Attch9_Asbestos Abated Areas Test Results.pdf
PDF 4 MB Posted
- Attached to
- FXSB 21-1077, Bunkroom Hallway Rpr Federal contract opportunity
- Solicitation number
- fa500021R0080
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation Amendment_FA500021R00800001 (Summary of Changes).pdf | ||
| Attch11_Q and A.docx | DOCX document | |
| Attch5_JBER Lock Standards.pdf | ||
| Attch1_FXSB 21-1077 SOW.pdf | ||
| Attch4_Revised JBER CAD.pdf | ||
| Attch8_Environmental Protection Specs on JBER (28 Oct 2020 Rev 3).pdf | ||
| Attch7_ JBER Telecom Criteria Requirements.pdf | ||
| Attch6_Contractors Fire Safety Guide.pdf | ||
| Attch2_ Price Schedule.pdf | ||
| Solicitation - FA500021R0080.pdf | ||
| Attch3_Drawing Set.pdf | ||
| Attch10_ AF_66 Submittal-FXSB 21-1077 X.xlsx.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A B C D E F G H
SHEET
REFERENCE
NUMBER
SHEET OF
ANSI D
AF PROJECT NUMBER:
AEC FILE NAME:
DRAWING SCALE:
PLOT SCALE:
SYMBOL DATE DESCRIPTION
REVISIONS
F I L
E
N
O
JOINT BASE ELMENDORF-RICHARDSON, AK
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJ. ENG.
RECORD
AS-BUILT
DRAWINGS
CONTRACTOR_DESIGNER LOGOS
1:1
AF CONTRACT NUMBER:
INV. NUMBER:
BUILDING OR FACILITY:
DATE APPR
DATE:
DATE:
DATE:
DATE:
DRAWING NO:
11-08 BLDG UPDATED
FIRE_STATION_1
11415
FLOOR_1
1 1
3/32"=1'
XXXXXXXX
DACAXXXXXXXX
XXXXXXXXXX
X.DWG
NAME
NAME
NAME
NAME
X-X xx-month-xxxx
A R
C H
I V
E
F I L
E
N U
M B
E R xx - month - xxxx xx - month - xxxx xx - month - xxxx xx - month - xxxx
XXX-XXX
8672698-11415- Wall 1
8672698-11415- Floor 1
8672698-11415- Floor 2
8672698-11415- Wall 2
A B C D E F G H
SHEET
REFERENCE
NUMBER
SHEET OF
ANSI D
AF PROJECT NUMBER:
AEC FILE NAME:
DRAWING SCALE:
PLOT SCALE:
SYMBOL DATE DESCRIPTION
REVISIONS
F I L
E
N
O
JOINT BASE ELMENDORF-RICHARDSON, AK
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJ. ENG.
RECORD
AS-BUILT
DRAWINGS
CONTRACTOR_DESIGNER LOGOS
1:1
AF CONTRACT NUMBER:
INV. NUMBER:
BUILDING OR FACILITY:
DATE APPR
DATE:
DATE:
DATE:
DATE:
DRAWING NO:
11-08 BLDG UPDATED
FIRE_STATION_1
11415
FLOOR_1
1 1
3/32"=1'
XXXXXXXX
DACAXXXXXXXX
XXXXXXXXXX
X.DWG
NAME
NAME
NAME
NAME
X-X xx-month-xxxx
A R
C H
I V
E
F I L
E
N U
M B
E R xx - month - xxxx xx - month - xxxx xx - month - xxxx xx - month - xxxx
XXX-XXX
11415-9396579-P1
11415-9396579-P2
11415-9396579-P3
11415-9396579-P4 11415-9396579-P6 11415-9396579-P7 11415-9396579-P8 11415-9396579-P9
11415-9396579-P5
A B C D E F G H
SHEET
REFERENCE
NUMBER
SHEET OF
ANSI D
AF PROJECT NUMBER:
AEC FILE NAME:
DRAWING SCALE:
PLOT SCALE:
SYMBOL DATE DESCRIPTION
REVISIONS
F I L
E
N
O
JOINT BASE ELMENDORF-RICHARDSON, AK
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJ. ENG.
RECORD
AS-BUILT
DRAWINGS
CONTRACTOR_DESIGNER LOGOS
1:1
AF CONTRACT NUMBER:
INV. NUMBER:
BUILDING OR FACILITY:
DATE APPR
DATE:
DATE:
DATE:
DATE:
DRAWING NO:
11-08 BLDG UPDATED
FIRE_STATION_1
11415
FLOOR_1
1 1
3/32"=1'
XXXXXXXX
DACAXXXXXXXX
XXXXXXXXXX
X.DWG
NAME
NAME
NAME
NAME
X-X xx-month-xxxx
A R
C H
I V
E
F I L
E
N U
M B
E R xx - month - xxxx xx - month - xxxx xx - month - xxxx xx - month - xxxx
XXX-XXX
11415-9396579-D111415-9396579-P2
11415-9396579-P3
11415-9396579-P4
11415-9396579-P5
11415-9396579-P6
11415-9396579-P7
A B C D E F G H
SHEET
REFERENCE
NUMBER
SHEET OF
ANSI D
AF PROJECT NUMBER:
AEC FILE NAME:
DRAWING SCALE:
PLOT SCALE:
SYMBOL DATE DESCRIPTION
REVISIONS
F I L
E
N
O
JOINT BASE ELMENDORF-RICHARDSON, AK
DESIGNED BY:
DRAWN BY:
CHECKED BY:
PROJ. ENG.
RECORD
AS-BUILT
DRAWINGS
CONTRACTOR_DESIGNER LOGOS
1:1
AF CONTRACT NUMBER:
INV. NUMBER:
BUILDING OR FACILITY:
DATE APPR
DATE:
DATE:
DATE:
DATE:
DRAWING NO:
11-08 BLDG UPDATED
FIRE_STATION_1
11415
FLOOR_1
1 1
3/32"=1'
XXXXXXXX
DACAXXXXXXXX
XXXXXXXXXX
X.DWG
NAME
NAME
NAME
NAME
X-X xx-month-xxxx
A R
C H
I V
E
F I L
E
N U
M B
E R xx - month - xxxx xx - month - xxxx xx - month - xxxx xx - month - xxxx
XXX-XXX
8934629 -11415 - W1
8934629 -11415 - F3
8934629 -11415 - W2
8934629 -11415 - F2
8934629 -11415 - F1
December 14, 2020
773rd CES Attn: Mr. Jonathan Murdock 4241 Finletter Avenue
JBER, AK 99506
Dear Mr. Murdock, RE: PO A052 Building 11415 Samples.
This letter is in regards to the asbestos bulk samples that were dropped off at Satori Group’s office on December 3rd, 2020 from Building 11415.
The bulk samples were shipped under Chain of Custody procedures to LA Testing in South Pasadena, California. LA Testing is fully accredited by the National Voluntary Laboratory Accreditation Program (NVLAP) for bulk asbestos fiber analysis. The samples were analyzed using polarized light microscopy (PLM) with dispersion staining in accordance with USEPA 600/R-93/116 test method.
For samples containing more than one separable layer of material, the report will include findings for each layer. Each layer will be labeled with the sample number and material type (E.g. B0303-02-Tile, B0303-02-Mastic).
Review of the enclosed results indicates the following samples tested positive for asbestos:
Sample # Description Type
11415-8934629-Floor 1 Mastic 3% Chrysotile
11415-8934629-Floor 2 Mastic 3% Chrysotile
11415-8934629-Floor 3 Mastic 3% Chrysotile
We recommend that the removal and disposal of all asbestos containing materials (ACM) be completed by an accredited abatement contractor in accordance with all applicable local, state, and federal regulations pertaining to the removal of asbestos.
Please note that the sample(s) referenced in this letter were not collected by Satori, therefore Satori makes no representations regarding the material sampled or the sampling methodology.
This report is considered confidential by Satori Group. Satori Group will not release this report to any persons who have not been previously approved in writing. Please do not hesitate to contact us if you have any questions concerning your results, or for any additional technical assistance.
Respectfully, Alan Caldwell CSP Operations Manager Encl. Laboratory Report
LA Testing 5431 Industrial Drive Huntington Beach, CA 92649
Tel/Fax: (714) 828-4999 / (714) 828-4944 http://www.LATesting.com / gardengrovelab@latesting.com
332022048LA Testing Order:
Customer ID: 32EHS30
Customer PO:
Project ID:
Attention: Phone:Jill Lucas (907) 350-9919
Fax:Satori Group, Inc
Received Date:1310 East 66th Avenue 12/05/2020 4:40 PM
Analysis Date:Suite 2 12/11/2020
Collected Date:Anchorage, AK 99518 11/24/2020
Project: 30699
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
11415-8934629-Floor
1-Floor Tile
332022048-0001
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Training room - 9x9 tile, mastic
11415-8934629-Floor
1-Mastic
332022048-0001A
3% ChrysotileNon-fibrous (Other)97%Black
Non-Fibrous
Homogeneous
Training room - 9x9 tile, mastic
11415-8934629-Floor
1-Foam
332022048-0001B
None DetectedNon-fibrous (Other)94%Cellulose6%Gray
Non-Fibrous
Homogeneous
Training room - 9x9 tile, mastic
11415-8934629-Floor
1-Leveler
332022048-0001C
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Training room - 9x9 tile, mastic
11415-8934629-Floor
2-Floor Tile
332022048-0002
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Training room - 9x9 tile, mastic
11415-8934629-Floor
2-Mastic
332022048-0002A
3% ChrysotileNon-fibrous (Other)97%Black
Non-Fibrous
Homogeneous
Training room - 9x9 tile, mastic
11415-8934629-Floor
2-Foam
332022048-0002B
None DetectedNon-fibrous (Other)92%Synthetic8%Gray/Blue
Fibrous
Heterogeneous
Training room - 9x9 tile, mastic
11415-8934629-Floor
3-Floor Tile
332022048-0003
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Training room - 9x9 tile, mastic
11415-8934629-Floor
3-Mastic
332022048-0003A
3% ChrysotileNon-fibrous (Other)97%Black
Non-Fibrous
Homogeneous
Training room - 9x9 tile, mastic
11415-8934629-Wall
1-Adhesive
332022048-0004
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Training room - GWB, mud, tape, adhesive
Mud and tape not present
11415-8934629-Wall
1-Gypsum Wallboard
332022048-0004A
None DetectedNon-fibrous (Other)88%Cellulose
Glass
10%
2%
Brown/White
Fibrous
Heterogeneous
Training room - GWB, mud, tape, adhesive
11415-8934629-Wall
2-Adhesive
332022048-0005
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Training room - GWB, mud, tape, adhesive
Mud not present
Initial report from: 12/11/2020 17:43:27
Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 12/11/2020 2:43 PM
Tel/Fax: (714) 828-4999 / (714) 828-4944 http://www.LATesting.com / gardengrovelab@latesting.com
332022048LA Testing Order:
Customer ID: 32EHS30
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
11415-8934629-Wall
2-Tape
332022048-0005A
None DetectedNon-fibrous (Other)2%Cellulose98%White
Fibrous
Homogeneous
Training room - GWB, mud, tape, adhesive
11415-8934629-Wall
2-Gypsum Wallboard
332022048-0005B
None DetectedNon-fibrous (Other)87%Cellulose
Glass
10%
3%
Brown/Pink
Fibrous
Heterogeneous
Training room - GWB, mud, tape, adhesive
Analyst(s)
Brittany Quiring (14) Michael Chapman, Laboratory Manager or Other Approved Signatory
LA Testing maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by LA Testing. LA Testing bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim
Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by
NVLAP, NIST or any agency of the federal government . Non-friable organically bound materials present a problem matrix and therefore LA Testing recommends gravimetric reduction prior to analysis .
Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by LA Testing Huntington Beach, CA NVLAP Lab Code 101384-0, CA ELAP 1406
Initial report from: 12/11/2020 17:43:27
Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 12/11/2020 2:43 PM
OrderID: 332022048
OrderID: 332022048
March 30, 2021
773rd CES Attn: Mr. Jonathan Murdock 4142 Finletter Avenue
JBER, AK 99506
Dear Mr. Murdock, This letter is in regards to the asbestos bulk samples that were dropped off at Satori Group’s offices on March 22nd, 2021.
The bulk samples were shipped under Chain of Custody procedures to LA Testing in South Pasadena, California. LA Testing is fully accredited by the National Voluntary Laboratory Accreditation Program (NVLAP) for bulk asbestos fiber analysis. The samples were analyzed using polarized light microscopy (PLM) with dispersion staining in accordance with USEPA 600/R-93/116 test method.
For samples containing more than one separable layer of material, the report will include findings for each layer. Each layer will be labeled with the sample number and material type (E.g. B0303-02-Tile, B0303-02-Mastic).
Review of the enclosed results indicates the following samples tested positive for asbestos:
Sample # Description Type
111415-10396579-P3-TSI Truck bay overhead pipe – cloth wrap
& TSI
20% Amosite
111415-10396579-P8-TSI Truck bay overhead pipe – cloth wrap
& TSI
20% Amosite
We recommend that the removal and disposal of all asbestos containing materials (ACM) be completed by an accredited abatement contractor in accordance with all applicable local, state, and federal regulations pertaining to the removal of asbestos.
This report is considered by Satori Group as high confidential. As such we will not release this report to any persons who have not been previously approved in writing. Please do not hesitate to contact Satori Group if you have any questions concerning your results, or for any additional technical assistance.
Respectfully, Alan Caldwell Operations Manager acaldwell@gosatori.com
Tel/Fax: (714) 828-4999 / (714) 828-4944 http://www.LATesting.com / gardengrovelab@latesting.com
332105648LA Testing Order:
Customer ID: 32EHS30
Customer PO:
Project ID:
Attention: Phone:Mike Williams (907) 350-9919
Fax:Satori Group, Inc
Received Date:1310 East 66th Avenue 03/23/2021 10:35 AM
Analysis Date:Suite 2 03/30/2021
Collected Date:Anchorage, AK 99518 03/18/2021
Project: 30736
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
11415-9396579-P1-Clot h Wrap
332105648-0001
None DetectedNon-fibrous (Other)35%Cellulose65%Brown/White
Fibrous
Heterogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
TSI not found
11415-10396579-P2-Clo th Wrap
332105648-0002
None DetectedNon-fibrous (Other)35%Cellulose65%Brown
Fibrous
Heterogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
TSI not found
11415-10396579-P3-Clo th Wrap
332105648-0003
None DetectedNon-fibrous (Other)55%Cellulose45%White/Beige
Fibrous
Heterogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
11415-10396579-P3-TSI
332105648-0003A
20% AmositeNon-fibrous (Other)80%White
Fibrous
Homogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
11415-10396579-P4-Clo th Wrap
332105648-0004
None DetectedNon-fibrous (Other)35%Cellulose65%Brown/White
Fibrous
Heterogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
TSI not found
11415-10396579-P5-Clo th Wrap
332105648-0005
None DetectedNon-fibrous (Other)35%Cellulose65%Brown/White
Fibrous
Heterogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
TSI not found
11415-10396579-P6-Clo th Wrap
332105648-0006
None DetectedNon-fibrous (Other)35%Cellulose65%Brown/White
Fibrous
Heterogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
TSI not found
11415-10396579-P7-Clo th Wrap
332105648-0007
None DetectedNon-fibrous (Other)35%Cellulose65%Brown/White
Fibrous
Heterogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
TSI not found
11415-10396579-P8-Clo th Wrap
332105648-0008
None DetectedNon-fibrous (Other)55%Cellulose45%White/Beige
Fibrous
Heterogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
11415-10396579-P8-TSI
332105648-0008A
20% AmositeNon-fibrous (Other)80%White
Fibrous
Homogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
11415-10396579-P9-Clo th Wrap
332105648-0009
None DetectedNon-fibrous (Other)35%Cellulose65%Brown/White
Fibrous
Heterogeneous
Truck bay overhead pipe - Cloth wrap &
TSI
TSI not found
Initial report from: 03/30/2021 13:14:30
Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 3/30/2021 10:14 AM
Tel/Fax: (714) 828-4999 / (714) 828-4944 http://www.LATesting.com / gardengrovelab@latesting.com
332105648LA Testing Order:
Customer ID: 32EHS30
Customer PO:
Project ID:
Analyst(s)
Brian Magumcia (11) Michael Chapman, Laboratory Manager or Other Approved Signatory
LA Testing maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by LA Testing. LA Testing bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim
Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by
NVLAP, NIST or any agency of the federal government . Non-friable organically bound materials present a problem matrix and therefore LA Testing recommends gravimetric reduction prior to analysis .
Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by LA Testing Huntington Beach, CA NVLAP Lab Code 101384-0, CA ELAP 1406
Initial report from: 03/30/2021 13:14:30
Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 3/30/2021 10:14 AM