Exhibit_C,_A1_Project_Plans.pdf
PDF 713 KB Posted
- Attached to
- DNR - Lodging within Duluth MN Aug 24-27, 2026
- Solicitation number
- 2000018389
- Issued by
- St. Louis County, Minnesota
About this file
This file is a comprehensive project specification document prepared by the State of Minnesota Department of Military Affairs (MN DMA) for the Marshall National Guard Armory Building Automation System (BAS) installation. The document encompasses multiple sections detailing HVAC testing, adjusting, and balancing (Section 23 05 93); HVAC piping insulation (Section 23 07 19); instrumentation and control devices (Section 23 09 13); and a direct digital control system for HVAC (Section 23 09 23). The project requires furnishing and installation of all labor, materials, equipment, and services necessary to demolish existing BAS controls and install a new integrated system that communicates via BACnet protocol with the existing Minnesota Department of Military Affairs Building Automation System Network Center located at Camp Ripley. Key deliverables include system architecture design diagrams, sequence of control documentation, installation design details, shop drawings, startup testing plans and reports, operation and maintenance manuals, all software and firmware files, and as-built documentation reflecting actual installations. The specifications require compliance with multiple standards including ASHRAE 135-2016 BACnet Standard, AABC National Standards for Total System Balance (7th Edition, 2016), NEBB Procedural Standard for Testing, Adjusting and Balancing (2019), and relevant ASTM and UL standards for materials and safety.
The approved manufacturer and installation contractor is Johnson Controls Inc., with the specific requirement that work be performed by the Johnson Controls Branch Office in Duluth, Minnesota under project manager Brian Schmidt. Testing, adjusting, and balancing adjustments must be made to within plus or minus 10 percent of design specifications for hydronic systems, with final reports submitted in digital format including instrument calibration documentation. All control panels and equipment must be installed in NEMA 1 enclosures in mechanical rooms at locations pre-approved by the MN DMA Owner's Representative, with temperature control systems utilizing 24-volt low-voltage Class 2 rated power supplies. The contractor must provide a 12-month warranty period commencing upon Owner acceptance, with 24-hour response requirements for warranty service requests and 4-hour response requirements for critical systems. The project requires integration with the Department of Defense controlled network infrastructure, with all supervisory devices communicating via BACnet/IP, and demands submission of all proprietary software, licensing agreements, and project databases to the State of Minnesota as owner property upon completion. Training must be provided to State personnel on system operation and maintenance documentation six weeks prior to formal training delivery.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Testing, Adjusting, and Balancing for HVAC 23 05 93 - 1
EXHIBIT C, A1 PROJECT PLANS
PART 1 GENERAL
SECTION 23 05 93
TESTING, ADJUSTING, AND BALANCING FOR HVAC
1.01 SECTION INCLUDES
A. Testing, adjustment, and balancing of hydronic systems.
1.02 RELATED REQUIREMENTS
1.03 REFERENCE STANDARDS
A. AABC (NSTSB) - AABC National Standards for Total System Balance, 7th Edition; 2016.
B. ASHRAE Std 111 - Measurement, Testing, Adjusting, and Balancing of Building HVAC
Systems; 2024, with Errata (2025).
C. NEBB (TAB) - Procedural Standard for Testing, Adjusting and Balancing of Environmental
Systems; 2019, with Errata (2022).
1.04 SUBMITTALS
A. Final Report: Indicate deficiencies in systems that would prevent proper testing, adjusting, and balancing of systems and equipment to achieve specified performance.
1. Submit draft copies of report for review prior to final acceptance of Project. Provide final copies for Architect and for inclusion in operating and maintenance manuals.
2. Provide reports in an organized digital format, complete with cover identification, table of contencts and bookmarked page identification. Include set of reduced drawings with air outlets and equipment identified to correspond with data sheets.
3. Include actual instrument list, with manufacturer name, serial number, and date of calibration.
4. Form of Test Reports: Where the TAB standard being followed recommends a report format use that; otherwise, follow ASHRAE Std 111.
5. Units of Measure: Report data in I-P (inch-pound) units only.
6. Include the following on the title page of each report:
a. Name of Testing, Adjusting, and Balancing Agency.
b. Address of Testing, Adjusting, and Balancing Agency.
c. Telephone number of Testing, Adjusting, and Balancing Agency.
d. Project name.
e. Project location.
f. Project Architect.
g. Project Engineer.
h. Project Contractor.
i. Report date.
PART 2 PRODUCTS - NOT USED
PART 3 EXECUTION
3.01 GENERAL REQUIREMENTS
A. Begin work after completion of systems to be tested, adjusted, or balanced and complete work prior to Substantial Completion of the project.
B. Where HVAC systems and/or components interface with life safety systems, including fire and smoke detection, alarm, and control, coordinate scheduling and testing and inspection procedures with the authorities having jurisdiction.
C. TAB Agency Qualifications:
1. Company specializing in the testing, adjusting, and balancing of systems specified in this section.
2. Having minimum of three years documented experience.
3. Certified by one of the following:
for HVAC 23 05 93 - 2
a. NEBB, National Environmental Balancing Bureau
b. TABB, The Testing, Adjusting, and Balancing Bureau of National Energy
Management Institute D. TAB Supervisor and Technician Qualifications: Certified by same organization as TAB agency.
3.02 EXAMINATION
A. Verify that systems are complete and operable before commencing work. Ensure the following conditions:
1. Systems are started and operating in a safe and normal condition.
2. Temperature control systems are installed complete and operable.
3. Proper thermal overload protection is in place for electrical equipment.
4. Air coil fins are cleaned and combed.
5. Hydronic systems are flushed, filled, and vented.
6. Pumps are rotating correctly.
7. Proper strainer baskets are clean and in place.
8. Service and balance valves are open.
B. Submit field reports. Report defects and deficiencies that will or could prevent proper system balance.
C. Beginning of work means acceptance of existing conditions.
3.03 ADJUSTMENT TOLERANCES
A. Hydronic Systems: Adjust to within plus or minus 10 percent of design.
3.04 RECORDING AND ADJUSTING
A. Field Logs: Maintain written logs including:
1. Running log of events and issues.
2. Discrepancies, deficient or uncompleted work by others.
3. Contract interpretation requests.
4. Lists of completed tests.
B. Ensure recorded data represents actual measured or observed conditions.
C. Permanently mark settings of valves, dampers, and other adjustment devices allowing settings to be restored. Set and lock memory stops.
D. Mark on drawings the locations where traverse and other critical measurements were taken and cross reference the location in the final report.
E. After adjustment, take measurements to verify balance has not been disrupted or that such disruption has been rectified.
F. Leave systems in proper working order, replacing belt guards, closing access doors, closing doors to electrical switch boxes, and restoring thermostats to specified settings.
G. At final inspection, recheck random selections of data recorded in report. Recheck points or areas as selected and witnessed by the Owner.
3.05 WATER SYSTEM PROCEDURE
A. Adjust water systems to provide required or design quantities.
B. Use calibrated Venturi tubes, orifices, or other metered fittings and pressure gauges to determine flow rates for system balance. Where flow metering devices are not installed, base flow balance on temperature difference across various heat transfer elements in the system.
C. Adjust systems to provide specified pressure drops and flows through heat transfer elements prior to thermal testing. Perform balancing by measurement of temperature differential in conjunction with air balancing.
D. Effect system balance with automatic control valves fully open to heat transfer elements.
for HVAC 23 05 93 - 3
E. Effect adjustment of water distribution systems by means of balancing cocks, valves, and fittings. Do not use service or shut-off valves for balancing unless indexed for balance point.
3.06 SCOPE
A. Test, adjust, and balance the following:
1. HVAC Pumps.
2. Air Cooled Water Chillers.
3.07 MINIMUM DATA TO BE REPORTED
A. Electric Motors:
1. Manufacturer.
2. Model/Frame.
3. HP/BHP.
4. Phase, voltage, amperage; nameplate, actual, no load.
5. RPM.
6. Service factor.
7. Starter size, rating, heater elements.
8. Sheave Make/Size/Bore.
B. Pumps:
1. Identification/number.
2. Manufacturer.
3. Size/model.
4. Impeller.
5. Service.
6. Design flow rate, pressure drop, BHP.
7. Actual flow rate, pressure drop, BHP.
8. Discharge pressure.
9. Suction pressure.
10. Total operating head pressure.
11. Shut off, discharge and suction pressures.
12. Shut off, total head pressure.
C. Chillers:
1. Identification/number.
2. Manufacturer.
3. Capacity.
4. Model number.
5. Serial number.
6. Evaporator entering water temperature, design and actual.
7. Evaporator leaving water temperature, design and actual.
8. Evaporator pressure drop, design and actual.
9. Evaporator water flow rate, design and actual.
10. Condenser entering water temperature, design and actual.
11. Condenser pressure drop, design and actual.
12. Condenser water flow rate, design and actual.
D. Cooling Coils:
1. Identification/number.
2. Location.
3. Service.
4. Manufacturer.
5. Water flow, design and actual.
6. Water pressure drop, design and actual.
7. Entering water temperature, design and actual.
for HVAC 23 05 93 - 4
8. Leaving water temperature, design and actual.
END OF SECTION 23 05 93
HVAC Piping Insulation 23 07 19 - 1
1.01 SECTION INCLUDES
A. Piping insulation.
SECTION 23 07 19
HVAC PIPING INSULATION
B. Flexible removable and reusable blanket insulation.
C. Jacketing and accessories.
1.02 RELATED REQUIREMENTS
A. Section 07 84 00 - Firestopping.
B. Section 23 05 29 - Hangers and Bracing for HVAC Piping.
C. Section 23 21 13 - Hydronic Piping: Placement of hangers and hanger inserts.
D. Section 23 23 00 - Refrigerant Piping: Placement of inserts.
1.03 REFERENCE STANDARDS
A. ASTM B209/B209M - Standard Specification for Aluminum and Aluminum-Alloy Sheet and
Plate; 2021a.
B. ASTM C534/C534M - Standard Specification for Preformed Flexible Elastomeric Cellular
Thermal Insulation in Sheet and Tubular Form; 2025.
C. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials;
2026.
D. ASTM E96/E96M - Standard Test Methods for Gravimetric Determination of Water Vapor
Transmission Rate of Materials; 2024a.
E. UL 723 - Standard for Test for Surface Burning Characteristics of Building Materials; Current
Edition, Including All Revisions.
1.04 SUBMITTALS
A. Product Data: Provide product description, thermal characteristics, list of materials and thickness for each service, and locations.
B. Manufacturer's Instructions: Indicate installation procedures that ensure acceptable workmanship and installation standards will be achieved.
1.05 DELIVERY, STORAGE, AND HANDLING
A. Accept materials on site, labeled with manufacturer's identification, product density, and thickness.
1.06 FIELD CONDITIONS
A. Maintain ambient conditions required by manufacturers of each product.
B. Maintain temperature before, during, and after installation for minimum of 24 hours.
PART 2 PRODUCTS
2.01 REGULATORY REQUIREMENTS
A. Surface Burning Characteristics: Flame spread index/Smoke developed index of 25/50, maximum, when tested in accordance with ASTM E84 or UL 723.
2.02 FLEXIBLE ELASTOMERIC CELLULAR INSULATION
A. Manufacturers:
1. Aeroflex USA, Inc
2. Armacell LLC
3. K-Flex USA LLC
HVAC Piping Insulation 23 07 19 - 2
B. Insulation: Preformed flexible elastomeric cellular rubber insulation complying with ASTM C534/C534M Grade 1; use molded tubular material wherever possible.
1. Minimum Service Temperature: Minus 40 degrees F.
2. Maximum Service Temperature: 180 degrees F.
3. Connection: Waterproof vapor barrier adhesive.
C. Elastomeric Foam Adhesive: Air dried, contact adhesive, compatible with insulation.
2.03 JACKETING AND ACCESSORIES
A. PVC Plastic.
1. Jacket: One piece molded type fitting covers and sheet material, off-white color.
a. Minimum Service Temperature: 0 degrees F.
b. Maximum Service Temperature: 150 degrees F.
c. Moisture Vapor Permeability: 0.002 perm inch, maximum, when tested in accordance with ASTM E96/E96M.
d. Connections: Brush on welding adhesive.
2. Covering Adhesive Mastic: Compatible with insulation.
B. Aluminum Jacket:
1. Comply with ASTM B209/B209M, Temper H14, minimum thickness of 0.016 inch with factory-applied polyethylene and kraft paper moisture barrier on the inside surface.
2. Thickness: 0.016 inch sheet.
3. Type: Factory-applied, self-adhesive jacketing.
4. Finish: Embossed.
5. Joining: Longitudinal slip joints and 2 inch laps.
6. Fittings: 0.016 inch thick die-shaped fitting covers with factory-attached protective liner.
7. Metal Jacket Bands: 3/8 inch wide; 0.015 inch thick aluminum.
PART 3 EXECUTION
3.01 EXAMINATION
A. Test piping for design pressure, liquid tightness, and continuity prior to applying insulation materials.
B. Verify that surfaces are clean and dry, with foreign material removed.
3.02 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Install in accordance with NAIMA National Insulation Standards.
C. Exposed Piping: Locate insulation and cover seams in least visible locations.
D. Inserts and Shields:
1. Application: Refer to Section 23 05 29 for application requirements.
2. Shields: Galvanized steel between pipe hangers or pipe hanger rolls and inserts.
3. Insert location: Between support shield and piping and under the finish jacket.
4. Insert Configuration: Minimum 6 inches long, of same thickness and contour as adjoining insulation; may be factory fabricated.
5. Insert Material: Hydrous calcium silicate insulation or other heavy density insulating material suitable for the planned temperature range.
E. Continue insulation through walls, sleeves, pipe hangers, and other pipe penetrations. Finish at supports, protrusions, and interruptions. At fire separations, see Section 07 84 00.
F. Pipe Exposed in Mechanical Equipment Rooms or Finished Spaces: Finish with PVC jacket and fitting covers.
G. Exterior Applications: Provide vapor barrier jacket. Insulate fittings, joints, and valves with insulation of like material and thickness as adjoining pipe, and finish with glass mesh reinforced vapor barrier cement. Cover with aluminum jacket with seams located on bottom side of horizontal piping.
HVAC Piping Insulation 23 07 19 - 3
3.03 SCHEDULE
A. Cooling Systems:
1. Interior Exposed Chilled Water Supply and Return:
a. Flexible Elastomeric Cellular Insulation
1) All pipe sizes
2) Thickness: 1 inches.
b. Jacket: PVC
2. Exterior Chilled Water Supply and Return:
a. Flexible Elastomeric Cellular Insulation
1) All pipe sizes
2) Thickness: 1 inches.
b. Jacket: Aluminum
END OF SECTION 23 07 19
Instrumentation and Control Devices for HVAC 23 09 13 - 1
SECTION 23 09 13
INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
1.01 SECTION INCLUDES
A. Control panels.
B. Control Valves:
1. Globe pattern.
2. Electronic operators.
C. Pressure independent valves and actuators.
D. Dampers.
E. Damper Operators:
1. Electric operators.
F. HVAC&R Sensors:
1. Temperature sensors.
2. Humidity sensors.
3. Static pressure (air pressure) sensors.
4. Current sensors.
5. Carbon dioxide sensors.
G. Emergency Operator Stations.
1. Boiler emergency shutdown station.
2. HVAC emergency shutdown station.
H. Thermostats:
1. Room thermostat accessories.
2. Airstream thermostats.
3. Electric low limit duct thermostats.
I. Sensors with transmitters:
1. Building static pressure transmitters.
2. Pressure transmitters.
3. Air pressure transmitters.
4. Water pressure transmitters (liquid differential pressure transmitters).
5. Temperature transmitters.
6. Humidity transmitters.
J. Push Button Operators K. Flow Sensors and Transmitters:
1. Turbine flow meters.
2. Flow switches.
1.02 RELATED REQUIREMENTS
A. Section 23 21 13 - Hydronic Piping: Installation of control valves, flow switches, temperature sensor sockets, and gauge taps.
B. Section 26 05 83 - Wiring Connections: Electrical characteristics and wiring connections.
C. Section 26 27 26 - Wiring Devices: Elevation of exposed components.
1.03 SUBMITTALS
A. Product Data: Provide description and engineering data for each control system component.
Include sizing as requested. Provide data for each system component and software module.
B. Shop Drawings: Indicate complete operating data, system drawings, wiring diagrams, and written detailed operational description of sequences. Submit schedule of valves indicating
Devices for HVAC 23 09 13 - 2 size, flow, and pressure drop for each valve. For automatic dampers indicate arrangement, velocities, and static pressure drops for each system.
C. Manufacturer's Instructions: Provide for all manufactured components.
D. Operation and Maintenance Data: Include inspection period, cleaning methods, recommended cleaning materials, and calibration tolerances.
E. Project Record Documents: Record actual locations of control components, including panels, thermostats, and sensors. Accurately record actual location of control components, including panels, thermostats, and sensors.
1. Revise shop drawings to reflect actual installation and operating sequences.
1.04 QUALITY ASSURANCE
PART 2 PRODUCTS
2.01 EQUIPMENT - GENERAL
A. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories Inc., as suitable for the purpose specified and indicated.
2.02 CONTROL PANELS
A. Controllers in mechanical rooms shall be mounted in NEMA 1 enclosures.
B. Mount on walls at an approved location or provide a free standing rack. Panels shall be constructed of 16 gauge, furniture-quality steel, or extruded-aluminum alloy, totally enclosed, with hinged doors and keyed lock and with ANSI 61 gray polyester-powder painted finish, UL listed. Provide common keying for all panels.
C. Provide power supplies for control voltage power.
D. Dedicate 1 power supply to the DDC controller. Other devices shall be on a separate power supply, unless the power for the control device is derived from the controller terminations.
E. Power supplies for controllers shall be a transformer with a fuse or circuit breaker. Power supplies for other devices can be plain transformers.
F. All power supplies for 24V low voltage wiring shall be class 2 rated and less than 100VA. If low voltage devices require more amps, then provide multiple power supplies. If a single device requires more amps, then provide a dedicated power supply in a separate enclosure and run a separate, non-class 2 conduit to the device.
G. Surge transient protection shall be incorporated in design of system to protect electrical components in all DDC Controllers and operator’s workstations.
H. All devices in a panel shall be permanently mounted, including network switches, modems, media converters, etc.
I. Provide a pocket to hold documentation.
2.03 WIRE FRAME PROTECTIVE COVERS
A. Manufacturers:
1. Kele; Model ATK
2. Johnson Controls
3. Or an approved equal.
B. Provide wire frame covers to protect controls and instrumentation sensors where indicated on the drawings. Cover shall be suited for horizontal or vertical mounting.
C. Coordinate size of the wire frame cover with the sensor being protected.
2.04 2-WAY AND 3-WAY CHARACTERIZED CONTROL VALVES
A. Manufacturers:
1. Johnson Controls Inc.
2. Belimo Aircontrols (USA)
3. Substitutions: Not permitted.
Devices for HVAC 23 09 13 - 3
B. Nickel-plated forged brass body, stainless steel ball and blowout proof stem, with a dual EPDM O-ring packing design, fiberglass reinforced Teflon PTFE seats, female NPT end fittings and a stainless steel flow characterizing disc.
C. Equal percentage characteristics.
D. Flow-characterizing disc installed in the inlet of two-way and in the control port of three-way valves.
E. 5 psig maximum pressure drop at design flow rate.
F. Valve shall not be less than half of the corresponding line size.
G. Electronic Operators:
1. Manufacturers:
a. Johnson Controls Inc.
b. Belimo Aircontrols (USA)
c. Substitutions: Not permitted.
2. Valves shall spring return to normal position as indicated on freeze or temperature protection.
a. Hot water heating valves shall fail open.
b. Chilled water cooling valves shall fail closed.
3. Select operator for full shut off at maximum pump differential pressure.
4. Voltage: 24V
2.05 2-WAY PRESSURE INDEPENDENT CONTROL VALVES
A. Manufacturers:
1. Johnson Controls Inc.; Model VP140
2. Belimo USA; Model PICCV Series
3. Substitutions: Not permitted.
B. Control Valves: Factory fabricated of type, body material, and pressure class based on maximum pressure and temperature rating of the piping system, unless otherwise indicated.
C. The modulating control valves shall be pressure independent.
D. The control valves shall accurately control the flow from 0 to 100% full rated flow with an equal percentage flow characteristic. The flow shall not vary more than +/- 5% due to system pressure fluctuations across the valve with a minimum of 5 PSID across the valve.
E. Internal pressure regulator shall be located upstream of the ball valve to maintain a constant pressure differential while operating in the 5 to 50 psig pressure differential range.
1. P/T ports that are not integral to the valve shall be provided and installed in accordance with manufacturers recommendations or as indicated on the plans.
F. Construction: Forged brass body rated at no less than 400 PSI, stainless steel or chrome plated brass ball and stem, teflon PTFE ball seals, female NPT union ends, dual EPDM lubricated O-rings for stem seal and characterizing disc for equal flow percentage.
G. Combination of actuator and valve shall provide a minimum close-off pressure rating of 200
PSID.
H. All actuators shall be electronically programmed by use of a handheld programming device or external computer software. Programming using actuator mounted switches or multi-turn actuators are NOT acceptable.
I. The actuator shall be the same manufacturer as the valve, integrally mounted to the valve at the factory via a single screw on a four-way DIN mounting-base.
J. Electronic Operators:
1. Manufacturers:
a. Johnson Controls Inc.
b. Belimo Aircontrols (USA)
c. Substitutions: Not permitted.
Devices for HVAC 23 09 13 - 4
2. Valves shall spring return to normal position as indicated on freeze or temperature protection.
a. Hot water heating valves shall fail open.
b. Chilled water cooling valves shall fail closed.
3. Select operator for full shut off at maximum pump differential pressure.
4. Voltage: 24V
2.06 LOW LEAKAGE DAMPERS
A. Manufacturers:
1. Ruskin.
2. Greenheck.
3. Cesco.
4. Johnson Controls; Model VD-1330
5. Or an approved equal
B. Performance: Test in accordance with AMCA 500-D.
C. Class 1 low leakage dampers with with galvanized steel airfoil blades.
D. Frames: Galvanized steel, welded or riveted with corner reinforcement, minimum 16 gage,
0.0635 inch.
E. Blades: Extruded aluminum, maximum blade size 8 inches wide, 48 inches long, minimum 16 gage, 0.0635 inch, attached to minimum 1/2 inch shafts with set screws.
F. Blade Seals: Synthetic elastomeric mechanically attached, field replaceable.
G. Jamb Seals: Spring stainless steel.
H. Shaft Bearings: Graphite impregnated nylon sleeve, with thrust washers at bearings.
I. Linkage Bearings: Graphite impregnated nylon.
J. Leakage shall meet AMCA Class 1A criteria.
K. Temperature Limits: -40 to 200 degrees F.
2.07 DAMPER OPERATORS
A. General: Provide smooth proportional control with sufficient power for air velocities 20 percent greater than maximum design velocity and to provide tight seal against maximum system pressures. Provide spring return for two position control and for fail safe operation.
1. Provide sufficient number of operators to achieve unrestricted movement throughout damper range.
2. Provide one operator for maximum 36 sq ft damper section.
B. Coupling: V-bolt dual nut clamp with a V-shaped, toothed cradle; directly couple and mount to the valve bonnet stem; or ISO-style direct-coupled mounting pad.
C. Mounting: Actuators shall be capable of being mechanically and electrically paralleled to increase torque if required.
D. Overload protected electronically throughout rotation E. Electric Operators:
1. Manufacturers:
a. Belimo.
b. Johnson Controls;
c. Substitutions: Not permitted.
2. Spring return, adjustable stroke motor having oil immersed gear train, with auxiliary end switch.
2.08 RELAYS
A. Provide all control relays.
1. Unless indicated otherwise, relay coils shall be 24 volt and include an override switch.
Devices for HVAC 23 09 13 - 5
2. Relay contact ratings are to be silver-cadmium and shall meet or exceed NEMA B300: 10 amp current rating.
3. Control relays shall be plug-in type, UL listed, tube type base with 8-pin or 11-pin base and matching screw terminal socket and shall have a plastic dust cover and LED "energized" indicator.
4. Contact rating, configuration, and coil voltage shall be suitable for application.
B. Release time shall have a maximum of 20 MS and a temperature range of -30 degrees F to
140 degrees F.
C. Manufacturer:
1. Functional Devices Inc.
2. General Electric.
3. Square D.
4. Allen-Bradley.
5. Cutler Hammer.
6. Or an approved equal.
2.09 VOLTAGE TRANSFORMERS
A. Provide all transformers. Size to handle maximum rated connected load plus 10%.
B. AC voltage transformers shall be Class 2 , 120 volt primary, 24-volt secondary:
1. UL/CSA recognized, 600 Vac rated, and shall have built-in fuse protection or with integral non-interchangeable resettable current limiting device.
2. Transformers shall be suitable for ambient temperatures of 40°F-130°F and shall provide ±0.5% accuracy at 24 Vac and 5 VA load.
3. Windings (except for terminals) shall be completely enclosed with metal or plastic.
4. With mounting feet for panel mounting.
C. Manufacturer:
1. Functional Devices Inc.
2. Edwards.
3. Honeywell.
4. Or an approved equal.
2.10 CURRENT SENSORS AND SWITCHES
A. Provide all current transducers. Sensor range shall be no more than 150% of expected full load equipment amps.
1. AC current transmitters shall be self-powered, combination split-core current transformer type with built-in rectifier and high-gain servo amplifier with 4-20 mA two-wire output. Full-scale unit ranges shall be 10 A, 20 A, 50 A, 100 A, 150 A, and 200 A, with internal zero and span adjustment. Unit accuracy shall be ±1% full-scale at 500 ohm maximum burden.
2. Transmitter shall meet or exceed ANSI/ISA S50.1 requirements and shall be UL/CSA recognized.
3. Unit shall be split-core type for clamp-on installation on existing wiring.
4. Current-operated switches shall be self-powered, solid-state with adjustable trip current.
Select switches to match application current and DDC system output requirements.
5. Switch shall use a LED indicator light to illustrate the switch being open or closed.
B. Manufacturer:
1. Johnson Controls; Model CSD Series
2. Veris Industries Digital Sensor; Model H600 or H800.
3. Veris Industries Analog Sensor; Model H822.
4. Mamac Digital Sensor; Model CT.
5. Mamac Analog Sensor; Model CU.
6. Or an approved equal.
Devices for HVAC 23 09 13 - 6
2.11 AIR DIFFERENTIAL PRESSURE SWITCHES:
A. Diaphragm type air differential pressure transmitter with a NEMA-2 housing to protect against moisture and dirt, and an adjustable setpoint using an external potentiometers. The transmitter pressure range shall be suited for the application. These switches shall be utilized for filter status.
B. Repeatability: < 10% of setting.
C. Temperature Limits: -30 to 180°F, 5 to 95% RH.
D. Pressure Limits: 3.6 psig.
E. Contact Ratings: 28 VA, 24 VAC or 5A resistive, 125 VAC.
F. Switch Type: SPDT silver contacts.
G. Product:
1. Dwyer; Model Series 1900.
2. BAPI.
3. Automation Components Inc.
4. Setra.
5. Or an approved equal.
2.12 HVAC&R SENSORS
A. Networked Room Temperature For Staffed or Private Spaces
1. Approved network temperature only sensor shall be Johnson Controls Model
NSB8BTN240-0.
a. Previous model cross reference: NS-BTB7003-0.
2. Sensor shall feature BACnet® Master-Slave/Token-Passing (MS/TP) protocol communication.
3. Large backlit LCD fixed segment display or LCD full color graphical display provides real-time status of the environment with backlighting activated during user interaction.
4. Warmer/Cooler interface: this interface incorporates cap touch buttons with seven LED lights that represent the current setpoint status and allow simple temperature setpoint adjustment.
5. Temporary occupancy timed override command, which temporarily initiates a space temperature override when occupancy is different than the schedule.
6. Fahrenheit/Celsius (F/C) button to toggle the display temperature between °C and °F
a. Temperature measurement range 32°F to 104°F.
b. Temperature resolution ±0.5°F.
c. Tempertature accuracy ±1°F.
7. Communication to controllers shall be through screw terminal connections.
8. Networked space sensors shall be addressable.
B. Networked Room Temperature and CO2 sensors for Staffed or Private Spaces
1. Approved network temperature only sensor shall be Johnson Controls Model
NSB8BT240-0.
2. Sensor shall feature BACnet® Master-Slave/Token-Passing (MS/TP) protocol communication.
3. Large backlit LCD fixed segment display or LCD full color graphical display provides real-time status of the environment with backlighting activated during user interaction.
4. Warmer/Cooler interface: this interface incorporates cap touch buttons with seven LED lights that represent the current setpoint status and allow simple temperature setpoint adjustment.
5. CO2 range and accuracy:
a. CO2 sensor operation range 32°F to 122°F.
b. CO2 measurement range 0 ppm to 2000 ppm.
c. Accuracy ±30 ppm ±3% of CO2 reading at 77°F and 978 hPa
Devices for HVAC 23 09 13 - 7
d. Temperature dependence ±1.4 ppm/°F.
e. CO2 sensor lifespan 10 years under standard operating conditions.
6. Communication to controllers shall be through screw terminal connections.
7. Networked space sensors shall be addressable.
C. Networked Room Temperature and humidity sensors for Staffed or Private Spaces.
1. Approved network temperature only sensor shall be Johnson Controls Model
NSB8BHN240-0.
2. Sensor shall feature BACnet® Master-Slave/Token-Passing (MS/TP) protocol communication.
3. Large backlit LCD fixed segment display or LCD full color graphical display provides real-time status of the environment with backlighting activated during user interaction.
4. Warmer/Cooler interface: this interface incorporates cap touch buttons with seven LED lights that represent the current setpoint status and allow simple temperature setpoint adjustment.
5. Humidity range and accuracy:
a. Humidity sensor type Thin film capacitive sensor.
b. Humidity element accuracy: ±3% RH for 20% to 80% RH at 50°F to 95°F and ±6%
RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F.
6. Communication to controllers shall be through screw terminal connections.
7. Networked space sensors shall be addressable.
D. Networked Room Combination Temperature, CO2 and Humidity sensors for Staffed or Private Spaces.
1. Approved network temperature only sensor shall be Johnson Controls Model
NSB8BHC240-0.
2. Sensor shall feature BACnet® Master-Slave/Token-Passing (MS/TP) protocol communication.
3. Large backlit LCD fixed segment display or LCD full color graphical display provides real-time status of the environment with backlighting activated during user interaction.
4. Warmer/Cooler interface: this interface incorporates cap touch buttons with seven LED lights that represent the current setpoint status and allow simple temperature setpoint adjustment.
5. Communication to controllers shall be through screw terminal connections.
6. Networked space sensors shall be addressable.
E. Networked Room Temperature Sensors For Public, Entry and Storage Spaces
1. Approved network sensor shall be Johnson Controls Model TE-6800
2. Sensor shall feature BACnet® Master-Slave/Token-Passing (MS/TP) protocol communication.
3. Simple temperature setpoint adjustment to change the setpoint with the turn of a dial.
4. Temporary occupancy timed override command, which temporarily initiates a space temperature override when occupancy is different than the schedule.
5. Communication to controllers shall be through screw terminal connections.
6. Networked space sensors shall be addressable.
F. Temperature Sensors:
1. Use thermistor or RTD type temperature sensing elements with characteristics resistant to moisture, vibration, and other conditions consistent with the application without affecting accuracy and life expectancy.
2. Construct RTD of nickel or platinum with base resistance of 1000 ohms at 70 degrees F.
3. 100 ohm platinum RTD is acceptable if used with project DDC controllers.
4. Temperature Sensing Device: Compatible with project DDC controllers.
5. Performance Characteristics:
a. RTD:
1) Room Sensor Accuracy: Plus/minus 0.50 degrees F minimum.
Devices for HVAC 23 09 13 - 8
2) Duct Averaging Accuracy: Plus/minus 0.50 degrees F minimum.
3) Chilled Water Accuracy: Plus/minus 0.50 degrees F minimum.
4) All Other Accuracy: Plus/minus 0.75 degrees F minimum.
5) Range: Minus 40 degrees F through 220 degrees F minimum.
b. Thermistor:
1) Accuracy (All): Plus/minus 0.36 degrees F minimum.
2) Range: Minus 25 degrees F through 122 degrees F minimum.
3) Heat Dissipation Constant: 2.7 mW per degree C.
c. Temperature Transmitter:
1) Accuracy: 0.10 degree F minimum or plus/minus 0.20 percent of span.
2) Output: 4 to 20 mA.
d. Sensing Range:
1) Provide limited range sensors if required to sense the range expected for a respective point.
2) Use RTD type sensors for extended ranges beyond minus 30 to 230 degrees F.
3) Use temperature transmitters in conjunction with RTD's when RTD's are incompatible with DDC controller direct temperature input.
e. Outside Air Sensors: Watertight inlet fitting shielded from direct rays of the sun.
f. Temperature Averaging Elements:
1) Use on duct sensors for ductwork 10 sq ft or larger.
2) Use averaging elements where prone to stratification with sensor length 16 ft.
3) Provide for all mixed air and heating coil discharge sensors regardless of duct size.
g. Insertion Elements:
1) Use in ducts not affected by temperature stratification or smaller than 11 sq inches.
2) Provide dry type, insertion elements for liquids, installed in immersion wells, with minimum insertion length of 2.5 inches.
G. Humidity Sensors:
1. Duct Mounted Sensor: Voltage type encased in a die-cast metal, weather-proof housing.
a. Input Power, Voltage Type: Class 2; 12-30 VDC/24 VAC, 15mA max.
b. Input Power, mA Type: Class 2; Loop powered 12-30 VDC only, 30 mA max.
c. Output Voltage Type: 3-wire observed polarity.
d. Output mA Type: 2-wire, not polarity sensitive (clipped and capped).
e. Humidity:
1) HS Element: Digitally profiled thin-film capacitive.
2) Accuracy: Plus/minus five percent between 10 to 80 percent relative humidity at
77 degrees F, multi-point calibration, NIST traceable.
(a) Plus/minus 1 percent at 20 to 40 percent RH in mA output mode; (multi-point calibration, NIST traceable).
3) Scaling: 0 to 100 percent RH.
f. Temperature Effect:
1) Duct Mounted: Plus/minus 0.18 percent per degree F.
2) Outdoor Mounted: 4 to 20mA version: (0.0013 x percent RH x (Tdegree C -
25)).
g. Hysteresis: 1.5 percent typical.
h. Linearity: Included in accuracy specification.
i. Reset Rate: 24 hours.
j. Stability: Plus/minus 1 percent at 68 degrees F (20 degrees C) annually, for two years.
k. Temperature Monitoring:
1) Temperature Transmitter Output: Digital, 4 to 20mA (clipped and capped) or 0- 5V/0-10V output.
Devices for HVAC 23 09 13 - 9
l. Operating Environment:
1) Operating Humidity Range: 0 to 100 percent RH noncondensing.
2) Operating Temperature Range: Minus 40 to 122 degrees F.
H. Current Sensors:
1. Status Inputs for Fans: Adjustable trip current sensors as specified.
2. Status Inputs for Pumps: Adjustable trip current sensors as specified.
3. Status Inputs for Electric Motors: Current sensing relay with current transformers, adjustable and set to 175 percent of rated motor current.
I. Carbon Dioxide Sensors, Duct:
1. Manufacturers:
a. Veris Industries
b. Johnson Controls Inc..
c. Air Test Technologies.
d. Or an approved equal.
2. General: Provide nondispersive infrared (NDIR), diffusion sampling CO2 sensors with integral transducers and linear output.
a. Linear, CO2 Concentration Range Display: 0 to 2000 / 5000 ppm, programmable.
b. Accuracy: Plus/minus 30 ppm or plus/minus 2 percent of measured value, measured at NTP.
c. Repeatability: Plus/minus 20 ppm or plus/minus 2 percent of measured value.
d. Response Time: Less than 60 seconds for 90 percent step change.
e. Output:
f. Analog: 4-20 mA or 0-10 VDC.
g. Communication Protocol: BACnet MS/TP.
1) Connection: 2-wire, RS-485.
2) Data Rate: 9600 bps.
3) Parity: None.
3. Air Temperature: Range of 32 to 122 degrees F.
4. Relative Humidity: Range of 0 to 95 percent (noncondensing).
5. Power Input: Class 2; 12 to 30VDC or 24VAC 50/60 Hz; 100mA max.
6. Calibration Characteristics:
a. Automatically compensating algorithm for sensor drift due to sensor degradation.
b. Maximum Drift: 2 percent.
c. User calibratable with a minimum calibration interval of 5 years.
7. Construction:
a. Sensor Chamber: Noncorrosive material for neutral effect on carbon dioxide sample.
b. Provide duct mounted sensors with duct probe designed to protect sensing element from dust accumulation and mechanical damage.
c. Housing: High impact plastic.
2.13 EMERGENCY OPERATOR STATIONS
A. Manufacturers:
1. Kele; Model ST120 Series.
2. Pilla Electrical Products.
3. Or an approved equal.
B. General: Provide and install a highly visible emergency shutdown station. Station shall use a red mushroom style push/pull button with a clear protective hinged cover.
C. Operator shall be provided with a set of contacts for monitoring status by the Owner's Building Automation System.
D. Label:
1. Emergency shutdown switch for the boiler plant:
a. "EMERGENCY - BOILER SHUT-DOWN"
Devices for HVAC 23 09 13 - 10
2. Emergency HVAC shutdown switch:
a. "EMERGENCY - HVAC SHUT-DOWN"
E. Refer to Project Plans for exact locations.
2.14 BUILDING OCCUPANCY OVERRIDE BUTTON
A. Manufacturers:
1. IDEC; Model HW4L-M1F10QD-G-24V
2. Or an approved equal.
B. Momentary round push buttom operator with metal bezel designed for flush mounting. Button shall be backlit with an LED light which shall illuminate a colored green lens.
C. Operator: Round Flush D. Contact Arrangement: NO E. Lamp and Lamp Voltage: LED, 24V.
F. Lens Color: Green.
G. Provide a box mounted metal wall plate with 7/8 inch diameter hole for operator mounting.
2.15 THERMOSTATS
A. Room Thermostat Accessories:
1. Insulating Bases: For thermostats located on exterior walls.
2. Thermostat Guards: Metal mounted on separate base.
B. Immersion Thermostats:
1. Remote bulb or bimetallic rod and tube type, proportional action with adjustable setpoint and adjustable throttling range.
C. Airstream Thermostats:
1. Remote bulb or bimetallic rod and tube type, proportional action with adjustable setpoint in middle of range and adjustable throttling range.
2. Averaging service remote bulb element: 20 feet.
D. Electric High/Low Limit Duct Thermostats:
1. Snap acting, single pole, single throw, with automatic reset via software time delay reset switch that trips if temperature sensed across any 12 inches of bulb length is equal to or below setpoint,
2. Bulb length: Minimum 20 feet.
3. Provide one thermostat for every 20 sq ft of coil surface.
2.16 SENSORS WITH TRANSMITTERS
A. Building Static Pressure Transmitters:
1. One pipe, direct acting, double bell, scale range 0.01 to 6.0 in-wc positive or negative, and sensitivity of 0.0005 in-wc. Transmit electronic signal to receiver with matching scale range.
B. Pressure Transmitters:
1. One pipe direct acting for gas, liquid, or steam service, range suitable for system, proportional electronic output.
C. Water Pressure Transmitters (Liquid Differential Pressure Transmitters):
1. Provide a low differential pressure transducer designed for wet-to-wet differential pressure measurements of liquids or gases. A fast-response capacitance sensor and signal conditioned electronic circuitry provide a highly accurate, linear analog output proportional to pressure. Unit shall feature a no liquid fill diaphragm and NEMA 4 housing.
2. Output: 4 to 20 mA, two-wire.
3. Supply Voltage: 11 to 30 VDC.
4. Loop Resistance: 0 to 1000?.
5. Maximum Line Pressure: 250 psig.
Devices for HVAC 23 09 13 - 11
6. Maximum Overload Pressure: (High side) 1 to 5 psi: 20 FS, 10 to 25 psi: 10 FS, 50 psi: 5 FS; (Low side) 2-3 FS.
7. Zero and Span: Adjustable, non-interactive, ±1 mA.
8. Accuracy: ±0.25% FS.
9. Temperature Limits: Operating: 0 to 175°F.
10. Response Time: 30 to 50 msec.
11. Thermal Effects: (includes zero and span) ±0.02% FS/°F, 30 to 150°F.
12. Wetted Parts: 17-4 PH stainless steel, 300 Series stainless steel, Viton and Silicone O-rings and bleed screw seals.
13. Housing: Stainless steel/Aluminum NEMA 4.
14. Process Connection: 1/4 - 18 NPT(F).
15. Electrical Connection: Barrier strip terminal block with conduit enclosure and .875" diameter conduit opening.
16. Accessories:
a. Provide a 3-valve manifold assembly.
17. Product:
a. Dwyer; Model 645.
b. Setra; Model 230
c. Automation Components Inc.
d. Or an approved equal.
D. Temperature Transmitters:
1. One pipe, directly proportional output signal to measured variable, linearity within plus or minus 1/2 percent of range for 200 degrees F span and plus or minus 1 percent for 50 degrees F span, with 50 degrees F. temperature range, compensated bulb, averaging capillary, or rod and tube operation on 20 psig input pressure and 3 to 15 psig output.
E. Humidity Transmitters:
1. One pipe, directly proportioned output signal to measured variable, linearity within plus or minus 1 percent for 70 percent relative humidity span, capable of withstanding 95 percent relative humidity without loss of calibration.
2.17 CONDENSATE PAN FLOAT DETECTION SWITCHES
A. Manufacturers:
1. Diversitech; Model CC-1
2. Kele
3. RectorSeal
4. Or an approved equal.
B. Plenum rated float switch which is capable of clamping onto a formed plastic or galvanized steel condensate drain pan. Switch must clamp or set screw to the side of the pan, not through hole fasteners are allowed.
C. Operates contactor coils up to 1.25 amps.
D. Operates in series with a 24 VAC contactor load.
E. Trip water level shall be about 1 inch depth from bottom of probe.
F. Complete with 5 feet long wire leads and clamping screws.
2.18 FLOW SENSORS AND TRANSMITTERS
A. Turbine Flow Meters:
1. Manufacturers:
2. Dual Axial Insertion Type: Include ball valve and threadolet. Provide other hardware required to allow meter insertion and removal with system in service to avoid shutdown(s).
3. Accuracy for the Insertion Turbine Flow Meter: Plus/minus 0.5 percent of the rate at calibrated velocity, within plus/minus of the rate over a 10 to 1 turn down and within plus/minus 2 percent of the rate over a 50 to 1 turn down.
Devices for HVAC 23 09 13 - 12
4. Repeatability: Plus/minus 0.25 percent of reading.
5. The meter flow sensing element to operate over a range suitable for the installed location with a pressure loss limited to 1 percent of operating pressure at maximum flow rate.
6. Include dry contact outputs, 4 to 20 mA, 0 to 10 VDC.
7. Fabricate the turbine rotor assembly of Series 300 stainless steel and use Teflon seats.
B. Flow Switches:
1. Manufacturers:
a. Johnson Controls
b. Kele.
c. Or an approved equal.
2. Repetitive Accuracy: Plus/minus 10 percent of actual flow setting.
3. Switch Actuation: Adjustable over the operating range and sized for the application, such that the setpoint is between 25 and 75 percent of the full range.
4. Provide Form C snap-action contacts, rated for the application.
5. Furnish nonflexible paddle with magnetically actuated contacts, rated for service at a pressure greater than the installed conditions.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify existing conditions before starting work.
B. Verify that systems are ready to receive work.
C. Beginning of installation means installer accepts existing conditions.
D. Sequence work to ensure installation of components is complementary to installation of similar components in other systems.
E. Coordinate installation of system components with installation of mechanical systems equipment such as air handling units and air terminal units.
F. Ensure installation of components is complementary to installation of similar components.
3.02 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Check and verify location of space sensors with plans and room details before installation.
Locate 60 inches above floor. Align with lighting switches. Refer to Section 26 27 26.
C. Mount freeze protection thermostats using flanges and element holders.
D. Mount outdoor reset thermostats and outdoor sensors indoors, with sensing elements outdoors with sun shield.
E. Provide separable sockets for liquids and flanges for air bulb elements.
F. Provide valves with position indicators and with pilot positioners where sequenced with other controls.
G. Provide mixing dampers of opposed blade construction arranged to mix streams. Provide pilot positioners on mixed air damper motors.
H. Provide isolation (two position) dampers of parallel blade construction.
I. Install damper motors on outside of duct in warm areas. Do not install motors in locations at outdoor temperatures.
J. Mount control panels adjacent to associated equipment on vibration free walls or free standing angle iron supports. One cabinet may accommodate more than one system in same equipment room. Provide engraved plastic nameplates for instruments and controls inside cabinet and engraved plastic nameplates on cabinet face.
K. Install "hand/off/auto" selector switches to override automatic interlock controls when switch is in "hand" position.
Devices for HVAC 23 09 13 - 13
L. Provide conduit and electrical wiring in accordance with Section 26 05 83. Electrical material and installation shall be in accordance with appropriate requirements of .
END OF SECTION 23 09 13
Direct Digital Control System for
HVAC 23 09 23 - 1
SECTION 23 09 23
DIRECT DIGITAL CONTROL SYSTEM FOR HVAC
1.01 SECTION INCLUDES
A. Control equipment network and hardware.
B. Software
1.02 GENERAL
A. Provide all labor, materials, equipment, installation, service and training necessary for a complete, operational, and fully commissioned Building Automation System (BAS) system for the facilities identified on the contract drawings. The BACnet Building Controllers (B-BC) or supervisory controllers shall use TCP/IP communication at the network level of the architecture.
B. Provide all labor, materials, equipment, service, and training necessary to integrate the new BAS systems into the existing DOD MN DMA BAS network. The communications protocol used by the Minnesota Department of Military Affairs (MN DMA) is BACnet MS/TP.
C. Control systems shall be installed by experienced personnel regularly engaged in such installations and in the full employ of the manufacturer or in the employ of a franchised licensee of the manufacturer.
D. The controls contractor shall include minor items, which are obviously and reasonably necessary to complete the installation and usually included in similar work even though not specifically mentioned in the Contract Documents.
E. Temperature control panels and/or enclosures in equipment rooms shall be located at readily accessible walkup locations approved by the MN DMA Owner Representative.
F. Building Automation Systems Network Center
1. The Minnesota Department of Military Affairs Building Automation System Network Center
(BASNC) utilizes the Department of Defense (DOD) controlled network, which provides central monitoring of HVAC systems. Each new BAS shall be designed and standardized to work with the MN DMA existing BASNC.
2. The BASNC is presently located in Building 2-99 at Camp Ripley.
Building Automation Systems Administrator:
Wade Sandbakken Email: wade.j.sandbakken.nfg@mail.mil Direct: 320-616-3161 Cell: 320-412-6091
G. Department of Defense, Minnesota Department of Military Affairs (DOD MN DMA) Network
1. The DOD owns and operates a dedicated mixed-mode network (fiber and copper) for building-to-building and building-to-BAS Network Center communications. The DOD MN DMA Network is responsible for network design and network device maintenance. All systems using this network need to be approved by the DOD. The DOD MN DMA Network is a protected network with limited internet connections.
2. The controls contractor shall consider the DOD MN DMA network an existing military network system to which the specific building control system will be connected.
3. All supervisory devices must communicate using BACnet/IP and must support the objects and services listed in this specification. The MN DMA is committed to integration so that point status and automatic control can be channeled into a common protocol. The MN DMA has established BACnet as the common protocol.
H. MN DMA BAS Functions
1. The general categories of the automated capabilities of the MN DMA BAS system are:
a. Monitoring and Scheduling: Includes starting, stopping, observing, and reporting the operating status of the equipment, systems, and subsystems.
mailto:wade.j.sandbakken.nfg@mail.mil
HVAC 23 09 23 - 2
b. Intervention: The ability to automatically or manually shift to an alternate operating mode from a remote location when weather or other conditions warrant it.
c. Integration: The ability to coordinate the operation of several systems within a building, or several subsystems within a system, to ensure most efficient operation.
d. Management Information: The ability to provide cumulative operating data such as system run time, units of energy consumed, and preventive maintenance schedules.
2. All vendor BAS systems must be capable of functioning in the following modes:
a. All building systems points can be monitored and commanded, including equipment scheduling, by the BASNC during work hours
b. System alarms shall be displayed and acknowledged by the BASNC during work hours I. BACnet Integration:
1. Due to the complexity and size of the MN DMA BACnet system, integration requires stringent cooperation between the BASNC and the selected temperature Controls contractor. The MN DMA requires direct communication with the manufacturer's highest level of customer support, and may need to converse with the manufacturer's BACnet development team during project design, implementation, commissioning, and warranty phases.
2. The MN DMA is committed to integrating different manufacturer’s temperature control systems on a common LAN using a master workstation for all existing and future temperature control systems that may be installed. MN DMA BACnet required conformance is limited to B-Side or BACnet building controllers, only. The temperature Controls contractor must provide labor, software, materials, wiring, fiber coordination and expertise to install the BACnet Building Controller.
3. BACnet communication shall be via the DOD directly from the supervisory controllers without having to route or convert it from a proprietary source. When supervisory network controllers are used for core BACnet communications, the field level panels on its sub LAN, such as VAVs and unitary level controllers, can utilize BACnet MS/TP.
1.03 BACNET CONFORMANCE
A. BACnet conformance disputes that may arise in the temperature control contractors installed
BACnet Building Controller will be resolved by MN DMA working directly with the temperature Controls contractor’s factory. Cost of translation between non-English speaking testers, developers and customer support personal whether overseas or in the USA will be the responsibility of the controls contractor. On site device testing will be conducted using the BACnet Manufacturers Association / BACnet Testing Laboratories (BMA/BTL) Virtual Test Shell
3.5.0 (VTS) program. Virtual Test Shell (VTS) is an application for testing the BACnet functionality of various devices used in BAS. It is available at http://sourceforge.net/projects/vts/. Conformance issue fault will be agreed on and resolved using ANSI/ASHRAE Standards 135-2016 publication.
1.04 DEFINITION OF TERMS/ACRONYMS/ABBREVIATIONS
A. Additional definitions of terms or acronyms are included on the contract drawings and in other sections of this specification.
B. In the preparation of submittals and reports, the contractor shall use these definitions and abbreviations. Any terms or abbreviations used by the contractor in submittals and reports that have not been defined in this section shall be defined by the contractor in the first section of the submittal or report prior to their use.