This document appears to contain several related files regarding a federal contract opportunity to replace the HVAC systems at the Maintenance and Curatorial buildings in Skagway, Alaska.
The key details include:
- The solicitation number is 140P9724R0010, with the opportunity titled "Replace HVAC at Maintenance & Curatorial Bldgs - Skagway AK".
- The federal agency involved is the Department of the Interior National Park Service Alaska Region.
- The document includes building-specific HVAC load calculations, equipment sizing, pump head loss calculations, and humidity load calculations to support the HVAC replacement requirements.
- There are also flue/vent sizing calculations for the boiler and heating equipment.
- No specific award date or pricing terms are provided, but the opportunity appears to be for a solicitation with an unspecified response deadline.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| B08_Attachment_10_Payment_Bond.pdf | ||
| Sol_140P9724R0010.pdf | ||
| B08_Attachment_13_-_Project_Design_-_Combined.pdf | ||
| B08_Attachment_5_-_CloseoutandOM_KLGO_Mech_and_Elect_10_12.xls | XLS spreadsheet | |
| B08_Attachment_11_Performance_Bond.pdf | ||
| B08_Attachmen_12_-_Subcontracting___Worksheet.xlsx | XLSX spreadsheet | |
| B08_Attachmen_12_-_Subcontracting___Worksheet_1.xlsx | XLSX spreadsheet | |
| B08_Attachment_3_-_Curatorial_Photos.pdf | ||
| B08_Attachment_4__KLGO_248830_CM-16_Submittal_Form.doc | DOC document | |
| B08_Attachment_1_Combo_Div_1___Specs.pdf | ||
| B08_Attachment_7__ITM_Hot_Work_Permit.pdf | ||
| B08_Attachment_6_-_SubmittalList-KLGO_Mech_and_Elect_3_14_24.xls | XLS spreadsheet | |
| B08_Attachment_9_Past_Performance_Questionnaire_Aug_2021.doc | DOC document |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
11/29/22, 2:32 PM about:blank about:blank 1/2
2017 ASHRAE Handbook - Foundamentals (IP)
SKAGWAY AP, AK, USA (WMO: 703620)
Lat:59.456N Long:135.324W Elev:20 StdP: 14.69 Time zone:-9.00 Period:96-14 WBAN:25335 Annual Heating and Humidification Design Conditions
Coldest Month
Heating DB Humidification DP/MCDB and HR Coldest month WS/MCDB MCWS/PCWD to 99.6% DB99.6% 99% 0.4% 1%
99.6% 99% DP HR MCDB DP HR MCDB WS MCDB WS MCDB MCWS PCWD
1 0.8 5.8 -18.8 2.0 2.8 -14.0 2.6 7.6 39.9 20.1 36.8 22.2 24.8 30
Annual Cooling, Dehumidification, and Enthalpy Design Conditions
Hottest Month
Hottest Month
DB
Range
Cooling DB/MCWB Evaporation WB/MCDB MCWS/PCWD to 0.4% DB0.4% 1% 2% 0.4% 1% 2%
DB MCWB DB MCWB DB MCWB WB MCDB WB MCDB WB MCDB MCWS PCWD
7 10.5 71.6 57.4 67.7 55.9 64.5 55.0 59.1 67.8 57.6 64.8 56.4 62.6 10.6 210 Dehumidification DP/MCDB and HR Enthalpy/MCDB Extreme
Max
WB
0.4% 1% 2% 0.4% 1% 2% DP HR MCDB DP HR MCDB DP HR MCDB Enth MCDB Enth MCDB Enth MCDB
55.2 64.8 60.0 54.2 62.6 59.2 53.3 60.6 58.4 25.6 67.9 24.8 65.2 24.0 62.7 77.0
Extreme Annual Design Conditions
Extreme Annual WS
Extreme Annual Temperature n-Year Return Period Values of Extreme Temperature
Mean Standard deviation n=5 years n=10 years n=20 years n=50 years
1% 2.5% 5% Min Max Min Max Min Max Min Max Min Max Min Max
33.7 29.8 26.6 DB -0.2 78.8 4.7 4.6 -3.6 82.1 -6.3 84.8 -9.0 87.4 -12.4 90.7
WB -1.7 62.1 4.7 4.8 -5.1 65.5 -7.8 68.3 -10.4 71.0 -13.8 74.5
Monthly Climatic Design Conditions
Annual Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Temperatures, Degree-Days and Degree-
Hours
DBAvg 42.0 26.5 30.2 32.2 40.9 49.4 55.3 57.2 56.4 50.7 43.0 33.1 28.7 DBStd 13.00 11.83 8.68 7.75 4.94 4.79 3.70 3.22 3.54 3.78 4.90 8.19 9.12
HDD50 3602 727 554 551 279 70 2 0 1 34 218 506 660
HDD65 8384 1192 974 1016 723 485 293 242 269 428 681 956 1125
CDD50 697 0 0 0 6 51 160 224 198 56 2 0 0
CDD65 4 0 0 0 0 0 1 1 2 0 0 0 0
CDH74 57 0 0 0 0 2 15 18 22 0 0 0 0
CDH80 10 0 0 0 0 0 0 5 5 0 0 0 0
Wind WSAvg 10.4 14.0 12.0 11.9 9.1 9.7 10.0 9.4 8.0 8.5 9.2 10.6 12.3
Precipitation
PrecAvg 40.60 3.90 3.20 2.60 2.10 1.60 1.50 1.70 2.90 5.20 6.90 4.80 4.30 PrecMax 66.90 11.00 6.00 8.50 6.80 3.80 3.80 4.30 6.40 11.30 16.40 12.10 9.30 PrecMin 26.50 0.70 0.00 0.00 0.10 0.20 0.30 0.60 0.10 1.70 1.20 0.20 0.20 PrecStd 8.10 2.30 1.60 1.70 1.50 0.80 0.80 0.80 1.50 1.90 3.20 2.60 2.00
Monthly Design Dry Bulb and
Mean Coincident Wet Bulb
Temperatures
0.4% DB 47.2 46.1 50.3 68.0 72.1 76.2 75.3 76.6 67.2 55.5 48.6 48.6
MCWB 41.7 39.7 40.3 50.3 53.1 58.7 59.8 56.8 52.9 49.5 43.9 44.6
2% DB 43.7 43.5 45.3 58.0 66.3 70.3 69.7 69.7 62.0 53.0 45.9 44.9
MCWB 39.7 38.6 38.6 44.4 51.0 58.1 58.4 57.7 52.6 47.3 41.6 41.2
5% DB 41.8 41.8 43.1 52.6 62.2 66.0 65.8 65.5 58.3 51.3 44.2 42.6
MCWB 38.2 37.8 38.0 42.3 49.9 55.7 56.9 56.3 51.8 46.2 40.2 39.1
10% DB 39.8 39.9 41.3 48.8 58.3 62.7 63.0 62.5 56.2 49.6 42.6 40.0
MCWB 36.7 36.3 36.8 41.2 48.5 54.1 55.9 55.5 51.0 44.8 39.1 37.0
11/29/22, 2:32 PM about:blank about:blank 2/2
Monthly Design Wet Bulb and
Mean Coincident Dry Bulb
Temperatures
0.4% WB 43.2 41.5 42.3 50.7 55.8 63.4 60.6 60.3 57.1 50.9 44.9 45.0
MCDB 45.9 44.8 46.7 66.7 65.0 67.5 71.0 71.2 63.4 54.0 47.5 48.2
2% WB 40.4 39.8 40.3 46.2 52.7 58.5 58.9 58.6 54.7 49.2 42.5 41.6
MCDB 43.5 42.8 44.0 55.2 63.1 67.7 67.3 66.5 59.3 51.9 45.0 44.6
5% WB 38.6 38.3 38.7 43.7 51.0 56.4 57.5 57.3 53.1 47.4 40.9 39.4
MCDB 41.3 41.1 42.1 50.2 59.7 64.5 64.3 63.6 56.5 50.2 43.5 42.0
10% WB 37.2 36.9 37.4 42.1 49.6 54.6 56.3 56.1 51.9 45.9 39.4 37.4
MCDB 39.4 39.5 40.4 47.9 57.3 61.5 62.2 61.3 55.1 48.7 42.0 39.5
Mean Daily Temperature
Range
MDBR 7.7 8.4 9.6 13.1 13.6 12.5 10.5 10.7 9.2 8.2 7.0 7.3
5% DB MCDBR 9.9 9.7 12.5 21.4 22.8 21.7 18.3 19.0 13.9 10.0 8.4 10.0
MCWBR 7.5 6.7 7.7 11.0 10.9 10.8 8.6 8.7 6.8 5.7 5.8 7.5
5% WB MCDBR 9.5 8.9 10.7 17.2 18.4 19.0 15.3 15.3 10.9 8.3 8.0 9.7
MCWBR 7.6 6.7 7.1 9.8 9.4 10.2 7.7 7.7 6.8 5.7 5.8 7.5
Clear Sky Solar
Irradiance taub 0.288 0.300 0.332 0.373 0.386 0.423 0.413 0.391 0.350 0.312 0.273 0.253 taud 1.979 2.080 2.014 1.949 2.044 2.067 2.174 2.250 2.318 2.188 2.009 1.944
Ebn,noon 143 217 247 257 265 256 256 252 245 211 148 110 Edn,noon 17 26 38 48 47 47 42 36 28 23 16 12
All-Sky Solar Radiation
RadAvg 136 426 949 1602 1915 1771 1581 1273 749 417 184 79 RadStd 11 28 43 49 152 193 107 119 54 30 13 10
CDDn Cooling degree-days base n°F, °F-day Lat Latitude, ° Period Years used to calculate the design conditions
CDHn Cooling degree-hours base n°F, °F-hour Long Longitude, ° Sd Standard deviation of daily average temperature, °F
DB Dry bulb temperature, °F MCDB Mean coincident dry bulb temperature, °F
StdP Standard pressure at station elevation, psi
DP Dew point temperature, °F MCDBR Mean coincident dry bulb temp.
range, °F taub Clear sky optical depth for beam irradiance
Ebn,noon Clear sky beam normal and diffuse horizontal irradiances at solar noon, Btu/h/ft2
MCDP
Mean coincident dew point temperature, °F taud Clear sky optical depth for diffuse irradiance
Edh,noon MCWB Mean coincident wet bulb temperature, °F
Tavg Average temperature, °F
Elev Elevation, ft MCWBR Mean coincident wet bulb temp.
range, °F
Time Zone Hours ahead or behind UTC
Enth Enthalpy, Btu/lb MCWS Mean coincident wind speed, mph WB Wet bulb temperature, °F
HDDn Heating degree-days base n°F, °F-day MDBR Mean dry bulb temp. range, °F
Hours 8/4 & 55/69
Number of hours between 8 a.m.
and 4 p.m with DB between 55 and 69 °F
PCWD Prevailing coincident wind direction, °,0 = North, 90 = East WS Wind speed, mph HR Humidity ratio, grains of moisture per lb of dry air
Curatorial Building
51,348 BTU/H
38,186 BTU/H
0 BTU/H Yes
0 BTU/H
0 BTU/H
0 BTU/H
0 BTU/H
Total: 89,534 BTU/H
BTU/H
BTU/H
BTU/H
BTU/H
BTU/H
100%
60,301 BTU/H
6 Deg F
50 Deg F
#DIV/0!
Envelope Heat Loss:
Ventilation Heat Loss:
Snowmelt Heat Loss:
Author Initials:
Boiler Sizing Worksheet
JMC
PROJECT NO: M2182 Date: 12/5/2022
Infiltration Heat Loss:
Load Per Boiler for
RSA Engineering Inc PROJECT: RSA HTG & Vent Calc
Total Design Heat Loss: 60,301
Number of Boilers:
Load Percent per Boiler:
Load per Boiler:
Load to maintain Building Temperature without Ventilation
Domestic Hot Water Heat Loss:
Domestic Hot Water Load Factor
(ASHRAE 2015 Applications Ch 50, Figure 25)
Ratio=
Ambient Temperature:
Hot-Water Heat Load 0.00
Hot-Water Factor=
Building Temperature:
0.00 Heating load
VAV Coils: Idle Load
100%
Heating Plant Safety Factor 8,953
Terminal Unit Safety Factor 4,668
Additional Boiler Load:
Total Boiler Load W/ Ventilation 22,115
Heating Design Temp
Total Boiler Load W/ Infiltration 60,301
Maintenance Shop
140,495 BTU/H
100,006 BTU/H
205,610 BTU/H Yes
0 BTU/H
0 BTU/H
0 BTU/H
0 BTU/H
Total: 446,111 BTU/H
BTU/H
BTU/H
BTU/H
BTU/H
BTU/H
100%
290,710 BTU/H
6 Deg F
60 Deg F
114,950 BTU/H
Envelope Heat Loss:
Ventilation Heat Loss:
Snowmelt Heat Loss:
Author Initials:
Boiler Sizing Worksheet
JMC
PROJECT NO: M2182 Date: 12/5/2022
Infiltration Heat Loss:
Load Per Boiler for
RSA Engineering Inc PROJECT: RSA HTG & Vent Calc
Total Design Heat Loss: 290,710
Number of Boilers:
Load Percent per Boiler:
Load per Boiler:
Load to maintain Building Temperature without Ventilation
Domestic Hot Water Heat Loss:
Domestic Hot Water Load Factor
(ASHRAE 2015 Applications Ch 50, Figure 25)
Ratio=
Ambient Temperature:
Hot-Water Heat Load 0.00
Hot-Water Factor=
Building Temperature:
0.00 Heating load
VAV Coils: Idle Load
100%
Heating Plant Safety Factor 44,611
Terminal Unit Safety Factor 12,772
Additional Boiler Load:
Total Boiler Load W/ Ventilation 290,710
Heating Design Temp
Total Boiler Load W/ Infiltration 185,106
RSA Engineering Inc
PDO
11/6/2023
1 feet H2O
4 feet H2O
3.5 feet H2O
0 feet H2O
2 feet H2O
0 feet H2O
0 feet H2O
0 feet H2O
10.50 feet H2O
0 feet
3 feet H2O
0.5
0 feet H2O
10.50 feet H2O
11.55 feet H2O
12.13 feet H2O
Project Title: Skagway Maintenance Author Initials:
Job Number: M2182 Date:
Heating Unit:
Strainer:
Pump Equipment
Heat Plant
Equipment
(In Boiler Room)
Terminal Heating
Equipment
Air Separator:
Balance Valve:
Control Valve:
Area Served:
Pump Designation:
Pump GPM:
Boiler Loop
BP-1/BP-2
Pump Head Loss Calculation
Pump Check Valve:
Pump Balance Valve:
RemarksLoss in feet of water
20 GPM
Boiler:
Remarks
Total Item Loss:
*Fitting Factor:
Piping Length of
Longest Run:
Loss per 100 feet:
Is there Glycol in System? YES
*If actual fitting loss is known, enter here:
feet H2O
Correction Factor: 5%
Total Pump Head (Including Glycol):
Piping Losses
Remarks
Total Piping Loss:
Remarks
Total System Loss:
Safety Factor: 10% 10% Standard Factor of Safety
Total H2O Pump Head:
11/6/2023
1 feet H2O
4 feet H2O
0 feet H2O
1 feet H2O
2 feet H2O
3 feet H2O
3 feet H2O
10 feet H2O
24.00 feet H2O
450 feet
2 feet H2O
0.5
13.5 feet H2O
37.50 feet H2O
41.25 feet H2O
49.50 feet H2O
Loss in feet of water Remarks
Pump Head Loss Calculation
Area Served: Main Hydronic Loop
Pump Designation: CP-1A/CP-2B
Pump GPM: 75 GPM
Pump Equipment
Pump Check Valve:
Pump Balance Valve:
Heat Plant
Equipment
(In Boiler Room)
Boiler:
Air Separator:
Strainer:
Terminal Heating
Equipment
Heating Unit
Balance Valve:
Control Valve:
Total Item Loss:
Remarks
Piping Losses
Piping Length of
Longest Run:
Loss per 100 feet:
*Fitting Factor:
Total H2O Pump Head:
*If actual fitting loss is known, enter here:
feet H2O
Total Piping Loss:
Remarks
Total System Loss:
Safety Factor: 10% 10% Standard Factor of Safety
Remarks
Is there Glycol in System? YES
Total Pump Head (Including Glycol): Factor of 20% added for Glycol
11/6/2023
1 feet H2O
2 feet H2O
0 feet H2O
1 feet H2O
2 feet H2O
1 feet H2O
3 feet H2O
10 feet H2O
20.00 feet H2O
200 feet
1.5 feet H2O
0.5
4.5 feet H2O
24.50 feet H2O
26.95 feet H2O
32.34 feet H2O
Loss in feet of water Remarks
Pump Head Loss Calculation
Area Served: Fan Room Loop
Pump Designation: CP-2A/CP-2B
Pump GPM: 23 GPM
Pump Equipment
Pump Check Valve:
Pump Balance Valve:
Heat Plant
Equipment
(In Boiler Room)
Boiler:
Air Separator:
Strainer:
Terminal Heating
Equipment
Heating Unit
Balance Valve:
Control Valve:
Total Item Loss:
Remarks
Piping Losses
Piping Length of
Longest Run:
Loss per 100 feet:
*Fitting Factor:
Total H2O Pump Head:
*If actual fitting loss is known, enter here:
feet H2O
Total Piping Loss:
Remarks
Total System Loss:
Safety Factor: 10% 10% Standard Factor of Safety
Remarks
Is there Glycol in System? YES
Total Pump Head (Including Glycol): Factor of 20% added for Glycol
City: Skagway
Application: NonCritical
Supply Air Flow: Final Relative Humidity: 45%
Minimum O/A Setting: Final Temperature: 70°F
Return Temperature: 70°F Final Load =
Initial Final
% O/A O/A O/A
Required O/A Mixed Moisture Moisture Humidification
O/A for Airflow Air O/A Load Load Load
Temp. 55°F S/A (cfm) Temp. % RH ( lbs/hr ) ( lbs/hr ) ( lbs/hr )
-20°F 100.0% 150 -20°F 20% 0.045 4.65 4.61
-15°F 100.0% 150 -15°F 20% 0.060 4.65 4.59
-10°F 100.0% 150 -10°F 20% 0.075 4.65 4.58
-5°F 100.0% 150 -5°F 20% 0.098 4.65 4.55
0°F 100.0% 150 0°F 20% 0.122 4.65 4.53
5°F 100.0% 150 5°F 20% 0.161 4.65 4.49
10°F 100.0% 150 10°F 20% 0.200 4.65 4.45
15°F 100.0% 150 15°F 20% 0.261 4.65 4.39
20°F 100.0% 150 20°F 20% 0.323 4.65 4.33
25°F 100.0% 150 25°F 20% 0.409 4.65 4.24
30°F 100.0% 150 30°F 20% 0.495 4.65 4.16
35°F 100.0% 150 35°F 20% 0.608 4.65 4.04
40°F 100.0% 150 40°F 20% 0.720 4.65 3.93
45°F 100.0% 150 45°F 20% 0.885 4.65 3.77
50°F 100.0% 150 50°F 20% 1.050 4.65 3.60
55°F 100.0% 150 55°F 20% 1.260 4.65 3.39
Peak Load ==> 4.61 lbs/hr
0.55 gal/hr
0.01 gal/min
Project Title: Skagway Heat Pump Page Title: Humidity Load Calculations
Project No. : M2182 Date: 10/18/23 By: Paul Owens
150 cfm
3.100 lbs/hr per 100 cfm
150 cfm
File Name: M2182_V-Humidity.xlsx Tab Name: Humidity Version 1.0
Revision: 0 Date:
Calculations By:
Prepared For:
System Parameters
Manufacturer/Model: DDR GT-334A Flow Rate: 332 CFM
Appliance Fuel Type: Fuel Oil # 2 Horizontal Length: 8.00 ft
Appliance Input: (Typ. x 2) 404 MBH Stack Height: 17.50 ft
Flue Gas Temperature: 350 °F Turndown: 1:1
Offsets: 8 Required Draft: -0.09 to 0 in. wc.
INFORMATION CONTAINED HEREIN IS PROPRIETARY TO THE SCHEBLER COMPANY
www.scheblerchimney.com P. 563.359.0110 2U3R V1.0.07 161909
NPS Gold Rush Mechanical Renovations
Conditions (1) takes all appliances at full fire ensuring the system we have selected, breeching and stack diameters, will allow for full operation at any ambient temperature.
Conditions (2) has all appliances at full fire besides a single off appliance. This is to ensure that the off appliance does not experience positive pressure at the exhaust outlet and thus no exhaust being forced back into the mechanical room.
Conditions (3) are calculated at 32°F temperature with variable capacities of 100% for the first appliance, 75% for the second, and 50% for the remaining (if applicable) to determine if the system will remain inside draft requirements.
Conditions (4) are calculated at minimum appliance capacity and at low ambient temperature. This is to determine if the outlet pressure will remain within draft requirements.
The purpose of this report is to properly size a common vented system for several, and sometimes various, appliances. There are four worst case scenarios that are investigated to ensure that the maximum BTU’s may be obtained under all extreme conditions. Results of these calculations are based on interpreted layout(s) and appliance selection(s).
Please note that the following calculation is based on the ASHRAE Chimney and
Duct Design Equations. The preparer of this document disclaims any responsibility for any improper vent system performance resulting from this software.
Paul Owens
Page | 1
Neil Sanchez
With: Proctor Sales Inc.
11/02/23
Calculation Results
Conditions (1): Maximum Capacity at 65 °F Ambient Temperature
Appliance Diameter Gas Velocity Total Loss Natural Draft Outlet Pressure No. (in.) (ft/min) (in. w.c.) (in. w.c.) (in. w.c.)
1 7 621.13 0.03023 0.08962 -0.05939 2 7 621.13 0.03509 0.08962 -0.05453
Run Run Diameter Gas Velocity Run Loss
No. (in.) (ft/min) (in. w.c.)
1 7 621.13 0.02297 2 7 621.13 0.02783 3 10 608.71 0.00726
Conditions (2): Back Draft at 65 °F Ambient Temperature
Appliance Diameter Gas Velocity Total Loss Natural Draft Outlet Pressure No. (in.) (ft/min) (in. w.c.) (in. w.c.) (in. w.c.)
1 7 621.13 0.01708 0.08962 -0.07254 2 7 0.04 -0.00137 0.05121 -0.05258
Run Run Diameter Gas Velocity Run Loss
No. (in.) (ft/min) (in. w.c.)
1 7 621.13 0.01506 2 7 0.04 -0.00339 3 10 304.37 0.00202
INFORMATION CONTAINED HEREIN IS PROPRIETARY TO THE SCHEBLER COMPANY 2U3R 161909 Page | 2
*The color green indicates that an outlet pressure is acceptable within draft requirements, with red indicating that an outlet pressure is outside of draft requirements. Orange indicates a slight deviation outside of draft requirements.
V1.0.07
Conditions (3): Variable Capacity at 65 °F Ambient Temperature
Appliance Diameter Gas Velocity Total Loss Natural Draft Outlet Pressure No. (in.) (ft/min) (in. w.c.) (in. w.c.) (in. w.c.)
1 7 621.13 0.02627 0.08962 -0.06335 2 7 465.85 0.02154 0.08962 -0.06809
Run Run Diameter Gas Velocity Run Loss No. (in.) (ft/min) (in. w.c.)
1 7 621.13 0.02060 2 7 465.85 0.01587 3 10 532.62 0.00567
Conditions (4): Minimum Capacity at -20 °F Ambient Temperature
Appliance Diameter Gas Velocity Total Loss Natural Draft Outlet Pressure No. (in.) (ft/min) (in. w.c.) (in. w.c.) (in. w.c.)
1 7 621.13 0.03023 0.13883 -0.10860 2 7 621.13 0.03509 0.13883 -0.10374
Run Run Diameter Gas Velocity Run Loss No. (in.) (ft/min) (in. w.c.)
1 7 621.13 0.02297 2 7 621.13 0.02783 3 10 608.71 0.00726
INFORMATION CONTAINED HEREIN IS PROPRIETARY TO THE SCHEBLER COMPANY 2U3R 161909 Page | 3V1.0.07
Solution Results
Conditions 1: Outlet Pressure Controlled Draft Damper Type: Barometric Appliance 1 -0.05939 -0.05939 Appliance 2 -0.05453 -0.05453
Conditions 2: Outlet Pressure Controlled Draft Appliance 1 -0.07254 -0.07254 Appliance 2 -0.05258 -0.05258
Conditions 3: Outlet Pressure Controlled Draft Appliance 1 -0.06335 -0.06335 Appliance 2 -0.06809 -0.06809
Conditions 4: Outlet Pressure Controlled Draft Appliance 1 -0.10860 -0.06300 Appliance 2 -0.10374 -0.06300
INFORMATION CONTAINED HEREIN IS PROPRIETARY TO THE SCHEBLER COMPANY
2U3R 161909 Page | 4V1.0.07
Add barometric dampers to each boiler to regulate overdraft
Results Summary:
| ASHRAE Fundamentals_2017 |
| M2182_Heat and Clg_Curatorial |
| M2182_Heat and Clg_Maintenance |
| M2182_Pump Head Loss Calculation |
| M2182_V-Humidity |
| NPS Gold Rush Mechanical Renovations Flue Calculation_R0 |