Sheet1 Attachment 2 - EXHIBIT 2 - NPS WWI Memorial Equipment, Systems, and Maintenance Items
LIGHTING
Equipment Qty Structure Room Location Description Required Maintenance
| Interior Lights | ||||||
| G | 12 | 01 Storage | West Below Grade Structure | LED vaportight linear indoor rated | Maintain fixture and replace LED board if outage occurs | |
| G2 | 3 | 01 Storage | West Below Grade Structure | LED vandal-proof indoor sconce | Maintain fixture and replace LED board if outage occurs | |
| E1 | 3 | 01 Storage | West Below Grade Structure | LED thermoplastic emergency battery unit | Self-diagnostic test button monthly to confirm battery is charging properly | |
| E2 | 2 | 01 Storage | West Below Grade Structure | LED thermoplastic emergency battery unit and exit sign | Self-diagnostic test button monthly to confirm battery is charging properly | |
| G | 3 | 02 Electrical Room | West Below Grade Structure | LED vaportight linear indoor rated | Maintain fixture and replace LED board if outage occurs | |
| E1 | 1 | 02 Electrical Room | West Below Grade Structure | LED thermoplastic emergency battery unit | Self-diagnostic test button monthly to confirm battery is charging properly | |
| G | 2 | 03 Stair | West Below Grade Structure | LED vaportight linear indoor rated | Maintain fixture and replace LED board if outage occurs | |
| G1 | 1 | 03 Stair | West Below Grade Structure | LED vaportight linear outdoor rated | Maintain fixture and replace LED board if outage occurs | |
| E1 | 2 | 03 Stair | West Below Grade Structure | LED thermoplastic emergency battery unit with wet guard | Self-diagnostic test button monthly to confirm battery is charging properly | |
| G | 8 | 04 Fountain Equipment Room | West Below Grade Structure | LED vaportight linear indoor rated | Maintain fixture and replace LED board if outage occurs | |
| E1 | 1 | 04 Fountain Equipment Room | West Below Grade Structure | LED thermoplastic emergency battery unit | Self-diagnostic test button monthly to confirm battery is charging properly | |
| Exterior Lights | ||||||
| FA/FA-1 | 29 | Outdoors | 15th Street, Pennsylvania Ave, 14th Street | LED Pole | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FB/FB-1 | 38 | Outdoors | Throughout | LED Pole | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FC | 40lf | Outdoors | Pershing Memorial | LED Bench Light | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FD/FD-1 | 34 | Outdoors | Belvedere, South Berm Ramp, Lower Plaza (North) | LED Step Light | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FE/FE-1 | 51lf | Outdoors | Pershing Memorial | LED Strip Light | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FF | 9 | Outdoors | Pennsylvania Ave | LED Pole | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FG | 61lf | Outdoors | Belvedere | LED Strip Light | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FJ/FJ-1 | 2 | Outdoors | South Terrace, Lower Plaza (North) | LED Pole | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FK | 14 | Outdoors | Pool | LED Fountain Light | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FL | 2 | Outdoors | Pershing Memorial | LED Pole | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FM | 12 | Outdoors | Upper Terrace | LED Uplight | Maintain fixture and replace LED board and / or driver if outage occurs | |
| FR | 12 | Outdoors | Upper Terrace | LED Pole | Maintain fixture and replace LED board and / or driver if outage occurs | |
| PLUMBING SYSTEMS |
Equipment Qty Structure Room Location Description Required Maintenance
| Condensate Sump Pump | 1 | Security Closet | Little Giant Model VCMA-15 | Annual - Inspect Unit, clean tank and line, manually operate valve. | |
| Trap Primer Valve | 1 | Fountain Equipment Room | PPP Model PT1320 | Annual - Inspect Unit, manually test operation with traps exposed to verify. | |
| Fixtures | |||||
| Drinking Fountain | 1 | Outdoors | MDF Model 10145SMFA | Maintain Fixture with no longer than a 24 hour down time during the active season As Needed - Unclog and Repair Valves faucets, etc. |
Every 6 Months - Rebuild Regulators
| *toilet | *Future addition of restroom | ||||
| *sink | *Future addition of restroom | ||||
| *mop sink | *storage area | ||||
| Drainage | |||||
| Floor Drain | 3 | Fountain Equipment Room | Josam Model 32300-81 | As Needed - Unclog/snake | |
| Backflow Preventer | |||||
| Backflow Preventer | 1 | Fountain Equipment Room | Zurn Model 375XL | Annual - Test, Calibrate, and Certify by Certified Backflow Technician and repair as |
needed
| Backwater Valve BWV-1 | Fountain Equipment Room | Josam Model 67500 | Annual - Inspect/clean |
| Backwater Vavle BWV-2 | Fountain Equipment Room | Josam Model 67720 | Annual - Inspect/clean |
MECHANICAL SYSTEMS
Equipment Qty Structure Room Location Description Required Maintenance
EF-1 1 Fountain Equipment Room Inline - Suspended Greenheck Model BSQ-180-5 Every 3 Months - Check Belt Tension (Adjust/Replace When Needed) Annual - Lubricate SAE 20 Electric Motor Oil Annual Exercise Shutoff Switch
| EF-2 | 1 | Electrical Room | Inline - Suspended | Greenheck Model BSQ-070-4 | |
| EF-3 | 1 | Storage | Inline - Suspended | Greenheck Model BSQ-130HP-3 | |
| UH-1 | 1 | Fountain Equipment Room | Propeller | Markel Model F2F5103N | Annual - Inspect unit and Clean Unit Casing, Fan, and Motor |
Annual - Inspect Wiring and Contactors Annual - Exercise Shutoff Switch
| UH-2 | 1 | Fountain Equipment Room | Propeller | Markel Model F2F5103N | |
| UH-3 | 1 | Fountain Equipment Room | Propeller | Markel Model F2F5103N | |
| UH-4 | 1 | Fountain Equipment Room | Propeller | Markel Model F2F5103N | |
| UH-5 | 1 | Storage | Wall Mounted | Markerl Model J3455T | Annual - Inspect unit and Clean Unit Casing, Fan, and Motor |
Annual - Inspect Wiring and Contactors Annual - Exercise Shutoff Switch UH-6 1 Electrical Room Propeller Markel Model F2F5105N Annual - Inspect unit and Clean Unit Casing, Fan, and Motor Annual - Inspect Wiring and Contactors Annual - Exercise Shutoff Switch
| UH-7 | 1 | Storage | Propeller | Markel Model F2F5105N | |
| UH-8 | 1 | Storage | Propeller | Markel Model F2F5105N | |
| UH-9 | 1 | Storage | Propeller | Markel Model F2F5105N | |
| UH-10 | 1 | Storage | Propeller | Markel Model F2F5105N | |
| UH-11 | 1 | Storage | Propeller | Markel Model F2F5105N | |
| UH-12 | 1 | Storage | Wall Mounted | Markerl Model J3455T | Annual - Inspect unit and Clean Unit Casing, Fan, and Motor |
Annual - Inspect Wiring and Contactors Annual - Exercise Shutoff Switch ACU-1 1 Security Closet Wall Mounted Mitsubishi Model PUY-A24NHA7 Monthly - Inspect Unit and Replace Filters Monthly - Inspect and Replace Belt as Needed (B-55) Every 3 Months - Check/Add Refrigerant as Needed Annual - Inspect Contactors, Wiring and Relays Annual - Exercise Shutoff Switch ACCU-1 1 Storage Wall Mounted Mitsubishi Model PKA-A24KA7 Monthly - Inspect unit Every 3 Months - Check/Add Refrigerant as Needed Annual - Inspect/Tighten Wiring Annual - Clean Unit Annual - Exercise Shutoff Switch Annual - Clean Condenser Coils Fire Dampers 6 Electrical Room Duct Mounted Ruskin DIBD40 Annual - Inspect/test per NFPA
ELECTRICAL SYSTEMS
Equipment Qty Structure Room Location Description Required Maintenance
| System | ||||||
| Electrical Distribution System | 1 | West Below Grade Structure | Utility meter, distribution switchboard, panelboards, lighting and controls, mechanical equipment, water feature equipment | As required: A licensed electrician should be available to troubleshoot and repair electrical malfunctions. | ||
| Grounding and Bonding | 1 | Pool | Equipotential grounding grid below pool surfaces | Annual test to ensure integrity of grounding and bonding system to protect patrons that may enter the water feature areas. | ||
| Lighting Protection | 1 | Flag pole, sculpture | Lightning protection conductors, air terminals, and copper plates | Annual test to inspect connections and ensure integrity of system. | ||
| Panels | ||||||
| DP-1 | 1 | Electrical Room | West Below Grade Structure | 2000A, 208Y/120V,3PH,4W switchboard, service entrance rated | Annual - clean dust from panelboard interiors and electrical room Annual - inspect for loose wiring connections and tighten. | |
| RP1 | 1 | Electrical Room | West Below Grade Structure | 100A MLO, 208Y/120V,3PH,4W receptacle panelboard, 42-poles | ||
| LP1 | 1 | Electrical Room | West Below Grade Structure | 225A MLO, 208Y/120V,3PH,4W lighting panelboard, 54-poles | ||
| CPPA | 1 | Fountain Equipment Room | West Below Grade Structure | 300A MCB, 208Y/120V,3PH,4W water feature panelboard | ||
| Lighting Racks | ||||||
| Lighting Control Panel | 2 | Electrical Room | West Below Grade Structure | 24/32-pole lighting relay panels for site lighting controls | Biannual cleaning of dust from interior of panels, fans, and filters. | |
| GFCI | ||||||
| GFCI receptacles | West Below Grade Structure | GFCI rated receptacles | Annual - test GFCI and reset, clean from dust and debris | |||
| GFCI receptacles | Site | GFCI rated receptacles with weatherproof cover | Annual - test GFCI and reset, clean from dust and debris, replace damaged covers |
IRRIGATION SYSTEM
| Equipment | Qty | Structure | Room | Location | Description | Required Maintenance |
| Pump | 1 | Fountain Equipment Room (04) | West Below Grade Structure | Model No.: SHSTV-1-(?K)-3-460-3-21-60 | Turn off the pump in late october to early november, turn on in spring (after last frost) - refer to winterization procedure |
per warranty, during warranty period
| Raindbird controller | 1 | Fountain Equipment Room (04) | West Below Grade Structure | ESP4ME3 w/ expansion ESPSM6 | bi-weekly to monthly use the water budget feature to adjust system run times based on current weather conditions |
| Wireless rain/freeze sensors | 1 | Exterior wall (TBD) | model WR2-RFC | ||
| Dripline | 20K' | All through out the landscaping | Rain Bird XFCV-06-12 | Visually check for leaks weekly repair as needed | |
| Air Relief Valve | 18 | In landscaped beds | Rain Bird ARV050 | Keep area around valve clear |
BRONZE SCULPTURE CONSERVATION
Material Qty Structure Area/Item Required Maintenance
Bronze 1 Sculpture* Fountain Wall (install late '23 NLT May '24) Triannual - Wash, cold wax and buff Quarterly - Remove cobwebs (4 times per year) 3rd year of contract - Hot wax
| 1 | Medallion | Belvedere | ||
| 1 | Pershing Statue | |||
| Tactile Model | Belvedere | |||
| Skate Stops | Triannual - Wash, cold wax and buff | |||
| Handrails | Annual - clean with soft cotton rag and mild degergent, spot patinate as needed | |||
| GENERAL MASONRY CLEANING |
Equipment Qty Structure Location Required Maintenance
Granite Masonry Biannual - cleaning of general soiling Every five years - Handwash with non-acidic gel/heat pressurized water, rinse until neutral pH achieved
| WATER AND POOL FEATURES | ||||||
| See Fountain Technologies O & M manuals for additional maintenance routine | ||||||
| Equipment | Qty | Structure | Room | Location | Description | Required Maintenance |
| Pool Area Caulking | Total Caulk | Prior to Spring Startup - Repair/Caulk Pool Joints Approx. Recaulk up to 500 LF | |||
| Pumps | |||||
| DP-1 | 1 | Fountain Equipment Room | 15 HP Display Feature Pump | Monthly | |
| DP-2 | 1 | Fountain Equipment Room | 25 HP Display Feature Pump | Visual Inspection for corrosion Odor test for burnt windings | |
| DP-3 | 1 | Fountain Equipment Room | 5 HP Display Feature Pump | Odor test for burnt windings | |
| FP-1 | 2 | Fountain Equipment Room | 7.5 HP Filter Pump | Heat test for over heating of motors & operating temperature | |
| RP-1 | 1 | Fountain Equipment Room | 3 HP Recirculating Pump | ||
| Filtration Tanks | |||||
| FA-1 | 1 | Fountain Equipment Room | Filter Assembly | Weekly - Pressure change increase check & back wash system as required | |
| BS-1 | 1 | Fountain Equipment Room | 16" Basket Strainer | Daily - Visual Inspection for debris and clean out as required | |
| BS-2 | 1 | Fountain Equipment Room | 10" Basket Strainer | Daily - Visual Inspection for debris and clean out as required | |
| Water Treatment | |||||
| CHMT-1 | 3 | Fountain Equipment Room | 40 Gallon Tank | Daily - Visual Inspection for liquid chemical levels and fill as required | |
| CHMP-1 | 3 | Fountain Equipment Room | Chemical Pumps | Weekly - Visual inpsection of pumps & verification of operating parameters | |
| UV -1 | 1 | Fountain Equipment Room | UV Sterilizer and UV Strainer | Weekly - UV bulb inspection, operating temperature, dosing rate | |
| Monthly - UV bulb cleaning | |||||
| WH-1 | 1 | Fountain Equipment Room | Hot Water Heater | Daily - Winter season check tempertaure set points are being maintained | |
| WH-2 | 1 | Fountain Equipment Room | Hot Water Heater | Daily - Winter season check tempertaure set points are being maintained | |
| Fountain Electrical Equipment | |||||
| VFD-1 | 1 | Fountain Equipment Room | 15 HP Variable Frequency Drive | Monthly - Audio check of proper operation, manual inspection for overheating | |
| VFD-2 | 1 | Fountain Equipment Room | 25 HP Variable Frequency Drive | Monthly - Audio check of proper operation, manual inspection for overheating | |
| VFD-3 | 1 | Fountain Equipment Room | 5 HP Variable Frequency Drive | Monthly - Audio check of proper operation, manual inspection for overheating | |
| VFD-4 | 1 | Fountain Equipment Room | 7.5 HP Variable Frequency Drive | Monthly - Audio check of proper operation, manual inspection for overheating | |
| VFD-5 | 1 | Fountain Equipment Room | 3 HP Variable Frecuency Drive | Monthly - Audio check of proper operation, manual inspection for overheating | |
| CPPA-1 | 1 | Fountain Equipment Room | Control Panel | Quarterly - Visual check for burnt or loose connections, HMI check for errors | |
| UV -1 | 1 | Fountain Equipment Room | UV Sterilizer Control Panel | Quarterly - Visual check for burnt or loose connections | |
| WT-1 | 1 | Fountain Equipment Room | Water Treatment Controller | Daily - Manually check chemical readings to pool water samples, alarms or errors | |
| Fountain Miscellaneous Equipment | |||||
| EW-1 | 1 | Fountain Equipment Room | Emergency Eyewash & Heater | Quarterly - Manual check for proper operation | |
| V-X | Fountain Equipment Room | Motorized, Actuated, Solenoid Controlled Valves | Quarterly - Manual check for proper operation |