EXHIBIT A - SCOPE OF SERVICES.pdf
PDF 547 KB Posted
- Solicitation number
- DR140153
- Issued by
- California
About this file
This is a Scope of Services document issued by the Los Angeles County Metropolitan Transportation Authority (LACMTA or Metro) for the procurement of ten (10) Uninterruptible Power Supply (UPS) systems to replace end-of-life backup power batteries at the G-Line (Metro Orange Line) Bus Station Cabinet Facility (BSCF). Each UPS system shall include a 10KVA capacity controller with maintenance bypass switch mode, smart UPS remote monitoring capability with SNMP protocol, mechanical dry contact alarm, 19-inch rack compatibility, four (4) scalable battery packs per station with battery replacement cartridge options, and an in-line surge protector. The systems must accept 240VAC/120VAC single-phase input with 240VAC/120VAC output consisting of two (2) L5-30R outlets and one (1) L14-40R outlet. The contractor is required to deliver comparable equipment to the specified APC Smart-UPS SRT models or approved equivalents, with APC controllers and battery packs matched together for compatibility. The contract specifies a two-phase delivery schedule: the first delivery of 5 UPS controllers, 24 battery packs, and 5 surge protectors within 90 calendar days from Notice to Proceed, and the final delivery of an additional 5 UPS controllers, 24 battery packs, and 5 surge protectors within 180 calendar days from Notice to Proceed.
The contractor shall deliver all products to 590 South Santa Fe Avenue, Los Angeles, CA 90013, between 8:00 AM and 3:00 PM Monday through Friday (PDT), excluding Metro-observed holidays. Submittals must include assembly of parts, wiring connections, schematic drawings (five hard copies and one electronic copy each), device descriptions and functions, system configuration procedures, and installation and operational/maintenance manuals. All equipment must comply with applicable Telecommunication industry standards, Underwriters Laboratory requirements, and NFPA 70. Controllers and batteries shall include standard manufacturer's warranty. The document references existing electrical schematics (Figures 1 and 2) showing the local utility source providing 240VAC input to the Metro electrical panel and subsequently to the BSCF UPS systems.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Scope of Services G Line Bus Station Uninterruptible Power Supply (UPS)
03/16/2026
Part 1 - General
1.1 Background
Los Angeles County Metropolitan Transportation Authority’s (LACMTA or “Metro”) seeks a qualified Contractor to furnish ten (10) Uninterruptible Power Supply (UPS) systems for its G-Line (Metro Orange Line) Bus Station Cabinet Facility (BSCF) backup power batteries that have reached end-of-life. Several BSCF Uninterruptible Power Supply (UPS) battery packs aren’t able to sustain power requirement during power outage. In addition, some UPS controllers are also defective and BSCFs are currently in “BYPASS” mode.
1.2 Scope of Work
The Contractor shall furnish, deliver, and provide technical documentation for ten (10) UPS systems.
Each system shall include:
• Equipment with a capacity of 10KVA.
• One (1) UPS Controller o UPS controller shall have a “Maintenance Bypass Switch” mode.
o UPS controller shall be smart UPS with a remote monitoring capability and
SNMP (Simple Network Management Protocol) for remote access.
o UPS controller shall be equipment with summary alarm mechanical “dry” contact.
o UPS controller shall fit on a 19-inch rack.
• Four (4) battery packs per BSCF station.
o Battery packs shall be scalable up to four packs with sufficient cable length interconnection.
o Battery packs shall have an option of “battery replacement Cartridges”.
• An in-line Surge Protector for each UPS.
• Local Utility Source is 240VAC (L1+L2+Grnd) supply the main Metro electrical panel to BSCF UPS.
o UPS input voltage shall be 240VAC/120VAC, 3 wires, single phase.
o UPS output voltage shall have 240VAC/120VAC.
o VAC outputs shall consist of two (2) L5-30R and one (1) L14-40R.
o UPS Controller and Battery packs shall be compatible manufacturer.
1.3 Products
The Contractor shall provide the following comparable power capacity, functionality, superior and reliable equipment.
Item Manufacturer Part # Description Quantity
APC
(or approved equivalent)
SRT10KRMXLT- 10KTF
Smart-UPS SRT 10KVA-RM w/ 208VAC/240VAC to
240VAC/120VAC10KVA.
Standard warranty
SRT192RMBP2
Smart-UPS SRT 192V 8 and 10KVA RM Battery pack.
Standard warranty
Line surge Protector 240V/120V
1.3 Products Note
Item 1 and 2 shall be matched together to remove incompatibility performance, functionality, charger, telemetry and other factors that may damage or shorten the UPS Controller life cycle.
Item 3 is the Line Surge Protector 240VAC/120VAC single phase outdoor and need not be compatible with the UPS Controller and Battery packs. Item 3-part number is not required.
1.4 UPS System Requirement:
The Contractor shall provide UPS systems minimum requirements:
A. Utility Source:
• Input Voltage: 240VAC (L1+L2+ Ground) single phase
B. Output Voltages:
• 120VAC: (2) x L5-30R
• 240V/120V: 2P single phase (1) x L14-40R.
C. Other Requirements
• Alarm contact relay 1 x (NO/NC)
• Network Management Connectivity
D. UPS Controller Display Interface
• Power On/OFF
• Battery status
• Controllable Outlet status icons
• Load Icon: Disable/Mute audible
• UPS Status Information
• Buttons: OK, ESC, UP/Down and OK
• Operation Mode ICON
• Rack mount controller
1.5 Local Utility UPS Existing Input Power Source BSCF Figures The Contractor shall reference the local utility UPS existing input power source BSCF Figures 1 and 2.
• The Local Utility Source provide 240VAC (L1+L2+Grnd) to main Metro electrical panel schedule (see Figure 1 and 2) and then to inside BSCF UPS.
Figure 1
Figure 2
Part 2 - Submittals / Deliverables The Contractor shall submit product data to include, at a minimum, the following:
A. Assembly of parts.
B. Wiring connections in five (5) hard copies and one (1) ecopy.
C. Schematic Drawing in five (5) hard copies and one (1) ecopy.
D. Brief description of devices and their functions and special features.
E. Procedure for configuration of the system.
F. Installation manual and recommend Operational and Maintenance Manual for their product.
Part 3 - References Standard The Contractor shall adhere to the following:
A. All applicable Telecommunication industry standards.
B. Underwriters Laboratory
C. NFPA 70
Part 4 - Period of Performance The Contractor shall deliver all products deliverables as follows:
A. First delivery is 5 UPS Controllers, 24 Battery Packs and 5 Surge Protectors within 90 calendar days or sooner from the Notice to Proceed.
B. Final delivery is 5 UPS Controllers, 24 Battery Packs and 5 Surge Protectors within 180 or sooner calendar days from the Notice to Proceed.
Warranty: Controllers and Batteries shall include standard manufacturer’s warranty.
Part 5 - Delivery Location:
The Contractor shall deliver all furnished product to:
• Address: 590 South Sante Fe Avenue, Los Angeles, CA 90013.
• Date and Time: Monday to Friday, 8:00 AM to 3:00 PM (PDT), except Metro observed holidays.
• Contact: Project Manager Tony Bernardino, (213) 819-1976, email:
bernardinoa@metro.net
END OF SCOPE OF SERVICES