Williamstown Drainage Repairs - Combined Bid Set
This combined bid set comprises engineering plans and specifications for drainage repairs at the West Virginia Army National Guard facility in Williamstown, Wood County, West Virginia. The project, identified as T80-11652 and issued for bid by The Thrasher Group engineering firm (ATTN: Nicole M. Price, PE), involves comprehensive storm water management improvements including the installation and replacement of HDPE drainage pipe ranging from 12 inches to 24 inches in diameter, totaling approximately 1,134 linear feet across four primary drainage areas. The work encompasses the installation of modified Type B drainage inlets with associated wingwalls, removal and replacement of existing concrete ditch lining with concrete channels incorporating water stops, re-establishment of grass swales and vegetated ditches, placement of reinforced concrete anchors where slope conditions exceed 18 percent, and backfilling of eroded channels with unclassified material. The project site is located at the West Virginia Army Reserve National Guard facility, with coordinates and elevation data provided for all drainage inlet structures. The plans are intended for full-color plotting on ANSI D (22" x 34") sheets and include detailed specifications for inlet construction, pipe bedding, outlet protection, erosion control measures, and all construction joint details. Engineering contact is Nicole M. Price, PE at The Thrasher Group, Bridgeport, WV office, (304) 624-4108.
The bid set includes detailed specifications requiring Class B concrete for all structural elements, new billet steel reinforcement conforming to project specifications, and geotextile separation materials for culvert protection and ditch applications. Contractor responsibilities include notification to the One-Call System at least 48 hours prior to excavation, temporary removal and daily reinstallation of fence fabric to maintain airfield security, field verification of inlet rim elevations, and field adjustment of culvert slope to minimize water outfall height not to exceed two feet. Concrete anchors must be installed on all storm sewer lines where slopes exceed 18 percent, with spacing requirements varying from 15 to 30 feet center-to-center depending on slope steepness. The project incorporates erosion and sediment control measures as required by the West Virginia Department of Environmental Protection for storm water permitting purposes. All wingwall and concrete work is compensated through unit price bidding, with reinforcing steel costs included in the concrete bid price. The document was issued for permits and indicates the project is authorized by the WV Army National Guard with project management contact Jim Skaggs at (304) 719-8745.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_CRFQ_0603_ADJ2700000020_1_WV_CRFQ_FORM.PDF | ||
| CRFQ ADJ27_20 Solictitation Documents.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLAN REPRODUCTION WARNING
THESE PLANS ARE INTENDED TO BE PLOTTED ON ANSI D (22" X 34") SHEETS. FOR REDUCTIONS, REFER TO
GRAPHIC SCALE. THESE PLANS HAVE BEEN CREATED FOR FULL COLOR PLOTTING. ANY SET OF THESE PLANS THAT IS NOT PLOTTED IN FULL COLOR SHALL NOT BE CONSIDERED ADEQUATE FOR CONSTRUCTION PURPOSES.
**WARNING**: INFORMATION MAY BE LOST IN COPYING AND/OR GRAY SCALE PLOTTING.
ENGINEER
THE THRASHER GROUP
ATTN: NICOLE M. PRICE, PE
(304) 423-5991
THE INFORMATION CONTAINED HEREIN IS THE SOLE PROPERTY OF THE THRASHER GROUP INC.
REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR IN PART, FOR ANY REASON WITHOUT PRIOR WRITTEN
PERMISSION, IS STRICTLY PROHIBITED.
PHONE: (304) 561-6317
1703 COONSKIN DR.
CHARLESTON, WV 25311-1085
CLIENT'S CONTACT
WV ARMY NATIONAL GUARD
ATTN: JIM SKAGGS
(304)-719-8745
CONTACTS
WEST VIRGINIA ARMY
RESERVE NATIONAL GUARD
FOR
WILLIAMSTOWN
T80-11652
WOOD COUNTY, WEST VIRGINIA
AUGUST 2026
APPROXIMATE SITE LOCATION
WEST VIRGINIA ARMY NATIONAL GUARD
APPROXIMATE SITE LOCATION
THIS PLAN SET DEPICTS THE NECESSARY INFORMATION FOR EROSION AND SEDIMENT CONTROL MEASURES AS
REQUIRED BY THE WVDEP FOR STORM WATER PERMITTING PURPOSES.
ISSUED FOR PERMITS BY:
NICOLE M. PRICE, WV P.E. #21372
DATE:
ISSUED FOR BID BY:DATE:
ISSUED FOR CONSTRUCTION BY:DATE:
BRIDGEPORT, WV OFFICE
600 WHITE OAKS BLVD.
BRIDGEPORT, WV 26330
(304) 624-4108
PO BOX 940
CONTRACTOR SHALL NOTIFY THE ONE-CALL SYSTEM OF THE INTENDED EXCAVATION OR DEMOLITION NOT LESS THAN FORTY-EIGHT (48) HOURS, EXCLUDING SATURDAYS, SUNDAYS AND LEGAL FEDERAL OR STATE HOLIDAYS, NOR MORE THAN TEN (10) WORK DAYS PRIOR TO THE BEGINNING OF SUCH WORK.
CALL811.COM/811-IN-YOUR-STATE
SHEET INDEX
SHEET DESCRIPTION
C1.00 GENERAL NOTES
C2.00 OVERALL SITE PLAN
C2.01-C2.04 SITE PLAN
C3.00-C3.02 DETAILS
g
Source: Esri, Vantor, GeoEye, Earthstar Geographics, CNES/Airbus DS, USDA, USGS, AeroGRID, IGN, and the GIS User Community Powered by Esri
A g g g g g g g g g g g g g g g g g g g g g g g g g g g g g
A g g g g g g g g g g g g
P (304) 624-4108
600 WHITE OAKS BLVD,
P.O. BOX 940
BRIDGEPORT, WV 26330
www.thethrashergroup.com
F (304) 624-7831
T80-11652
W
IL
L
IA
M S
T O
W N
W
V A
N G
W O
O D
C O
U N
T Y
, W E
S T
V
IR
IG
N
IA
W E
S T
V
IR
IG
N
IA
A
R M
Y N
A T
IO
N
A L
G U
A R
D
D R
A
IN
A G
E R
E P
A
IR
S
SEE SHEET C2.04
SEE SHEET C2.01
SEE SHEET C2.02
S E
E S
H E
E T C
2.03
OVERALL SITE PLAN
g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g
830830
835835
110 LF OF 12" HDPE PIPE
73 LF OF 18" HDPE PIPE
12 LF OF 12" HDPE PIPE
RE-ESTABLISH
MOWABLE GRASS
SWALE ON
SURFACE (TYP)
14 LF OF 24" HDPE PIPE
8 LF OF 24" HDPE
PIPE
24 LF OF 24" HDPE PIPE
12 LF OF 24" HDPE PIPE
DI 1-1
N: 316334.9952 E: 1419392.0045
RIM ELEV: 839.77
INV OUT (12") 837.27'
DI 1-2
N: 316279.6443
E: 1419489.9415
RIM ELEV: 839.13
INV IN (12") 836.17'
INV OUT (18") 835.57'
DI 1-4
N: 316248.2588
E: 1419568.4114
RIM ELEV: 838.94
INV OUT (12") 836.44'
DI 1-3 (MODIFIED TYPE B)
N: 316239.2741
E: 1419555.8348
RIM ELEV: 838.15
INV IN (18") 834.84
INV IN (12") 834.84
INV OUT (24") 834.34'
CONNECT EXISTING
CMP PIPE INTO INLET
DI 1-3 (MODIFIED TYPE B)
N: 316230.2041
E: 1419544.0621
RIM ELEV: 835.30
INV IN (24") 831.80'
INV OUT (24") 831.70'
DI 1-6 (MODIFIED TYPE B)
N: 316220.0919
E: 1419539.1179
RIM ELEV: 832.73
INV IN (24") 831.62'
INV OUT (24") 831.52'
DI 1-7 (MODIFIED TYPE B)
N: 316194.3261
E: 1419530.3033
RIM ELEV: 826.59
INV IN (24") 823.09'
INV OUT (24") 822.99'
DI 1-8 (MODIFIED TYPE B)
N: 316181.8827 E: 1419534.9756
RIM ELEV: 819.35
INV IN (24") 815.85'
INV OUT (24" - EXISTING)
EX. STEEL PLATE TO BE REMOVED
P (304) 624-4108
600 WHITE OAKS BLVD,
P.O. BOX 940
BRIDGEPORT, WV 26330
www.thethrashergroup.com
F (304) 624-7831
T80-11652
W
IL
L
IA
M S
T O
W N
W
V A
N G
W O
O D
C O
U N
T Y
, W E
S T
V
IR
IG
N
IA
W E
S T
V
IR
IG
N
IA
A
R M
Y N
A T
IO
N
A L
G U
A R
D
D R
A
IN
A G
E R
E P
A
IR
S
REMOVE EXISTING WINGWALL AND PIPE
FENCE FABRIC CAN BE REMOVED BUT WILL
NEED TO BE REINSTALLED AT THE END OF
EACH WORKING DAY TO KEEP AIRFIELD
SECURE.
SITE PLAN
CONTRACTOR TO USE UNCLASSIFIED
BACKFILL MATERIAL TO BACKFILL ERODED
CHANNEL AS SHOWN ON PLANS.
g g g g g g g g g g g g g g g g g g g
41 LF OF 12"
HDPE PIPE
35 LF OF 12"
HDPE PIPE
RE-ESTABLISH GRASS SWALE ON SURFACE TO
BE INCIDENTAL TO THE LINEAR FOOT OF
PIPE(TYP)
DI 2-1
N: 316302.4959
E: 1419137.9335
RIM ELEV: 842.27' (FIELD VERIFY)
INV IN (8") 840.58'
INV OUT (12") 840.25'
DI 2-2
N: 316274.3775 E: 1419173.0098
RIM ELEV: 841.04
INV IN (12") 838.54'
INV OUT (12") 838.44'
4 LF OF 12"
HDPE PIPE
DI 2-3
N: 316249.6715 E: 1419201.9504
RIM ELEV: 839.85
INV IN (12") 837.35'
INV OUT (12") 837.25'
PROPOSED WINGWALL
P (304) 624-4108
600 WHITE OAKS BLVD,
P.O. BOX 940
BRIDGEPORT, WV 26330
www.thethrashergroup.com
F (304) 624-7831
T80-11652
W
IL
L
IA
M S
T O
W N
W
V A
N G
W O
O D
C O
U N
T Y
, W E
S T
V
IR
IG
N
IA
W E
S T
V
IR
IG
N
IA
A
R M
Y N
A T
IO
N
A L
G U
A R
D
D R
A
IN
A G
E R
E P
A
IR
S
SITE PLAN
RE-ESTABLISH MOWABLE SWALE
g g g g g g g g g g g g g g g g g g g g g g g g g ggggggg g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g g
102 LF OF 18"
HDPE PIPE
154 LF OF 18"
HDPE PIPE
94 LF OF 18"
HDPE PIPE
64 LF OF 24"
HDPE PIPE
TIE INTO EXISTING INLET
CLEAN DEBRIS FROM
INLET
RE-ESTABLISH 273 LF EXISTING DITCH
LINE. REMOVE EXISTING CONCRETE DITCH
LINING AND RESHAPE AND REPLACE WITH
A CONCRETE CHANNEL FROM INLET
BEGIN CONCRETE
DITCH LINING AND
RESHAPE AND
REPLACE WITH A
CONCRETE
CHANNEL WITH
WATER STOP (SEE
DETAIL)
RE-ESTABLISH
GRASS SWALE
RE-ESTABLISH
GRASS SWALE
EXISTING DITCH
TO REMAIN
DI 3-1
N: 316918.0627
E: 1419233.9662
RIM ELEV: 843.83
INV OUT (18") 841.33'
DI 3-2 (MOD. TYPE B)
N: 316825.3608 E: 1419185.4404
RIM ELEV: 842.82
INV IN (18") 837.10'
INV IN (18") 837.20'
INV OUT (24") 837.00'
DI 3-3
N: 316687.6572 E: 1419110.6061
RIM ELEV: 841.24
INV IN (18") 838.74'
INV OUT (18") 838.64'
DI 3-4
N: 316604.4066 E: 1419064.0637
RIM ELEV: 840.67
INV OUT (18") 838.17'
RE-ESTABLISH
DITCH LINE
INSTALL
CONCRETE
ANCHOR
P (304) 624-4108
600 WHITE OAKS BLVD,
P.O. BOX 940
BRIDGEPORT, WV 26330
www.thethrashergroup.com
F (304) 624-7831
T80-11652
W
IL
L
IA
M S
T O
W N
W
V A
N G
W O
O D
C O
U N
T Y
, W E
S T
V
IR
IG
N
IA
W E
S T
V
IR
IG
N
IA
A
R M
Y N
A T
IO
N
A L
G U
A R
D
D R
A
IN
A G
E R
E P
A
IR
S
SITE PLAN
EXISTING GROUTED CHANNEL TO
BE REMOVED AND RE-INSTALLED.
AREAS ERODED AROUND FENCE
POSTS TO BE REPAIRED.
A g g g g g g g g g g g g g g g g g g g g g g
A
PROPOSED WINGWALL
63 LF OF 18"
HDPE PIPE
64 LF OF 18"
HDPE PIPE
RE-ESTABLISH
GRASS
SWALE ON
SURFACE
(TYP)
DI 4-2
N: 316953.2641
E: 1419555.5332
RIM ELEV: 843.85
INV IN (18") 840.36'
INV OUT (18") 840.26'
DI 4-3
N: 316921.2669
E: 1419612.3507
RIM ELEV: 843.19
INV IN (18") 839.63'
INV OUT (18") 839.53'
DI 4-1
N: 316986.5952
E: 1419495.6649
RIM ELEV: 844.50'
INV IN (12") 841.51'
INV OUT (18") 841.00'
14 LF OF 18"
HDPE PIPE
FENCE FABRIC TO BE REMOVED AND
REINSTALLED. EXISTING PLATE TO
BE REMOVED ONCE AREA IS
BACKFILLED.
P (304) 624-4108
600 WHITE OAKS BLVD,
P.O. BOX 940
BRIDGEPORT, WV 26330
www.thethrashergroup.com
F (304) 624-7831
T80-11652
W
IL
L
IA
M S
T O
W N
W
V A
N G
W O
O D
C O
U N
T Y
, W E
S T
V
IR
IG
N
IA
W E
S T
V
IR
IG
N
IA
A
R M
Y N
A T
IO
N
A L
G U
A R
D
D R
A
IN
A G
E R
E P
A
IR
S
EXISTING GROUND
PROPOSED GRADE
3.0' 10:1 10:1
DITCH TYPICAL SECTION A-A
NOT TO SCALE
PROPOSED STORM PIPE
SITE PLAN
NOTE: SWALE CONSTRUCTION TO BE INCIDENTAL TO THE CUBIC YARD PRICE
FOR UNCLASSIFIED BORROW EXCAVATION
TYPE B INLET
NOT TO SCALE
WITH SHALLOW FRAME
3" MIN.
2" M
IN
2" M
IN
. 3" MIN.
3" MIN.
2" MIN.
2" MIN.
CONSTRUCTION JOINT DETAILS
1. UNLESS OTHERWISE SPECIFIED ON THE PLANS, TYPE B INLETS
ARE TO BE CONSTRUCTED IN THE SHAPE SHOWN.
2. CONSTRUCTION MAY BE CAST-IN-PLACE, PRECAST IN ONE OR
MORE MULTIPLE SECTIONS, OR ANY COMBINATION OF
CAST-IN-PLACE AND PRECAST.
3. OPTIONAL CONSTRUCTION JOINTS LABELED "CJ" MAY BE
ROUGHENED CONCRETE, KEYED OR DOWELED AS PER THE
TYPICAL DETAILS SHOWN HEREIN, OR AS APPROVED BY THE
ENGINEER. NON SHRINK GROUT MEETING THE REQUIREMENTS
OF SUBSECTION 715.5 OF THE SPECIFICATIONS MAY BE USED TO
A DEPTH OF 1/2" FOR LEVELING BETWEEN PRECAST SECTIONS.
THICKER DEPTHS WILL BE ALLOWED AS PER THE
MANUFACTURER'S RECOMMENDATIONS.
4. THE FINAL INSTALLED TOP SURFACE OF INLET AND GRATE SHALL
BE FLUSH WITH ADJACENT FINISHED SURFACES SUCH AS
PAVEMENT, GUTTERS, CURBS, AND SIDEWALKS. TOP OF GRATE
ELEVATION, IF SHOWN ON THE PLANS, IS FOR INFORMATION
ONLY.
5. REBARS ARE TO BE INSTALLED AT THE QUARTER POINTS TO
CONNECT CURB TO INLET. REBARS ARE NOT REQUIRED IF CURB
IS POURED MONOLITHICALLY WITH THE INLET OR IF TYPE V OR VI
MEDIAN IS SPECIFIED ON THE PLANS.
6. THE CONTRACTOR MAY, AT HIS OPTION, OMIT USE OF THE
SHALLOW FRAME BY FORMING A LEDGE IN THE CONCRETE.
7. SPECIAL CARE SHALL BE EXERCISED IN FORMING THE 2" WIDE
CONCRETE LEDGE TO PROVIDE A SMOOTH, EVEN SURFACE FOR
SUPPORTING THE GRATE IF A FRAME IS NOT USED. NO
PROJECTIONS SHALL EXIST ON THE GRATE AND THE GRATE
SHALL SEAT ON THE LEDGE WITHOUT ROCKING.
8. FIBRE FORM SHALL BE REMOVED PRIOR TO COMPLETION OF THE
PROJECT.
9. PC (MINIMUM PIPE COVER) SHALL BE 12" BELOW INLET TOP FOR
PIPES PLACED UNDER SIDEWALK OR GRASSED AREA OR 24"
BELOW INLET TOP FOR PIPES PLACED UNDER PAVEMENT OR
SHOULDER.
10.CURB, IF SPECIFIED, MAY BE EITHER CONCRETE PLACED ON THE
INLET BACKWALL AS DETAILED HEREIN OR AN APPROVED CURB
BOX AS MANUFACTURED WITH THE GRATE AND FRAME.
DIMENSIONS OF THE CURB BOX SHOULD REASONABLY CONFORM
TO THE STANDARD CURB AS SPECIFIED IN THE PLANS. THE CURB
WILL BE PAID FOR PER SECTION 610, IN EITHER CASE.
11.THIS INLET SHALL NOT BE PLACED IN A PEDESTRIAN CROSS
WALK.
12.THE MINIMUM DISTANCE FROM THE TOP OF ANY PIPE OPENING
TO ANY CONSTRUCTION JOINT ABOVE THE OPENING SHALL BE
FOUR (4) INCHES.
13.THE NUMBER AND LOCATION OF PIPE OPENINGS SHALL BE AS
SHOWN IN THE PLANS. THE CONTRACTOR AT NO ADDITIONAL
COST, SHALL BE RESPONSIBLE FOR ANY TEMPORARY BRACING
REQUIRED TO TRANSPORT PRECAST INLET SECTIONS DUE TO
MULTIPLE OPENINGS.
NOTES:
PLAN
SECTION A-A
1. SQUARE INLET STRUCTURE SHOWN. SQUARE OR CIRCULAR
STYLE MAY BE USED.
NOTE:
1. SHALLOW FRAMES ARE ONLY TO BE USED IN THE LAWN AREAS.
NOTE:
FACE OF CURB
WHEN SPECIFIED
1/2" EXPANSION JOINT
MATERIAL WHEN
ABUTTING CONCRETE
1/2" REBAR (SEE
NOTES)
1/2" REBARS AT 8" C/C
AROUND PERIMETER
MAXIMUM DEPTH OF REQUIRED
OUTSIDE NEAT FORMING:
10" ADJACENT TO CONCRETE
3" ADJACENT TO ASPHALT
CJ
CJ
H E
IG
H
T A
S S
H O
W N
CJ
PEDESTRIAN GRATE
AA
2" T
Y P
1' -8
8"
M
IN
8"
M
IN
1'-8"2" 2"
8" MIN. 8" MIN.
8" M
IN
6" 6"
1' -8
DEEP FRAME FOR 2' X 2' INLET GRADE (GRATE
SHALL HAVE AN H-20 LOAD RATING UNLESS
OTHERWISE SPECIFIED)
CJ
3" X 2 1/2" X 3/8" ANGLE
6.6 Lb./L.F.
2 3/4" X 7/16"
STRAP (TYP.)
3" X 2 1/2" X 3/8" ANGLE 6.6
Lb./L.F.
3/8" FILLET WELD
1. OPTIONAL CONSTRUCTION JOINTS LABELED "CJ" MAY BE KEYED
OR DOWELED AS PER THE TYPICAL DETAILS SHOWN HEREIN OR
AS APPROVED BY THE ENGINEER.
NOTES:
SECTION A-A
(2' X 2' DEEP FRAME SHOWN)
8"
MIN.
A
8"
MIN.
8"
MIN.
A
8"
MIN.
8"
MIN.
A
A
A
B
PLAN
B
B
MODIFIED TYPE G INLET WITH
2' X 2' INLET GRATE
NOT TO SCALE
3"
MIN. 2"
MIN.
2"
MIN.
3"
MIN.
3"
MIN. 2"
MIN.
2"
MIN.
CONSTRUCTION JOINT DETAILS
DIMENSIONS
PIPE
SIZE
A B C D H
(min)
18"
21"
24"
27"
30"
33"
36"
42"
48"
2'-8"
2'-8"
2'-8"
3'-0"
3'-6"
3'-9"
4'-0"
4'-6"
5'-0"
3'-2"
3'-2"
3'-2"
3'-6"
4'-0"
4'-3"
4'-6"
5'-0"
5'-6"
2'-7 3/4"
2'-7 3/4"
2'-7 3/4"
3'-1 3/4" 2'-0"
3'-1 3/4"
3'-1 3/4"
2'-3"
2'-6"
2'-11 3/4" 3'-5 3/4" 2'-9"
3'-5 3/4" 3'-11 3/4" 3'-0"
3'-8 3/4" 4'-2 3/4" 3'-3"
3'-11 3/4" 4'-5 3/4" 3'-6"
4'-5 3/4" 4'-11 3/4" 4'-0"
4'-11 3/4" 5'-5 3/4" 4'-6"
8"
MIN.
CONCRETE TOP SIZE SHALL BE ADJUSTED BASED
ON PIPE AND BOX SIZE IN THE TABLE BELOW. THE
CONCRETE TOP SHALL BE DESIGNED BY THE BOX
MANUFACTURER TO MEET HL-20 LOAD
REQUIREMENTS8" MIN.
2.0'
PEDESTRIAN GRATE
CJ
P (304) 624-4108
600 WHITE OAKS BLVD,
P.O. BOX 940
BRIDGEPORT, WV 26330
www.thethrashergroup.com
F (304) 624-7831
T80-11652
W
IL
L
IA
M S
T O
W N
W
V A
N G
W O
O D
C O
U N
T Y
, W E
S T
V
IR
IG
N
IA
W E
S T
V
IR
IG
N
IA
A
R M
Y N
A T
IO
N
A L
G U
A R
D
D R
A
IN
A G
E R
E P
A
IR
S
DETAILS
v
INSIDE
DIA.
OF
PIPE
DIMENSIONS
A B C D E F G H
SLOPE
OF
FILL
REINFORCEMENT QUANTITIES
MARK SIZE
NO.
OF
BARS
LENGTH
a b TOTAL
TYPE
CONC.
(RCP)
C.Y.
CONC.
(CMP
or SPP) C.Y.
STEEL
LBS.
12"/15" 2:1 0'-10" 1'-11" 2'-0" 6'-7 1/2" 3'-3 1/4" #4 2 1'-10" 3'-2 1/2" 8'-3" BENT 0.61 0.62 41.2h1
#4 1 6'-1" ST.h2
#4 13 3'-0" BENTv t2'-2"
*2'-0" *0'-8" *0'-5 3/8" t0'-6" t0'-2 1/2"
BEVEL: DEPTH = 3/4" - LENGTH = 1"
18" 2:1 1'-1" 2'-2" 2'-3" 6'-10 1/2" 3'-3 1/4" #4 2 2'-1" 3'-2 1/2" 8'-6" BENT 0.67 0.68 41.8h1
#4 1 6'-4" ST.h2
#4 13 3'-0" BENT
t2'-2"
*2'-0" *0'-8" *0'-5 3/8" t0'-6" t0'-2 1/2"
BEVEL: DEPTH = 3/4" - LENGTH = 1 1/4"
24" 2:1 1'-4" 2'-9" 2'-11" 8'-10 1/2" 4'-2 1/2" #4 2 2'-9" 4'-1 1/2" 11'-0" BENT 1.01 1.02 52.4h1
#4 1 8'-4" ST.h2
#4 16 3'-0" BENTv t2'-10"
*2'-8" *0'-8" *0'-5 3/8" t0'-6" t0'-2 1/2"
BEVEL: DEPTH = 1" - LENGTH = 1 1/2"
30" 2:1 1'-7" 3'-3" 3'-5" 10'-4 1/2" 4'-11" #4 2 3'-3" 4'-10 1/2" 13'-0" BENT 1.32 1.37 58.1h1
#4 1 9'-10" ST.h2
#4 17 3'-0" BENTv t3'-4"
*3'-1" *0'-9" *0'-6 3/4" t0'-6" t0'-2 1/2"
BEVEL: DEPTH = 1 1/4" - LENGTH = 2"
36" 2:1 1'-10" 3'-10" 4'-1" 12'-4 1/2" 5'-10 1/2" #4 2 3'-11" 5'-9 1/2" 15'-6" BENT 1.79 1.86 70.8h1
#4 1 11'-10" ST.h2
#4 21 3'-0" BENTv t4'-0"
*3'-9" *0'-9" *0'-6 3/4" t0'-6" t0'-2 1/2"
BEVEL: DEPTH = 1 1/2" - LENGTH = 2 1/4"
* DIMENSIONS FOR INLET WINGWALLS ON CORRUGATED METAL PIPE (TO ACCOMMODATE THE BEVEL).
t DIMENSIONS FOR INLET WINGWALLS ON CONCRETE PIPE AND ALL OUTLET WINGWALLS.
A
A
D I.D
H
F
3" #4h1 BAR
A G
1/
4"
6"
E
#4v BARS @ 18" C-C
#4h2 BAR
#4 v B
ARS @
2" C
-C
CL
1/
4"
6"
PLAN VIEW
ELEVATION
CL
CL
SYMMETRICAL
ABOUT
#4v BARS @ 18" C-C
#4v BARS @ 12" C-C
#4h1 BAR
#4h2 BAR
FOR CONCRETE PIPE ONLY
(SEE BACKWALL DETAIL)
B
C 2'
-0
B E
V E
L (3
A R
C
IN
S
ID
E
D
IA
. O F
P
IP
E
CONSTRUCTION DETAIL - SKEWED PIPE
TOE OF FILLTOE OF FILL
SECTION A-A
C
1' -6
B
6"
2' -0
6" #4v BARS @ 18" C-C
SEE BACKWALL
DETAIL (FOR
CONCRETE PIPE)
#4h2 BAR
SEE WATERSTOP DETAIL
#4h1 BAR
#4h1 BAR
SEE BEVEL DETAIL
EMBANKMENT SLOPE
#4v BARS @ 12" C-C
6"
G A
3"
4"
DETAIL OF BENT BARS
a b b
#4v BARS
#4h1 BARS
BACKWALL DETAIL
(FOR CONCRETE PIPE)
6" MIN.
UNDER PIPE
12"
G
I.D
6" MIN.
0.063 x I.D.
= BEVEL
LENGTH
0.042 x I.D. =
BEVEL
DEPTH
BEVEL DETAIL
WATERSTOP DETAIL
CONCRETE
GUTTER
WINGWALL
WATERSTOP
3"
1. ALL CONCRETE SHALL BE CLASS B CONCRETE.
2. REINFORCING STEEL SHALL BE NEW BILLET STEEL AND SHALL
CONFORM TO THE REQUIREMENTS OF 709.1 OF THE
SPECIFICATIONS.
3. THE COVERING FOR REINFORCING STEEL SHALL BE 2"
MEASURED FROM THE SURFACE OF THE CONCRETE TO THE
FACE OF THE BAR, UNLESS OTHERWISE NOTED ON THE PLANS.
REINFORCEMENT IN MEMBERS WHERE CONCRETE IS DEPOSITED
ON THE GROUND SHALL HAVE 3" OF CONCRETE FROM THE FACE
OF THE BAR TO THE GROUND CONTACT SURFACE.
4. ALL EXPOSED EDGES SHALL HAVE A 3/4" x 45° CHAMFER.
CHAMFER ON VERTICAL EDGES SHALL BE CONTINUED A MINIMUM
OF ONE FOOT BELOW FINISHED GROUND LINE.
5. WHEN WINGWALLS ARE PLACED ON THE INLET END OF
CORRUGATED METAL OR STRUCTURAL PLATE PIPE, A BEVEL
SHALL BE USED AT THE INLET OPENING. THE END OF THE PIPE
SHALL BE SET IN FROM THE FACE OF THE WALL AS SHOWN ON
THE "BEVEL DETAIL", AND THE BEVEL CONSTRUCTED FROM THE
END OF THE PIPE TO THE FACE OF THE WALL.
6. WHEN WINGWALLS ARE PLACED ON THE INLET END OF
CONCRETE PIPE, THE "BELL" OR "GROOVE" OF THE PIPE SHALL
BE PLACED IN THE WALL, AND THE INSIDE OF THE "BELL" OR
"GROOVE" SHALL BE FILLED WITH CONCRETE UP TO THE FLOW
LINE.
7. BEVELS ARE NOT REQUIRED ON OUTLET WINGWALLS OR ON
INLET WINGWALLS FOR CONCRETE PIPE.
8. KEYED OR DOWELED TYPE CONSTRUCTION JOINTS,
ACCEPTABLE TO THE ENGINEER, MAY BE USED DURING
CONSTRUCTION.
9. IF EMBANKMENT SLOPE ABOVE WINGWALLS IS FLATTER THAN
2:1, PROVIDE WINGS FOR 2:1 SLOPE AND WARP EMBANKMENT TO
2:1 SLOP AT WINGWALL.
10.THE PAY QUANTITY FOR WINGWALLS, CONSTRUCTED IN
ACCORDANCE WITH THE DETAILS HEREIN, WILL BE THE CUBIC
YARDS OF CLASS B CONCRETE SPECIFIED ON THIS SHEET. COST
OF ALL REINFORCING STEEL SHALL BE INCLUDED IN THE UNIT
PRICE BID FOR CLASS B CONCRETE.
11.WATERSTOP MEETING THE REQUIREMENTS OF 708.10 SHALL BE
PLACED AS SHOWN WHEN CONCRETE GUTTER IS TO ABUT THE
WINGWALL.
NOTES:
P (304) 624-4108
600 WHITE OAKS BLVD,
P.O. BOX 940
BRIDGEPORT, WV 26330
www.thethrashergroup.com
F (304) 624-7831
T80-11652
W
IL
L
IA
M S
T O
W N
W
V A
N G
W O
O D
C O
U N
T Y
, W E
S T
V
IR
IG
N
IA
W E
S T
V
IR
IG
N
IA
A
R M
Y N
A T
IO
N
A L
G U
A R
D
D R
A
IN
A G
E R
E P
A
IR
S
DETAILS
OUTLET PROTECTION
NOT TO SCALE
1. CONTRACTOR SHALL USE TAILWATER < 0.5D UNLESS OTHERWISE
SPECIFIED ON PLANS.
2. GEOTEXTILE (SEPARATION) SHALL BE BURIED BENEATH THE
PROPOSED CULVERT A MINIMUM ON TEN (10) FEET MEASURED
FROM WHERE THE CULVERT DAYLIGHTS.
3. CULVERT SLOPE SHALL BE FIELD ADJUSTED AS NEEDED TO
MINIMIZE THE WATER OUTFALL HEIGHT. (SLOPE SHALL NOT BE
LESS THAN THE MINIMUM SLOPE SHOWN IN PROPOSED CULVERT
DETAIL OR NOTED ON PLANS.)
4. THE WATER OUTFALL HEIGHT SHALL NOT EXCEED TWO (2) FEET.
5. THE MAXIMUM AGGREGATE SIZE SHALL BE TWELVE (12) INCH.
6. LENGTH OF OUTLET PROTECTION SHALL EXTEND BEYOND THE
TOE OF ANY FILL SLOPE SO AS TO DISCHARGE ONTO
UNDISTURBED GROUND.
NOTES:
TAILWATER ≥ 0.5Do
2' MIN.
SECTION A-A VIEW
PLAN VIEW
CULVERT DISCHARGE
La
W=3Do+0.4La
TAILWATER < 0.5Do
Do
3Do
A
A
W=3Do+La
A
A
Do
3Do
La
GEOTEXTILE
(SEPARATION)
EX. GROUND
CULVERT
12"
10' MIN.
Do
PLAN VIEW
SECTION B-B VIEW - VEGETATED DITCH
SECTION B-B VIEW - ROCK LINED DITCH
PROPOSED DITCH, SEE
PLAN FOR LINER
MATERIAL
B
B
10' MIN.
20' MIN.
PROPOSED VEGETATED
(EROSION CONTROL
MATTING) DITCH
EX.
GROUND
COMPACTED
EARTH BACKFILL
GEOTEXTILE (SEPARATION)
24" MIN.
12"
12"
2' MIN.
GEOTEXTILE (SEPARATION)
PROPOSED ROCK
LINED DITCH EX.
GROUND
COMPACTED
EARTH BACKFILL
18" MIN.
MOUNDING DETAIL DITCHES
DITCH GRADE
INLET MOUND
INLET
DITCH GRADE
DITCH GRADE
1' VERTICAL HEIGHT
(ABOVE DITCH GRADE)
4'
ROUNDING
L2 F2
7'
2:
12:1
1'
M
IN
TIE INTO EXISTING
SLOPES
GROUTED DUMP
ROCK 1.5XD50 THICK
(D50 = 12")
GROUTED DITCH
NOT TO SCALE
CONCRETE GUTTER
NOT TO SCALE
CUT-OFF WALL
NOT TO SCALE
1. WATERSTOP SHALL BE 5" WIDE MIN; WEB MIN. THICKNESS 3/16";
END SECTION AND/OR RIBS LESS THAN 1.67 WEB THICKNESS.
2. THE WATERSTOP DIAGRAMS ARE FOR INFORMATIONAL
PURPOSES ONLY. ALL WATERSTOPS SHALL CONFORM TO THE
GENERAL SHAPE SHOWN AND MEET THE REQUIREMENTS OF
SECTION 708.10 OF THE WVDOH SPECIFICATIONS.
3. THE "CONCRETE GUTTER TREATMENT AT INLETS" DETAIL AS
SHOWN IS FOR TRANSITIONING A V DITCH SECTION TO THE
WIDTH OF THE INLET. THE 15' LENGTH IS TO BE USED TO MAKE
THIS TRANSITION REGARDLESS OF THE WIDTH OF THE
APPROACH DITCH.
1/2" EXPANSION JOINT
2'
6"
6"
6"
MAX. 50' SPACING FLOW LINE OF GUTTER
WATERSTOP
4 (1/2") BARS 4'-2", SPACED 6"
CTR. TO CTR., BENT AS SHOWN.
BARS SHALL HAVE A MIN.
CONCRETE COVER OF 2"
WATERSTOP
WELDED WIRE FABRIC
(6'x12" - 6/6 GAGE)
CONFORMING TO THE
REQUIREMENTS IN 709.4
OF THE SPECIFICATION
1.5'
2"
1" 10'
2"
6"
CUT-OFF WALLS
2.5'
REINFORCED CONCRETE ANCHOR
NOT TO SCALE
1. CONCRETE ANCHORS SHALL BE INSTALLED ON ALL STORM
SEWER LINES WHERE THE SLOPE IS 18% OR GREATER.
2. SEE BELOW FOR ANCHOR SPACING BASED ON SLOPE:
2.1. < 18% - NO ANCHORS NECESSARY
2.2. 18% TO 35% - MAX SPACING 30' C-C
2.3. 35% TO 50% - MAX SPACING 20' C-C
2.4. > 50% - MAX SPACING 15' C-C
NOTES:
PLAN VIEW
SECTION VIEW
UNDISTURBED EARTH
1' MIN.
6" + R
3000 psi CONCRETE
UNDISTURBED
EARTH
3000 psi CONCRETE
ANCHOR
1'-0"
UNDISTURBED
EARTH
1'-0"
1'-0"
TRENCH WIDTH
VARIES
1'-0"1'-0"
TRENCH WIDTH
VARIES
V A
R
IE
S
P (304) 624-4108
600 WHITE OAKS BLVD,
P.O. BOX 940
BRIDGEPORT, WV 26330
www.thethrashergroup.com
F (304) 624-7831
T80-11652
W
IL
L
IA
M S
T O
W N
W
V A
N G
W O
O D
C O
U N
T Y
, W E
S T
V
IR
IG
N
IA
W E
S T
V
IR
IG
N
IA
A
R M
Y N
A T
IO
N
A L
G U
A R
D
D R
A
IN
A G
E R
E P
A
IR
S
DETAILS
BEDDING FOR STORM SEWER PIPE
EXCAVATED MATERIAL <
8" IN SIZE OR SELECT
BACKFILL
VARIES
(SEE
PLAN)
EXCAVATED MATERIAL <
2" IN SIZE OR SELECT
BACKFILL
C O
M P
A C
T E
D B
A C
K F
IL
L
12" + R
6" + R
NO. 10 STONE