CALCIUM_OXIDE_–_QUICKLIME_Chemical_Specification_Sheet.pdf
PDF 149 KB Posted
- Attached to
- Chemicals for Water Treatment Plant
- Solicitation number
- ITB-31-2026
- Issued by
- Rutherford County, Tennessee
About this file
This is a chemical specification sheet for calcium oxide (quicklime) for the Stonewall Regional Water Treatment Plant (SRWTP), associated with a sealed bid solicitation by the City of Murfreesboro, Tennessee for chemicals for water treatment. The City of Murfreesboro is seeking bids for quicklime with an estimated annual usage of 1,250 tons or 2,500,000 pounds. Sealed bids must be received no later than Wednesday, April 8, 2026, at 2:00 pm CST under ITB-31-2026. The product must be supplied in bulk and must be suitable for pneumatic unloading by the hauler with uniform particle size.
The specification requires that calcium oxide must meet NSF/ANSI Standard 60 (latest revision) and AWWA Specification B202 (latest revision), including the slake test requirement in Section 4.3. The chemical composition must contain a minimum of 94.5% available calcium oxide (CaO) and specified magnesium oxide (MgO) content. Bidders must submit pricing for the product price per pound and a separate freight charge per pound for a total bid amount. The highly reactive nature of quicklime and the large annual volume indicate this is a critical material for the water treatment process at this municipal facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CALCIUM OXIDE – QUICKLIME
For potable water treatment at the SRWTP
1. CALCIUM OXIDE (QUICKLIME) HIGHLY REACTIVE – BULK
ESTIMATED ANNUAL USAGE – 1,250 tons / 2,500,000 lbs
BID AMOUNTS Brand Bid Price/lb
Quicklime _______
Freight Charge per pound _______
TOTAL _______
PRODUCT SPECIFICATIONS
General Requirements
Must meet NSF/ANSI Standard 60 latest revision. Must meet or exceed AWWA Specification B202, latest revision, including requirement for slake test, Section 4:3, and shall be suitable for pneumatic unloading by the hauler; material of uniform particle size.
Chemical and Physical Requirements
CaO 94.5% available CaO MgO <1.00%
Silica <0.80% Heavy Metals 0% Loss on ignition 0.75% Granular ¼” minus
Must rise 40° C within first 3 minutes of reactivity test as stated in AWWA Standard B202.
Sample must come from truck at time of delivery.
Meets NSF/ANSI Standard 60 Meets AWWA Standard B202
Location from which chemical will be shipped:
TERMS
Bidder's Firm Name Salesperson's Name
Street Address Title
City
State Zip Code Signature
Signature above confirms that product meets NSF 60 certification and AWWA standard B202.
File details come from the government source that posted it. Updated .