Submit Documentation for the following items:
Qualification of Manufacturer ; G Qualification of Installation Contractor ; G Sample Warranty ; G
SD-02 Shop Drawings
Installation Drawings ; G
SD-03 Product Data
Submit Manufacturer's catalog data for the following items:
Wall Panels ; G
Factory Color Finish ; G Closure Materials ; G Sealants and Caulking ; G
Accessories ; G
SD-04 Samples
Submit as required each of the following samples:
Wall Panels , 12 inches long by actual panel width; G Provide color chips; G
Submit manufacturer's color chips, approximately 4 by 4 inches, showing full range of colors, textures and patterns available for wall panels with factory applied finishes.
SD-05 Design Data
Wind load design analysis ; G
SECTION 07 42 13 Page 5
As applicable, submit the following wind load design analysis data, to include, but not limited to:
wind speed exposure category,co-efficient,importance factor type of facility negative pressures for each zone methods and requirements of attachment
SD-06 Test Reports
Submit test reports for the following in accordance with the referenced articles in this section.
Wind Load Tests ; G Coating Tests; G Chalking Tests; G Seismic Tests ; G
SD-08 Manufacturer's Instructions
Include detailed application instructions and standard manufacturer drawings altered as required by these specifications.
Installation of Wall panels; G
SD-11 Closeout Submittals
Warranty ; G Maintenance Instructions ; G
20 year "No Dollar Limit" warranty for labor and material
1.5 QUALITY ASSURANCE
1.5.1 Pre-Installation Conference
Upon notification of submittal receipt and approval by the Contracting Officer; and prior to the commencement of the work, the Contractor must attend a pre-installation conference to review the following:
a. Drawings and Specifications.
b. Qualification of Installer.
c. Sustainable acquisition
d. Approved Warranty
e. Sample wall panels, 12 inches long by actual panel width
f. Sample metal closure strips, 10 inches long of each type
g. Color charts and chips
h. Coatings and base metal tests, chalking tests
i. Construction schedule, availability of materials, Installer's
SECTION 07 42 13 Page 6 personnel, equipment and facilities required to progress with the work without delay.
j. Methods and procedures related to installation of wall panels, including manufacturer's written instructions. Explicitly identify in writing, differences between manufacturer's instructions and the specified requirements.
k. Support conditions for compliance with requirements, including alignment between and attachment to structural members.
l. Flashing, special siding details, wall penetrations, openings, and condition of other construction that will affect metal wall panels.
m. Governing regulations and requirements for insurance, certificates, and tests and inspections if applicable.
n. Temporary protection requirements for metal wall panel assembly during and after installation.
o. Wall panel observation and repair procedures after metal wall panel installation. Provide detailed written instructions including copies of Safety Data Sheets for maintenance and repair materials, and manufacturer's maintenance instructions.
1.5.1.1 Installation Drawings
Installation shop drawings for wall panels, flashing, accessories, and anchorage systems must indicate completely dimensioned structural frame and erection layouts, openings in the wall, special framing details, and construction details at corners, building intersections and flashing, location and type of mastic and metal filler strips.
1.5.1.2 Wind Load Design Analysis
Wind design analysis must include wall plan delineating dimensions and attachment patterns for each zone. Wind design analysis must be prepared and sealed by Licensed Project Engineer in the geographic area where the construction will take place.
1.5.2 Manufacturer's Technical Representative
The representative must have authorization from manufacturer to approve field changes and be thoroughly familiar with the products and installations in the geographical area where construction will take place.
1.5.3 Qualification of Manufacturer
Certify that metal wall panel system manufacturer has a minimum of five
(5) years experience in manufacturing metal wall system and accessory products.
Manufacturer must also provide engineering services by an authorized engineer; currently licensed in the geographical area where construction will take place, having a minimum of four (4) years experience as an engineer knowledgeable in wind load design analysis, protocols and procedures per MBMA MBSM, "Metal Building Systems Manual"; ASCE 7-16 , and ASTM E1592 and seismic design conforming to AISC 341 .
SECTION 07 42 13 Page 7
Provide certified engineering calculations, using the products submitted, for Wind load requirements in accordance with ASCE 7-16 .
1.5.4 Certified Qualification of Installation Contractor
The installation contractor must be approved and certified by the metal wall panel manufacturer prior to beginning the installation of the metal wall panel system. Subcontracting by Certified Contractor for the metal wall panel work is not permitted.
1.5.5 Single Source
Obtain each type of metal wall panels, clips, closure materials and other accessories from the standard products of the single source from a single manufacturer to operate as a complete system for the intended use.
1.5.6 Manufacturer's Maintenance Instructions
Provide manufacturer's detailed written instructions including copies of Safety Data Sheets for maintenance and repair materials.
1.6 DELIVERY, HANDLING, AND STORAGE
Deliver and protect package components, sheets, metal wall panels, and other manufactured items to prevent damage or deformation during transportation and handling.
Unload, store, and erect metal wall panels in a manner to prevent bending, warping, twisting, and surface damage.
Stack and store metal wall panels horizontally on platforms or pallets, covered with suitable weather-tight and ventilated covering to ensure dryness, with positive slope for drainage of water. Do not store metal wall panels in contact with other materials that might cause staining, denting, or other surface damage.
Retain strippable protective covering on metal wall panel until actual installation.
1.7 PROJECT CONDITIONS
1.7.1 Field Measurements
Verify locations of wall framing and opening dimensions by field measurements before metal wall panel fabrication and indicate measurements on Shop Drawings.
1.7.2 Weather Limitations
Proceed with installation preparation only when existing and forecasted weather conditions permit Work to proceed without water entering into wall system or building.
1.8 WARRANTY
Warranty must conform to the Sample Warranty as reviewed and approved by the Contracting Officer.
SECTION 07 42 13 Page 8
1.8.1 20 Year "No Dollar Limit" Warranty for Labor and Material
Furnish manufacturer's no-dollar-limit warranty for the metal wall panel system. The warranty period is to be no less than twenty (20) years from the date of Government acceptance of the work. The warranty is to be issued directly to the Government. The warranty is to provide that if within the warranty period the metal wall panel system shows evidence of corrosion, perforation, rupture or excess weathering due to deterioration of the wall panel system resulting from defective materials and correction of the defective workmanship is to be the responsibility of the metal wall panel system manufacturer. Repairs that become necessary because of defective materials and workmanship while metal wall panel system is under warranty are to be performed within 24 hours after notification, unless additional time is approved by the Contracting Officer. Failure to perform repairs within 24 hours of notification will constitute grounds for having emergency repairs performed by others and not void the warranty.
PART 2 PRODUCTS
2.1 FABRICATION
Unless approved otherwise, fabricate and finish metal wall panels and accessories at the factory to greatest extent possible, by manufacturer's standard procedures and processes and as necessary to fulfill indicated and specified performance requirements. Comply with indicated profiles and with dimensional and structural requirements.
Provide panel profile, including major ribs and intermediate stiffening ribs, if any, for full length of panel. Fabricate metal wall panel side laps with factory-installed captive gaskets or separator strips that provide a tight seal and prevent metal-to-metal contact, in a manner that will seal weather-tight and minimize noise from movements within panel assembly.
2.1.1 Sheet Metal Accessories
Fabricate flashing and trim to comply with recommendations in SMACNA 1793 that apply to the design, dimensions, metal, and other characteristics of item indicated:
a. Form exposed sheet metal accessories that are without excessive oil canning, buckling, and tool marks and that are true to line and levels indicated, with exposed edges folded back to form hems.
b. End Seams: fabricate nonmoving end seams with flat-lock seams. Form seams and seal with epoxy seam sealer. Rivet joints for additional strength.
c. Sealed Joints: form non-expansion but movable joints in metal to accommodate elastomeric sealant to comply with SMACNA 1793.
d. Conceal fasteners and expansion provisions where possible. Exposed fasteners are not allowed on faces of accessories exposed to view.
e. Fabricate cleats and attachment devices of size and metal thickness recommended by SMACNA 1793 or by metal wall panel manufacturer for application, but not less than thickness of metal being secured.
SECTION 07 42 13 Page 9
2.2 PANEL MATERIALS
2.2.1 Aluminum Sheet
Roll-form aluminum wall panels to the specified profile, with fy = 40 ksi , .040 inches thickness and depth as indicated. Material must be plumb and true, and within the tolerances listed:
a. Aluminum Sheet conforming to ASTM B209, AA ASD1 and AA ADM.
b. Individual panels must be have continuous length to cover the entire length of any wall area with no joints or seams and formed without warping, waviness, or ripples that are not part of the panel profile and free of damage to the finish coating system.
c. Provide panels with thermal expansion and contraction consistent with the type of system specified.
1. Profile and coverage to be a minimum height and width from manufacturer's standard for the indicated wall area.
7. Profile to be a 7/8 inch high angled box ribs at 4 inches o.c., 16 inch overall width.
10. Smoothsurface texture.
2.2.2 Factory Color Finish
Comply with NAAMM AMP 500 for recommendations for applying and designating finishes. Noticeable variations in same piece are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the range of approved samples and are assembled or installed to minimize contrast.
All panels are to receive a factory-applied Kynar 500/Hylar 5000 finish consisting of a baked-on top-coat with a manufacturer's recommended prime coat conforming to the following:
2.2.2.1 Metal Preparation
Carefully prepare all metal surface for painting on a continuous process coil coating line by alkali cleaning, hot water rinsing, application of chemical conversion coating, cold water rinsing, sealing with acid rinse, and thorough drying.
2.2.2.2 Prime Coating
Apply a base coat of epoxy paint, specifically formulated to interact with the top-coat, to the prepared surfaces by roll coating to a dry film thickness of 0.20 plus 0.05 mils. Prime coat must be oven cured prior to application of finish coat.
2.2.2.3 Exterior Finish Coating
Roll coat the finish coating over the primer by roll coating to dry film thickness of 0.80 plus 5 mils (3.80 plus 0.50 mils for Vinyl Plastisol) for a total dry film thickness of 1.00 plus 0.10 mils (4.00 plus 0.10 mils for Vinyl Plastisol). Oven-cure finish coat.
SECTION 07 42 13 Page 10
2.2.2.4 Interior Finish Coating
Apply a wash-coat on the reverse side over the primer by roll coating to a dry film thickness of 0.30 plus 0.05 mils for a total dry film thickness of 0.50 plus 0.10 mils. Oven-cured the wash coat.
2.2.2.5 Color
Provide exterior finish color Fed. Standard 595B Color No. 37769 .
2.2.2.6 Physical Properties
Coating must conform to the industry and manufacturer's standard performance criteria as listed by the following certified test reports:
General: ASTM D5894 and ASTM D4587
Abrasion: ASTM D968
Adhesion: ASTM D3359
Chalking: ASTM D4214
Chemical Pollution: ASTM D1308
Color Change and Conformity: ASTM D2244
Creepage: ASTM D1654
Cyclic Corrosion Test: ASTM D5894
Flame Spread: ASTM E84
Flexibility: ASTM D522/D522M
Formability: ASTM D522/D522M
Gloss at 60 and 85 degrees: ASTM D523
Humidity: ASTM D2247 and ASTM D714
Oxidation: ASTM D610
Pencil Hardness: ASTM D3363
Reverse Impact: ASTM D2794
Salt Spray: ASTM B117
Weatherometer: ASTM G152, ASTM G153 and ASTM D822
2.3 MISCELLANEOUS METAL FRAMING
Cold-formed metallic-coated steel sheet conforming to ASTM A653/A653M and
SECTION 07 42 13 Page 11 specified in Section 05 40 00 COLD-FORMED METAL FRAMING unless otherwise indicated.
2.3.1 Fasteners for Miscellaneous Metal Framing
Type, material, corrosion resistance, size and sufficient length to penetrate the supporting member a minimum of 1 inch with other properties required to fasten miscellaneous metal framing members to supporting members and substrates in accordance with the wall panel manufacturer's and ASCE 7-16 requirements.
2.4 FASTENERS
2.4.1 General
2.4.1.1 Hidden Fasteners
Provide corrosion resistant fasteners recommended by the manufacturer to meet the performance requirements and design loads.
2.4.1.2 Screws
Screws to be corrosion resistant coated steel, aluminum and/or 305 - series stainless steel being the type and size recommended by the manufacturer to meet the performance requirements.
2.4.1.3 Rivets
Rivets to be closed-end type, corrosion resistant coated steel, aluminum or stainless steel where watertight connections are required.
2.4.1.4 Attachment Clips
Fabricate clips from steel hot-dipped galvanized in accordance with ASTM A653/A653M , Z275 G 90 or Series 300 stainless steel. Size, shape, thickness and capacity as required meeting the insulation thickness and design load criteria specified.
2.5 ACCESSORIES
2.5.1 General
All accessories must be compatible with the metal wall panels. Sheet metal flashing, trim, metal closure strips, caps and similar metal accessories must not be less than the minimum thickness specified for the wall panels.
Exposed metal accessories/finishes to match the panels furnished, except as otherwise indicated. Molded foam rib, ridge and other closure strips must be non-absorbent closed-cell or solid-cell synthetic rubber or pre-molded neoprene to match configuration of the panels.
2.5.2 Rubber Closure Strips
Provide closed-cell, expanded cellular rubber conforming to ASTM D1056 and ASTM D1667; extruded or molded to the configuration of the specified wall panel and in lengths supplied by the wall panel manufacturer.
2.5.3 Metal Closure Strips
Provide factory fabricated aluminum closure strips to be the same thickness, SECTION 07 42 13 Page 12 color, finish and profile of the specified wall panel.
2.5.4 Joint Sealants
2.5.4.1 Sealants and Caulking
Provide approved gun type sealants for use in hand- or air-pressure caulking guns at temperatures above 40 degrees F (or frost-free application at temperatures above 10 degrees F with minimum solid content of 85 percent of the total volume. Sealants must dry with a tough, durable surface skin which permit remaining soft and pliable underneath, providing a weather-tight joint. No migratory staining is permitted on painted or unpainted metal, stone, glass, vinyl, or wood.
Prime all joints receiving sealants with a compatible one-component or two-component primer as recommended by the wall panel manufacturer.
2.5.4.2 Shop-Applied
Sealant for shop-applied caulking must be non-curing butyl compliant with AAMA 800 to ensure the sealant's plasticity at the time of field erection.
2.5.4.3 Field-Applied
Sealant for field-applied caulking must be an approved gun grade, non-sag one component polysulfide or two-component polyurethane with an initial maximum Shore A durometer hardness of 25, and conforming to ASTM C920, Type II. Color to match panel colors.
2.6 SHEET METAL FLASHING AND TRIM
2.6.1 Fabrication
Shop fabricate sheet metal flashing and trim where practicable to comply with recommendations in SMACNA 1793 that apply to design, dimensions, metal, and other characteristics of item indicated. Obtain field measurements for accurate fit before shop fabrication.
Fabricate sheet metal flashing and trim without excessive oil canning, buckling, and tool marks and true to line and levels indicated, with exposed edges folded back to form hems.
2.7 REPAIR OF FINISH PROTECTION
Repair paint for color finish enameled wall panel must be compatible paint of the same formula and color as the specified finish furnished by the wall panel manufacturer. Provide pints of repair paint matching the specified wall panels.
PART 3 EXECUTION
3.1 EXAMINATION
Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances, metal wall panel supports, and other conditions affecting performance of the Work.
Examine primary and secondary wall framing to verify that rafters, purlins, angles, channels, and other structural panel support members and
SECTION 07 42 13 Page 13 anchorages have been installed within alignment tolerances required by metal wall panel manufacturer, UL, ASTM, ASCE 7-16 and as required for the geographical area where construction will take place.
Examine solid wall sheathing to verify that sheathing joints are supported by framing or blocking and that installation is within flatness tolerances required by metal wall panel manufacturer.
Examine roughing-in for components and systems penetrating metal wall panels to verify actual locations of penetrations relative to seam locations of metal wall panels before metal wall panel installation.
Submit to the Contracting Officer a written report, endorsed by Installer, listing conditions detrimental to performance of the Work. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
Clean substrates of substances harmful to insulation, including removing projections capable of interfering with insulation attachment.
Miscellaneous framing installation, including sub-purlins, girts, angles, furring, and other miscellaneous wall panel support members and anchorage must be according to metal wall panel manufacturer's written instructions.
3.3 WALL PANEL INSTALLATION
Provide full length metal wall panels, from sill to eave as indicated, unless otherwise indicated or restricted by shipping limitations. Anchor metal wall panels and other components of the Work securely in place, with provisions for thermal and structural movement in accordance with MBMA MBSM.
Erect wall panel system in accordance with the approved erection drawings, the printed instructions and safety precautions of the manufacturer.
Sheets are not to be subjected to overloading, abuse, or undue impact.
Bent, chipped, or defective sheets shall not be applied.
Sheets must be erected true and plumb and in exact alignment with the horizontal and vertical edges of the building, securely anchored, and with the indicated eave, and sill.
Work is to allow for thermal movement of the wall panel, movement of the building structure, and to provide permanent freedom from noise due to wind pressure.
Field cutting metal wall panels by torch is not permitted.
3.3.1 Aluminum Wall Panels
Use aluminum or stainless-steel fasteners for exterior surfaces and aluminum or galvanized steel fasteners for interior surfaces.
3.3.2 Metal Protection
Where dissimilar metals will contact each other or corrosive substrates, protect against galvanic action by painting contact surfaces with bituminous coating, by applying rubberized-asphalt underlayment to each contact surface, or by other permanent separation as recommended by metal wall panel manufacturer.
SECTION 07 42 13 Page 14
3.3.3 Joint Sealers
Install gaskets, joint fillers, and sealants where indicated and where required for weatherproof performance of metal wall panel assemblies.
Provide types of gaskets, fillers, and sealants indicated or, if not indicated, types recommended by metal wall panel manufacturer.
3.4 FASTENER INSTALLATION
Anchor metal wall panels and other components of the Work securely in place, using manufacturer's approved fasteners according to manufacturers' written instructions.
3.5 FLASHING, TRIM AND CLOSURE INSTALLATION
3.5.1 General Requirements
Comply with performance requirements, manufacturer's written installation instructions, and SMACNA 1793. Provide concealed fasteners where possible, and set units true to line and level as indicated. Install work with laps, joints, and seams to form permanently watertight and weather resistant.
Install sheet metal work is to form weather-tight construction without waves, warps, buckles, fastening stresses or distortion, and allow for expansion and contraction. Cutting, fitting, drilling, and other operations in connection with sheet metal required to accommodate the work of other trades is to be performed by sheet metal mechanics.
3.5.2 Metal Flashing
Install exposed metal flashing at building corners, sills and eaves, junctions between metal siding and walling. Exposed metal flashing must be the same material, color, and finish as the specified metal wall panel.
Fasten flashing at a minimum of 8 inches on center, except where flashing is held in place by the same screws that secure covering sheets.
Flashing is to be furnished in at least 8 foot lengths. Exposed flashing is to have 1 inch locked and blind-soldered end joints, and expansion joints at intervals of not more than 16 feet .
Exposed flashing and flashing subject to rain penetration to be bedded in the specified joint sealant.
Isolate flashing which is in contact with dissimilar metals by means of the specified asphalt mastic material to prevent electrolytic deterioration.
Form drips to the profile indicated, with the edge folded back 1/2 inch to form a reinforced drip edge.
3.5.3 Closures
Install metal closure strips at open ends of corrugated or ribbed pattern walls, and at intersection of wall and wall unless open ends are concealed with formed eave flashing; and in other required areas.
SECTION 07 42 13 Page 15
Install mastic closure strips at intersection of the wall with metal walling; top and bottom of metal siding; heads of wall openings; and in other required locations.
3.6 WORKMANSHIP
Make lines, arises, and angles sharp and true. Free exposed surfaces from visible wave, warp, buckle, and tool marks. Fold back exposed edges neatly to form a 1/2 inch hem on the concealed side. Make sheet metal exposed to the weather watertight with provisions for expansion and contraction.
Make surfaces to receive sheet metal plumb and true, clean, even, smooth, dry, and free of defects and projections which might affect the application. For installation of items not shown in detail or not covered by specifications conform to the applicable requirements of SMACNA 1793.
Provide sheet metal flashing in the angles formed where roof decks abut walls, curbs, ventilators, pipes, or other vertical surfaces and wherever indicated and necessary to make the work watertight.
3.7 ACCEPTANCE PROVISIONS
3.7.1 Erection Tolerances
Erect metal wall panels straight and true with plumb vertical lines correctly lapped and secured in accordance with the manufacturer's written instructions.
3.7.2 Repairs to Finish
Scratches, abrasions, and minor surface defects of finish may be repaired with the specified repair materials. Finished repaired surfaces must be uniform and free from variations of color and surface texture.
Repaired metal surfaces that are not acceptable to the project requirements and/or Contracting Officer are to be immediately removed and replaced with new material.
3.8 CLEAN-UP AND DISPOSAL
Clean all exposed sheet metal work at completion of installation. Remove metal shavings, filings, nails, bolts, and wires from work area. Remove grease and oil films, excess sealants, handling marks, contamination from steel wool, fittings and drilling debris and scrub the work clean.
Exposed metal surfaces must be free of dents, creases, waves, scratch marks, solder or weld marks, and damage to the finish coating.
Collect and place scrap/waste materials in containers. Promptly dispose of demolished materials. Do not allow demolished materials to accumulate on-site; transport demolished materials from government property and legally dispose of them.
-- End of Section --