B08_Attachment_2_-_Calculations.pdf

PDF 923 KB Posted

Attached to
Replace HVAC at Maintenance & Curatorial Bldgs - S Federal contract opportunity
Solicitation number
140P9724R0010
Issued by
Department of the Interior National Park Service Alaska Region

About this file

This document appears to contain several related files regarding a federal contract opportunity to replace the HVAC systems at the Maintenance and Curatorial buildings in Skagway, Alaska.

The key details include:

  • The solicitation number is 140P9724R0010, with the opportunity titled "Replace HVAC at Maintenance & Curatorial Bldgs - Skagway AK".
  • The federal agency involved is the Department of the Interior National Park Service Alaska Region.
  • The document includes building-specific HVAC load calculations, equipment sizing, pump head loss calculations, and humidity load calculations to support the HVAC replacement requirements.
  • There are also flue/vent sizing calculations for the boiler and heating equipment.
  • No specific award date or pricing terms are provided, but the opportunity appears to be for a solicitation with an unspecified response deadline.

View the file

Other files for this federal contract opportunity

Other files attached to Replace HVAC at Maintenance & Curatorial Bldgs - S, newest first.
File Type Posted
B08_Attachment_10_Payment_Bond.pdf PDF
Sol_140P9724R0010.pdf PDF
B08_Attachment_13_-_Project_Design_-_Combined.pdf PDF
B08_Attachment_5_-_CloseoutandOM_KLGO_Mech_and_Elect_10_12.xls XLS spreadsheet
B08_Attachment_11_Performance_Bond.pdf PDF
B08_Attachmen_12_-_Subcontracting___Worksheet.xlsx XLSX spreadsheet
B08_Attachmen_12_-_Subcontracting___Worksheet_1.xlsx XLSX spreadsheet
B08_Attachment_3_-_Curatorial_Photos.pdf PDF
B08_Attachment_4__KLGO_248830_CM-16_Submittal_Form.doc DOC document
B08_Attachment_1_Combo_Div_1___Specs.pdf PDF
B08_Attachment_7__ITM_Hot_Work_Permit.pdf PDF
B08_Attachment_6_-_SubmittalList-KLGO_Mech_and_Elect_3_14_24.xls XLS spreadsheet
B08_Attachment_9_Past_Performance_Questionnaire_Aug_2021.doc DOC document
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

11/29/22, 2:32 PM about:blank about:blank 1/2

2017 ASHRAE Handbook - Foundamentals (IP)

SKAGWAY AP, AK, USA (WMO: 703620)

Lat:59.456N Long:135.324W Elev:20 StdP: 14.69 Time zone:-9.00 Period:96-14 WBAN:25335 Annual Heating and Humidification Design Conditions

Coldest Month

Heating DB Humidification DP/MCDB and HR Coldest month WS/MCDB MCWS/PCWD to 99.6% DB99.6% 99% 0.4% 1%

99.6% 99% DP HR MCDB DP HR MCDB WS MCDB WS MCDB MCWS PCWD

1 0.8 5.8 -18.8 2.0 2.8 -14.0 2.6 7.6 39.9 20.1 36.8 22.2 24.8 30

Annual Cooling, Dehumidification, and Enthalpy Design Conditions

Hottest Month

Hottest Month

DB

Range

Cooling DB/MCWB Evaporation WB/MCDB MCWS/PCWD to 0.4% DB0.4% 1% 2% 0.4% 1% 2%

DB MCWB DB MCWB DB MCWB WB MCDB WB MCDB WB MCDB MCWS PCWD

7 10.5 71.6 57.4 67.7 55.9 64.5 55.0 59.1 67.8 57.6 64.8 56.4 62.6 10.6 210 Dehumidification DP/MCDB and HR Enthalpy/MCDB Extreme

Max

WB

0.4% 1% 2% 0.4% 1% 2% DP HR MCDB DP HR MCDB DP HR MCDB Enth MCDB Enth MCDB Enth MCDB

55.2 64.8 60.0 54.2 62.6 59.2 53.3 60.6 58.4 25.6 67.9 24.8 65.2 24.0 62.7 77.0

Extreme Annual Design Conditions

Extreme Annual WS

Extreme Annual Temperature n-Year Return Period Values of Extreme Temperature

Mean Standard deviation n=5 years n=10 years n=20 years n=50 years

1% 2.5% 5% Min Max Min Max Min Max Min Max Min Max Min Max

33.7 29.8 26.6 DB -0.2 78.8 4.7 4.6 -3.6 82.1 -6.3 84.8 -9.0 87.4 -12.4 90.7

WB -1.7 62.1 4.7 4.8 -5.1 65.5 -7.8 68.3 -10.4 71.0 -13.8 74.5

Monthly Climatic Design Conditions

Annual Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Temperatures, Degree-Days and Degree-

Hours

DBAvg 42.0 26.5 30.2 32.2 40.9 49.4 55.3 57.2 56.4 50.7 43.0 33.1 28.7 DBStd 13.00 11.83 8.68 7.75 4.94 4.79 3.70 3.22 3.54 3.78 4.90 8.19 9.12

HDD50 3602 727 554 551 279 70 2 0 1 34 218 506 660

HDD65 8384 1192 974 1016 723 485 293 242 269 428 681 956 1125

CDD50 697 0 0 0 6 51 160 224 198 56 2 0 0

CDD65 4 0 0 0 0 0 1 1 2 0 0 0 0

CDH74 57 0 0 0 0 2 15 18 22 0 0 0 0

CDH80 10 0 0 0 0 0 0 5 5 0 0 0 0

Wind WSAvg 10.4 14.0 12.0 11.9 9.1 9.7 10.0 9.4 8.0 8.5 9.2 10.6 12.3

Precipitation

PrecAvg 40.60 3.90 3.20 2.60 2.10 1.60 1.50 1.70 2.90 5.20 6.90 4.80 4.30 PrecMax 66.90 11.00 6.00 8.50 6.80 3.80 3.80 4.30 6.40 11.30 16.40 12.10 9.30 PrecMin 26.50 0.70 0.00 0.00 0.10 0.20 0.30 0.60 0.10 1.70 1.20 0.20 0.20 PrecStd 8.10 2.30 1.60 1.70 1.50 0.80 0.80 0.80 1.50 1.90 3.20 2.60 2.00

Monthly Design Dry Bulb and

Mean Coincident Wet Bulb

Temperatures

0.4% DB 47.2 46.1 50.3 68.0 72.1 76.2 75.3 76.6 67.2 55.5 48.6 48.6

MCWB 41.7 39.7 40.3 50.3 53.1 58.7 59.8 56.8 52.9 49.5 43.9 44.6

2% DB 43.7 43.5 45.3 58.0 66.3 70.3 69.7 69.7 62.0 53.0 45.9 44.9

MCWB 39.7 38.6 38.6 44.4 51.0 58.1 58.4 57.7 52.6 47.3 41.6 41.2

5% DB 41.8 41.8 43.1 52.6 62.2 66.0 65.8 65.5 58.3 51.3 44.2 42.6

MCWB 38.2 37.8 38.0 42.3 49.9 55.7 56.9 56.3 51.8 46.2 40.2 39.1

10% DB 39.8 39.9 41.3 48.8 58.3 62.7 63.0 62.5 56.2 49.6 42.6 40.0

MCWB 36.7 36.3 36.8 41.2 48.5 54.1 55.9 55.5 51.0 44.8 39.1 37.0

11/29/22, 2:32 PM about:blank about:blank 2/2

Monthly Design Wet Bulb and

Mean Coincident Dry Bulb

Temperatures

0.4% WB 43.2 41.5 42.3 50.7 55.8 63.4 60.6 60.3 57.1 50.9 44.9 45.0

MCDB 45.9 44.8 46.7 66.7 65.0 67.5 71.0 71.2 63.4 54.0 47.5 48.2

2% WB 40.4 39.8 40.3 46.2 52.7 58.5 58.9 58.6 54.7 49.2 42.5 41.6

MCDB 43.5 42.8 44.0 55.2 63.1 67.7 67.3 66.5 59.3 51.9 45.0 44.6

5% WB 38.6 38.3 38.7 43.7 51.0 56.4 57.5 57.3 53.1 47.4 40.9 39.4

MCDB 41.3 41.1 42.1 50.2 59.7 64.5 64.3 63.6 56.5 50.2 43.5 42.0

10% WB 37.2 36.9 37.4 42.1 49.6 54.6 56.3 56.1 51.9 45.9 39.4 37.4

MCDB 39.4 39.5 40.4 47.9 57.3 61.5 62.2 61.3 55.1 48.7 42.0 39.5

Mean Daily Temperature

Range

MDBR 7.7 8.4 9.6 13.1 13.6 12.5 10.5 10.7 9.2 8.2 7.0 7.3

5% DB MCDBR 9.9 9.7 12.5 21.4 22.8 21.7 18.3 19.0 13.9 10.0 8.4 10.0

MCWBR 7.5 6.7 7.7 11.0 10.9 10.8 8.6 8.7 6.8 5.7 5.8 7.5

5% WB MCDBR 9.5 8.9 10.7 17.2 18.4 19.0 15.3 15.3 10.9 8.3 8.0 9.7

MCWBR 7.6 6.7 7.1 9.8 9.4 10.2 7.7 7.7 6.8 5.7 5.8 7.5

Clear Sky Solar

Irradiance taub 0.288 0.300 0.332 0.373 0.386 0.423 0.413 0.391 0.350 0.312 0.273 0.253 taud 1.979 2.080 2.014 1.949 2.044 2.067 2.174 2.250 2.318 2.188 2.009 1.944

Ebn,noon 143 217 247 257 265 256 256 252 245 211 148 110 Edn,noon 17 26 38 48 47 47 42 36 28 23 16 12

All-Sky Solar Radiation

RadAvg 136 426 949 1602 1915 1771 1581 1273 749 417 184 79 RadStd 11 28 43 49 152 193 107 119 54 30 13 10

CDDn Cooling degree-days base n°F, °F-day Lat Latitude, ° Period Years used to calculate the design conditions

CDHn Cooling degree-hours base n°F, °F-hour Long Longitude, ° Sd Standard deviation of daily average temperature, °F

DB Dry bulb temperature, °F MCDB Mean coincident dry bulb temperature, °F

StdP Standard pressure at station elevation, psi

DP Dew point temperature, °F MCDBR Mean coincident dry bulb temp.

range, °F taub Clear sky optical depth for beam irradiance

Ebn,noon Clear sky beam normal and diffuse horizontal irradiances at solar noon, Btu/h/ft2

MCDP

Mean coincident dew point temperature, °F taud Clear sky optical depth for diffuse irradiance

Edh,noon MCWB Mean coincident wet bulb temperature, °F

Tavg Average temperature, °F

Elev Elevation, ft MCWBR Mean coincident wet bulb temp.

range, °F

Time Zone Hours ahead or behind UTC

Enth Enthalpy, Btu/lb MCWS Mean coincident wind speed, mph WB Wet bulb temperature, °F

HDDn Heating degree-days base n°F, °F-day MDBR Mean dry bulb temp. range, °F

Hours 8/4 & 55/69

Number of hours between 8 a.m.

and 4 p.m with DB between 55 and 69 °F

PCWD Prevailing coincident wind direction, °,0 = North, 90 = East WS Wind speed, mph HR Humidity ratio, grains of moisture per lb of dry air

Curatorial Building

51,348 BTU/H

38,186 BTU/H

0 BTU/H Yes

0 BTU/H

0 BTU/H

0 BTU/H

0 BTU/H

Total: 89,534 BTU/H

BTU/H

BTU/H

BTU/H

BTU/H

BTU/H

100%

60,301 BTU/H

6 Deg F

50 Deg F

#DIV/0!

Envelope Heat Loss:

Ventilation Heat Loss:

Snowmelt Heat Loss:

Author Initials:

Boiler Sizing Worksheet

JMC

PROJECT NO: M2182 Date: 12/5/2022

Infiltration Heat Loss:

Load Per Boiler for

RSA Engineering Inc PROJECT: RSA HTG & Vent Calc

Total Design Heat Loss: 60,301

Number of Boilers:

Load Percent per Boiler:

Load per Boiler:

Load to maintain Building Temperature without Ventilation

Domestic Hot Water Heat Loss:

Domestic Hot Water Load Factor

(ASHRAE 2015 Applications Ch 50, Figure 25)

Ratio=

Ambient Temperature:

Hot-Water Heat Load 0.00

Hot-Water Factor=

Building Temperature:

0.00 Heating load

VAV Coils: Idle Load

100%

Heating Plant Safety Factor 8,953

Terminal Unit Safety Factor 4,668

Additional Boiler Load:

Total Boiler Load W/ Ventilation 22,115

Heating Design Temp

Total Boiler Load W/ Infiltration 60,301

Maintenance Shop

140,495 BTU/H

100,006 BTU/H

205,610 BTU/H Yes

0 BTU/H

0 BTU/H

0 BTU/H

0 BTU/H

Total: 446,111 BTU/H

BTU/H

BTU/H

BTU/H

BTU/H

BTU/H

100%

290,710 BTU/H

6 Deg F

60 Deg F

114,950 BTU/H

Envelope Heat Loss:

Ventilation Heat Loss:

Snowmelt Heat Loss:

Author Initials:

Boiler Sizing Worksheet

JMC

PROJECT NO: M2182 Date: 12/5/2022

Infiltration Heat Loss:

Load Per Boiler for

RSA Engineering Inc PROJECT: RSA HTG & Vent Calc

Total Design Heat Loss: 290,710

Number of Boilers:

Load Percent per Boiler:

Load per Boiler:

Load to maintain Building Temperature without Ventilation

Domestic Hot Water Heat Loss:

Domestic Hot Water Load Factor

(ASHRAE 2015 Applications Ch 50, Figure 25)

Ratio=

Ambient Temperature:

Hot-Water Heat Load 0.00

Hot-Water Factor=

Building Temperature:

0.00 Heating load

VAV Coils: Idle Load

100%

Heating Plant Safety Factor 44,611

Terminal Unit Safety Factor 12,772

Additional Boiler Load:

Total Boiler Load W/ Ventilation 290,710

Heating Design Temp

Total Boiler Load W/ Infiltration 185,106

RSA Engineering Inc

PDO

11/6/2023

1 feet H2O

4 feet H2O

3.5 feet H2O

0 feet H2O

2 feet H2O

0 feet H2O

0 feet H2O

0 feet H2O

10.50 feet H2O

0 feet

3 feet H2O

0.5

0 feet H2O

10.50 feet H2O

11.55 feet H2O

12.13 feet H2O

Project Title: Skagway Maintenance Author Initials:

Job Number: M2182 Date:

Heating Unit:

Strainer:

Pump Equipment

Heat Plant

Equipment

(In Boiler Room)

Terminal Heating

Equipment

Air Separator:

Balance Valve:

Control Valve:

Area Served:

Pump Designation:

Pump GPM:

Boiler Loop

BP-1/BP-2

Pump Head Loss Calculation

Pump Check Valve:

Pump Balance Valve:

RemarksLoss in feet of water

20 GPM

Boiler:

Remarks

Total Item Loss:

*Fitting Factor:

Piping Length of

Longest Run:

Loss per 100 feet:

Is there Glycol in System? YES

*If actual fitting loss is known, enter here:

feet H2O

Correction Factor: 5%

Total Pump Head (Including Glycol):

Piping Losses

Remarks

Total Piping Loss:

Remarks

Total System Loss:

Safety Factor: 10% 10% Standard Factor of Safety

Total H2O Pump Head:

11/6/2023

1 feet H2O

4 feet H2O

0 feet H2O

1 feet H2O

2 feet H2O

3 feet H2O

3 feet H2O

10 feet H2O

24.00 feet H2O

450 feet

2 feet H2O

0.5

13.5 feet H2O

37.50 feet H2O

41.25 feet H2O

49.50 feet H2O

Loss in feet of water Remarks

Pump Head Loss Calculation

Area Served: Main Hydronic Loop

Pump Designation: CP-1A/CP-2B

Pump GPM: 75 GPM

Pump Equipment

Pump Check Valve:

Pump Balance Valve:

Heat Plant

Equipment

(In Boiler Room)

Boiler:

Air Separator:

Strainer:

Terminal Heating

Equipment

Heating Unit

Balance Valve:

Control Valve:

Total Item Loss:

Remarks

Piping Losses

Piping Length of

Longest Run:

Loss per 100 feet:

*Fitting Factor:

Total H2O Pump Head:

*If actual fitting loss is known, enter here:

feet H2O

Total Piping Loss:

Remarks

Total System Loss:

Safety Factor: 10% 10% Standard Factor of Safety

Remarks

Is there Glycol in System? YES

Total Pump Head (Including Glycol): Factor of 20% added for Glycol

11/6/2023

1 feet H2O

2 feet H2O

0 feet H2O

1 feet H2O

2 feet H2O

1 feet H2O

3 feet H2O

10 feet H2O

20.00 feet H2O

200 feet

1.5 feet H2O

0.5

4.5 feet H2O

24.50 feet H2O

26.95 feet H2O

32.34 feet H2O

Loss in feet of water Remarks

Pump Head Loss Calculation

Area Served: Fan Room Loop

Pump Designation: CP-2A/CP-2B

Pump GPM: 23 GPM

Pump Equipment

Pump Check Valve:

Pump Balance Valve:

Heat Plant

Equipment

(In Boiler Room)

Boiler:

Air Separator:

Strainer:

Terminal Heating

Equipment

Heating Unit

Balance Valve:

Control Valve:

Total Item Loss:

Remarks

Piping Losses

Piping Length of

Longest Run:

Loss per 100 feet:

*Fitting Factor:

Total H2O Pump Head:

*If actual fitting loss is known, enter here:

feet H2O

Total Piping Loss:

Remarks

Total System Loss:

Safety Factor: 10% 10% Standard Factor of Safety

Remarks

Is there Glycol in System? YES

Total Pump Head (Including Glycol): Factor of 20% added for Glycol

City: Skagway

Application: NonCritical

Supply Air Flow: Final Relative Humidity: 45%

Minimum O/A Setting: Final Temperature: 70°F

Return Temperature: 70°F Final Load =

Initial Final

% O/A O/A O/A

Required O/A Mixed Moisture Moisture Humidification

O/A for Airflow Air O/A Load Load Load

Temp. 55°F S/A (cfm) Temp. % RH ( lbs/hr ) ( lbs/hr ) ( lbs/hr )

-20°F 100.0% 150 -20°F 20% 0.045 4.65 4.61

-15°F 100.0% 150 -15°F 20% 0.060 4.65 4.59

-10°F 100.0% 150 -10°F 20% 0.075 4.65 4.58

-5°F 100.0% 150 -5°F 20% 0.098 4.65 4.55

0°F 100.0% 150 0°F 20% 0.122 4.65 4.53

5°F 100.0% 150 5°F 20% 0.161 4.65 4.49

10°F 100.0% 150 10°F 20% 0.200 4.65 4.45

15°F 100.0% 150 15°F 20% 0.261 4.65 4.39

20°F 100.0% 150 20°F 20% 0.323 4.65 4.33

25°F 100.0% 150 25°F 20% 0.409 4.65 4.24

30°F 100.0% 150 30°F 20% 0.495 4.65 4.16

35°F 100.0% 150 35°F 20% 0.608 4.65 4.04

40°F 100.0% 150 40°F 20% 0.720 4.65 3.93

45°F 100.0% 150 45°F 20% 0.885 4.65 3.77

50°F 100.0% 150 50°F 20% 1.050 4.65 3.60

55°F 100.0% 150 55°F 20% 1.260 4.65 3.39

Peak Load ==> 4.61 lbs/hr

0.55 gal/hr

0.01 gal/min

Project Title: Skagway Heat Pump Page Title: Humidity Load Calculations

Project No. : M2182 Date: 10/18/23 By: Paul Owens

150 cfm

3.100 lbs/hr per 100 cfm

150 cfm

File Name: M2182_V-Humidity.xlsx Tab Name: Humidity Version 1.0

Revision: 0 Date:

Calculations By:

Prepared For:

System Parameters

Manufacturer/Model: DDR GT-334A Flow Rate: 332 CFM

Appliance Fuel Type: Fuel Oil # 2 Horizontal Length: 8.00 ft

Appliance Input: (Typ. x 2) 404 MBH Stack Height: 17.50 ft

Flue Gas Temperature: 350 °F Turndown: 1:1

Offsets: 8 Required Draft: -0.09 to 0 in. wc.

INFORMATION CONTAINED HEREIN IS PROPRIETARY TO THE SCHEBLER COMPANY

www.scheblerchimney.com P. 563.359.0110 2U3R V1.0.07 161909

NPS Gold Rush Mechanical Renovations

Conditions (1) takes all appliances at full fire ensuring the system we have selected, breeching and stack diameters, will allow for full operation at any ambient temperature.

Conditions (2) has all appliances at full fire besides a single off appliance. This is to ensure that the off appliance does not experience positive pressure at the exhaust outlet and thus no exhaust being forced back into the mechanical room.

Conditions (3) are calculated at 32°F temperature with variable capacities of 100% for the first appliance, 75% for the second, and 50% for the remaining (if applicable) to determine if the system will remain inside draft requirements.

Conditions (4) are calculated at minimum appliance capacity and at low ambient temperature. This is to determine if the outlet pressure will remain within draft requirements.

The purpose of this report is to properly size a common vented system for several, and sometimes various, appliances. There are four worst case scenarios that are investigated to ensure that the maximum BTU’s may be obtained under all extreme conditions. Results of these calculations are based on interpreted layout(s) and appliance selection(s).

Please note that the following calculation is based on the ASHRAE Chimney and

Duct Design Equations. The preparer of this document disclaims any responsibility for any improper vent system performance resulting from this software.

Paul Owens

Page | 1

Neil Sanchez

With: Proctor Sales Inc.

11/02/23

Calculation Results

Conditions (1): Maximum Capacity at 65 °F Ambient Temperature

Appliance Diameter Gas Velocity Total Loss Natural Draft Outlet Pressure No. (in.) (ft/min) (in. w.c.) (in. w.c.) (in. w.c.)

1 7 621.13 0.03023 0.08962 -0.05939 2 7 621.13 0.03509 0.08962 -0.05453

Run Run Diameter Gas Velocity Run Loss

No. (in.) (ft/min) (in. w.c.)

1 7 621.13 0.02297 2 7 621.13 0.02783 3 10 608.71 0.00726

Conditions (2): Back Draft at 65 °F Ambient Temperature

Appliance Diameter Gas Velocity Total Loss Natural Draft Outlet Pressure No. (in.) (ft/min) (in. w.c.) (in. w.c.) (in. w.c.)

1 7 621.13 0.01708 0.08962 -0.07254 2 7 0.04 -0.00137 0.05121 -0.05258

Run Run Diameter Gas Velocity Run Loss

No. (in.) (ft/min) (in. w.c.)

1 7 621.13 0.01506 2 7 0.04 -0.00339 3 10 304.37 0.00202

INFORMATION CONTAINED HEREIN IS PROPRIETARY TO THE SCHEBLER COMPANY 2U3R 161909 Page | 2

*The color green indicates that an outlet pressure is acceptable within draft requirements, with red indicating that an outlet pressure is outside of draft requirements. Orange indicates a slight deviation outside of draft requirements.

V1.0.07

Conditions (3): Variable Capacity at 65 °F Ambient Temperature

Appliance Diameter Gas Velocity Total Loss Natural Draft Outlet Pressure No. (in.) (ft/min) (in. w.c.) (in. w.c.) (in. w.c.)

1 7 621.13 0.02627 0.08962 -0.06335 2 7 465.85 0.02154 0.08962 -0.06809

Run Run Diameter Gas Velocity Run Loss No. (in.) (ft/min) (in. w.c.)

1 7 621.13 0.02060 2 7 465.85 0.01587 3 10 532.62 0.00567

Conditions (4): Minimum Capacity at -20 °F Ambient Temperature

Appliance Diameter Gas Velocity Total Loss Natural Draft Outlet Pressure No. (in.) (ft/min) (in. w.c.) (in. w.c.) (in. w.c.)

1 7 621.13 0.03023 0.13883 -0.10860 2 7 621.13 0.03509 0.13883 -0.10374

Run Run Diameter Gas Velocity Run Loss No. (in.) (ft/min) (in. w.c.)

1 7 621.13 0.02297 2 7 621.13 0.02783 3 10 608.71 0.00726

INFORMATION CONTAINED HEREIN IS PROPRIETARY TO THE SCHEBLER COMPANY 2U3R 161909 Page | 3V1.0.07

Solution Results

Conditions 1: Outlet Pressure Controlled Draft Damper Type: Barometric Appliance 1 -0.05939 -0.05939 Appliance 2 -0.05453 -0.05453

Conditions 2: Outlet Pressure Controlled Draft Appliance 1 -0.07254 -0.07254 Appliance 2 -0.05258 -0.05258

Conditions 3: Outlet Pressure Controlled Draft Appliance 1 -0.06335 -0.06335 Appliance 2 -0.06809 -0.06809

Conditions 4: Outlet Pressure Controlled Draft Appliance 1 -0.10860 -0.06300 Appliance 2 -0.10374 -0.06300

INFORMATION CONTAINED HEREIN IS PROPRIETARY TO THE SCHEBLER COMPANY

2U3R 161909 Page | 4V1.0.07

Add barometric dampers to each boiler to regulate overdraft

Results Summary:

ASHRAE Fundamentals_2017
M2182_Heat and Clg_Curatorial
M2182_Heat and Clg_Maintenance
M2182_Pump Head Loss Calculation
M2182_V-Humidity
NPS Gold Rush Mechanical Renovations Flue Calculation_R0