Bid_24-23_Attachment_A_RJS_MCF_Drawings.pdf
PDF 22 MB Posted
- Solicitation number
- 24-23
- Issued by
- Florida
About this file
This is a comprehensive permit set of architectural, mechanical, electrical, and structural documents for the Raymond James Stadium Main Concourse Fans project in Tampa, Florida, involving Tampa Sports Authority as the client and multiple engineering firms including Populous (architect), Walter P Moore (structural engineer), and ME Engineers (mechanical/electrical engineer). The project involves installing 14 Big Ass Fans (Essence 12' Black and Silver model) on the club concourse level to improve occupant comfort in exterior areas. The fans will be anchored to existing cast-in-place concrete beams and integrated with electrical controllers located in main concourse electrical rooms. The permit set is dated April 2, 2025, and includes detailed mechanical, electrical, and structural plans for four stadium quadrants (A, B, C, and D).
The fans will be powered by 208V single-phase electrical connections, with variable speed drives and controllers designed to integrate with the building management system via BACnet protocol. Each fan is rated at 54,135 CFM with 8 blades, 12-foot diameter, and 338W motors. The electrical design includes specific circuit requirements, with fan controllers positioned to allow scheduling, temperature-based ramping, and emergency shutdown through the fire alarm system. The structural design involves careful mounting considerations, including scanning existing concrete beams to avoid damaging existing reinforcement and using Hilti screw anchors for installation. The project is designed to comply with 2023 Florida Building Codes and follows prescribed wind load and structural integrity standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Copyright 2024
ARCHITECT
Populous 4800 Main Street, Suite 300 Kansas City, MO 64112
816.221.1500
STRUCTURAL ENGINEER
Walter P Moore 201 East Kennedy Boulevard, Suite 700 Tampa, Florida 33602 813-221-2424
M/E/P ENGINEER
ME Engineers 14143 Denver West Parkway, Suite 300 Golden, Colorado 80401 303-421-6655
Volume 1 OF 1
Mechanical Electrical
/1
/2
:1
:5
P
M
Copyright 2025
16:39:53-05'00'
Architecture - Interior Design - Landscape Design
Brand Activation - Wayfinding - Product Design
Event - Urban Design - Populous Design Build
DRAWING INDEX
X0-0 - DRAWING INDEX
M0-0 – MECHANICAL LEGEND
M0-1 – MECHANICAL NOTES & SCHEDULES
M2-3A - MAIN CONCOURSE ROOF LEVEL MECHANICAL PLAN - QUAD A
M2-3B - MAIN CONCOURSE ROOF LEVEL MECHANICAL PLAN - QUAD B
M2-3C - MAIN CONCOURSE ROOF LEVEL MECHANICAL PLAN - QUAD C
M2-3D - MAIN CONCOURSE ROOF LEVEL MECHANICAL PLAN - QUAD D
E0-0 - ELECTRICAL LEGEND
E0-1 - ELECTRICAL SPECIFICATIONS
E0-3 - ELECTRICAL SPECIFICATIONS
E0-5 - ELECTRICAL ONE-LINE - MSA4 AND MSB2
E0-6 - ELECTRICAL ONE-LINE - MSC2
E0-7 - ELECTRICAL ONE-LINE - MSD2
E0-8 - ELECTRICAL SCHEDULES
E2-2 - MAIN CONCOURSE ELECTRICAL REFERENCE PLAN
E2-3A - MAIN CONCOURSE ROOF LEVEL ELECTRICAL PLAN - QUAD A
E2-3B - MAIN CONCOURSE ROOF LEVEL ELECTRICAL PLAN - QUAD B
E2-3C - MAIN CONCOURSE ROOF LEVEL ELECTRICAL PLAN - QUAD C
E2-3D - MAIN CONCOURSE ROOF LEVEL ELECTRICAL PLAN - QUAD D
E8-0 - ELECTRICAL DETAILS
ARCHITECT
Populous
4800 Main Street, Suite 300
Kansas City, MO 64112
816.221.1500
STRUCTURAL ENGINEER
Walter P Moore
201 East Kennedy Boulevard, Suite 700
Tampa, Florida 33602
813-221-2424
M/E/P ENGINEER
ME Engineers
14143 Denver West Parkway, Suite 300
Golden, Colorado 80401
303-421-6655
REVISIONS
NO. DATE DESCRIPTION
D A
C B
PROJECT NAME
RAYMOND JAMES
STADIUM MAIN
CONCOURSE FANS
4201 N DALE MABRY HWY.
TAMPA, FLORIDA 33607
ISSUED NAME
PERMIT SET
ISSUED DATE
04/02/25
ISSUED BY
POPULOUS
PROJECT NUMBER
25.6259.00
PAPER SIZE
E1
SHEET NAME
DRAWING INDEX
SHEET NUMBER
X0-0
/1
/2
:1
:5
P
T O
T H
E B
E S
T O
F T
H E
A R
C H
IT
E
C T
'S K
N O
W L
E D
G E
T
H E
P L
A N
S A
N D
S P
E C
IF
IC
A T
IO
N
S C
O M
P L
Y W
IT
H
T H
E A
P P
L
IC
A B
L E
M
IN
IM
U
M B
U
IL
D
IN
G C
O D
E S
DUCTWORK
DUCT MOUNTED SMOKE DETECTOR
FIRE DAMPER
SMOKE DAMPER
FIRE/SMOKE
DAMPER
MOTORIZED DAMPER
BACKDRAFT
DAMPER
TRANSITION:
RECTANGULAR TO ROUND
ROUND DUCT UP
CONICAL TAP
RECTANGULAR
BRANCH TAP
SECTION NO.
SECTION VIEW SHEET
NO.
DETAIL
DESIGNATION
POWERED EQUIPMENT
DESIGNATION
NON POWERED
EQUIPMENT DESIGNATION
BASEBOARD EQUIPMENT
DESIGNATION
SHEET KEY NOTES
INDICATES TYPE OF EQUIPMENT
INDICATES UNIT NUMBER WITHIN AREA
LEVEL
C - CLUB LEVEL
INDICATES AREA (A,B,C,D) ETC.
PIPING SYMBOLS
PRESSURE/TEMPERATUR
E PORT TAPS
CONCENTRIC REDUCER
ECCENTRIC REDUCER
EXPANSION JOINT
THERMOMETER W/
THERMOWELL
UNION
AIR VENT
FLEXIBLE PIPE
CONNECTOR
FLOW SWITCH
PRESSURE SWITCH
P&T
CR
ER
EJ
U
T
FS
PS
AV
FC
PRESSURE GAUGE W/
GAUGE COCK
ELBOW UP
ELBOW DOWN
TEE UP
TEE DOWN
ISOLATION VALVE, RE:
SPECS
PG
IV
OUTSIDE STEM AND
YOKE
OS&Y
DRAIN VALVE W/ HOSE
END CONNECTION
DV
PIPE CAP OR PLUG
ABBREVIATIONSYMBOL DESCRIPTION
BALL VALVE W/ HOSE
CONNECTION
CHECK VALVE WITH
INDICATION OF FLOW
DIRECTION
PRESSURE REDUCING
VALVE
CIRCUIT SETTER OR
BALANCING VALVE
GLOBE VALVE
(STRAIGHT PATTERN)
GLOBE VALVE (ANGLE
PATTERN)
BUTTERFLY VALVE
CV
PRV
GLV
BFV
CS,BV
GLV
BALL VALVE
AUTOMATIC
TEMPERATURE CONTROL
VALVE, 2-WAY
AUTOMATIC
TEMPERATURE CONTROL
VALVE, 3-WAY
BALANCING VALVE
TEMPERATURE/PRESSURE
RELIEF VALVE
STRAINER W/ BLOW-OFF &
CAPPED HOSE END
CONNECTION
BV
TCV
TCV
BV
TMP
STR
STEAM TRAPST
VALVE IN
RISER
PIPING TYPES
CHILLED WATER
SUPPLY
CHILLED WATER
RETURN
HEATING
WATER SUPPLY
HEATING WATER
RETURN
CONDENSER
WATER RETURN
CONDENSER
WATER SUPPLY
CONDENSATE
DRAIN
HIGH PRESSURE
STEAM SUPPLY
MEDIUM
PRESSURE STEAM
SUPPLY
LOW PRESSURE
STEAM SUPPLY
CHS
CHR
HWS
HWR
CWS
CWR
MPS
LPS
DR
HPS
HIGH PRESSURE
CONDENSATE RETURN
MEDIUM PRESSURE
CONDENSATE RETURN
LOW PRESSURE
CONDENSATE RETURN
REFRIGERANT
SUCTION
REFRIGERANT
LIQUID
CONTROL AIR
(PNEUMATIC)
CHS
CHR
HWS
HWR
CWS
CWR
MPS
LPS
DR
HPS
HPRHPR
MPRMPR
LPRLPR
RSRS
RLRL
AA
BOILER BLOW
DOWN
BDBD
BOILER FEEDBFBF
BLOW OFFBOBO
CHEMICAL
FEEDER
CFCF
PROCESS COOLING
WATER SUPPLY/RETURN
PCS/R
PCS/R
HIGH TEMP. HOT WATER
SUPPLY/RETURN
HTWS/RHTWS/R
PRIMARY OR DISTRICT
HEATING WATER
SUPPLY/RETURN
PHWS/RPHWS/R
PRIMARY OR DISTRICT
CHILLED WATER
SUPPLY/RETURN
PCHS/RPCHS/R
PUMPED CONDENSATE
RETURN
PRPR
EXISTING PIPING(E)(E)
EXISTING PIPING TO
BE REMOVED
(E)(E)
REFRIGERANT
HOT GAS
RHGRHG
SINGLE LINE PIPING
(UP TO 2")
DOUBLE LINE PIPING
(2" AND ABOVE)
PIPE
TYPE
MISCELLANEOUS
SUPPLY
DIFFUSER-4-WAY
THROW
SUPPLY
DIFFUSER-3-WAY
THROW
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
UC
POINT OF
DISCONNECTION
UNDERCUT DOOR (UNDER
ARCH. SECTION)
D/L DOOR LOUVER (UNDER
ARCH. SECTION)
L/D
LOUVER DOOR FULL
HEIGHT. (UNDER ARCH.
SECTION)
ARROW INDICATES
DIRECTION OF FLOW
EXTERIOR WALL LOUVER
SUPPLY
DIFFUSER-2-WAY
THROW
SUPPLY DIFFUSER-1-WAY
THROW
EQUIPMENT DESIGNATION
POINT OF CONN. (CONN.
NEW TO EXISTING)
SUPPLY OR
OUTSIDE AIR DN
NEW DUCTWORK
20"x16"
DUCT DIMENSIONS
(WIDTH x HEIGHT)
TURNING VANES
SPLITTER DAMPER
TRANSITION-RECT. TO RECT. OR
ROUND TO ROUND
UP DN
RISE IN DIRECTION
OF AIRFLOW
RETURN OR
EXHAUST AIR UP
EXHAUST AIR UP
DROP IN DIRECTION
OF AIRFLOW
RETURN OR
EXHAUST AIR DN
EXHAUST AIR DN
FITTINGS:
EJ
FS
PS
S
SV SOLENOID VALVE
F
S
F/S
M
B
A101
SIM
A
M1-01
AHU
1.01
VAV
1.01
TYPE
LENGTH
12"
FCU
CA01
S
EXHAUST GRILLE
RETURN GRILLE
H
CEILING ACCESS
PANEL
FLEXIBLE DUCT
CONNECTION
HUMIDIFIER
RETURN/EXHAUST
AIR FLOW SYMBOL
SUPPLY AIR
FLOW SYMBOL
HEAT TRACE
EXISTING
DIFFUSER
EXISTING
DUCTWORK
TO BE
REMOVED
EXISTING
DUCTWORK
ABBREVIATIONS:
ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
Y
Z
EXISTING THERMOSTAT
NEW THERMOSTAT
SPACE TEMPERATURE SENSOR
SPACE HUMIDISTAT
SPACE HUMIDITY SENSOR
SPACE PRESSURE SENSOR
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
(E)T
T
TS
H
HS
PS
CD
CO
NITROGEN DIOXIDE SENSOR ND
A AIR (COMPRESSED)
ABV ABOVE
A/C AIR CONDITIONING
AC ALTERNATING CURRENT
AIR COMPRESSOR
ACCH AIR COOLED CHILLER
ACCU AIR COOLED CONDENSING UNIT
ACFM ACTUAL CUBIC FEET PER MINUTE
AD ACCESS DOOR
AREA DRAIN
ADJ ADJUSTABLE
AF AIR FILTER
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHRI AIR-CONDITIONING, HEATING, AND
REFRIGERATION INSTITUTE
AHU AIR HANDLING UNIT
AL ALUMINUM
AMB AMBIENT
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AMERICAN SOCIETY OF HEATING,
REFRIGERATION, AND AIR-
CONDITIONING ENGINEERS
ARCH ARCHITECT
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATION, AND AIR-
CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
ASTM AMERICAN SOCIETY OF TESTING
AND MATERIALS
AV ACID VENT
AIR VENT
AVG AVERAGE
AW ACID WASTE
AWS AMERICAN WELDING SOCIETY
AUX AUXILIARY
B BOILER
BC BELOW COUNTER
BFV BUTTERFLY VALVE
BHP BRAKE HORSEPOWER
BLDG BUILDING
BM BENCHMARK
BOD BOTTOM OF DUCT (AFF)
BOF BOTTOM OF FOOTING
BOS BOTTOM OF STRUCTURE
BT BATH TUB
BREAK TANK
BTU BRITISH THERMAL UNIT
BV BALL VALVE
BWV BACK WATER VALVE
C CELSIUS
CAB CABINET
CAV CONSTANT AIR VOLUME
CB CATCH BASIN
CC COOLING COIL
CD CONDENSATE DRAIN LINE
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CI CAST IRON
CIRC CIRCULATING
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMP CORRIGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CPVC CHLORINATED POLYVINYL
CHLORIDE
CO CLEANOUT
COL COLUMN
COMB COMBINATION
COMP COMPRESSOR
CONC CONCRETE
CONCENTRIC
COND CONDENSER
CONDENSATE
CONN CONNECTION
CONT CONTINUOUS
CONTINUATION
CONTR CONTROLLER
CONTRACTOR
COP COEFFICIENT OF PERFORMANCE
CRAC COMPUTER ROOM A/C UNIT
CRU CONDENSATE RETURN UNIT
CT COOLING TOWER
CTR CENTER
CU COPPER
CW COLD WATER
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
CV CONSTANT VOLUME
dB DECIBEL
DB DRY-BULB
DC DIRECT CURRENT
DCV DEMAND CONTROLLED VENTILATION
DDC DIRECT DIGITAL CONTROL
DESIG DESIGNATION
DEFL DEFLECTION
DTL DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFUSER
DIM DIMENSION
DISC DISCONNECT
DN DOWN
DOAS DEDICATED OUTSIDE AIR SYSTEM
DP DISCHARGE PLENUM
DPR DAMPER
DR DRAIN
CONDENSATE DRAIN
DS DOUNSPOUT
DOUBLE SUCTION
DW DISHWASHER
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWP DOMESTIC WATER PUMP
DX DIRECT EXPANSION
(E) EXISTING
EA EACH OR EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
ELECTRONICALLY COMMUTATED
ECC ECCENTRIC
ECM ELECTRONICALLY COMMUTATED
MOTOR
EDB ENTERING DRY BULB
EDF ELECTRIC DRINKING FOUNTAIN
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
EJ EXPANSION JOINT
EL ELEVATION
EMRG EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
ENT ENTERING
ES END SUCTION
EMERGENCY SHOWER
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETR EXISTING TO REMAIN
EVAP EVAPORATOR
EWB ENTERING WET BULB
EWT ENTERING WATER
TEMPERATURE
EX EXPLOSION PROOF
EXT EXTERNAL
EXTG EXISTING
F DEGREE FAHRENHEIT
FBO FURNISHED BY OTHERS
FCO FLOOR CLEAN OUT
FCS FLOOR CONTROL SWITCH
FCU FAN COIL UNIT
FD FLOOR DRAIN
FIRE DAMPER
FDS FIRE DEPARTMENT SIAMESE
FDV FIRE DEPARTMENT VALVE
FG FIBERGLASS
FF FINAL FILTER
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FHR FIRE HOSE RACK
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLR FLOOR
FP FAN POWERED MIXING BOX
FIRE PUMP
FPI FINS PER INCH
FPM FEET PER MINUTE
FRIC FRICTION
FRZR FREEZER
FS FLOW SWITCH
FIRE SPRINKLER
FSK FLOOR SINK
FT FOOT
FEET
FLASH TANK
FT WC FEET, WATER COLUMN
FUT FUTURE
G GAS
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEA GREASE EXHAUST AIR
GLV GLOBE VALVE
GND GROUND
GPD GALLONS PER DAY
GPM GALLONS PER MINUTE
GV GATE VALVE
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HUB DRAIN
HF HUMIDIFIER
HORIZ HORIZONTAL
HP HORSEPOWER
HPA HOISTWAY PRESSURIZATION
AIR
HPU HEAT PUMP UNIT
HKP HOUSEKEEPING PAD
HSC HORIZONTAL SPLIT CASE
HSPF HEATING SEASONAL
PERFORMANCE FACTOR
HSTAT HUMIDISTAT
HT HEIGHT
HTG HEATING
HTR HEATER
HU HUMIDIFIER SECTION
HW HOT WATER
HWC HOT WATER CIRCULATOR
HWP HOT WATER PUMP
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HX HEAT EXCHANGER
HZ HERTZ
ID INSIDE DIAMTER
IE INVERT ELEVATION
IH INFRARED HEATER
IN INCH
IN WC INCH, WATER COLUMN
INSUL INSULATION
INT INTERNAL
INTERIOR
INITIAL
IPLV INTEGRATED PART LOAD
VALUE
ISOL ISOLATOR
IW INDIRECT WASTE
JB JUNCTION BOX
JP JOCKEY PUMP
KEC KITCHEN EQUIPMENT
CONTRACTOR
KO KNOCKOUT
KVA KILOVOLT AMPS
KW KILOWATT
L LENGTH
LAT LEAVING AIR TEMPERATURE
LAV LAVATORY
LBS POUNDS
LBS/HR POUNDS PER HOUR
LF LINEAR FEET
LP LOW PRESSURE
LRA LOCKED ROTOR AMPS
LVG LEAVING
MA MAKE-UP AIR
MAT MIXED AIR TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTUH
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MERV MINIMUM EFFICIENCY
REPORTING VALUE
MFR MANUFACTURER
MH MANHOLE
MI MALLEABLE IRON
MIN MINIMUM
MOCP MAXIMUM OVER CURRENT
PROTECTION
MP MEDIUM PRESSURE
MS MOP SINK
MTD MOUNTED
MTL METAL
MU MAKE-UP
MUA MAKE-UP AIR UNIT
MVD MANUAL VOLUME DAMPER
(N) NEW
NC NORMALLY CLOSED
NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NUMBER
NPLV NON-STANDARD PART LOAD
VALUE
NPSHA NET POSITIVE SUCTION HEAD
AVAILABLE
NPSHR NET POSITIVE SUCTION HEAD
REQUIRED
NTS NOT TO SCALE
OA OUTSIDE AIR
OAF OUTSIDE AIR FAN
OAHU OUTSIDE AIR HANDLING UNIT
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
OVERFLOW DRAIN
OFCU OUTSIDE AIR FAN COIL UNIT
OPG OPENING
OS&Y OPEN STEM AND YOLK
P PUMP
PLUMBING EQUIPMENT
PC PLUMBING CONTRACTOR
PCR PUMPED CONDENSATE
RETURN
PD PRESSURE DROP
PLANTER DRAIN
PF PRE-FILTER
PH PHASE
POST HYDRANT
PIV POST INDICATOR VALVE
PLBG PLUMBING
PLEV PART LOAD EFFICIENCY VALUE
PNEU PNEUMATIC
PNL PANEL
PNTH PENTHOUSE
PP POLYPROPYLENE
PPM PARTS PER MILLION
PRESS PRESSURE
PRI PRIMARY
PRS PRIMARY REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH,
GAUGE
PT PLUMBING TRIM
PV PLUG VALVE
PVC POLYVINYL CHLORIDE
PWL SOUND POWER LEVEL
QTY QUANTITY
(R) REMOVE
RELOCATE
RA RETURN AIR
RAD REFRIGERATED AIR DRYER
RAF RETURN AIR FAN
RAG RETURN AIR GRILLE
RAT RETURN AIR TEMPERATURE
RCP REFLECTED CEILING PLAN
REINFORCED CONCRETE PIPE
RD ROOF DRAIN
RE REFERENCE
REFER
RECIRC RECIRCULATE
RED REDUCER
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCING
REQD REQUIRED
REV REVISION
REVISE
RF RETURN FAN
RELIEF FAN
RH RELATIVE HUMIDITY
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RLA RUNNING LOAD AMPS
RM ROOM
REFRIGERANT MACHINE
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOFTOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAF SUPPLY AIR FAN
SAG SUPPLY AIR GRILLE
SAN SANITARY SEWER
SAR SUPPLY AIR REGISTER
SCHED SCHEDULE
SCFM STANDARD AIR CUBIC FEET
PER MINUTE
SCR SILICON CONTROLLED
RECTIFIER
SD STORM DRAIN
SE SEWAGE EJECTOR
SEC SECONDARY
SECT SECTION
SEER SEASONAL ENERGY
EFFICIENCY RATIO
SENS SENSIBLE
SF SQUARE FEET
SUPPLY FAN
SH SHOWER
SHT SHEET
SIM SIMILAR
SJ SEISMIC JOINT
SK SINK
SM SHEET METAL
SP STATIC PRESSURE
SUMP PUMP
SPA STAIR PRESSURIZATION AIR
SPEC SPECIFICATION
SPR SPRINKLER
SQ SQUARE
SS STAINLESS STEEL
SERVICE SINK
SSD SUBSURFACE DRAIN
SSFU SANITARY SEWER FIXTURE
UNITS
SSSC SOLID STATE SPEED
CONTROL
STD STANDARD
STL STEEL
STR STRAINER
SURF SURFACE
SUSP SUSPEND
SV SANITARY VENT
ST SOUND TRAP
TA TRANSFER AIR
TC TEMPERATURE CONTROL
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TER TOTAL ENERGY RATIO
TF TRANSFER FAN
TG TRANSFER GRILLE
TH BLK THRUST BLOCK
TOD TOP OF DUCT (AFF)
TOP TOP OF PIPE (AFF)
TP TRAP PRIMER
TPD TRAP PRIMER DEVICE
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TYP TYPICAL
U URINAL
U/F UNDERFLOOR
U/S UNDERSLAB
UCD UNDERCUT DOOR
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UNO UNLESS NOTED OTHERWISE
UTR UP THROUGH ROOF
V VOLT, VENT
VA VOLT-AMPERE
VAC VACUUM
VAV VARIABLE AIR VOLUME
VB VALVE BOX
VACUUM BREAKER
VCP VITRIFIED CLAY PIPE
VD VOLUME DAMPER
VEL VELOCITY
VERT VERTICAL
VFD VARIABLE FREUENCY DRIVE
VIB VALVE IN BOX
VOV VALVE ON VERTICAL
VP VACUUM PUMP
VR VARIABLE AIR VOLUME
REHEAT
VSD VARIABLE SPEED DRIVE
VTR VENT THROUGH ROOF
W WATT
WASTE
WIDTH
W/ WITH
W/O WITHOUT
WB WETBULB
WC WATER CLOSET
WCO WALL CLEANOUT
WF WATER FILTER
WH WALL HYDRANT
WM WATER METER
WMS WELDED WIRE MESH SCREEN
WP WEATHERPROOF
WPD WATER PRESSURE DROP
WWF WELDED WIRE FABRIC
WT WATER TIGHT
WEIGHT
Y YARD HYDRANT
Z ZONE
APPLICABLE CODES
DESIGNED UNDER THE FOLLOWING CODES AND STANDARDS:
2023 FLORIDA BUILDING CODE (8TH EDITION): BUILDING
2023 FLORIDA BUILDING CODE (8TH EDITION): ENERGY CONSERVATION
2023 FLORIDA BUILDING CODE (8TH EDITION): PLUMBING
2023 FLORIDA BUILDING CODE (8TH EDITION): MECHANICAL
2023 FLORIDA BUILDING CODE (8TH EDITION): FUEL GAS
FLORIDA ELECTRIC CODE 2020
2023 (8TH EDITION) FLORIDA FIRE PREVENTION CODE
NFPA 13
NFPA 72
SUPPLY AIR OR
OUTSIDE AIR UP
SEISMIC JOINTSJ
SJ
PIPE ANCHORANCH
PIPE GUIDEGD
LVL LEVEL
LWB LEAVING WET BULB
LWCO LOW WATER CUT OFF
LWT LEAVING WATER
TEMPERATURE
A
EXHAUST
DIFFUSER
RETURN
DIFFUSER
SUPPLY SLOT DIFFUSER
LOW PRESSURE
FLEXIBLE DUCT
CONICAL SPIN-IN FITTING
W/ MANUAL VOLUME DAMPER
DIFFUSER
TYPE
SUPPLY
DIFFUSER
ROUND DUCT
DOWN
(QTY)A
SIZE
CFM
D e n v e r W e st
P k w y
S u it e
G o ld e n
C O
.4
.6 w w .m e -e n g in e e rs
.c o m
SHEET TITLE:
ISSUANCE
ISSUE DATE:
PROJECT #:
KEY PLAN
TRUE NORTHPLAN NORTH
/1
/2
:2
:1
P
M C
R e v it P ro je c ts
\2
\R J S
C o n c F a n s M
E
R a u s ti n
.k ip p Y
Q C
C D
.r v t
04/02/2025
MECHANICAL
LEGEND
M0-0
DV25036
R A
Y M
O N
D J
A M
E S
S T
A D
IU
M
M A
IN
C
O N
C O
U R
S E
F A
N S
N
D A
L E
M A
B R
Y H
W Y
T
A M
P A
F
L O
R
ID
A
ISSUE FOR PERMIT
REVISIONS
NO. DATE DESCRIPTION
This item has been digitally signed and sealed by Jeremy Keiling, PE, on 4/11/2025.
Printed copies of this document are not considered signed an sealed . The signature must be verified on electronic copies.
GENERAL MECHANICAL CONTRACT REQUIREMENTS:
GENERAL:
1. UNLESS OTHERWISE NOTED, THE WORK DESCRIBED ON THE PLANS AND
SPECIFICATIONS SHALL INCLUDE THE FURNISHING AND INSTALLATION OF
ALL LABOR AND MATERIALS NECESSARY FOR COMPLETE AND
OPERATIONAL HVAC, FIRE PROTECTION AND PLUMBING SYSTEMS.
CONTRACTOR SHALL FURNISH THESE EVEN IF ITEMS REQUIRED TO
ACHIEVE THIS (I.E. OFFSETS, ISOLATION AND BALANCING DEVICES,
MAINTENANCE CLEARANCES, ETC.) ARE NOT SPECIFICALLY SHOWN.
2. DATA GIVEN ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED.
ABSOLUTE ACCURACY IS NOT GUARANTEED AND THE CONTRACTOR
SHALL OBTAIN AND VERIFY EXACT LOCATIONS, MEASUREMENTS, LEVELS,
SPACE REQUIREMENTS, POTENTIAL CONFLICTS WITH OTHER TRADES,
ETC. AT THE SITE AND SHALL SATISFACTORILY ADAPT HIS WORK TO THE
ACTUAL CONDITIONS OF THE JOB.
3. THE DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND SHALL NOT BE
SCALED. THEY SHOW CERTAIN PHYSICAL RELATIONSHIPS WHICH MUST BE
ESTABLISHED WITHIN THE DIVISION 21,22 AND 23 WORK AND ITS
INTERFACE WITH OTHER WORK. ESTABLISHING THIS RELATIONSHIP IN THE
FIELD IS THE EXCLUSIVE RESPONSIBILITY OF THE CONTRACTOR. THIS
DIVISION SHALL COORDINATE ITS WORK WITH ALL DIVISIONS OF THE
WORK AND ADJUST ITS WORK AS REQUIRED BY THE ACTUAL CONDITIONS
OF THE PROJECT.
A. THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING A
BID TO BECOME THOROUGHLY FAMILIAR WITH THE ACTUAL
CONDITIONS OF THE PROJECT. NO EXTRAS WILL BE ALLOWED DUE
TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS.
B. CERTAIN SYSTEMS REQUIRE ENGINEERING OF INSTALLATION
DETAILS BY CONTRACTOR. UNLESS FULLY DETAILED IN THE
CONTRACT DOCUMENTS, SUCH ENGINEERING IS THE EXCLUSIVE
RESPONSIBILITY OF THE CONTRACTOR.
C. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE WHERE
CLEARANCES ARE LIMITED, AND WHERE INSTALLATION DRAWINGS
OR SCHEMATICS, "CONSTRUCTION DRAWINGS", OR COORDINATION
DRAWINGS MAY BE REQUIRED IN EXCESS OF THOSE REQUIRED BY
THE SPECIFICATIONS. THE CONTRACTOR SHALL PREPARE ALL
SUCH COORDINATION DRAWINGS AS PART OF THE BASE
CONTRACT. SUCH DRAWINGS MAY BE SUBMITTED TO THE
ARCHITECT/ENGINEER FOR RECORD AND COMMENT. ANY WORK
INSTALLED WITHOUT APPROVED COORDINATION DRAWINGS IS
DONE AT THE CONTRACTOR'S RISK.
EXISTING BUILDING:
1. EXISTING CONDITIONS REPRESENTED ON MECHANICAL, ELECTRICAL, AND
PLUMBING DRAWINGS HAVE BEEN DEVELOPED USING VARIOUS EXISTING
DESIGN DRAWINGS AND SITE OBSERVATIONS. EXISTING DESIGN
DRAWINGS MAY OR MAY NOT REFLECT THE ACTUAL INSTALLED
CONDITION FOR SYSTEMS INDICATED. SITE OBSERVATIONS MAY BE
INCOMPLETE AS CONCEALED CONDITIONS CANNOT BE VISUALLY
VERIFIED. WHILE SITE INVESTIGATION HAS BEEN CONDUCTED, THE
ENGINEER CANNOT ASSURE THE OWNER OR THE CONTRACTOR THAT THE
EXISTING DESIGN DRAWINGS AND INFORMATION GATHERED DURING SITE
INVESTIGATION COMPLETELY AND ACCURATELY REFLECT EXISTING
CONDITIONS. FOR THIS REASON, THE SCOPE INCLUDED IN THIS DRAWING
PACKAGE CANNOT BE ASSURED TO INCLUDE ALL CONTINGENCIES. FIELD
COORDINATION DURING CONSTRUCTION IS REQUIRED TO FULLY
UNDERSTAND AND EXECUTE THE PROJECT SCOPE OF WORK.
REASONABLE CONTINGENCIES SHALL BE INCLUDED FOR UNFORESEEN
SCOPE ITEMS.
2. THE CONTRACTOR'S ATTENTION IS CALLED TO THE FACT THAT THE
EXISTING BUILDING WILL BE OCCUPIED BY THE OWNER DURING
CONSTRUCTION. CONTINUED OPERATION OF THE FACILITY SHALL NOT BE
HINDERED BY THIS WORK. THE CONTRACTOR SHALL ACCOUNT FOR ALL
ADDITIONAL COSTS WHICH MAY BE INCURRED BY THE CONTRACTOR DUE
TO THE DIFFICULTY OF WORKING OVER AND AROUND EMPLOYEES, DESKS,
EQUIPMENT, ETC.; AND DUE TO THE HOURS OF THE DAY IN WHICH AN
AREA MAY BE AVAILABLE. CONTRACTOR'S BID SHALL TAKE THESE
FACTORS INTO ACCOUNT.
3. MAINTAIN A MARK-UP SET OF DRAWINGS WHICH INDICATE VARIATIONS IN
THE ACTUAL INSTALLATION FROM THE ORIGINAL DESIGN. SURRENDER
DRAWINGS TO OWNER UPON COMPLETION.
4. COORDINATE ALL PENETRATIONS OF FLOOR SLABS, CONCRETE WALLS,
AND OTHER STRUCTURAL ELEMENTS WITH ARCHITECT AND STRUCTURAL
ENGINEER PRIOR TO COMMENCING WORK. UTILIZE X-RAY AND VISUAL
INVESTIGATION OF EXISTING CONDITIONS AS REQUIRED TO DETERMINE
PENETRATION LOCATIONS. SUBMIT PENETRATION SHOP DRAWINGS TO
ARCHITECT AND ENGINEER FOR REVIEW PRIOR TO DRILLING OR CUTTING.
COORDINATE ALL NEW PENETRATIONS WITH OTHER DIVISIONS OF THE
WORK. ALL CONTRACTORS ARE INDIVIDUALLY RESPONSIBLE FOR ALL
PENETRATIONS REQUIRED BY THEIR DIVISIONS.
ELECTRICAL/FIRE ALARM COORDINATION:
1. VERIFY THE ELECTRICAL SERVICE PROVIDED BY THE ELECTRICAL
CONTRACTOR BEFORE ORDERING ANY MECHANICAL EQUIPMENT
REQUIRING ELECTRICAL CONNECTIONS.
GENERAL INSTALLATION:
1. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADEQUATE
SUPPORT FOR ALL DIVISION 23 WORK. SUSPEND EACH TRADE'S WORK
SEPARATELY FROM THE STRUCTURE. DO NOT SHARE HANGERS BETWEEN
PIPING, DUCTWORK, CONDUIT, AND EQUIPMENT. DUCTWORK, PIPING, AND
CONDUIT SHALL BE HELD TIGHT TO STRUCTURE EXCEPT WHERE
OTHERWISE SHOWN.
2. EXCEPT WHERE MORE STRINGENT REQUIREMENTS ARE INDICATED OR
LOCAL CODE TAKES PRECEDENCE, COMPLY WITH THE PRODUCT
MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
RECOMMENDATIONS.
3. PROVIDE MANUFACTURER'S RECOMMENDED SERVICE CLEARANCE
AROUND ALL EQUIPMENT REQUIRING SAME. PROVIDE A MEANS OF
ACCESS (ACCESS PANELS, ACCESS DOORS, REMOVABLE CEILING TILES,
ETC.) WHERE REQUIRED FOR ADEQUATE MAINTENANCE AND
EQUIPMENT/COMPONENT REPLACEMENT. WHERE EQUIPMENT IS
INSTALLED ABOVE CEILINGS, INSTALL SUCH EQUIPMENT AT A HEIGHT
READILY ACCESSIBLE THROUGH THE CEILING.
CUTTING, PATCHING AND DEMOLITION:
1. KEEP DEMOLITION & CUTTING TO MINIMUM REQUIRED FOR PROPER
EXECUTION OF WORK.
2. BE RESPONSIBLE FOR ALL CUTTING AND PATCHING NECESSARY FOR THE
COMPLETION OF THE WORK.
3. NO CUTTING (NOT SHOWN ON THE CONTRACT DOCUMENTS) SHALL BE
DONE WITHOUT THE APPROVAL OF THE ARCHITECT AS TO LOCATIONS,
METHOD AND EXTENT OF THE CUTTING.
4. REPAIR ALL ACCIDENTAL OR INTENTIONAL DAMAGE TO MATCH EXISTING
CONSTRUCTION WITH NO NOTICEABLE DIFFERENCE IN CONTINUITY,
APPEARANCE OR FUNCTION.
FIRE STOPPING:
1. PENETRATIONS THROUGH FIRE RATED WALLS AND FIRE RATED
HORIZONTAL ASSEMBLIES SHALL BE PROVIDED WITH AN APPROVED FIRE
STOPPING SYSTEM.
2. PENETRATIONS THROUGH NON-FIRE RATED FLOOR OR FLOOR/CEILING
ASSEMBLIES SHALL BE PROVIDED WITH AN APPROVED FIRE STOPPING
SYSTEM.
3. INSTALL FIRE STOPPING MATERIALS IN ACCORDANCE WITH THEIR UL AND
ASTM TESTED METHODS.
GENERAL SYSTEM DESCRIPTION:
1. ADDING (14) HVLS FANS TO CLUB CONCOURSE LEVEL FOR ADDITIONAL
OCCUPANT COMFORT IN EXTERIOR AREA.
ENERGY CODE COMPLIANCE:
1. THE PROJECT HAS BEEN DESIGNED UNDER THE ENERGY CODE INDICATED
ON THE LEGEND SHEET.
2. THE PROJECT IS UTILIZING THE PRESCRIPTIVE PATH OF THE
INTERNATIONAL ENERGY CONSERVATION CODE INCLUDING ALL
APPLICABLE MANDATORY AND PRESCRIPTIVE CODE PROVISIONS.
D e n v e r W e st
P k w y
S u it e
G o ld e n
C O
.4
.6 w .m e -e n g in e e rs
.c o m
SHEET TITLE:
ISSUANCE
ISSUE DATE:
PROJECT #:
KEY PLAN
TRUE NORTHPLAN NORTH
/1
/2
:2
:1
P
M C
R e v it P ro je c ts
\2
\R J S
C o n c F a n s M
E
R a u s ti n
.k ip p Y
Q C
C D
.r v t
04/02/2025
MECHANICAL
NOTES &
SCHEDULES
M0-1
DV25036
R A
Y M
O N
D J
A M
E S
S T
A D
IU
M
M A
IN
C
O N
C O
U R
S E
F A
N S
N
D A
L E
M A
B R
Y H
W Y
T
A M
P A
F
L O
R
ID
A
ISSUE FOR PERMIT
I. PROVIDE MANUFACTURER BAFCON RTC 0-10V CONTROLLER KIT TO CONTROL (7) FANS PER SIDE. CONTROLLERS TO BE MOUNTED IN MAIN CONCOURSE CENTER ELECTRICAL ROOMS 02.07.04 & 02.40.04. COORDINATE EXACT MOUNTING LOCATION WITH ARCHITECT AND OWNER. CONTROLLERS TO BE INTEGRATED INTO BMS VIA BACNET TO ALLOW FOR SCHEDULING AND CONTROL. INTEGRATED FAN CONTROL TO ALLOW THE FANS TO RAMP UP UPON INCREASED OUTDOOR TEMPERATURE. FANS SHALL BE PROVIDED WITH A FIRE RELAY TO DE-ENERGIZE FANS UPON ACTIVATION OF THE FIRE
ALARM SYSTEM.
1. PROVIDE MANUFACTURER UNIVERSAL MOUNT, 4' EXTENSION TUBE, AND CONCRETE MOUNT KIT FOR SUPPORTING FROM CONCRETE BEAM STRUCTURE ABOVE. MAINTAIN MANUFACTURER REQUIRED CLEARANCES. COORDINATE STRUT OR GUY CABLES (TO PREVENT LATERAL MOVEMENT) WITH STRUCTURAL. SET FAN FOR DOWNFLOW OPERATION.
CONTROL(CTRL): MOUNTING (MTG):
1. VSD=VARIABLE SPEED DRIVE.
2. PROVIDE PREMIUM EFFICIENCY MOTORS FOR MOTORS 1 HP AND OVER PER MENA STANDARD MG1-2003, TABLES 12-12
AND 12-13.
3. COORDINATE AIRFOIL AND HARDWARE COLORS WITH ARCHITECT.
4. PROVIDE BLACK HEAT SINK.
GENERAL NOTES: REMARK NOTES:
DESTRATIFICATION FAN SCHEDULE
TYPE MARK MANUFACTURER MODEL NO. AREA SERVED CFM MAX RPM NO. OF BLADES DIAMETER (FT) DRIVE
ELECTRICAL
MTG CTRL WEIGHT (LBS) REMARKSMOTOR (W) VOLT PH FLA DISC. FEEDER FUSE
DSF CA01 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CA02 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CA03 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CA04 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CB01 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CB02 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CB03 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CB04 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CC01 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CC02 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CC03 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CD01 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CD02 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
DSF CD03 BIG ASS FANS ESSENCE CLUB LEVEL CONCOURSE 54135 56 8 12 VSD 338 208 1 0.0 T.O. SWITCH (3#12,#12G)3/4"C - 1 I 100
H-W
30.7
27.1
40 37.4
33.9
E
D
F-W
A
C
B
G-W
CA01
DSF
CA02
DSF
CA03
DSF
CA04
DSF
D e n v e r W e st
P k w y
S u it e
G o ld e n
C O
.4
.6 w .m e -e n g in e e rs
.c o m
SHEET TITLE:
ISSUANCE
ISSUE DATE:
PROJECT #:
KEY PLAN
TRUE NORTHPLAN NORTH
/1
/2
:2
:1
P
M C
R e v it P ro je c ts
\2
\R J S
C o n c F a n s M
E
R a u s ti n
.k ip p Y
Q C
C D
.r v t
04/02/2025
MAIN CONCOURSE
ROOF LEVEL
MECHANICAL PLAN
QUAD A
M2-3A
DV25036
R A
Y M
O N
D J
A M
E S
S T
A D
IU
M
M A
IN
C
O N
C O
U R
S E
F A
N S
N
D A
L E
M A
B R
Y H
W Y
T
A M
P A
F
L O
R
ID
A
ISSUE FOR PERMIT
1/16" = 1'-0"
MAIN CONCOURSE ROOF LEVEL MECHANICAL PLAN QUAD A
KEYNOTES
1. THE DRAWINGS ARE DIAGRAMMATIC IN
NATURE. THE CONTRACTOR IS
RESPONSIBLE FOR ALL OFFSETS,
TRANSITIONS, ELBOWS, ETC. AS
REQUIRED IN DUCTWORK, PIPING,
SUPPORTS, ETC. TO COMPLETE THE
WORK IN A CLEAN FUNCTIONAL
INSTALLATION THAT IS FULLY
COORDINATED WITH ALL OTHER
TRADES. ANY PRICING EFFORT SHALL
TAKE THESE FACTORS INTO ACCOUNT.
2. COORDINATE SPACE TEMPERATURE
SENSORS AND THERMOSTAT
LOCATIONS TO ALIGN VERTICALLY WITH
LIGHT SWITCHES.
3. TEMPERATURE CONTROLS
CONTRACTOR SHALL SUBMIT PLANS
INDICATING ALL SPACE TEMPERATURE
SENSORS, T-STATS, HUMIDITY
SENSORS, ETC. AS PART OF SUBMITTAL
PROCESS FOR A/E REVIEW PRIOR TO
ROUGH-IN.
4. ALL DUCT/PIPE PENETRATIONS
THROUGH FIRE RATED/SMOKE RATED
PARTITIONS SHALL BE CAULKED AND
SEALED TO MEET THE RATING
REQUIRED. REFER TO LIFE SAFETY
DRAWINGS FOR FIRE/SMOKE RATING
REQUIREMENTS.
MECH GENERAL NOTES:
H-E
23.3
16.8
27.1
10 15
F-E
E
D
A
C
B
G-E
CB01
DSF
CB02
DSF
CB03
DSF
CB04
DSF
D e n v e r W e st
P k w y
S u it e
G o ld e n
C O
.4
.6 w .m e -e n g in e e rs
.c o m
SHEET TITLE:
ISSUANCE
ISSUE DATE:
PROJECT #:
KEY PLAN
TRUE NORTHPLAN NORTH
/1
/2
:2
:1
P
M C
R e v it P ro je c ts
\2
\R J S
C o n c F a n s M
E
R a u s ti n
.k ip p Y
Q C
C D
.r v t
04/02/2025
MAIN CONCOURSE
ROOF LEVEL
MECHANICAL PLAN
QUAD B
M2-3B
DV25036
R A
Y M
O N
D J
A M
E S
S T
A D
IU
M
M A
IN
C
O N
C O
U R
S E
F A
N S
N
D A
L E
M A
B R
Y H
W Y
T
A M
P A
F
L O
R
ID
A
ISSUE FOR PERMIT
1. THE DRAWINGS ARE DIAGRAMMATIC IN
NATURE. THE CONTRACTOR IS
RESPONSIBLE FOR ALL OFFSETS,
TRANSITIONS, ELBOWS, ETC. AS
REQUIRED IN DUCTWORK, PIPING,
SUPPORTS, ETC. TO COMPLETE THE
WORK IN A CLEAN FUNCTIONAL
INSTALLATION THAT IS FULLY
COORDINATED WITH ALL OTHER
TRADES. ANY PRICING EFFORT SHALL
TAKE THESE FACTORS INTO ACCOUNT.
2. COORDINATE SPACE TEMPERATURE
SENSORS AND THERMOSTAT
LOCATIONS TO ALIGN VERTICALLY WITH
LIGHT SWITCHES.
3. TEMPERATURE CONTROLS
CONTRACTOR SHALL SUBMIT PLANS
INDICATING ALL SPACE TEMPERATURE
SENSORS, T-STATS, HUMIDITY
SENSORS, ETC. AS PART OF SUBMITTAL
PROCESS FOR A/E REVIEW PRIOR TO
ROUGH-IN.
4. ALL DUCT/PIPE PENETRATIONS
THROUGH FIRE RATED/SMOKE RATED
PARTITIONS SHALL BE CAULKED AND
SEALED TO MEET THE RATING
REQUIRED. REFER TO LIFE SAFETY
DRAWINGS FOR FIRE/SMOKE RATING
REQUIREMENTS.
MECH GENERAL NOTES:
KEYNOTES
1/16" = 1'-0"
MAIN CONCOURSE ROOF LEVEL MECHANICAL PLAN QUAD B
63.7
H-E
54 76
66.9
4.4
62.6
59.9
F-E
E
D
A
C
B
G-E
CC01
DSF
CC02
DSF
CC03
DSF
CB01
DSF
D e n v e r W e st
P k w y
S u it e
G o ld e n
C O
.4
.6 w .m e -e n g in e e rs
.c o m
SHEET TITLE:
ISSUANCE
ISSUE DATE:
PROJECT #:
KEY PLAN
TRUE NORTHPLAN NORTH
/1
/2
:2
:1
P
M C
R e v it P ro je c ts
\2
\R J S
C o n c F a n s M
E
R a u s ti n
.k ip p Y
Q C
C D
.r v t
04/02/2025
MAIN CONCOURSE
ROOF LEVEL
MECHANICAL PLAN
QUAD C
M2-3C
DV25036
R A
Y M
O N
D J
A M
E S
S T
A D
IU
M
M A
IN
C
O N
C O
U R
S E
F A
N S
N
D A
L E
M A
B R
Y H
W Y
T
A M
P A
F
L O
R
ID
A
ISSUE FOR PERMIT
1. THE DRAWINGS ARE DIAGRAMMATIC IN
NATURE. THE CONTRACTOR IS
RESPONSIBLE FOR ALL OFFSETS,
TRANSITIONS, ELBOWS, ETC. AS
REQUIRED IN DUCTWORK, PIPING,
SUPPORTS, ETC. TO COMPLETE THE
WORK IN A CLEAN FUNCTIONAL
INSTALLATION THAT IS FULLY
COORDINATED WITH ALL OTHER
TRADES. ANY PRICING EFFORT SHALL
TAKE THESE FACTORS INTO ACCOUNT.
2. COORDINATE SPACE TEMPERATURE
SENSORS AND THERMOSTAT
LOCATIONS TO ALIGN VERTICALLY WITH
LIGHT SWITCHES.
3. TEMPERATURE CONTROLS
CONTRACTOR SHALL SUBMIT PLANS
INDICATING ALL SPACE TEMPERATURE
SENSORS, T-STATS, HUMIDITY
SENSORS, ETC. AS PART OF SUBMITTAL
PROCESS FOR A/E REVIEW PRIOR TO
ROUGH-IN.
4. ALL DUCT/PIPE PENETRATIONS
THROUGH FIRE RATED/SMOKE RATED
PARTITIONS SHALL BE CAULKED AND
SEALED TO MEET THE RATING
REQUIRED. REFER TO LIFE SAFETY
DRAWINGS FOR FIRE/SMOKE RATING
REQUIREMENTS.
MECH GENERAL NOTES:
KEYNOTES
1/16" = 1'-0"
MAIN CONCOURSE ROOF LEVEL MECHANICAL PLAN QUAD C
49.8 46
H-W
57.5
53.1
48 4450
56.3
59.9
EE DD
F-W
A
CC
B
G-W
CD01
DSF
CD02
DSF
CD03
DSF
CA01
DSF
D e n v e r W e st
P k w y
S u it e
G o ld e n
C O
.4
.6 w .m e -e n g in e e rs
.c o m
SHEET TITLE:
ISSUANCE
ISSUE DATE:
PROJECT #:
KEY PLAN
TRUE NORTHPLAN NORTH
/1
/2
:2
:1
P
M C
R e v it P ro je c ts
\2
\R J S
C o n c F a n s M
E
R a u s ti n
.k ip p Y
Q C
C D
.r v t
04/02/2025
MAIN CONCOURSE
ROOF LEVEL
MECHANICAL PLAN
QUAD D
M2-3D
DV25036
R A
Y M
O N
D J
A M
E S
S T
A D
IU
M
M A
IN
C
O N
C O
U R
S E
F A
N S
N
D A
L E
M A
B R
Y H
W Y
T
A M
P A
F
L O
R
ID
A
ISSUE FOR PERMIT
1. THE DRAWINGS ARE DIAGRAMMATIC IN
NATURE. THE CONTRACTOR IS
RESPONSIBLE FOR ALL OFFSETS,
TRANSITIONS, ELBOWS, ETC. AS
REQUIRED IN DUCTWORK, PIPING,
SUPPORTS, ETC. TO COMPLETE THE
WORK IN A CLEAN FUNCTIONAL
INSTALLATION THAT IS FULLY
COORDINATED WITH ALL OTHER
TRADES. ANY PRICING EFFORT SHALL
TAKE THESE FACTORS INTO ACCOUNT.
2. COORDINATE SPACE TEMPERATURE
SENSORS AND THERMOSTAT
LOCATIONS TO ALIGN VERTICALLY WITH
LIGHT SWITCHES.
3. TEMPERATURE CONTROLS
CONTRACTOR SHALL SUBMIT PLANS
INDICATING ALL SPACE TEMPERATURE
SENSORS, T-STATS, HUMIDITY
SENSORS, ETC. AS PART OF SUBMITTAL
PROCESS FOR A/E REVIEW PRIOR TO
ROUGH-IN.
4. ALL DUCT/PIPE PENETRATIONS
THROUGH FIRE RATED/SMOKE RATED
PARTITIONS SHALL BE CAULKED AND
SEALED TO MEET THE RATING
REQUIRED. REFER TO LIFE SAFETY
DRAWINGS FOR FIRE/SMOKE RATING
REQUIREMENTS.
MECH GENERAL NOTES:
KEYNOTES
1/16" = 1'-0"
MAIN CONCOURSE ROOF LEVEL MECHANICAL PLAN QUAD D
CITY OF TAMPA REQUIREMENTS
NO ELECTRICAL MATERIALS, APPARATUS, DEVICES, APPLIANCES, FIXTURES OR EQUIPMENT SHALL BE SOLD OR INSTALLED IN THE CITY UNLESS THEY ARE IN CONFORMANCE WITH PROVISIONS OF THIS CODE, THE LAWS OF THE STATE OF FLORIDA AND ANY APPLICABLE RULES AND REGULATIONS ISSUED UNDER THE AUTHORITY OF THE STATE STATUTES. THE MAKER'S NAME, TRADEMARK, OR OTHER IDENTIFICATION SYMBOL SHALL BE PLACED ON ALL ELECTRICAL MATERIALS, APPARATUS, DEVICES, APPLIANCES, FIXTURES AND EQUIPMENT USED OR INSTALLED UNDER THE PROVISIONS OF THIS CODE. ALL ELECTRICAL MATERIAL AND EQUIPMENT SHALL BE LISTED AND LABELED FOR THE INTENDED USE AND SHALL BE INCLUDED IN A LIST PUBLISHED BY AN APPROVED AGENCY.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
ALL EXPOSED RACEWAYS ARE TO BE INSTALLED PARALLEL OR PERPENDICULAR TO WALLS OR STRUCTURAL MEMBERS SUCH THAT THEY FOLLOW STRUCTURAL SURFACE CONTOURS AND SHALL BE INSTALLED SUCH THAT THEY DO NOT OBSTRUCT PASSAGEWAYS OR ACCESS TO EQUIPMENT. MULTIPLE RACEWAYS SHOULD BE INSTALLED GROUPED TOGETHER. THE LOCATION OF PUBLICLY VISIBLE RACEWAYS SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. (EXTRA TIME SHOULD BE ALLOWED FOR THIS REVIEW AND
APPROVAL.)
THE DISCONNECTING MEANS FOR ALL MECHANICAL EQUIPMENT SHALL BE ACCESSIBLE AND HAVE THE
CLEARANCE IN FRONT AS REQUIRED BY NEC AMENDMENTS.
ALL CEILING ATTACHED OBJECTS AND FLOOR ATTACHED EQUIPMENT INCLUDING BUT NOT LIMITED TO PENDANT LIGHTING FIXTURES, GENERAL LIGHTING, MULTIPLE RACEWAYS, GENERATOR, TRANSFORMER ELECTRICAL SWITCHGEAR, AND SWITCHBOARDS SHALL BE INSTALLED IN ACCORDANCE WITH SUPPORTING
OBJECTS FOR SEISMIC ZONE AS REQUIRED BY STATE AND LOCAL CODES.
ALL SWITCHGEAR, SWITCHBOARDS AND TRANSFORMERS SHALL HAVE A 4 INCH HOUSE KEEPING PAD. UNDER
NO CONDITION SHALL THE HIGHEST SWITCH OR BREAKER EXCEED 6'-6" AFF.
DATA GIVEN ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED. ABSOLUTE ACCURACY IS NOT GUARANTEED AND THE CONTRACTOR SHALL OBTAIN AND VERIFY EXACT LOCATIONS, MEASUREMENTS, LEVELS, SPACE REQUIREMENTS, POTENTIAL CONFLICTS WITH OTHER TRADES, ETC. AT THE SITE AND SHALL SATISFACTORILY ADAPT HIS WORK TO ACTUAL CONDITIONS AT THE BUILDINGS. THE DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND SHALL NOT BE SCALED. HOWEVER THIS DOES NOT RELIEVE ANY SUB- CONTRACTOR FROM COORDINATING HIS WORK WITH ALL OTHER TRADES AND FROM ADJUSTING HIS WORK AS REQUIRED BY THE ACTUAL CONDITIONS OF THE PROJECT. THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING COSTS TO BECOME THOROUGHLY FAMILIAR WITH THE ACTUAL CONDITIONS OF THE PROJECT.
COORDINATE AND ADJUST ALL WORK BETWEEN TRADES AND EXISTING CONDITIONS IN ORDER TO ACCOMPLISH A NEAT, INTEGRATED AND EFFICIENT INSTALLATION WHICH INCLUDE BUT ARE NOT LIMITED TO:
a. EXAMINE THE CONTRACT DOCUMENTS OF ALL TRADES (IE. THE ARCHITECTURAL REFLECTED CEILING PLAN, MECHANICAL HVAC DRAWINGS, ELECTRICAL LIGHTING PLAN, FIRE PROTECTION PLAN, ETC.).
b. COORDINATE NECESSARY EQUIPMENT, FIXTURES, ETC. SO THAT THE FINAL INSTALLATION IS COMPATIBLE
WITH THE MATERIALS AND EQUIPMENT OF THE OTHER TRADES.
c. THIS CONTRACTOR SHALL ASSIST THE DIVISION 23 CONTRACTOR IN PREPARING SHOP DRAWINGS FOR COORDINATING INSTALLATION OF ALL WORK (IE. LOCATING ALL LIGHTING FIXTURES IN CEILING WITH CEILING
CLEARANCES, RACEWAYS, PIPING, EQUIPMENT FOR CLEARANCE THROUGHOUT).
d. THE ELECTRICAL DRAWINGS INDICATE THE ELECTRICAL REQUIREMENTS FOR A SIGNIFICANT PORTION OF THE MECHANICAL AND PLUMBING SYSTEMS. ADDITIONAL MECHANICAL AND PLUMBING EQUIPMENT IS INDICATED ON THE DIVISION 23 DRAWINGS. REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. PROVIDE COMPLETE WIRING AND FUSIBLE DISCONNECTING MEANS FOR ALL
MECHANICAL AND PLUMBING EQUIPMENT.
DEFINITIONS:
a. "FURNISH" MEANS TO "SUPPLY" AND USUALLY REFERS TO AN ITEM OF EQUIPMENT.
b. "INSTALL" MEANS TO "SET IN PLACE, CONNECT AND PLACE IN FULL OPERATIONAL ORDER".
c. "PROVIDE" MEANS TO "FURNISH AND INSTALL".
d. "EQUIVALENT" MEANS "MEETS THE SPECIFICATIONS OF THE REFERENCE PRODUCT OR ITEM IN ALL
SIGNIFICANT ASPECTS." SIGNIFICANT ASPECTS SHALL BE DETERMINED BY THE ENGINEER.
e. "RE: DIVISION", AND SIMILAR EXPRESSIONS MEANS WORK TO BE PERFORMED UNDER THE CONTRACT DOCUMENTS, BUT NOT NECESSARILY UNDER THE DIVISION OR SECTION OF THE WORK ON WHICH THE NOTE APPEARS. IT IS THE CONTRACTORS SOLE RESPONSIBILITY TO COORDINATE THE WORK OF THE CONTRACT BETWEEN HIS/HER SUPPLIERS, SUBCONTRACTORS, AND EMPLOYEES. IF CLARIFICATION IS REQUIRED, CONSULT ARCHITECT.
"FIRESTOPPING" REQUIREMENT. ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM-E-814. ALL PENETRATIONS
SHALL MEET F AND T RATINGS AS REQUIRED BY THE BUILDING CODE.
WHERE DISCONNECTS ARE INDICATED ON DRAWINGS CONTRACTOR SHALL PROVIDE FINAL CONNECTION
FROM DISCONNECT TO EQUIPMENT BEING SERVED.
CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS SUPPORTS AS REQUIRED FOR A COMPLETE OPERABLE ELECTRICAL INSTALLATION INCLUDING MISCELLANEOUS STEEL, UNI-STRUT, ALL-THREAD, AIRCRAFT CABLE, ETC.
PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR ALL SINGLE PHASE CIRCUITS. A SHARED NEUTRAL
CONDUCTOR IS NOT ACCEPTABLE ON SINGLE PHASE CIRCUITS.
EQUIPMENT INTERRUPTING RATINGS INDICATED ON THE DRAWINGS ARE BASED ON PRELIMINARY INFORMATION AND ARE SHOWN FOR BIDDING PURPOSES ONLY. VERIFY EQUIPMENT INTERRUPTING CAPACITY
REQUIREMENTS PRIOR TO ORDERING ANY RELATED ELECTRICAL DISTRIBUTION EQUIPMENT.
PROVIDE NEW TYPE WRITTEN DIRECTORIES FOR ALL PANELBOARDS INSTALLED OR MODIFIED UNDER THIS
CONTRACT.
ALL CIRCUIT BREAKER LUGS SHALL BE RATED FOR A MINIMUM OF 75 DEGREES CELSIUS.
ALL MATERIALS IN CEILING PLENUMS NOT ENCLOSED IN METALLIC CONDUIT SHALL HAVE CLASS, FLAME
SPREAD AND SMOKE DEVELOPMENT RATINGS AS REQUIRED FOR USE IN OPEN PLENUMS.
VOLTAGE DROP: THE ELECTRICAL CONTRACTOR SHALL ENSURE THAT VOLTAGE DROP FOR FEEDERS TO DISTRIBUTION EQUIPMENT DOES NOT EXCEED 2% AND VOLTAGE DROP IN BRANCH CIRCUITING DOES NOT EXCEED 3% FOR OVERALL VOLTAGE DROP OF 5% (MAXIMUM). FEEDERS LISTED ON SCHEDULES AND THE ELECTRICAL ONE-LINE DIAGRAM ARE A BASE FEEDER/BRANCH CIRCUIT SIZE AND SHALL BE ADJUSTED AS
NEEDED BASED ON ACTUAL LENGTH OF CONDUCTORS.
REFER TO GENERAL NOTES FOR NUMBER OF PANEL SECTIONS AND QUANTITY OF CIRCUIT BREAKERS PANEL
SCHEDULES SUPERCEDE ALL NOTES.
REFER TO SPECIFICATIONS FOR ADDITIONAL PROJECT REQUIREMENTS.
NOTES
NOTES:
1.
2.
3.
4.
5.
6.
7.
MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE.
CONTRACTOR SHALL ENSURE THAT ALL MOUNTING HEIGHTS COMPLY WITH CURRENT
ADA AND A117.1 REQUIREMENTS.
WHERE EVER DEVICES ARE INDICATED TO BE ABOVE DOORS, DEVICE SHALL BE CENTERED BETWEEN TOP OF
DOOR TRIM AND CEILING LINE.
ALL ABOVE COUNTER (DESIGNATED BY "AC") SHALL BE MOUNTED 8" ABOVE COUNTER OR MAXIMUM HEIGHT OF
44" TO TOP OF DEVICE. VERIFY HEIGHTS WITH ARCHITECT.
FOR CEILINGS BELOW 7'-4", FIRE ALARM STROBE OR HORN/STROBES SHALL BE WALL MOUNTED 6" BELOW
FINISHED CEILING.
SWITCH TO BE MOUNTED ON LATCH SIDE OF THE DOOR WITHIN 12" OF THE DOOR.
DEVICES AT SAME HEIGHT LOCATED NEXT TO EACH OTHER TO BE ALIGNED VERTICALLY TO THE BOTTOM OF
THE DEVICE.
FACP
FAAP
CONTROL
PANELS
TH
E
EN
TI
R E
LE
N
SE
N
O T
LE
SS
T H
AN
0" A
N D
N O
T G
R
EA
TE
R
T H
AN
6" A
FF
6' -6
U
.N .O
6' -0
U
.N .O
5' -4
U
.N .O
4' -0
U
.N .O
TOP OF PANEL
TOP OF CABINET
TOP OF CABINET
TO
P
O F
D
EV
IC
E
BO
TT
O M
O F
D
EV
IC
E
" A
FF
U
.N .O
-G
YP
-B
LO
C
K
"A
FF
U .N
.O
-B
LO
C K
(6
NOTE:
ALL DEVICES INDICATED
TO BE INSTALLED AT
DIFFERENT MOUNTING
HEIGHTS AND LOCATED
WITHIN ONE STUD SPACE
FROM EACH OTHER
SHALL ALIGN VERTICALLY,
ON THE SAME SIDE OF
THE STUD. WHERE WALL
MOUNTED TELEPHONES
OCCUR OVER LIGHT
SWITCHES, VOLUME
CONTROLS, ETC. OFFSET
ONE STUD SPACE.
FINISHED FLOORNOT TO SCALE
TOP OF DEVICE
TYPICAL DEVICE MOUNTING HEIGHTS
CODES AND STANDARDS
DESIGNED UNDER THE FOLLOWING CODES AND STANDARDS:
2020 NATIONAL ELECTRICAL CODE
2023 FLORIDA BUILDING CODES
2023 FLORIDA ENERGY CONSERVATION CODE
2023 FLORIDA FIRE CODE
NFPA 72 NATIONAL FIRE ALARM CODE
A
TAG OUTLET RATING NEMA/CAT NO FEEDER (NOTE 1) WIRING NOTES
B NON-LOCKING, 30A, 125V, 1PH 5-30R 2#10,#10G,3/4"C (60FT) HOT-NEUT-GND
C NON-LOCKING, 20A, 250V, 1PH 6-20R 2#12,#12G,3/4"C (100FT) HOT-HOT-GND
D NON-LOCKING, 30A, 250V, 1PH 6-30R 2#10,#10G,3/4"C (120FT) HOT-HOT-GND
E NON-LOCKING, 50A, 250V, 1PH 6-50R 2#6,#10G,3/4"C (150FT) HOT-HOT-GND
F NOT USED - - -
G NON-LOCKING, 20A, 125/250V, 1PH 14-20R 3#12,#12G,3/4"C (100FT) HOT-HOT-NEUT-GND
H NON-LOCKING, 50A, 125/250V, 1PH 14-50R 3#6,#10G,1"C (100FT) HOT-HOT-NEUT-GND
I NOT USED - - -
J LOCKING, 20A, 125V, 1PH L5-20R 2#12,#12G,3/4"C (50FT) HOT-NEUT-GND
K LOCKING, 30A, 125V, 1PH L5-30R 2#10,#10G,3/4"C (60FT) HOT-NEUT-GND
L LOCKING, 20A, 250V, 1PH L6-20R 2#12,#12G,3/4"C (100FT) HOT-HOT-GND
M LOCKING, 30A, 250V, 1PH L6-30R 2#10,#10G,3/4"C (120FT)
N NOT USED - - -
O NOT USED - - -
P LOCKING, 20A, 125/250V, 1PH L14-20R 3#12,#12G,3/4"C (100FT) HOT-HOT-NEUT-GND
Q LOCKING, 30A, 125/250V, 1PH L14-30R 3#10,#10G,3/4"C (120FT)
R NOT USED - - -
S LOCKING, 20A, 208Y/120V, 3PH L21-20R 4#12,#12G,3/4"C (120FT) HOT-HOT-HOT-NEUT-GND
T LOCKING, 30A, 208Y/120V, 3PH L21-30R 4#10,#10G,3/4"C (130FT)
V LOCKING, 50A, 250V, 3PH HBL CS8369 3#6,#10G,1"C (175FT) HOT-HOT-HOT-GND
W PIN & SLEEVE, 60A, 208Y/120V, 3PH HBL 560R9W 4#4,#10G,1-1/4"C (200FT) HOT-HOT-HOT-NEUT-GND
X PIN & SLEEVE, 100A, 208Y/120V, 3PH HBL 5100R9W 4#1,#8G,1-1/2"C (250FT)
Y NOT USED - - -
Z NOT USED - - -
HOT-HOT-GND
HOT-HOT-NEUT-GND
HOT-HOT-HOT-NEUT-GND
HOT-HOT-HOT-NEUT-GND
NOTE: DISTANCE NOTED IS MAXIMUM RUN LENGTH FOR WIRE SIZE.
INCREASE PER NEC, INCLUDING GROUND, FOR LONGER RUNS OR FOR DERATING FACTORS (AMB TEMP, EXTERIOR, ETC.)
SYMBOLS
RECEPTACLE MODIFIER TAGS
MOTOR
MOTOR AND DISCONNECT
MOTOR AND FUSED DISCONNECT
NON-FUSED DISCONNECT
CIRCUIT BREAKER
BRANCH CIRCUIT OR POWER PANEL
FUSED DISCONNECT
LIGHTING CONTROL PANEL
VARIABLE FREQUENCY DRIVE/MOTOR CONTROLLER
MOTOR AND CIRCUIT BREAKER DISCONNECT
METER
CURRENT TRANSFORMER
GROUND
POWER TRANSFORMER
DELTA/WYE WITH GROUND
FUSE & SWITCH
CIRCUIT BREAKER
DRAWOUT CIRCUIT BREAKER
KIRK-KEY INTERLOCK
GROUND FAULT INTERRUPTER BREAKER
CIRCUIT MONITORING DEVICE
MECHANICAL EQUIPMENT IDENTIFICATION TAG
SURGE PROTECTION DEVICE
THERMAL OVERLOAD
MOTOR AND THERMAL OVERLOAD
AUTOMATIC TRANSFER SWITCH
M
K
G
D
SPD
TO
TO
T
SHORT CIRCUIT FAULT CALCULATION TAG
REFER TO TABLE ON ONE-LINE DIAGRAMX
EQUIPMENT IDENTIFICATION TAG
REFER TO ELECTRICAL EQUIPMENT SCHEDULEEQ-#
ELECTRICAL PANEL
NAME
EQUIPMENT
ELECTRICAL EQUIPMENT
FREESTANDING OR WALL MOUNT
POWER
WALL SIMPLEX RECEPTACLE
WALL DUPLEX RECEPTACLE
WALL FOURPLEX RECEPTACLE
WALL DUPLEX RECEPTACLE (EMERGENCY)
WALL FOURPLEX RECEPTACLE (EMERGENCY)
WALL SPECIAL RECEPTACLE
(FOR "X" SEE RECEPTACLE MODIFER TAGS TABLE)
X
EMERGENCY POWER OFF
X
TV
J
FLOOR DUPLEX RECEPTACLE
CEILING / FLOOR SPECIAL RECEPTACLE
(FOR "X" SEE RECEPTACLE MODIFER TAGS TABLE)
CEILING DUPLEX RECEPTACLE
CEILING FOURPLEX RECEPTACLE
CEILING RECEPTACLE
WALL CLOCK RECEPTACLE
WALL COMBINATION TV / POWER OUTLET
WALL JUNCTION BOX
FLOOR FURNITURE FEED
CEILING JUNCTION BOX
POWER POLE
SINGLE TOGGLE SWITCH
PLUGMOLD
SINGLE PUSH BUTTON
DUPLEX PUSH BUTTON
CEILING TV OUTLET
JUNCTION BOX
AV
J
WALL FURNITURE FEEDJ
J
TV
J
FLOOR FOURPLEX RECEPTACLE (POWER/DATA/COMBO
DEVICE. REFER TO TECHNOLOGY DRAWINGS)
FLOOR FOURPLEX RECEPTACLE WITH AV
(POWER/DATA/AV COMBO DEVICE.
REFER TO TECH. DRAWINGS)
CONVENTION CENTER FLOOR BOX.
EPO
WALL SPECIAL RECEPTACLE (EMERGENCY)
(FOR "X" SEE RECEPTACLE MODIFER TAGS TABLE)
X
WALL DUPLEX WITH CONTROL OF ONE OUTLET
FP FLAT PANEL BACK BOX - POWER MOUNTED WITHIN
AV BACK BOX
POWER DEVICE GENERAL NOTES:
1.
2.
3.
4.
REFER TO SPECIFICATION SECTION 26 27 26 FOR SPECIFIC
FLOOR DEVICE PRODUCT INFORMATION.
REFER TO TECHNOLOGY AND/OR AV LEGEND AND FLOOR PLANS
TO CONFIRM ALL LOCATIONS THAT HAVE DATA OR DATA/AV
REQUIREMENTS COMBINED WITH POWER IN FLOOR BOXES.
REFER TO TECHNOLOGY (AND/OR AV) DRAWINGS FOR
DEDICATED LOW VOLTAGE CONDUIT AND FLOOR BOX DEVICE
MOUNTING PLATE REQUIREMENTS. LOW VOLTAGE CONDUIT
REQUIREMENTS ARE NOT DOCUMENTED ON POWER DRAWINGS.
REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING
HEIGHTS OF TVS. MOUNT BEHIND TV DISPLAY OR ON TV
MOUNTING BRACKET/SUPPORT"
WALL DUPLEX WITH USBU
RACEWAY LEGEND
BRANCH CIRCUIT HOMERUN TO PANELBOARD.
PANEL NAME : CIRCUIT NUMBER(S)
BRANCH CIRCUIT HOMERUN CONTROLLED BY LIGHTING CONTROL SYSTEM. FIRST HEXAGON LETTER CORRESPONDS TO FIRST CIRCUIT NUMBER. (ie. CIRCUIT #2 IS ON ZONE A). REFER TO LIGHTING CONTROL MATRIX FOR LIGHTING ZONES.
UNDERGROUND FEEDER
UNDERGROUND BRANCH CIRCUIT HOMERUN
CONDUIT UP
CONDUIT DOWN
CONDUIT RUNS UNDERFLOOR OR BELOW GRADE
CONDUIT RUN CONCEALED IN WALLS OR CEILING, OR EXPOSED WHEN CEILING ARE NOT PRESENT.
A:2
A:2,4 A
MOTOR CONNECTION
STRIP LIGHT
WALL MOUNTED LINEAR
RECESSED LINEAR
SURFACE MOUNTED 2'X4'
SURFACE MOUNTED 2'X2'
SURFACE MOUNTED 1'X4'
RECESSED WALL / STEP LIGHT
WALL MOUNTED FLOODLIGHT
WALL MOUNTED SCONCE
SURFACE MOUNTED WALL WASH
SURFACE MOUNTED DOWN LIGHT
RECESSED DOWN LIGHT
RECESSED WALL WASH
RECESSED 1X4 WALL WASH
PENDANT LIGHT
MONOPOINT TRACKHEAD
LINEAR LIGHT
TRACK WITH TRACKHEADS
POLE MOUNTED LIGHT WITH ARM
POLE MOUNTED LIGHT POST TOP MOUNTING/BOLLARD
EMERGENCY LIGHTING UNIT
TOUCH SCREEN CONTROL STATION
OCCUPANCY SENSOR - CEILING MOUNTED
OCCUPANCY SENSOR - WALL BOX 180°
SWITCH - SINGLE POLE
SWITCH - 3 WAY
SWITCH - 4 WAY
POWER SUPPLY
DAYLIGHT SENSOR - CEILING MOUNTED
TS
BURIAL FIXTURE
SCENE CONTROL STATION
S
DIMMER/OCCUPANCY SENSOR COMBINATION SWITCH
OS
RECESSED 2'X4'
RECESSED 2'X2'
WALL MOUNTED STRIP LIGHT
DIMMER SWITCH
LIGHTING
PS
ABBREVIATIONS
V
VFD
VM
V VOLT
VARIABLE FREQUENCY DRIVE
VOLTMETER
VAV VARIABLE AIR VOLUME
VA VOLT-AMPERE
W W W/
WATT
WITH
W/O WITHOUT
WLAN WIRELESS-LOCAL AREA NETWORK
XFMR
WPL
WHM
WP
XP
WT
WH
WEATHER PROOF LOCKABLE ENCLOSURE.
WATT HOUR METER
EXPLOSION PROOF
WEATHERPROOF
WATERTIGHT
TRANSFORMER
WATT HOUR
X
MAIN BREAKERS
MILLIAMPERE
MAXIMUMMAX
MB
MA
MTGB
OD
NTS
NIC
NEC
OC
NO
NC
NF
N
MV
MAIN TELECOMMUNICATIONS GROUND BUS
OUTSIDE DIAMETER
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
ON CENTER
MEDIUM VOLTAGE
NEUTRAL
NON FUSED
MPOE
MDF
MTG
MSB
MTD
MOV
MTG
MLO
MIN
MFR
MECH
MDP
MCC
MCP
MS
MH
MC
MAIN POINT OF ENTRY
MAIN SWITCHBOARD
MANHOLE
MOTOR OPERATED VALVE
MOUNTING HEIGHT
MOTOR STARTER
MOUNTED
MOUNTING
MAIN LUGS ONLY
MINIMUM
MAIN DISTRIBUTION FRAME
MAIN DISTRIBUTION PANEL
MOTOR CIRCUIT PROTECTOR
MOTOR CONTROL CENTER
MECHANICAL CONTRACTOR OR METAL CLAD
MANUFACTURER
MECHANICAL
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
M
MOCP MAXIMUM OVERCURRENT PROTECTION
MTS MANUAL TRANSFER SWITCH
N
NL NIGHT LIGHT
O
OCP OVERCURRENT PROTECTION
OH OVERHEAD
SERVICE PROVIDERSP
SECURITY CONTROL PANELSCP
SMPOE
SWBD
STD
SHT
SPDT
SECT
SEC
RPM
REC
RGS
PRI
PVC
PWR
PNL
PR
SW
ST
RM
R
P
PT
PH
PF
PE
PA
PB
SECONDARY MAIN POINT OF ENTRY
SINGLE POLE, DOUBLE THROW
SWITCHBOARD
STANDARD
SWITCH
SHUNT TRIP
SECONDARY/SECOND
RIGID GALVANIZED STEEL
REVOLUTIONS PER MINUTE
SHEET
SECTION
ROOM
RECEPTACLE
POWER
EXISTING TO RELOCATE
POLE
POLYVINYL CHLORIDE
POTENTIAL TRANSFORMER
PUBLIC ADDRESS
PRIMARY
PANEL
PHASE
PAIR
POWER FACTOR
PUSH BUTTON
PHOTOELECTRIC
SURGE PROTECTIVE DEVICESPD
P
R
S
SWGR SWITCHEAR
T
TELCOM
TGB
UNO
UPS
UG
TEMP
TELCO
UL
UH
UC
TELECOMMUNICATIONS
TELECOMMUNICATIONS GROUND BUS
UNINTERRUPTIBLE POWER SUPPLY
UNDERWRITER LABORATORIES
UNLESS NOTED OTHERWISE
TELEPHONE COMPANY
UNDERGROUND
UNIT HEATER
TEMPERATURE
UNDER COUNTER
TBB
TEL
TC
T
TELECOMMUNICATIONS BONDING BACKBONE
TIME CLOCK
TWIST LOCK
TELEPHONE
TR TAMPER RESISTANT
TBD TO BE DETERMINED
TO THERMAL OVERLOAD
TYP TYPICAL
USB UNIVERSAL SERIAL BUS
U
UGP UNDERGROUND PRIMARY
UGS UNDERGROUND SECONDARY
ABOVE COUNTER
ANNUNCIATOR
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
AUTOMATIC TRANSFER SWITCH
AMPERE FUSE/FRAME
AMERICAN WIRE GAUGE
ANTENNA
AUTOMATIC
AUXILIARY
AWG
AUX
ANT
AUTO
ATS
ALUMINUM
AMMETER
ANN
AM
AL
AFG
AF
AFF
AMPERE
AC
A/AMP
AIR HANDLING UNITAHU
AMPERE INTERRUPTING CAPACITYAIC
AVAILABLE SHORT-CIRCUIT CURRENTASC
A
EXISTING TO BE REMOVED/RELOCATED
FOOTCANDLES
ELECTRIC WATER HEATER
FURNISHED BY OTHERS
FIRE ALARM CONTROL PANEL
ELECTRIC WATER COOLER
FLEXIBLE
FLOOR
FAN COIL UNIT
FLEX
FLR
FCU
FC
FBO
EXHAUST
FIRE ALARM
FUSE
F/A
FACP
F
EWH
EXH
EQUIPMENTEQP
ER
EWC
FIRE ALARM TERMINAL CABINETFATC
FEEDERFDR
F
FIRE ALARM POWER SUPPLYFAPS
FULL LOAD AMPSFLA
FAN POWERED BOXFPB
FUTUREFUT
INTERMEDIATE CROSS CONNECTIC
HC HORIZONTAL CROSS CONNECT
INTERMEDIATE DISTRIBUTION FRAME
HORSEPOWER
HAND-OFF-AUTO
INSIDE DIAMETER
INTERMEDIATE GRADE METALLIC CONDUIT
HIGH POWER FACTOR
HEATERHTR
IDF
ID
IMC
HAND HOLE
HOA
HP
HPF
HH
GROUND FAULT CIRCUIT INTERRUPTER
GALVANIZED
GENERATOR
HEAVY DUTY
GROUND
HD
GFCI
GND
GEN
GALV
GROUNDING BUSGB
G
H
I
KILOVOLT AMPERE
KILOWATT HOUR
JUNCTION BOX
THOUSAND OF CIRCULAR MILLSKCMIL/MCM
KILOWATT
KWH
KVA
KW
J-BOX
AUDIO CONNECTION BOXJBA
COACHES JUNCTION BOXJBC
ENG BROADCAST BOXJBE
NETWORK BROADCAST CONNECTION BOXJBT
K
J
L
LOCAL AREA NETWORKLAN
LIGHTNING ARRESTORLA
LIGHTING CONTROL PANELLCP
LIGHT EMITTING DIODELED
LIQUID TIGHT FLEXIBLE CONDUITLFC
LOW VOLTAGE
LOW TEMPERATURE RATED DEVICES OR SIMILARLT
LV
LIGHTINGLTG
ELECTRIC VEHICLEEV
PV PHOTOVOLTAIC
SEC SECONDARY CONNECTION CABINET
AUTOMATIC LOAD CONTROL RELAY (UL924)EM
OCCUPANCY SENSOR - CEILING/WALL MOUNTED 180°
DIMMER SWITCH - LOW VOLTAGE
LV
MTR MAIN TELECOM ROOM
Q
QE QUADRANT ELECTRICAL (ARENA SPECIFIC)
QT QUADRANT TELECOM (ARENA SPECIFIC)
COMPANY SWITCH OR CAM-LOK PANEL
B OR
GENERATOR DOCKING STATION
NOT USED - - -
LINEAR PENDANT
RECESSED LIGHTING FIXTURE W/DOWNLIGHTS
LINEAR PENDANT W/DOWNLIGHTS
CAMERACAM
CIRCUIT BREAKER
CONDUIT ONLY
CLOSED CIRCUIT TELEVISION
COMBINATION
CURRENT TRANSFORMER
COMPUTERCOMP
COPPER
CONDUCTOR
CU
CT
COND
CIRCUITCKT
COMB
CO
CB
CCTV
BELOW FINISHED CEILING
BELOW FINISHED GRADE
CONDUIT
CABINET
BREAKER
CAB
C
BFC
BFG
BKR
BACK OF HOUSEBOH
C
BUS-WAYBW
DIGITAL VIDEO RECORDERDVR
F/A END OF LINE RESISTOR
ELECTRONIC NEWS GATHERINGENG
EOL
DEMARCATION
ELECTRIC HEATING COIL
ELECTRIC OR ELECTRICAL
ELECTRIC METALLIC TUBING
DAMP LABEL
ELECTRICAL CONTRACTOR
EXHAUST FAN
EQUIPMENT GROUND
DISCONNECTDISC
ELEVATOR
EMERGENCY
EHC
EM
EMT
ELEC
ELEV
EG
DRAWING
EACH
EF
EA
EC
DWG
DL
DECIBEL
DEMARC
dB
EXISTINGE/EX
DEMOLISHD
DISTRIBUTION PANELDP
D
E
DOUBLE POLE, DOUBLE THROWDPDT
DISTRIBUTED ANTENNA SYSTEMDAS
EMERGENCY POWER OFFEPO
LV SWITCH - LOW VOLTAGE
LIGHTING CONTROL
ROOM CONTROLLERRC
CEILING MOUNTED EXIT SIGN
EXIT SIGN WITH ARROWS
WALL MOUNTED EXIT SIGN
SHADED PORTION
DENOTES
FACE LOCATION(S)
GENERAL NOTES:
226-350 FT
151-225 FT
101-150 FT
0-100 FT
LENGTH (2) WIRE SIZE CONDUIT
120V CIRCUITS:
SINGLE-PHASE 20-AMP CIRCUIT CONDUCTOR SIZING DUE TO VOLTAGE DROP
376-600 FT
251-375 FT
176-250 FT
0-175 FT
LENGTH (2) WIRE SIZE CONDUIT
208V/240V/277V CIRCUITS:
676-1000 FT #6 (1) 1-1/4"
451-675 FT #8 1"
276-450 FT #10 3/4"
0-275 FT #12 3/4"
LENGTH (2) WIRE SIZE CONDUIT
480V CIRCUITS:
#6 (1) 1-1/4"
#8 1"
#10 3/4"
#12 3/4"
#6 (1) 1-1/4"
#8 1"
#10 3/4"
#12 3/4"
(1) FOR TERMINATING IN PANELBOARDS, PROVIDE A UL486A/B LISTED, HYDRAULICALLY-APPLIED COMPRESSION PIN ADAPTER TERMINAL WITH INSULATED COVER THAT IS DESIGNED FOR #6 AWG COPPER
CONDUCTOR TO #8 PIN SIZE.
(2) CIRCUIT LENGTH IS MEASURED ONE-WAY TO THE THEORETICAL CENTER OF THE ELECTRICAL LOAD.
(3) GROUND CONDUCTOR TO BE UPSIZED BY THE SAME PERCENTAGE AS PHASE CONDUCTORS.
(4) WHERE SPECIFIC CONDUCTOR SIZES ARE INDICATED ON PLANS OR SCHEDULES, CONDUCTORS MUST STILL BE UPSIZED FOR VOLTAGE DROP ACCORDING TO THE CIRCUIT LENGTH PER THIS SCHEDULE.
FIRE ALARM
SMOKE DETECTOR
HEAT DETECTOR
DUCT DETECTOR
BEAM DETECTOR RECEIVER
BEAM DETECTOR TRANSMITTER
VOICE EVAC PANEL
ELEVATOR STATUS PANEL
FIRE SERVICE PHONE
ROTATING BEACON
MANUAL PULL STATION
TAMPER SWITCH
FLOW SWITCH
CEILING MOUNTED REMOTE INDICATOR LIGHT
WALL MOUNTED REMOTE INDICATOR LIGHT
WALL MOUNTED ADA STROBE
FIRE SMOKE DAMPER
CEILING MOUNTED STROBE
FIREMAN'S PHONE JACK
MAGNETIC DOOR HOLD OPEN DEVICE
ADDRESSABLE INPUT MODULE
FIRE ALARM ADDRESSABLE RELAY
ALARM BELL
SMOKE CONTROL DAMPER
CARBON MONOXIDE DETECTOR
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
WALL MOUNTED SILENTONE
WALL SMOKE DETECTOR
SMOKE/CARBON MONOXIDE DETECTOR
WALL SMOKE/CARBON MONOXIDE DETECTOR
TWO-WAY COMMUNICATION / AREA OF RESCUE
ASSISTANCE CALL BUTTON
TWO-WAY COMMUNICATION / AREA OF RESCUE
ASSISTANCE (BASE STATION)
BR
BT
CO
CO
EVAC
ESR
S
H
J
DH
RTS
RTS
IM
FR
FR
FAAP
FACP
TWC
TWCP
CO
CEILING MOUNTED
WALL MOUNTED
CEILING MOUNTED
WALL MOUNTED
SPEAKER
SPEAKER/STROBE
SPEAKER
SPEAKER/STROBE
1.
2.
SOME LIGHTING FIXTURE SYMBOLS APPEAR AS A 2D
PROJECTION OF A 3D ELEMENT AND MAY NOT APPEAR IN THIS
LEGEND. REFER TO FIXTURE TYPE AND LIGHTING FIXTURE
SCHEDULES FOR ADDITIONAL INFORMATION.
SHADED SYMBOLS DENOTE EMERGENCY FIXTURES
LIGHTING DEVICE GENERAL NOTES:
De nv er
W es t P kw y, S ui te
, G ol de n, C O
3.
1.
w
.m e-en gi ne er s.
co m
SHEET TITLE:
ISSUANCE
ISSUE DATE:
PROJECT #:
KEY PLAN
TRUE NORTHPLAN NORTH
4/
/2
:4 5:
A
M C
:\R ev it Pr oj ec ts \2
3\
R
JS
C on c Fa ns M
E_ R
_T ay lo r.W or le y.
rv t
04/02/2025
ELECTRICAL
LEGEND
E0-0
DV2503…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .