Attachment J-LEX-FY18-FAC LE403-Tank 3-FINAL.PDF

PDF 3 MB Posted

Attached to
SP-POL-CMP-INSPECT-FY24-LEXINGTON OKLAHOMA
Solicitation number
W9128F23Q0103
Issued by

About this file

This document summarizes an inspection report for an aboveground storage tank (AST) located at the A.A.S.F. #1 Lexington fuel facility in Lexington, Oklahoma. The inspection was conducted in accordance with STI SP001 standards to evaluate tank integrity and establish a database for future inspections. Key findings included the need to extend the catwalk for safe appurtenance access, add NFPA and equipment labeling, address piping system thread engagement and leaks, and repair the secondary containment which showed 500 feet of joint seal deterioration and 135 feet of cracks. The report provides engineering data on tank specifications, ultrasonic thickness readings, and calculates remaining shell life is greater than 30 years if conditions remain unchanged. It also identifies mandatory, required and recommended repairs grouped by priority level and includes photographs documenting issues.

The related federal contract opportunity is a solicitation for SP-POL-CMP-INSPECT-FY24-LEXINGTON OKLAHOMA to conduct inspections and repairs at the above facility, indicating the inspection report is being used to inform future work requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

USArmyCorpsofEngineers
OmahaDistrict
STISP001FormalExternalInspection
InspectionReport
AASF1Lexington
FacilityLE403

Tank 3

USArmyCorpsofEngineersCenterofExpertiseforPetroleum,Oils,andLubricants
(USACEPOL‐MCX)

12/6/2017

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

TableofContents
ACRONYMSANDABBREVIATIONS ............................................................................................................ 3

GENERAL SUMMARY

STI SP001 INSPECTION DETERMINATION

INSPECTION DATE

STATE REGULATIONS

PREVIOUS INSPECTION DATES

RECOMMENDED FUTURE INSPECTION DATES

A. GENERAL PROJECT INFORMATION

1. STI SP001 Inspection

2. Site Information

B. TANK INSPECTION COMMENTS

1. Tank Construction

2. Tank Foundation

3. Tank Appurtenances

4. Tank Coating

5. Tank Piping System

Thetankhasaboveground4‐inchstainlesssteelreceiptpipingand4‐inchaboveground
stainlesssteelissuepiping.Tanks1,2,3,and4sharethesameissueandreceiptpipingsystem.

6. Fire Protection System

7. Secondary Containment

C. FINDINGS AND RECOMMENDATIONS

1. MANDATORY REPAIRS per STI SP001, UFC 3‐460‐01, NFPA 30, or NFPA 30A

2. REQUIRED REPAIRS to Fully Comply with STI SP001 or Federal, State, and Local Codes . 12

3. RECOMMENDEDREPAIRStoFullyComplywithUFC3‐460‐01andAW78‐24‐27
StandardsorasPartofRegularMaintenance ................................................................................. 17

APPENDIX A: ENGINEERING CALCULATIONS AND DATA

APPENDIX B: ENGINEERING DRAWINGS

APPENDIX C: STI SP001 INSEPCTION CHECKLIST

APPENDIX D: PHOTOGRAPHS

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

ACRONYMS AND ABBREVIATIONS

API American Petroleum Institute

ASME American Society of Mechanical Engineers

ASNT American Society of Non‐Destructive Testing

ATG Automatic Tank Gauge

BBL Barrel

CFR Code of Federal Regulations

CP Cathodic Protection

DFT Dry Film Thickness

HLA High Level Alarm

HLCS High Level Control Shut‐Off

HHLA High‐High Level Alarm

LLA Low Level Alarm

LLLA Low‐Low Level Alarm

MFL Magnetic Flux Leakage

MT Magnetic Particle Testing

NACE National Association of Corrosion Engineers

NDT Non‐Destructive Testing

NFPA National Fire Protection Association

PSI Pounds per Square Inch

PT Penetrant Testing

P/V Pressure/Vacuum

RP Recommended Practice

PST Product Saver Tank

RT Radiography Testing

STI Steel Tank Institute

TML Thickness Measurement Location

TRV Thermal Relief Valve

UFC Unified Facilities Criteria

UFGS Unified Facilities Guide Specifications

ULS Ultra Low Sulfur

UT Ultrasonic Testing

VT Visual Testing

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

GENERALSUMMARY
AnSTISP001FormalExternalinspectionofTank3(FacilityLE403),locatedatA.A.S.F.1Lexington,
OklahomawascompletedonDecember6,2017toevaluatethetank’sintegrity,collectdata,and
establishadatabaseforfutureinspectionsandevaluations.Aservicelifeevaluationperformedon
thetankshowsitashavinggreaterthan30yearsofremainingshelllifeundercurrentconditions.
SignificantFindings:
Theexistingcatwalkdoesnotallowsafeaccesstoalltankappurtenances.
ThereisnoNFPAdiamondonthetankorenteringfuelfarm.
Thetankappurtenancesarenotlabeled.
Thereisimproperthreadengagementthroughouttheproductissueandreceiptpiping

system.

There is vegetation growing through deteriorated expansion joints in the fuel farm containment.

There are approximately 5oo feet of joint sealant deterioration in the facility containment

expansionjoint.
Thereareapproximately135feetofcracksonthefacilitycontainmentfloor.
Productleaking/fueldrippingwasnotedonthe2‐inchmetercontrolvalveneartheTank4
issue.The1‐inchTRVandsightglassonthesightflowindicatoraredrippingontheproduct
returnlinenearTank4.
Thepipesupportforthe1‐inchpressurerelieflineontheproductreceiptsidenearTank4
isnotengagedwiththepipe.
TheaudiblealarmfortheMorrisonBros.clockgaugedoesnotwork.
Theproductsavertankhasabrasscheckvalve.
Minorcoatingfailurewasnotedonthetankshell,appurtenances,valves,flangesofflex

connectors, strainers, filter separators, and pumps.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

STISP001INSPECTIONDETERMINATION
STISP001classifiestanksintothreecategories.AtankisrankedasaCategory1,2,or3depending
ontheriskatankposestotheenvironment.Category1tanksposetheleastamountofriskand
Category3thehighest.Theinspectiontypesandinspectionintervalsarebasedonthetanksizeand
tankcategory.Theriskfactorsincludespillcontrol,releasepreventionbarrier(RPB),continuous
releasedetectionmethod(CRDM),andtankdesignandconfiguration(seedefinitionsbelow).
SPILLCONTROL‐ameansofpreventingareleaseofliquidintotheenvironment,including
adjoiningpropertyandwaterways.Spillcontrolmethodsinclude:1)Remoteimpounding;
2)Secondarycontainmentdike/berm;3)SecondarycontainmentAST;and4)Secondary
containmentsystem.
CONTINUOUSRELEASEDETECTIONMETHOD(CRDM)–ameansofdetectingareleaseof
liquidthroughinherentdesign.CRDMispassivebecauseitdoesnotrequiresensorsor
powertooperate.Liquidreleasesarevisuallydetectedbyfacilityoperators.Thesystem
shallbedesignedinaccordancewithgoodengineeringpractice.Severalacceptableand
commonlyusedCRDMsystemsareasfollows:1)Releasepreventionbarrier(RPB);2)
SecondarycontainmentAST,includingdouble‐wallASTordouble‐bottomAST;and3)
ElevatedAST,withorwithoutreleasepreventionbarrier.
RELEASEPREVENTIONBARRIER(RPB)–aliquidcontainmentbarrierthatisinstalled
undertheAST.ItspurposeistodivertleakstowardtheperimeteroftheAST,wherethey
canbeeasilydetected,aswellastopreventliquidfromcontaminatingtheenvironment.
RPBsarecomposedofmaterialscompatiblewiththeliquidstoredintheASTandmeet
appropriateengineeringstandards.Examplesaresteel(asinsteeldouble‐bottomtanks),
concrete,elastomericliners,orothersuitablematerials,providedtheabovecriteriaare

met.

OVERFILLPREVENTION‐systems,procedures,ordevicesusedtopreventliquidinASTs
fromrunningoverorspillingoutoftheASTduringthefillingprocess.Havingaperson
physicallypresentandincontrolofashutoffdeviceduringtheentiretankfillingprocessis
anacceptableproceduretoachieveoverfillprotection.
Category1tanksareASTswithspillcontrol,withCRDM,andwithoverfillprevention.
Category2tanksareASTswithspillcontrol,withoutCRDM,andwithoverfillprevention.
Category3tanksareASTswithoutspillcontrol,withoutCRDM,and/orwithoutoverfill

prevention.

Note: Any tank not having overfill prevention is classified as a Category 3 tank.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

Table 1 shows some typical tank types and their corresponding AST categories.

Table 1: Tank Configuration and AST Category

Tank Configuration Tank has

CRDM

Tankhas
SpillControl?

AST

Category

SinglewallASTincontactwithgroundnono3
SinglewallASTincontactwithgroundnoyes2
Elevatedtankyesyes1
ASTwithRPByesyes1
ASTwithdouble‐bottomyesyes1
Double‐wallASTwithoverfillpreventionyesyes1
Double‐wallASTwithoutoverfillpreventionyesno3
Verticaltankrestingonconcrete(withRPB)yesyes1
Verticaltankrestingonconcrete(withRPB)yesno3

Table 2 shows the STI SP001 inspection guidance based on tank size and AST category.

Table 2: Table of Inspection Schedules

AST Type and Size (U.S. gallons) Category 1 Category 2 Category 3

Shop‐ Fabricated ASTs

0–1100
(0‐4164liters)PPP,E&L(10)
1101‐5,000
(4168‐18,927liters)PP,E&L(10)[P,E&L(5),I(10)]or
[P,L(2),E(5)]
5,001‐30,000

(18,931‐113,562 liters)

P,E(20)
[P,E(10),I(20)]

or [P, E(5), L(10)]

[P,E&L(5),I(10)]or
[P,L(1),E(5)]

30,001 ‐ 50,000 (113,566‐189,271 liters)

P, E(20) P, E&L(5), I(15) P, E&L(5), I(10)

P–PeriodicASTinspection
E–Formalexternalinspectionbycertifiedinspector
I–Formalinternalinspectionbycertifiedinspector
L–Leaktestbyownerorowner’sdesignee
()indicatesmaximuminspectionintervalinyears.Forexample,E(5)indicatesformal
externalinspectionevery5years.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

INSPECTIONDATE
InspectionDate:6December2017
EquipmentUsed:UltrasonicThicknessMeter
Manufacturer:GeneralElectric
ModelNumber:DMSII
CalibrationMethod:TwoPointCalibration
STATEREGULATIONS
StateRegulationforSTIIn‐ServiceTankInspectionsN/A
StateRegulationforSTIOut‐of‐ServiceTankInspectionsN/A
NOTE:IftherearenostateregulationsfortankinspectionsthenN/Ashallresidein‐placeofthe
numberofyearsbetweeninspections.Ifstateregulationsreside,therecommendedfuture
inspectionsdatesshallbebasedonwhicheverismorestringentbetweentheSTIinspector’s
calculationsandtheStateregulations.
PREVIOUSINSPECTIONDATES
InspectionDate:Unknown/NotProvided
RECOMMENDEDFUTUREINSPECTIONDATES
STIOut‐of‐Service(Internal)InspectionDate:N/A
STIIn‐Service(External)InspectionDate:December2022

Signature(s):

StephenM.Hollenzer,STISP001#1607
InterSpec,LLC.

Jack Steve

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

GENERAL TANK INFORMATION

ITEMDESCRIPTION
OwnerU.S.Army
LocationA.A.S.F.1Lexington
FacilityNumberLE403
TankNumberTank#3
State/CountryOklahoma,US
CityLexington
InspectionDateDecember6,2017
TankManufacturerServiceWelding&MachineCO,Inc.
DesignStandardUL‐2085
DateofConstructionCirca2002
TankContentsF‐24JetFuel
TankSerialNumber12363
TankDiameter10’6”
TankLength35’
ProductHeight10,445gallons
TankCapacity20,000gallons
TankFoundationMetallicSaddles
TankConstructionHorizontalCylinder,Lap‐WeldedCourses
InteriorCoatingSystemUnknown
ExteriorCoatingSystemUnknown
LevelGauging
Electronic(FranklinFuelingSystemsTS‐550)/
Morrisonclockgaugewithaudiblealarm

Venting 10 in. primary emergency vent, 6 in. normal vent, 10 in. secondary emergency vent.

StrappingCharts1/8‐inchincrements
Piping(SizeandMaterial)Receipt4‐inchStainlessSteel

Issue 4‐inch Stainless Steel

Water Draw‐Off ¾‐inch Stainless Steel

Level Alarms Alarm

Electronic(FranklinFueling
systemsTS‐550)Independent

High‐ High 98% (10.29 ft.) None

High95%(9.975ft.)
LowNANone
Low‐LowNANone

Secondary Containment Double‐Wall Tank

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

A. GENERAL PROJECT INFORMATION

1. STISP001Inspection
AnSTISP001inspectionwasperformedonthetankinaccordancewiththemostrecent
versionofSTISP001.Additionalconsiderationisgiventofederal,state,andlocal
regulations,aswellasanyapplicablemilitarycriteriaandgeneralindustrystandards.
2. SiteInformation
A.A.S.F.1LexingtonislocatedinLexington,OK.

B. TANK INSPECTION COMMENTS

1. TankConstruction
Tank3(FacilityLE403)isanominal20,000gallon,10‐foot6‐inchdiameterby35‐feet
long,abovegroundhorizontalcylindricalfueltankservicingF‐24jetfuel.Thetankis
constructedtotheUL‐2085standard.ManufacturerandULdataplateswereaffixedto
thetank.As‐builtdrawingsoftheoriginalconstructionwerenotavailableatthetimeof
theinspection.
2. TankFoundation
Thetankrestsontwosteelsaddleswhichrestonaconcretepad.Thesteelsaddleswere
inspectedforcorrosion,coatingfailure,andadherencetotheSTISP001andUL‐142
standards.Theconcreteportionofthefoundationwasinspectedforbrokenconcrete,
spalling,cracks,andvegetationgrowthagainstthebottomofthetank.

3. Tank Appurtenances

a. Venting

Normalventingallowsthereliefofexcessiveinternalpressureorvacuum
duringnormalstorageandoperations.Thenormalventshallbeatleastas
largeasthelargestfillingorwithdrawalconnectionbutinnocase,shallitbe
lessthan1.25in.(32mm)nominalinsidediameter.Thetankisventedfor
normaloperationviaa6‐inchventwithaflamearrestor.Thetankhasa4‐
inchreceiptlinefromthetruckfillstand.Theventisadequatelysizedin
accordancewithNFPA30andAPIStandard2000.
b. EmergencyVenting
Thetankisequippedwithtwo10‐inchMorrisonBros.244seriesemergency
vents(onefortheinnertankandonefortheannularspace).Theventhasa
listedventingcapacityof808,350CFM.Thetankmanufacturerrequires
498,600CFMofemergencyventingcapacityontheinnertank.Thetank
manufacturerrequires517,200CFMofemergencyventingcapacityonthe
annularspace.Therefore,theemergencyventingcapacityissatisfactoryfor
thistank.Theemergencyventwasinspectedforcoatingfailureandfreedom
ofmovement.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

c. Manways The tank has two 36‐inch manholes located on the top of the tank.

d. WaterDraw‐Off
Thetankhasawater‐drawofflinewithahandcrankpump.
e. HighLevelShut‐OffValve
Thetankhasasolenoidcontrolledhighlevelshutoffvalve(Cla‐Valve

model).

f. LevelAlarms
Thetankhigh,high‐high,low,andlow‐lowlevelalarmsareprovidedbythe
FranklinFuelingsystems.

g. Gauging

ThetankiselectronicallygaugedviatheFranklinFuelingsystems.Thetank
hasaMorrisonmechanicalfuellevelgauge.

h. Pumps

Productisreceivedandissuedviatrucksandtodispensers.Thecentrifugal
pumpwascheckedforleakageandproperprotectionfrommovingparts.
i. StairsandPlatforms
Aladderislocatedadjacenttothetanktoaccessthetopofthetank.
Platforms,grating,andrailingswereinspectedforcoatingfailureand
adherencetoOSHAstandards.Theladderandcatwalkareinsatisfactory

condition.

j. CathodicProtection
Thetankisnotincontactwiththeground,andcathodicprotectionisnot

required.

k. GroundingandBonding
Thetankisgroundedviaagroundingcableandisinsatisfactorycondition.
4. TankCoating
Thetankshellandappurtenancesarecoated.Thecoatingwasevaluatedfordisbonding,
adhesion,deterioration,anddiscoloration.Thetankshellandappurtenanceshave
minorcoatingfailurepresent.
5. TankPipingSystem
Thetankhasaboveground4‐inchstainlesssteelreceiptpipingand4‐inchaboveground
stainlesssteelissuepiping.Tanks1,2,3,and4sharethesameissueandreceiptpiping

system.

6. FireProtectionSystem
Thefiredepartmentprovidesfireprotection.
7. SecondaryContainment
40CFR112.7(c)statesthattheentiresecondarycontainmentsystem,“includingwalls
andfloor,mustbecapableofcontainingoilandmustbeconstructedsothatany
dischargefromaprimarycontainmentsystem...willnotescapecontainmentbefore

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

cleanupoccurs.”40CFR112.8(c)(2)and40CFR112.12(c)(2)statethatdikedareas
mustbe“sufficientlyimpervioustocontainoil.”Thepurposeofthesecondary
containmentrequirementistopreventdischarges,asdescribedin40CFR112.1(b);
therefore,effectivesecondarycontainmentmethodsmustbeabletocontainoiluntilthe
oiliscleanedup.Thetankisadouble‐walledtankwhichisafullyenclosedmetallic
secondarycontainmentstructure.Thesecondarycontainmentisofsufficientsizeto
containatotaltanklossperUFC3‐460‐1,Section8‐14.2.1.Theentiretankrestson
metallicbeamsonaconcretepadtoallowwatertodrainawayfromthetankin
accordancewithNFPA30.
Thetankfarmhasatruckfill/offloadcontainment.Thedimensionsare135feetby150
feet.Itisequippedwithasumpthatleadstoanoilywaterseparator.Theoilywater
separatorwasintheclosedpositionduringtheinspection.Thereisapproximately500
feetofjointsealdeteriorationand135feetofcontainmentcracking.
C. FINDINGSANDRECOMMENDATIONS
Thefollowinginformationidentifiesthesignificantfindingsfoundduringthetankinspection:
1. MANDATORYREPAIRSperSTISP001,UFC3‐460‐01,NFPA30,orNFPA30A
Mandatoryrepairsrepresentitemsthatrequireimmediateattention,inorderto
preventimminentrisktosystemoperators,equipmentintegrity,ortheadjacent
environment.Thetankshouldremainoutofserviceuntiltheserepairsarecompleted.

a. None.

2. REQUIRED REPAIRS to Fully Comply with STI SP001 or Federal, State, and Local Codes

Recommendedrepairsrepresentitemsthatshouldbeaddressedinatimelymanner,in
ordertopreventfuturepotentialriskstosystemoperators,equipmentintegrity,orthe
adjacentenvironment.Theseitemsmayberequiredbyfederal,state,andlocalcodes.
a. TheCatwalkdoesnotAllowSafeAccesstoAllTankAppurtenances
OBSERVATION:Theexistingcatwalkdoesnotallowsafeaccesstoalltank

appurtenances.

CODEREFERENCE:UFC3‐460‐01Table8.1(j).
RECOMMENDATION:Extendtheexistingcatwalktorunthelengthofthetankto
allowsafeaccesstoalltankappurtenances.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

b. NFPALabeling
OBSERVATION:ThetankdoeshaveaDOTlabel,butthetankdoesnothaveaNFPA
labelaffixedtothetank.
CODEREFERENCE:NFPA30andNFPA704.
RECOMMENDATION:InstallaNFPA704diamondlabel.
c. AppurtenanceLabeling
OBSERVATION:Thetankdoesnothaveproperlabelingoneachtankappurtenance.
Someofthelabelinghasbeenpaintedoverorhasdeterioratedduetoweather.
CODEREFERENCE:UL‐142(4.8.1.1).
RECOMMENDATION:InstalllabelsonalltankappurtenancesinaccordancewithUL‐

142.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

d. ThreadEngagement
OBSERVATION:Theproductreceiptpipingsystemandissuepipingsystemhave
improperthreadengagementandseverallooseboltswithoutwashersonflanged
connectionsthroughoutthesystem.
CODEREFERENCE:ASMEB31(335.2.3).
RECOMMENDATION:Checkandrefastenthehardwareandinstallwashersontheentire
productreceiptpipingsystemandissuepipingsysteminaccordancewithASMEB31.
e. VegetationinFacilityContainment
OBSERVATION:Thepipingcontainmenthasminorvegetationgrowthcomingthrough
thejointsealsinvariouslocations.
CODEREFERENCE:NFPA30,paragraph21.6.6.3.
RECOMMENDATION:RemovethevegetationinaccordancewithNFPA30,paragraph

21.6.6.

f. FacilityContainmentExpansionJointSealant
OBSERVATION:Thereisapproximately500feetofjointsealdeterioration.
CODEREFERENCE:40CFR112.7(c)statesthattheentiresecondarycontainment
system“includingwallsandfloor,mustbecapableofcontainingoilandmustbe
constructedsothatanydischargefromaprimarycontainmentsystem...willnot
escapecontainmentbeforecleanupoccurs.”40CFR112.8(c)(2)and40CFR
112.12(c)(2)statethatdikedareasmustbe“sufficientlyimpervioustocontainoil.”
Thepurposeofthesecondarycontainmentrequirementistopreventdischargesas
describedin40CFR112.1(b);therefore,effectivesecondarycontainmentmethods
mustbeabletocontainoiluntiltheoiliscleanedup.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

RECOMMENDATION:Removethedamagedjointsealantandinstallnewbackerrods
andsealantwithinthecontainment.Thesealantshallbeadequatetoaccommodate
jointcompressionequalto50percentofthewidthofthejoint.Thebackerrodshallbe
compressiblerodstockofpolyethylenefoam,polyurethanefoam,butylrubberfoam,
orotherflexible,non‐absorptivematerialasrecommendedbythesealant
manufacturer.ThesealantshallconformtoUFGS079200JointSealant(Quantity:
500linearfeet).
g. FacilityContainmentFloorCracks
OBSERVATION:Thereisapproximately135feetofcracksonthefacilitycontainment

floor.

CODEREFERENCE:40CFR112.7(c)statesthattheentiresecondarycontainment
system“includingwallsandfloor,mustbecapableofcontainingoilandmustbe
constructedsothatanydischargefromaprimarycontainmentsystem...willnot
escapecontainmentbeforecleanupoccurs.”40CFR112.8(c)(2)and40CFR
112.12(c)(2)statethatdikedareasmustbe“sufficientlyimpervioustocontainoil.”
Thepurposeofthesecondarycontainmentrequirementistopreventdischargesas
describedin40CFR112.1(b);therefore,effectivesecondarycontainmentmethods
mustbeabletocontainoiluntiltheoiliscleanedup.
RECOMMENDATION:Repairallexposedcracksinthecontainmentfloorbygrindingina
V‐shapepattern,withatleast¼‐inchwidthatthesurfaceandadepthofatleast¼‐
inchandsealingwithflexibleurethane(e.g.Sikaflex1c)orasimilarapprovedsealant.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

h.Leaking/FuelDrippingatTruckFillStand
OBSERVATION:Leaking/fueldrippingwasnotedonthe2‐inchmetercontrolvalve
neartheTank4issue.The1‐inchTRVandsightglassonthesightflowindicatorare
drippingontheproductreturnlinenearTank4.
CODEREFERENCE:NFPA30,paragraph27.3.2.
RECOMMENDATION:Allsightflowindicatorswithinpressurereliefpipingshallbe
removedandreplacedwithflangedspoolpieces.
i. PipeSupport
OBSERVATION:Thepipesupportforthe1‐inchpressurerelieflineontheproduct
receiptsidenearTank4isnotengagedwiththepipe.
CODEREFERENCE:NFPA30,paragraph27.6.1,“Pipingsystemsshallbesubstantially
supportedandprotectedagainstphysicaldamageandexcessivestressesarisingfrom
settlement,vibration,expansion,orcontraction.Theinstallationofnonmetallicpiping
shallbeinaccordancewiththemanufacturer’sinstructions.”(Also,seeAPI570‐7.5)
RECOMMENDATION:Repairthepipesupportforthe1‐inchpressurerelieflineonthe
productreceiptsidenearTank4inaccordancewithNFPA30,paragraph27.6.1.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

j. MorrisonBros.ClockGaugeOverfillAlarm
OBSERVATION:TheMorrisonBros.clockgaugeisequippedwithanaudiblealarm.The
alarmbatteryisdead,orthealarmisnotworking
CODEREFERENCE:NFPA30,paragraph22.11.4.5
RECOMMENDATION:RepairtheMorrisonBros.audiblealarminaccordancewithNFPA
30,paragraph22.11.4.5.
k. ProductSaverTank
OBSERVATION:Theproductsavertankhasabrasscheckvalve.Brassisconsidereda
lowmeltingpointmaterial.
CODEREFERENCE:NFPA30,paragraph27.4.3.2
RECOMMENDATION:ReplacethebrasscheckvalveinaccordancewithNFPA30,
paragraph27.4.3.2.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

3. RECOMMENDEDREPAIRStoFullyComplywithUFC3‐460‐01andAW78‐24‐27
StandardsorasPartofRegularMaintenance
Recommendedrepairsrepresentitemsthatshouldbeaddressedinatimelymanner,in
ordertopreventfuturepotentialriskstosystemoperators,equipmentintegrity,orthe
adjacentenvironment.
a. CoatingFailuresonTank
OBSERVATION:Minorcoatingfailurewasnotedonthetankshell,appurtenances,
valves,flangesofflexconnectors,strainers,filterseparators,andpumps.
CODEREFERENCE:NA
RECOMMENDATION:Abrasiveblastandrecoatareasofcoatingfailureonthetankshell,
appurtenances,valves,flangesofflexconnectors,strainers,filterseparators,and
pumps..Repairsshouldbeaccomplishedusinganepoxybasedcoatingsystemor

equivalent.

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

APPENDIX A: ENGINEERING CALCULATIONS AND DATA

1. RemainingLifeCalculation
2. UltrasonicThicknessData

InterSpec, LLC Rev.21505-2

12/6 2017

Tank #: 4 (LE 403) Plate Specification: Unknown T 55,000 Material: Y 30,000 Manufactured Date: 2002 Circa 23595

Horizontal 25960 Tank Specification Unit 0.80Y 0.429T Diameter (D) 10.500 feet Smaller of 24000 23595 Length (L) 35.000 feet Height (H) the two: 0.88Y 0.472T Volume (V) 20,073 gallon 26400 25960 S.G 0.88 N/A E 1 N/A *Smaller of Two specified minimum or 80,000(lb/in²) Y 15 years

Maximum Previous Current 2, 3 Minimum Next Next Product Allowable Measured Measured Acceptable Corrosion 1 Remaining VT UT Height Stress Joint Thickness Thickness Thickness Rate Life Inspection Inspection

Ft (psi) Efficiency (inches) (inches) (inches) (in./yr) (ca .) (years) (years) (feet) (S ) (E ) (t prev) (t act) (t min) (C r) (years) (I v) (I ut)

10.50 23,595 1 0.313 0.312 0.100 0.00001 >30 5 15

10.50 23,595 1 0.250 0.233 0.100 0.00113 >30 5 15

10.50 23,595 1 0.250 0.233 0.100 0.00113 >30 5 15

10.50 23,595 1 0.313 0.312 0.100 0.00001 >30 5 15

NOTE:

2 Acceptable roof thickness in any 100in. 2 shall not be less than 0.090 in 3 UL-142 Section 17.2.1 , 25.1, and 13.2.1 for Horz./Vertical and rectangular tanks <50,000 gal and >50,000 gal. API 653 Section 4.3.2.1, 4.3.4.1 and 4.4.1 VT and UT Intervals used are from API-653. See STI-SP001 Table 5.5 for inspection intervals for STI tanks.

1 The engineering data used to calculate in-service period of operation (Remaining Life) assumes the tank remains in the same service and all corrosion rates remain constant.

All other

Maximum allowable stress, first and second (lb/in ²)

Maximum allowable stress, for all other (lb/in²)

Bottom and second course

Shell (West Face) South Head

Shell (East Face)

Specified minimum tensile strength *(lb/in²)

Shell Life Evaluation : Data Result

Owner/Operator: US Army AASF1 - Lexington; Lexington, OK

Inspection Date :

Carbon Steel Specified minimum yield strength(lb/in ²)

North Head

Course Side

SConfiguration:

0.000

0.050

0.100

0.150

0.200

0.250

0.300

0.350

North Head Shell (East Face) Shell (West Face) South Head in ch es

Course #

Shell Life Evaluation tprev tact tmin

0.050

0.100

0.150

0.200

0.250

0.300

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 in ch es

Data Points

Shell (West Face)

0.050

0.100

0.150

0.200

0.250

0.300

0.350

1 3 5 7 9 11 13 15 17 19 in ch es

Data Points

South Head

0.050 0.100 0.150 0.200 0.250 0.300 0.350 0.400

1 3 5 7 9 11 13 15 17 19 in ch es

Data Points

North Head

0.050

0.100

0.150

0.200

0.250

0.300

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 in ch es

Data Points

Shell (East Face)

InterSpec,LLC Rev.21505-4 DATA Sheet: 1 Tank #:

1 0.340 1 0.241 1 0.241 1 0.330 2 0.342 2 0.242 2 0.242 2 0.328 3 0.340 3 0.241 3 0.239 3 0.332 4 0.342 4 0.241 4 0.236 4 0.330 5 0.341 5 0.243 5 0.241 5 0.330 6 0.340 6 0.239 6 0.240 6 0.330 7 0.341 7 0.240 7 0.239 7 0.330 8 0.341 8 0.236 8 0.243 8 0.333 9 0.341 9 0.240 9 0.242 9 0.330

10 0.342 10 0.239 10 0.240 10 0.332 11 0.343 11 0.241 11 0.240 11 0.330 12 0.343 12 0.241 12 0.243 12 0.332 13 0.341 13 0.241 13 0.244 13 0.331 14 0.343 14 0.240 14 0.245 14 0.332 15 0.343 15 0.241 15 0.245 15 0.332 16 0.343 16 0.233 16 0.244 16 0.331 17 0.341 17 0.241 17 0.243 17 0.331 18 0.341 18 0.242 18 0.242 18 0.327 19 0.340 19 0.244 19 0.249 19 0.331 20 0.340 20 0.246 20 0.243 20 0.332

Average 0.341 21 0.242 21 0.247 Average 0.331 Std.Dev. 0.001142481 22 0.243 22 0.243 Std.Dev. 0.001454575

23 0.244 23 0.240 24 0.239 24 0.241 25 0.243 25 0.247 26 0.241 26 0.236 27 0.241 27 0.246 28 0.240 28 0.238 29 0.239 29 0.236 30 0.238 30 0.233

Average 0.241 Average 0.242 Std.Dev. 0.002448551 Std.Dev. 0.003635078

4 (LE 403)

Owner/Operator:

North Head Shell (West Face) South HeadShell (East Face)

Tank Shell and Bottom/Roof/Heads UT Readings

US Army AASF1 - Lexington; Lexington, OK

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

APPENDIX B: ENGINEERING DRAWINGS

1. TankLayoutDrawing
2. TankFarmLayoutDrawing

Q - 3" PlugK - 4" Electronic A.T.G.

L - 2" Clock Gauge with Audible Alarm M - 3" Plug N - 4" to 2" Product Return O - 36" Manway P - 6" to 4" Product Issue

F - 3" Plug G - 36" Manway with 2" Product Return and 1" Water Draw H - 3" Manual Gauge Well I - 3" Plug J - 10" Emergency Vent

A - 2" Leak Detection B - 3" Plug C - 10" Emergency Vent D - 6" to 4" Product Receipt E - 6" Primary Vent

Tank 3 (LE403)

A.A.S.F. #1 Lexington; Lexington, OK

InterSpec, LLC.

12/6/2017 N/A N/A

ER

-A

.A

.S.F. #1 LEX

IN

G

TO

N

-LEX

IN

G

TO

N , O

K

-TA

N K

3-D

EC

EM

B

ER

/2017Description:

Remarks/Legend:

Drawing Title:

Owner:

Drawn By:

Date: Rev. No.: Scale:

Modified By: InterSpec, LLC.

IN

TER

SPEC

, LLC

-PR

O

PR

IETA

RY

IN

FO

R

M

ATIO

N

-FO

R O

FFIC

IA

L U

SE O

N

LY

AB C D

E

F G H I J

K

LMN O

P Q

Head 1 Head 2

Tank 3 Layout

Tank Farm Layout Tank Farm

A.A.S.F. #1 Lexington; Lexington, OK

InterSpec, LLC.

12/6/2017 N/A N/A

ER

-A

.A

.S.F. #1 LEX

IN

G

TO

N

-LEX

IN

G

TO

N , O

K

-TA

N K

FA

R

M -D

EC

EM

B

ER

/2017Description:

Remarks/Legend:

Drawing Title:

Owner:

Drawn By:

Date: Rev. No.: Scale:

Modified By: InterSpec, LLC.

IN

TER

SPEC

, LLC

-PR

O

PR

IETA

RY

IN

FO

R

M

ATIO

N

-FO

R O

FFIC

IA

L U

SE O

N

LY

150'-0"

135'-0"

Cracks and Joint Sealant

Concrete Bollard

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

APPENDIX C: STI SP001 INSPECTION CHECKLIST

1. STI SP001 INSPECTION CHECKLIST

STI SP001 Inspection Checklist

(*) designates an item in a non-conformance status. This indicates that action is required to address a problem.

The STI monthly, annular, and formal checklists were combined into one checklist.

Item/Task Status Comments

1.0 TANK CONTAINMENT

1.1 Containment Structure

a. Check for:

Holes or cracks in containment wall or floor Washout Liner degradation Corrosion Leakage Paint failure Tank settling Water Debris Fire hazards

☐ Yes* ☐ No ☐ N/A

1.2 Primary Tank

a. Check for water. ☐ Yes* ☐ No ☐ N/A

1.3 Containment Drain Valves

a. Operable and in a closed position ☐ Yes ☐ No* ☐ N/A

1.4 Pathways and Entry

a. Clear and gates/doors operable ☐ Yes ☐ No* ☐ N/A

2.0 LEAK DETECTION

2.1 Tank

a. Visible signs of leakage ☐ Yes* ☐ No ☐ N/A

2.2 Secondary Containment

a. Visible signs of leakage from tank into secondary containment ☐ Yes* ☐ No ☐ N/A

2.3 Surrounding Soil

2.4 Interstice

3.0 TANK FOUNDATION and SUPPORTS

3.1 Foundation

a. Settlement or foundation washout? ☐ Yes* ☐ No ☐ N/A

3.2 Concrete Pad or Ring Wall

a. Cracking or spalling? ☐ Yes* ☐ No ☐ N/A

3.3 Supports

a. Check for corrosion, paint failure, etc.

3.4 Water Drainage

a. Water drains away from tank? ☐ Yes ☐ No* ☐ N/A

3.5 Tank Grounding

a. Strap secured and in good condition?

☐ Yes ☐ No* ☐ N/A

4.0 CATHODIC PROTECTION

4.1 Gavlvanic Cathodic Protection System

a. Confirm system is functional, includes the wire connections for galvanic systems

☐ Yes ☐ No* ☐ N/A

4.2 Impressed current system

a. Inspect the operational components

(power switch, meters, and alarms).

b. Record hour meter, ammeter and voltmeter readings.

5.0 TANK SHELL, HEADS, ROOF

5.1 Coating

a. Check for coating failure ☐ Yes* ☐ No ☐ N/A

5.2 Steel Condition

Check for:

Dents Buckling Bulging Corrosion Cracking

5.3 Roof Slope

a. Check for low points and standing water

6.0 TANK EQUIPMENT

6.1 Vents

a. Verify that components are moving freely and vent passageways are not obstructed for:

Emergency vent covers Pressure/vacuum vent poppets Other moving vent components

6.2 Valves

a. Check the condition of all valves for leaks, corrosion and damage.

b. Tank drain valves must be kept locked.

6.3.1 Anti-Siphon, Check and Gate Valves

a. Cycle the valve open and closed and check for proper operation.

6.3.2 Pressure Regulator Valve

a. Check for proper operation. (Note that there may be small, 1/4 inch drain plugs in the bottom of the valve that are not visible by looking from above only)

☐ Yes ☐ No* ☐ N/A

6.3.3 Expansion Relief Valve

a. Check that the valve is in the proper orientation. (Note that fuel must be discharged back to the tank via a separate pipe or tubing.)

☐ Yes ☐ No* ☐ N/A

6.3.4 Solenoid Valves

a. Cycle power to valve to check operation.

(Electrical solenoids can be verified by listening to the plunger opening and closing. If no audible confirmation, the valve should be inspected for the presence and operation of the plunger.)

☐ Yes ☐ No* ☐ N/A

6.3.5 Fire and Shear Valves

a. Manually cycle the valve to ensure components are moving freely and that the valve handle or lever has clearance to allow valve to close completely.

☐ Yes ☐ No* ☐ N/A

b. Valves must not be wired in open position.

c. Make sure fusible element is in place and correctly positioned.

d. Be sure test ports are sealed with plug after testing is complete and no temporary test fixture or component remains connected to valve.

☐ Yes ☐ No* ☐ N/A

6.3 Interstitial Leak Detection Equipment

a. Check condition of equipment, including:

The window is clean and clear in sight leak gauges.

The wire connections of electronic gauges for tightness and corrosion

Activate the test button, if applicable.

☐ Yes ☐ No* ☐ N/A

6.4 Spill Containment Boxes on Fill Pipe

a. Inspect for debris, residue, and water in the box and remove.

☐ Yes* ☐ No ☐ N/A

b. Drain valves must be operable and closed.

☐ Yes ☐ No* ☐ N/A

c. If corrosion, damage, or wear has compromised the ability of the unit to perform spill containment functions, replace the unit.

☐ Yes* ☐ No ☐ N/A

d. Inspect the connections to the AST for tightness, as well as the bolts, nuts, washers for condition and replace if necessary.

☐ Yes ☐ No* ☐ N/A

e. Drain valves must be operable and closed

6.5 Strainer

a. Check that the strainer is clean and in good condition.

b. Access strainer basket and check cap and gasket seal as well as bolts.

☐ Yes ☐ No* ☐ N/A

6.6 Filter

a. Check that the filter is in good condition and is within the manufacturer’s expected service life.

Replace, if necessary.

☐ Yes ☐ No* ☐ N/A

b. Check for leaks and decreased fuel flow

6.7 Flame Arrestors

a. Follow manufacturer’s instructions.

Check for corrosion and blockage of air passages.

6.8 Leak Detector for Submersible Pump Systems

a. Test according to manufacturer's instructions and authority having jurisdiction (AHJ). Verify leak detectors are suited and properly installed for aboveground use.

☐ Yes ☐ No* ☐ N/A

6.9 Liquid Level Equipment

a. Both visual and mechanical devices must be inspected for physical damage.

b. Check that the device is easily readable

c. Has equipment been tested to ensure proper operation?

d. Does equipment operate as required?

e. Follow manufacturer’s instructions ☐ Yes ☐ No* ☐ N/A

6.10 Overfill Equipment

a. If equipped with a "test" button, activate the audible horn or light to confirm operation. This could be battery powered. Replace the battery if needed

☐ Yes ☐ No* ☐ N/A

b. If overfill valve is equipped with a mechanical test mechanism, actuate the mechanism to confirm operation.

c. Follow manufacturer’s instructions and regulatory requirements for inspection and functionality verification.

☐ Yes ☐ No* ☐ N/A

d. Confirm device is suited for above ground use by the manufacturer

6.11 Piping Connections

a. Check for leaks, corrosion and damage

7.0 INSULATED TANKS

7.1 Insulation

a. Check condition of insulation for:

Missing sections Areas of moisture Mold Damage

☐ Yes* ☐ No ☐ N/A

7.2 Insulation Cover or Jacket

a. Check for damage that will allow water intrusion

8.0 MISCELANEOUS

8.1 Electrical Wiring and Boxes

a. Are they in good condition? ☐ Yes ☐ No* ☐ N/A

8.2 Labels and Tags

a. Ensure that all labels and tags are intact and readable.

8.3 Ladder and Platform Structure

a. Secure with no sign of severe corrosion or damage?

8.4 Other Conditions

a. Are there other conditions that should be addressed for continued safe operation or that may affect the site spill prevention plan?

☐ Yes* ☐ No

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

APPENDIX D: PHOTOGRAPHS

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.1: Tank Ground and Steel Saddle D.2: Steel Saddle

D.3: Head 1 D.4: Overall View

D.5: Nozzles A, B, and C D.6: Nozzles D and E

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.7: Flame Arrestor D.8: Flame Arrestor

D.9: Nozzles F, G, and H D.10: Water Draw

D.11: Water Draw Hand Pump D.12: Nozzle H

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.13: Nozzle I D.14: Nozzle J and K

D.15: Electronic ATG D.16: Nozzle L

D.17: Overfill Alarm D.18: Nozzle M

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.19: Nozzles N, and O D.20: Nozzles N, O, and P

D.21: Nozzles O, P, and Q D.22: Nozzles P and Q

D.23: Catwalk Access D.24: Catwalk

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.25: Catwalk Access D.26: Receipt Filter Separator

D.27: Receipt Piping D.28: Receipt Piping

D.29: Receipt Piping D.30: Receipt Piping

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.31: Receipt Piping D.32: Receipt Piping

D.33: Thread Engagement D.34: Overall View

D.35: Issue Piping D.36: Issue Piping

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.37: Issue Piping D.38: Issue Piping

D.39: Issue Piping D.40: Issue Piping

D.41: Issue Piping D.42: Issue Spill Bucket

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.43: Issue Piping D.44: Fuel Dripping

D.45: Leaking Sight Flow Indicator D.46: Electronic ATG House

D.47: Electronic ATG Alarm D.48: Electronic ATG Read Out

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.49: Electronic ATG Control Panel D.50: Facility Containment

D.51: Facility Containment D.52: Facility Containment

D.53: Facility Containment D.54: Facility Containment

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.55: Containment Sump D.56: Containment Sump

D.57: Remote Impounding D.58: Remote Impounding

D.59: Expansion Joint Deterioration D.60: Expansion Joint Deterioration

STI In‐Service Inspection Report A.A.S.F.1 Lexington, OK

D.61: Vegetation D.62: Expansion Joint Deterioration

D.63: Expansion Joint Deterioration D.64: Containment Cracking

10 TANK CONTAINMENT:
11 Containment Structure:
undefined: No
Yes No NA:
12 Primary Tank:
a Check for water:
undefined_2: No_2
Yes No NA_2:
13 Containment Drain Valves:
a Operable and in a closed position:
undefined_3: Yes_3
Yes No NA_3:
14 Pathways and Entry:
a Clear and gatesdoors operable:
undefined_4: Yes_4
Yes No NA_4:
20 LEAK DETECTION:
21 Tank:
a Visible signs of leakage:
undefined_5: No_5
Yes No NA_5:
22 Secondary Containment:
undefined_6: No_6
Yes No NA_6:
23 Surrounding Soil:
a Visible signs of leakage_2:
undefined_7: No_7
Yes No NA_7:
24 Interstice:
a Visible signs of leakage_3:
undefined_8: No_8
Yes No NA_8:
30 TANK FOUNDATION and SUPPORTS:
31 Foundation:
a Settlement or foundation washout:
undefined_9: No_9
Yes No NA_9:
32 Concrete Pad or Ring Wall:
a Cracking or spalling:
undefined_10: Yes_10
Yes No NA_10: There is minor cracking and joint seal deterioration
ItemTask:
Status:
Comments:
33 Supports:
undefined_11: No_11
Yes No NA_11:
34 Water Drainage:
a Water drains away from tank:
undefined_12: Yes_12
Yes No NA_12:
35 Tank Grounding:
undefined_13: Yes_13
Yes No NA_13:
40 CATHODIC PROTECTION:
41 Gavlvanic Cathodic Protection System:
undefined_14: NA_14
Yes No NA_14:
42 Impressed current system:
undefined_15: NA_15
Yes No NA_15:
undefined_16: NA_16
Yes No NA_16:
50 TANK SHELL HEADS ROOF:
51 Coating:
a Check for coating failure:
undefined_17: Yes_17
Yes No NA_17: There is minor coating failure on the shell.
52 Steel Condition:
fill_28:
undefined_18: No_18
Yes No NA_18:
53 Roof Slope:
undefined_19: No_19
Yes No NA_19:
60 TANK EQUIPMENT:
61 Vents:
undefined_20: Yes_20
Yes No NA_20:
62 Valves:
undefined_21: No_21
Yes No NA_21:
undefined_22: Yes_22
Yes No NA_22:
631 AntiSiphon Check and Gate Valves:
undefined_23: NA_23
Yes No NA_23:
ItemTask_2:
Status_2:
Comments_2:
632 Pressure Regulator Valve:
undefined_24: NA_24
Yes No NA_24:
633 Expansion Relief Valve:
undefined_25: NA_25
Yes No NA_25:
634 Solenoid Valves:
undefined_26: NA_26
Yes No NA_26:
635 Fire and Shear Valves:
undefined_27: NA_27
Yes No NA_27:
undefined_28: NA_28
Yes No NA_28:
undefined_29: NA_29
Yes No NA_29:
undefined_30: NA_30
Yes No NA_30:
63 Interstitial Leak Detection Equipment:
undefined_31: Yes_31
Yes No NA_31:
64 Spill Containment Boxes on Fill Pipe:
undefined_32: No_32
Yes No NA_32:
undefined_33: Yes_33
Yes No NA_33:
undefined_34: No_34
Yes No NA_34:
undefined_35: Yes_35
Yes No NA_35:
undefined_36: NA_36
Yes No NA_36:
ItemTask_3:
Status_3:
Comments_3:
65 Strainer:
undefined_37: NA_37
Yes No NA_37:
undefined_38: NA_38
Yes No NA_38:
66 Filter:
undefined_39: NA_39
Yes No NA_39:
undefined_40: NA_40
Yes No NA_40:
67 Flame Arrestors:
undefined_41: NA_41
Yes No NA_41:
68 Leak Detector for Submersible Pump Systems:
undefined_42: NA_42
Yes No NA_42:
69 Liquid Level Equipment:
undefined_43: No_43
Yes No NA_43:
undefined_44: Yes_44
Yes No NA_44:
undefined_45: Yes_45
Yes No NA_45:
undefined_46: Yes_46
Yes No NA_46:
e Follow manufacturers instructions:
undefined_47: Yes_47
Yes No NA_47:
610 Overfill Equipment:
undefined_48: Yes_48
Yes No NA_48:
undefined_49: Yes_49
Yes No NA_49:
undefined_50: Yes_50
Yes No NA_50:
undefined_51: Yes_51
Yes No NA_51:
611 Piping Connections:
undefined_52: No_52
Yes No NA_52:
ItemTask_4:
Status_4:
Comments_4:
70 INSULATED TANKS:
71 Insulation:
undefined_53: NA_53
Yes No NA_53:
72 Insulation Cover or Jacket:
undefined_54: NA_54
Yes No NA_54:
80 MISCELANEOUS:
81 Electrical Wiring and Boxes:
a Are they in good condition:
undefined_55: Yes_55
Yes No NA_55:
82 Labels and Tags:
undefined_56: No_56
Yes No NA_56: Labels are coated and painted over
83 Ladder and Platform Structure:
undefined_57: Yes_57
Yes No NA_57:
84 Other Conditions:
undefined_58: No_58
Yes No: