Attachment 3 Technical Specifications-GAOA East Animas DM.pdf
PDF 618 KB Posted
- Attached to
- GAOA East Animas Bunkhouses Deferred Maintenance
- Solicitation number
- 1123781
- Issued by
-
Department of Agriculture Forest Service
About this file
This document contains technical specifications for a construction project to address deferred maintenance at two bunkhouses on the East Animas property, part of the San Juan National Forest in Durango, Colorado. The project includes work across various sections such as rough carpentry, wood patio decking, sheathing, roofing, joint sealants, gypsum board, ceramic tiling, plumbing, and electrical. Key requirements include preservative-treated wood products, standing-seam metal roofing, underlayments, sealants, and installation of tile, fixtures, and electrical components. The document provides detailed specifications for materials, installation, and performance standards for each work section. This appears to be a technical specification document associated with a federal contract opportunity for the GAOA East Animas Bunkhouses Deferred Maintenance project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| A003 SOI_GAOA East Animas DM.xlsx | XLSX spreadsheet | |
| A0003.pdf | ||
| A0004.pdf | ||
| 1282B124R0042 A0002.pdf | ||
| 1282B124R0042 A0001.pdf | ||
| East Animas DM- Pre-bid Meeting Q and A.docx | DOCX document | |
| Attachment 5 Drawing Set- GAOA East Animas DM.pdf | ||
| Attachment 2 Wage determination.pdf | ||
| Attachment 4 Past Performance Questionnaire.pdf | ||
| Attachment 1 SOW.pdf | ||
| 1282B124R0042.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Specifications GAOA East Animas Bunkhouses Deferred Maintenance
San Juan National Forest Durango, CO
Table of Contents:
SECTION 061000 - ROUGH CARPENTRY
SECTION 061533 - WOOD PATIO DECKING
SECTION 061600 - SHEATHING
SECTION 070150.19 - PREPARATION FOR REROOFING
SECTION 074113.16 - STANDING-SEAM METAL ROOF PANELS
SECTION 076200 - SHEET METAL FLASHING AND TRIM
SECTION 079200 - JOINT SEALANTS
SECTION 090190.52 - MAINTENANCE REPAINTING
SECTION 092900 - GYPSUM BOARD
SECTION 093013 - CERAMIC TILING
SECTION 096513 - RESILIENT BASE AND ACCESSORIES
SECTION 096519 - RESILIENT TILE FLOORING
SECTION 096813 - TILE CARPETING
SECTION 102116.19 - PLASTIC SHOWER AND DRESSING COMPARTMENTS
SECTION 221116 - DOMESTIC WATER PIPING
SECTION 223400 - FUEL-FIRED, DOMESTIC-WATER HEATERS
SECTION 224100 - RESIDENTIAL PLUMBING FIXTURES
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SECTION 260533.16 - BOXES AND COVERS FOR ELECTRICAL SYSTEMS
SECTION 061000 - ROUGH CARPENTRY
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Framing with dimension lumber.
2. Framing with engineered wood products.
3. Shear wall panels.
4. Rooftop equipment bases and support curbs.
5. Wood blocking and nailers.
6. Wood furring
7. Wood sleepers.
8. Plywood backing panels.
PART 2 - PRODUCTS
2.1 WOOD PRODUCTS, GENERAL
A. Lumber: Comply with DOC PS 20 and applicable rules of grading agencies indicated. If no grading agency is indicated, comply with the applicable rules of any rules-writing agency certified by the ALSC Board of Review. Grade lumber by an agency certified by the ALSC Board of Review to inspect and grade lumber under the rules indicated.
1. Factory mark each piece of lumber with grade stamp of grading agency.
2. For exposed lumber indicated to receive a stained or natural finish, mark grade stamp on end or back of each piece.
3. Dress lumber, S4S, unless otherwise indicated.
B. Maximum Moisture Content:
1. Boards: [19 percent]
2. Dimension Lumber: [19 percent]
3. Timber. [19 percent]
C. Engineered Wood Products: Acceptable to authorities having jurisdiction and for which current model code research or evaluation reports exist that show compliance with building code in effect for Project.
1. Allowable design stresses, as published by manufacturer, are to meet or exceed those indicated. Manufacturer's published values are to be determined from empirical data or by rational engineering analysis and demonstrated by comprehensive testing performed by a qualified independent testing agency.
2.2 PRESERVATIVE TREATMENT
A. Preservative Treatment by Pressure Process: AWPA U1; Use Category UC2 for interior construction not in contact with ground, Use Category UC3b for exterior construction not in contact with ground, and Use Category UC4a for items in contact with ground.
1. Preservative Chemicals: Acceptable to authorities having jurisdiction and containing no arsenic or chromium.
B. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent. Do not use material that is warped or that does not comply with requirements for untreated material.
C. Mark lumber with treatment quality mark of an inspection agency approved by the ALSC Board of Review.
D. Application: Treat items indicated on Drawings, and the following:
1. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members in connection with roofing, flashing, vapor barriers, and waterproofing.
2. Wood sills, sleepers, blocking, furring, and similar concealed members in contact with masonry or concrete.
3. Wood framing and furring attached directly to the interior of below-grade exterior masonry or concrete walls.
4. Wood framing members that are less than 18 inches (460 mm) above the ground in crawlspaces or unexcavated areas.
5. Wood floor plates that are installed over concrete slabs-on-grade.
2.4 DIMENSION LUMBER FRAMING
A. Non-Load-Bearing Interior Partitions by Grade: [Construction or No. 2] grade.
1. Application: [Interior partitions not indicated as load bearing].
2. Species:
a. Southern pine or mixed southern pine; SPIB.
b. Northern species; NLGA.
c. Eastern softwoods; NeLMA.
d. Western woods; WCLIB or WWPA.
B. Framing Other Than Non-Load-Bearing Partitions by Grade: [Construction or No. 2] grade.
1. Application: Framing other than [interior partitions not indicated as load bearing].
2. Species:
a. Hem-fir (north); NLGA.
b. Southern pine; SPIB.
c. Douglas fir-larch; WCLIB or WWPA.
d. Southern pine or mixed southern pine; SPIB.
e. Spruce-pine-fir; NLGA.
f. Douglas fir-south; WWPA.
g. Hem-fir; WCLIB or WWPA.
h. Douglas fir-larch (north); NLGA.
i. Spruce-pine-fir (south); NeLMA, WCLIB, or WWPA.
D. Exposed Framing: Hand-select material for uniformity of appearance and freedom from characteristics, on exposed surfaces and edges, that would impair finish appearance, including decay, honeycomb, knot-holes, shake, splits, torn grain, and wane.
1. Species and Grade: As indicated above for load-bearing construction of same type.
2.7 MISCELLANEOUS LUMBER
A. Provide miscellaneous lumber indicated and lumber for support or attachment of other construction, including the following:
1. Blocking.
2. Nailers.
3. Rooftop equipment bases and support curbs.
4. Cants.
5. Furring.
6. Grounds.
B. Dimension Lumber Items: [Construction or No. 3] grade lumber of any species.
C. Concealed Boards: [19] percent maximum moisture content and any of the following species and grades:
1. Mixed southern pine or southern pine; No. [3] grade; SPIB.
2. Eastern softwoods; No. [3] Common grade; NeLMA.
3. Northern species; No. [3] Common grade; NLGA.
4. Western woods; [Construction or No. 2 Common] grade; WCLIB or WWPA.
2.9 FASTENERS
A. General: Fasteners are to be of size and type indicated and comply with requirements specified in this article for material and manufacture. Provide nails or screws, in sufficient length, to penetrate not less than 1-1/2 inches (38 mm) into wood substrate.
1. Where rough carpentry is exposed to weather, in ground contact, pressure-preservative treated, or in area of high relative humidity, provide fasteners with hot-dip zinc coating complying with ASTM A153/A153M.
B. Power-Driven Fasteners: Fastener systems with an evaluation report acceptable to authorities having jurisdiction, based on ICC-ES AC70.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Framing Standard: Comply with AF&PA's WCD 1, "Details for Conventional Wood Frame Construction," unless otherwise indicated.
B. Framing with Engineered Wood Products: Install engineered wood products to comply with manufacturer's written instructions.
C. Set work to required levels and lines, with members plumb, true to line, cut, and fitted. Fit rough carpentry accurately to other construction. Locate furring, nailers, blocking, grounds, and similar supports to comply with requirements for attaching other construction.
D. Install shear wall panels to comply with manufacturer's written instructions.
E. Install metal framing anchors to comply with manufacturer's written instructions. Install fasteners through each fastener hole.
F. Do not splice structural members between supports unless otherwise indicated.
G. Comply with AWPA M4 for applying field treatment to cut surfaces of preservative-treated lumber.
H. Where wood-preservative-treated lumber is installed adjacent to metal decking, install continuous flexible flashing separator between wood and metal decking.
I. Securely attach rough carpentry work to substrate by anchoring and fastening as indicated, complying with the following:
1. Table 2304.9.1, "Fastening Schedule," in ICC's International Building Code (IBC).
2. Table R602.3(1), "Fastener Schedule for Structural Members," and Table R602.3(2), "Alternate Attachments," in ICC's International Residential Code for One- and Two- Family Dwellings.
3. ICC-ES evaluation report for fastener.
3.2 PROTECTION
A. Protect wood that has been treated with inorganic boron (SBX) from weather. If, despite protection, inorganic boron-treated wood becomes wet, apply EPA-registered borate treatment.
Apply borate solution by spraying to comply with EPA-registered label.
B. Protect rough carpentry from weather. If, despite protection, rough carpentry becomes wet enough that moisture content exceeds that specified, apply EPA-registered borate treatment. Apply borate solution by spraying to comply with EPA-registered label.
END OF SECTION 061000
SECTION 061533 - WOOD PATIO DECKING
PART 1 - GENERAL
SUMMARY
Section Includes:
1. Wood decking.
2. Plastic decking.
3. Stairs for elevated decks.
4. Railings for elevated decks.
5. Wood benches for elevated decks.
6. Support framing for elevated decks.
PART 2 - PRODUCTS
LUMBER, GENERAL
Comply with DOC PS 20 and with grading rules of lumber grading agencies certified by ALSC's Board of Review as applicable. If no grading agency is indicated, comply with the applicable rules of any rules-writing agency certified by ALSC's Board of Review.
1. Factory mark each item with grade stamp of grading agency.
2. For items that are exposed to view in the completed Work, mark grade stamp on end or back of each piece.
3. Provide dressed lumber, S4S, unless otherwise indicated.
Maximum Moisture Content:
4. Boards: 19 percent
5. Dimension Lumber: 19 percent
6. Timber. 19 percent
WOOD DECKING AND STAIR TREADS
Dimension Lumber Decking and Stair Treads: Construction or No. 2 grade and any of the following species:
7. Hem-fir or hem-fir (North); NLGA, WCLIB, or WWPA.
8. Douglas fir-larch, Douglas fir-larch (North), or Douglas fir-south; NLGA, WCLIB, or
WWPA.
9. Mixed southern pine; SPIB.
10. Redwood; RIS.
Dimension Lumber Decking and Stair Treads: Deck Common or Construction Common redwood; RIS.
Board Decking and Stair Treads: 1-1/4-inch (32-mm) actual thickness radius-edged decking of[ any of] the following species and grades:
11. Douglas fir-larch or Douglas fir-south, [Patio 1]; WWPA.
12. Douglas fir-larch, [Select Dex] WCLIB.
13. Douglas fir-larch (North), [Select Patio] NLGA.
14. Hem-fir, [Patio 1] WWPA.
15. Hem-fir, [Select Dex] WCLIB.
16. Hem-fir (North), [Select Patio] NLGA.
17. Redwood, [Heart Clear] RIS.
18. Southern pine, [Premium]; SPIB.
19. Western red cedar, [Patio 1] ; WWPA.
20. Western red cedar, [Select Dex]; WCLIB.
21. Western red cedar (North), [Select Patio]; NLGA.
WOOD RAILINGS
Dimension Lumber Railing Members: Construction or No. 2 grade and any of the following species:
22. Hem-fir or hem-fir (North); NLGA, WCLIB, or WWPA.
23. Douglas fir-larch, Douglas fir-larch (North), or Douglas fir-south; NLGA, WCLIB, or
WWPA.
24. Mixed southern pine; SPIB.
25. Redwood; RIS.
26. Spruce-pine-fir or spruce-pine-fir (South); NeLMA, NLGA, WCLIB, or WWPA.
Dimension Lumber Railing Members: Heart B or Select Heart redwood; RIS.
Railing Boards Any of the following species and grades;
27. Douglas fir, C & Btr finish or C Select; NLGA, WCLIB, or WWPA.
28. Hem-fir, C & Btr finish or C Select; NLGA, WCLIB, or WWPA.
29. Redwood, [Heart B or Select Heart]; RIS.
30. Southern pine, B & B finish; SPIB.
DIMENSION LUMBER FRAMING
Deck and Stair Framing: [Construction or No. 2] grade and any of the following species:
31. Hem-fir (North); NLGA.
32. Southern pine; SPIB.
33. Douglas fir-larch; WCLIB or WWPA.
34. Spruce-pine-fir; NLGA.
35. Douglas fir-south; WWPA.
36. Hem-fir; WCLIB or WWPA.
37. Douglas fir-larch (North); NLGA.
38. Spruce-pine-fir (South); NeLMA, WCLIB, or WWPA.
POSTS
Dimension Lumber Posts: Construction or No. 2 grade and any of the following species:
39. Hem-fir or hem-fir (North); NLGA, WCLIB, or WWPA.
40. Douglas fir-larch, Douglas fir-larch (North), or Douglas fir-south; NLGA, WCLIB, or
WWPA.
41. Mixed southern pine; SPIB.
42. Spruce-pine-fir or spruce-pine-fir (South); NeLMA, NLGA, WCLIB, or WWPA.
43. Northern species; NLGA.
44. Eastern softwoods; NeLMA.
45. Western woods; WCLIB or WWPA.
Timber Posts: Balsam fir, Douglas fir-larch, Douglas fir-larch (North), eastern hemlock tamarack (North), hem-fir, southern pine, western hemlock, or western hemlock (North); [No. 1] [No. 2];
NeLMA, NLGA, SPIB, WCLIB, or WWPA.
Timber Posts: Alaska cedar; [No. 2]; WCLIB.
Timber Posts: Southern pine; [No. 2]; SPIB.
PRESERVATIVE TREATMENT
Pressure treat boards and dimension lumber with waterborne preservative in accordance with AWPA U1; Use Category UC3b for exterior construction not in contact with the ground, and Use Category UC4a for items in contact with the ground.
Pressure treat timber with waterborne preservative in accordance with AWPA U1; Use Category UC4a.
Preservative Chemicals: Acceptable to authorities having jurisdiction.
46. Do not use chemicals containing arsenic or chromium, except for timber posts.
Use process that includes water-repellent treatment.
Use process that does not include water repellents or other substances that might interfere with application of indicated finishes.
After treatment, redry boards dimension lumber and timber to 19 percent maximum moisture content.
Mark treated wood with treatment quality mark of an inspection agency approved by ALSC's Board of Review. Retain first option in subparagraph below if authorities having jurisdiction require quality mark on all materials.
Application: Treat all wood unless otherwise indicated.
47. Framing members less than 18 inches (460 mm) above grade.
48. Sills and ledgers.
49. Members in contact with masonry or concrete.
50. Posts.
51. Round wood poles.
52. Decking.
53. Stair treads.
FASTENERS
General: Provide fasteners of size and type indicated, acceptable to authorities having jurisdiction, and that comply with requirements specified in this article for material and manufacture. Provide nails or screws, in sufficient length, to penetrate not less than 1-1/2 inches (38 mm) into wood substrate.
54. Use fasteners with hot-dip zinc coating complying with ASTM A153/A153M or ASTM F2329 unless otherwise indicated.
55. For pressure-preservative-treated wood, use stainless steel fasteners.
CONCEALED DECKING FASTENERS
Deck Splines: Corrosion-resistant metal or plastic splines that fit in grooves routed into the sides of decking material and are fastened to deck framing with screws. Splines provide uniform spacing of decking material.
Deck Clips: Black-oxide-coated, stainless steel clips designed to be fastened to deck framing with screws, and to secure decking material with teeth that also provide uniform spacing of decking material.
Deck Tracks: Formed metal strips designed to be fastened to deck framing and to secure decking material from underside with screws. Made from epoxy-powder-coated, hot-dip galvanized steel or stainless steel.
PART 3 - EXECUTION
INSTALLATION, GENERAL
Set work to required levels and lines, with members plumb, true to line, cut, and fitted. Fit work to other construction; scribe and cope as needed for accurate fit.
Framing Standard: Comply with AF&PA WCD1 unless otherwise indicated.
Install wood decking and stair treads with crown up (bark side down).
Install plastic lumber to comply with manufacturer's written instructions.
Secure decking to framing with deck splines, deck clips, deck tracks, or, screws.
Install metal framing anchors to comply with manufacturer's written instructions.
Do not splice structural members between supports unless otherwise indicated.
Apply copper naphthenate field treatment to comply with AWPA M4, to cut surfaces of preservative-treated lumber.
Securely attach exterior rough carpentry work to substrate by anchoring and fastening as indicated, complying with the following:
1. ICC-ES AC70 for power-driven fasteners.
2. "Fastening Schedule" in ICC's International Building Code.
3. "Fastener Schedule for Structural Members" and "Alternate Attachments" in ICC's
International Residential Code for One- and Two-Family Dwellings.
INSTALLATION OF ELEVATED DECK JOIST FRAMING
General: Install joists with crown edge up and support ends of each member with not less than 1-1/2 inches (38 mm) of bearing on wood or metal, or 3 inches (76 mm) on masonry. Attach floor joists where framed into wood supporting members by using wood ledgers as indicated or, if not indicated, by using metal joist hangers. Do not notch joists.
Lap members framing from opposite sides of beams or girders not less than 4 inches (102 mm,) or securely tie opposing members together.
INSTALLATION OF STAIRS
Provide stair framing with no more than 3/8-inch (9.5-mm) variation between largest and smallest treads and risers within each flight.
Treads and Risers: Secure by gluing and screwing to carriages. Countersink fastener heads, fill flush, and sand filler. Extend treads over carriages and finish with bullnose edge.
INSTALLATION OF RAILINGS
Balusters: Fit to railings, glue, and screw in place. Countersink fastener heads, fill flush, and sand filler.
Newel Posts: Secure to stringers and risers with countersunk-head wood screws and glue.
Railings: Secure wall rails with metal brackets. Fasten freestanding railings to newel posts and to trim at walls with countersunk-head wood screws or rail bolts and glue.
END OF SECTION 061533
SECTION 061600 - SHEATHING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Wall sheathing.
2. Roof sheathing.
3. Parapet sheathing.
4. Composite nail base insulated roof sheathing.
5. Subflooring.
6. Underlayment.
7. Sheathing joint and penetration treatment.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Fire-Resistance Ratings: As tested in accordance with ASTM E119; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Fire-Resistance Ratings: Indicated by design designations from UL's "Fire Resistance Directory" or from the listings of another qualified testing agency.
2.2 WOOD PANEL PRODUCTS
A. Emissions: Products are to meet the testing and product requirements of the California Department of Public Health's "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers."
2.3 PRESERVATIVE-TREATED PLYWOOD
A. Preservative Treatment by Pressure Process: AWPA U1; Use Category UC2 for interior construction not in contact with ground, Use Category UC3b for exterior construction not in contact with ground, and Use Category UC4a for items in contact with ground.
B. Mark plywood with appropriate classification marking of an inspection agency acceptable to authorities having jurisdiction.
C. Application: Treat all plywood unless otherwise indicated and plywood in contact with masonry or concrete or used with roofing, flashing, vapor barriers, and waterproofing.
2.4 FIRE-RETARDANT-TREATED PLYWOOD
A. General: Where fire-retardant-treated materials are indicated, use materials complying with requirements in this article that are acceptable to authorities having jurisdiction and with fire-test-response characteristics specified as determined by testing identical products per test method indicated by a qualified testing agency.
B. Fire-Retardant-Treated Plywood by Pressure Process: Products with a flame-spread index of 25 or less when tested in accordance with ASTM E84, and with no evidence of significant progressive combustion when the test is extended an additional 20 minutes, and with the flame front not extending more than 10.5 feet (3.2 m) beyond the centerline of the burners at any time during the test.
1. Exterior Type: Treated materials are to comply with requirements specified above for fire-retardant-treated plywood by pressure process after being subjected to accelerated weathering in accordance with ASTM D2898. Use for exterior locations and where indicated.
2. Interior Type A: Treated materials are to have a moisture content of 28 percent or less when tested in accordance with ASTM D3201/D3201M at 92 percent relative humidity. Use where exterior type is not indicated.
3. Design Value Adjustment Factors: Treated lumber plywood is to be tested in accordance with ASTM D5516 and design value adjustment factors are to be calculated in accordance with ASTM D6305. Span ratings after treatment are to be not less than span ratings specified.
C. Kiln-dry material after treatment to a maximum moisture content of 15 percent.
D. Identify fire-retardant-treated plywood with appropriate classification marking of qualified testing agency.
2.5 WALL SHEATHING
A. Plywood Sheathing, Walls: Exterior, Structural I sheathing.
B. Oriented-Strand-Board Sheathing, Walls: DOC PS 2, Exposure 1, Structural I sheathing.
C. Paper-Surfaced Gypsum Sheathing: ASTM C1396/C1396M, gypsum sheathing; with water-resistant-treated core and with water-repellent paper bonded to core's face, back, and long edges.
1. Type and Thickness: Regular, 1/2 inch (13 mm) thick.
D. Glass-Mat Gypsum Sheathing, Walls: ASTM C1177/C1177M.
1. Type and Thickness: Regular, 1/2 inch (13 mm) thick.
E. Cellulose Fiber-Reinforced Gypsum Sheathing: ASTM C1278/C1278M, gypsum sheathing.
1. Type and Thickness Regular, 1/2 inch (13 mm) thick.
F. Cementitious Backer Units, Walls: ASTM C1325, Type A.
1. Thickness: 1/2 inch (12.7 mm)
2.6 ROOF SHEATHING
A. Plywood Sheathing, Roofs: Exterior, Structural I sheathing.
B. Oriented-Strand-Board Sheathing, Roofs: DOC PS 2, Exposure 1, Structural I sheathing.
2.7 PARAPET SHEATHING
A. Plywood Sheathing, Parapets: Exterior, Structural I sheathing.
B. Oriented-Strand-Board Sheathing, Parapets: DOC PS 2, Exposure 1, Structural I nsheathing.
2.9 SUBFLOORING AND UNDERLAYMENT
A. Plywood Combination Subfloor-Underlayment: DOC PS 1, Exposure 1, Structural I, Underlayment single-floor panels.
B. Oriented-Strand-Board Combination Subfloor-Underlayment: DOC PS 2, Exposure 1 single-floor panels.
C. Plywood Subflooring: Exterior, Structural I single-floor panels or sheathing.
D. Oriented-Strand-Board Subflooring: DOC PS 2, Exposure 1 single-floor panels or sheathing.
E. Underlayment: Provide underlayment in nominal thicknesses indicated or, if not indicated, not less than 1/4 inch (6.4 mm) over smooth subfloors and not less than 3/8 inch (9.5 mm) over board or uneven subfloors.
1. Plywood Underlayment for Resilient Flooring: DOC PS 1, Exterior A-C with fully sanded face.
2. Plywood Underlayment for Ceramic Tile: DOC PS 1, Exterior, C-C Plugged, not less than 5/8-inch (15.9-mm) nominal thickness.
3. Plywood Underlayment for Carpet: DOC PS 1 Exposure 1, Underlayment.
4. Particleboard Underlayment: ANSI A208.1, [Grade PBU].
5. Hardboard Underlayment: ANSI A135.4, Class 4 (Service), Surface S1S; with back side sanded.
2.10 FASTENERS
A. General: Provide fasteners of size and type indicated that comply with requirements specified in this article for material and manufacture.
1. For roof parapet and wall sheathing, provide fasteners with hot-dip zinc coating complying with ASTM A153/A153M or Type 304 stainless steel.
2. For roof parapet and wall sheathing, provide fasteners with organic-polymer or other corrosion-protective coating having a salt-spray resistance of more than 800 hours in accordance with ASTM B117.
2.11 SHEATHING JOINT-AND-PENETRATION TREATMENT MATERIALS
A. Sealant for Paper-Surfaced Gypsum Sheathing: Elastomeric, medium-modulus, neutral-curing silicone joint sealant compatible with joint substrates formed by gypsum sheathing and other materials, recommended by sheathing manufacturer for application indicated and complying with requirements for elastomeric sealants specified in Section 079200 "Joint Sealants."
B. Sealant for Glass-Mat Gypsum Sheathing: Silicone emulsion sealant complying with ASTM C834, compatible with sheathing tape and sheathing and recommended by tape and sheathing manufacturers for use with glass-fiber sheathing tape and for covering exposed fasteners.
1. Sheathing Tape: Self-adhering glass-fiber tape, minimum 2 inches (50 mm) wide, 10 by 10 or 10 by 20 threads/inch (390 by 390 or 390 by 780 threads/m), of type recommended by sheathing and tape manufacturers for use with silicone emulsion sealant in sealing joints in glass-mat gypsum sheathing and with a history of successful in-service use.
C. Sheathing Tape for Foam-Plastic Sheathing: Pressure-sensitive plastic tape recommended by sheathing manufacturer for sealing joints and penetrations in sheathing.
2.12 MISCELLANEOUS MATERIALS
A. Adhesives for Field Gluing Panels to Wood Framing: Formulation complying with ASTM D3498 that is approved for use with type of construction panel indicated by manufacturers of both adhesives and panels.
PART 3 - EXECUTION
3.1 INSTALLATION, GENERAL
A. Do not use materials with defects that impair quality of sheathing or pieces that are too small to use with minimum number of joints or optimum joint arrangement. Arrange joints so that pieces do not span between fewer than three support members.
B. Cut panels at penetrations, edges, and other obstructions of work; fit tightly against abutting construction unless otherwise indicated.
C. Securely attach to substrate by fastening as indicated, complying with the following:
1. Table 2304.10.1, "Fastening Schedule," in the ICC's International Building Code.
2. Table R602.3(1), "Fastener Schedule for Structural Members," and Table R602.3(2), "Alternate Attachments," in the ICC's International Residential Code for One- and Two- Family Dwellings.
3. ICC-ES evaluation report for fastener.
D. Coordinate wall, parapet, and roof sheathing installation with flashing and joint-sealant installation so these materials are installed in sequence and manner that prevent exterior moisture from passing through completed assembly.
E. Do not bridge building expansion joints; cut and space edges of panels to match spacing of structural support elements.
3.2 WOOD STRUCTURAL PANEL INSTALLATION
A. General: Comply with applicable recommendations in APA Form No. E30, "Engineered Wood Construction Guide," for types of structural-use panels and applications indicated.
B. Fastening Methods: Fasten panels as indicated below:
1. Combination Subfloor-Underlayment:
a. Glue and nail to wood framing.
b. Screw to cold-formed metal framing.
c. Space panels 1/8 inch (3 mm) apart at edges and ends.
2. Subflooring:
a. Glue and nail to wood framing.
b. Screw to cold-formed metal framing.
c. Space panels 1/8 inch (3 mm) apart at edges and ends.
3. Wall and Roof Sheathing:
a. Nail or staple to wood framing. Apply a continuous bead of glue to framing members at edges of wall sheathing panels.
b. Screw to cold-formed metal framing.
c. Space panels 1/8 inch (3 mm) apart at edges and ends.
4. Underlayment:
a. Nail or staple to subflooring.
b. Space panels 1/32 inch (0.8 mm) apart at edges and ends.
c. Fill and sand edge joints of underlayment receiving resilient flooring immediately before installing flooring.
3.3 GYPSUM SHEATHING INSTALLATION
A. Comply with GA-253 and with manufacturer's written instructions.
1. Fasten gypsum sheathing to wood framing with screws.
2. Fasten gypsum sheathing to cold-formed metal framing with screws.
3. Install panels with a 3/8-inch (9.5-mm) gap where non-load-bearing construction abuts structural elements.
4. Install panels with a 1/4-inch (6.4-mm) gap where they abut masonry or similar materials that might retain moisture, to prevent wicking.
B. Seal sheathing joints in accordance with sheathing manufacturer's written instructions.
1. Apply elastomeric sealant to joints and fasteners and trowel flat. Apply sufficient amount of sealant to completely cover joints and fasteners after troweling. Seal other penetrations and openings.
2. Apply glass-fiber sheathing tape to glass-mat gypsum sheathing joints and apply and trowel sealant to embed entire face of tape in sealant. Apply sealant to exposed fasteners with a trowel so fasteners are completely covered. Seal other penetrations and openings.
3.4 CEMENTITIOUS BACKER UNIT INSTALLATION
A. Install panels and treat joints in accordance with ANSI A108.11 and manufacturer's written instructions for type of application indicated.
3.5 FOAM-PLASTIC SHEATHING INSTALLATION
A. Comply with manufacturer's written instructions.
B. Foam-Plastic Wall Sheathing: Install vapor-relief strips or equivalent for permitting escape of moisture vapor that otherwise would be trapped in stud cavity behind sheathing.
C. Apply sheathing tape to joints between foam-plastic sheathing panels and at items penetrating sheathing. Apply at upstanding flashing to overlap both flashing and sheathing.
3.6 PARTICLEBOARD UNDERLAYMENT INSTALLATION
A. Comply with CPA's recommendations for type of subfloor indicated. Fill and sand gouges, gaps, and chipped edges. Sand uneven joints flush.
1. Fastening Method: Glue and nail underlayment to subflooring.
3.7 HARDBOARD UNDERLAYMENT INSTALLATION
A. Comply with CPA's recommendations and hardboard manufacturer's written instructions for preparing and applying hardboard underlayment.
1. Fastening Method: Nail underlayment to subflooring.
END OF SECTION 0616
SECTION 070150.19 - PREPARATION FOR REROOFING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Full tear-off of roof system at areas indicated on Drawings.
2. Partial tear-off of roof areas indicated on Drawings.
3. Re-cover preparation of roof areas indicated on Drawings.
4. Removal of flashings and counter flashings.
1.7 FIELD CONDITIONS
A. Existing Roofing System: Metal exposed fasteners roofing.
C. Protect building to be reroofed, adjacent buildings, walkways, site improvements, exterior plantings, and landscaping from damage or soiling from reroofing operations.
D. Maintain access to existing walkways, corridors, and other adjacent occupied or used facilities.
E. Conditions existing at time of inspection for bidding will be maintained by Owner as far as practical.
1. A roof moisture survey of existing roofing system is available for Contractor's reference.
2. The results of an analysis of test cores from existing roofing system are available for
Contractor's reference.
3. Construction Drawings for existing roofing system are provided for Contractor's convenience and information, but they are not a warranty of existing conditions. They are intended to supplement rather than serve in lieu of Contractor's own investigations.
Contractor is responsible for conclusions derived from existing documents.
F. Limit construction loads on existing roof areas to remain, 40psf for uniformly distributed loads.
G. Weather Limitations: Proceed with reroofing preparation only when existing and forecasted weather conditions permit Work to proceed without water entering existing roofing system or building.
1. Remove only as much roofing in one day as can be made watertight in the same day.
PART 2 - PRODUCTS
2.1 AUXILIARY REROOFING MATERIALS
A. General: Use auxiliary reroofing preparation materials recommended by roofing system manufacturer for intended use and compatible with components of new roofing system.
B. Specific: See drawings and SOW for roofing material preference.
3.1 PREPARATION
A. Seal or isolate windows that may be exposed to airborne substances created in removal of existing materials.
B. Shut off rooftop utilities and service piping before beginning the Work.
C. Test existing roof drains to verify that they are not blocked or restricted.
1. Immediately notify COR of any blockages or restrictions.
D. Coordinate with Owner to shut down air-intake equipment in the vicinity of the Work.
1. Cover air-intake louvers before proceeding with reroofing work that could affect indoor air quality or activate smoke detectors in the ductwork.
E. During removal operations, have sufficient and suitable materials on-site to facilitate rapid installation of temporary protection in the event of unexpected rain.
F. Maintain roof drains in functioning condition to ensure roof drainage at end of each workday.
1. Prevent debris from entering or blocking roof drains and conductors.
a. Use roof-drain plugs specifically designed for this purpose.
b. Remove roof-drain plugs at end of each workday, when no work is taking place, or when rain is forecast.
2. If roof drains are temporarily blocked or unserviceable due to roofing system removal or partial installation of new roofing system, provide alternative drainage method to remove water and eliminate ponding.
a. Do not permit water to enter into or under existing roofing system components that are to remain.
3.2 ROOF TEAR-OFF
A. Notify COR each day of extent of roof tear-off proposed for that day and obtain authorization to proceed.
B. Lower removed roofing materials to ground and onto lower roof levels, using dust-tight chutes or other acceptable means of removing materials from roof areas.
D. Remove loose aggregate from aggregate-surfaced, built-up bituminous roofing using a power broom.
F. Full Roof Tear-off: Where indicated on Drawings, remove existing roofing and other roofing system components down to the existing roof deck.
1. Remove vapor retarder.
2. Remove base flashings and counter flashings.
3. Remove perimeter edge flashing and gravel stops.
4. Remove copings.
5. Remove expansion-joint covers.
6. Remove flashings at pipes, curbs, mechanical equipment, and other penetrations.
7. Remove wood blocking, curbs, and nailers.
9. Remove fasteners from deck or cut fasteners off slightly above deck surface.
3.3 DECK PREPARATION
A. Inspect deck after tear-off of roofing system.
B. If broken or loose fasteners that secure deck panels to one another or to structure are observed, or if deck appears or feels inadequately attached, immediately notify COR.
1. Do not proceed with installation until directed by COR.
C. If deck surface is unsuitable for receiving new roofing or if structural integrity of deck is suspect, immediately notify COR.
1. Do not proceed with installation until directed by COR.
D. Provide additional deck securement as indicated on Drawings.
H. Replace plywood roof sheathing as indicated on Drawings.
3.4 ROOF RE-COVER PREPARATION
A. Remove blisters, ridges, buckles and other substrate irregularities from existing roofing that inhibit new recover boards from conforming to substrate.
1. Remove loose aggregate from aggregate-surfaced, built-up bituminous roofing with a power broom.
2. Broom clean existing substrate.
3. Coordinate with Owner's inspector to schedule times for tests and inspections.
4. Verify that existing substrate is dry.
a. Spot check substrates with an electrical capacitance moisture-detection meter.
5. Remove materials that are wet or damp.
a. Removal will be paid for by adjusting the Contract Sum according to unit prices included in the Contract Documents.
3.5 BASE FLASHING REMOVAL
A. Remove existing base flashings.
1. Clean substrates of contaminants, such as asphalt, sheet materials, dirt, and debris.
B. Do not damage metal counterflashings that are to remain.
1. Replace metal counterflashings damaged during removal with counterflashings of same metal, weight or thickness, and finish as existing.
C. Inspect parapet sheathing, wood blocking, curbs, and nailers for deterioration and damage.
1. If parapet sheathing, wood blocking, curbs, or nailers have deteriorated, immediately notify Architect.
END OF SECTION 070150
SECTION 074113.16 - STANDING-SEAM METAL ROOF PANELS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Standing-seam metal roof panels.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer.
B. UL-Certified, Portable Roll-Forming Equipment: UL-certified, portable roll-forming equipment capable of producing metal panels warranted by manufacturer to be the same as factory-formed products. Maintain UL certification of portable roll-forming equipment for duration of work.
1.7 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of metal panel systems that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Two years from date of Substantial Completion.
B. Special Warranty on Panel Finishes: Manufacturer's standard form in which manufacturer agrees to repair finish or replace metal panels that show evidence of deterioration of factory-applied finishes within specified warranty period.
1. Finish Warranty Period: 20 years from date of Substantial Completion.
C. Special Weathertightness Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace standing-seam metal roof panel assemblies that fail to remain weathertight, including leaks, within specified warranty period.
1. Warranty Period: 20 years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
C. Energy Performance:
1. Provide roof panels that are listed on the EPA/DOE's ENERGY STAR "Roof Product List" for steep-slope roof products.
2. Provide roof panels according to one of the following when tested according to CRRC-1:
a. Three-year, aged solar reflectance of not less than 0.55 and emissivity of not less than 0.75
b. Three-year, aged Solar Reflectance Index of not less than 64 when calculated according to ASTM E1980.
D. Structural Performance: Provide metal panel systems capable of withstanding the effects of the following loads, based on testing according to ASTM E1592:
1. Snow Loads: 40psf
E. Air Infiltration: Air leakage of not more than 0.06 cfm/sq. ft. (0.3 L/s per sq. m) when tested according to ASTM E1680 at the following test-pressure difference:
F. Water Penetration under Static Pressure: No water penetration when tested according to ASTM E1646 at the following test-pressure difference:
G. Hydrostatic-Head Resistance: No water penetration when tested according to ASTM E2140.
H. Wind-Uplift Resistance: Provide metal roof panel assemblies that comply with UL 580 for wind-uplift-resistance class indicated.
1. Uplift Rating: UL 90.
I. FM Global Listing: Provide metal roof panels and component materials that comply with requirements in FM Global 4471 as part of a panel roofing system and that are listed in FM Global's "Approval Guide" for Class 1 or noncombustible construction, as applicable. Identify materials with FM Global markings.
1. Fire/Windstorm Classification: Class 1A-90.
J. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes by preventing buckling, opening of joints, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects. Base calculations on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.
1. Temperature Change (Range): 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surface.
2.2 STANDING-SEAM METAL ROOF PANELS
A. Provide factory-formed metal roof panels designed to be installed by lapping and interconnecting raised side edges of adjacent panels with joint type indicated and mechanically attaching panels to supports using concealed clips in side laps. Include clips, cleats, pressure plates, and accessories required for weathertight installation.
1. Steel Panel Systems: Unless more stringent requirements are indicated, comply with
ASTM E1514.
2. Aluminum Panel Systems: Unless more stringent requirements are indicated, comply with
ASTM E1637.
B. Vertical-Rib, Snap-Joint, Standing-Seam Metal Roof Panels: Formed with vertical ribs at panel edges and a flat pan between ribs; designed for sequential installation by mechanically attaching panels to supports using concealed clips located under one side of panels, engaging opposite edge of adjacent panels, and snapping panels together.
1. Metallic-Coated Steel Sheet: Zinc-coated (galvanized) steel sheet complying with
ASTM A653/A653M, G90 (Z275) coating designation, or aluminum-zinc alloy-coated steel sheet complying with ASTM A792/A792M, Class AZ50 (Class AZM150) coating designation; structural quality. Prepainted by the coil-coating process to comply with
ASTM A755/A755M.
a. Nominal Thickness: 0.022 inch (0.56 mm)
b. Exterior Finish: Two-coat fluoropolymer.
c. Color: As selected by Architect from manufacturer's full range
3. Aluminum Sheet: Coil-coated sheet, ASTM B209 (ASTM B209M), alloy as standard with manufacturer, with temper as required to suit forming operations and structural performance required.
a. Thickness: [0.032 inch (0.81 mm)].
b. Surface: [Smooth, flat] [Embossed] finish.
c. Exterior Finish: [Two-coat fluoropolymer].
d. Color: As selected by Architect from manufacturer's full range.
4. Clips: One-piece fixed to accommodate thermal movement.
5. Material:
a. 0.028-inch- (0.71-mm) nominal thickness, zinc-coated (galvanized) or aluminum-zinc alloy-coated steel sheet.
b. 0.025-inch- (0.64-mm-) thick, stainless-steel sheet.
6. Panel Coverage: 16 inches (406 mm).
7. Panel Height: 1.0 inch (25 mm).
2.3 UNDERLAYMENT MATERIALS
A. Self-Adhering, High-Temperature Underlayment: Provide self-adhering, cold-applied, sheet underlayment, a minimum of 30 mils (0.76 mm) thick, consisting of slip-resistant, polyethylene-film top surface laminated to a layer of butyl or SBS-modified asphalt adhesive, with release-paper backing. Provide primer when recommended by underlayment manufacturer.
1. Thermal Stability: Stable after testing at 240 deg F (116 deg C); ASTM D1970.
2. Low-Temperature Flexibility: Passes after testing at minus 20 deg F (29 deg C);
ASTM D1970.
B. Felt Underlayment: ASTM D226/D226M, Type II (No. 30), asphalt-saturated organic felts.
C. Slip Sheet: Manufacturer's recommended slip sheet, of type required for application.
2.4 MISCELLANEOUS MATERIALS
A. Miscellaneous Metal Subframing and Furring: ASTM C645; cold-formed, metallic-coated steel sheet, ASTM A653/A653M, G90 (Z275) hot-dip galvanized coating designation or ASTM A792/A792M, Class AZ50 (Class AZM150) coating designation unless otherwise indicated. Provide manufacturer's standard sections as required for support and alignment of metal panel system.
B. Panel Accessories: Provide components required for a complete, weathertight panel system including trim, copings, fasciae, mullions, sills, corner units, clips, flashings, sealants, gaskets, fillers, closure strips, and similar items. Match material and finish of metal panels unless otherwise indicated.
1. Closures: Provide closures at eaves and ridges, fabricated of same metal as metal panels.
2. Backing Plates: Provide metal backing plates at panel end splices, fabricated from material recommended by manufacturer.
3. Closure Strips: Closed-cell, expanded, cellular, rubber or crosslinked, polyolefin-foam or closed-cell laminated polyethylene; minimum 1-inch- (25-mm-) thick, flexible closure strips; cut or premolded to match metal panel profile. Provide closure strips where indicated or necessary to ensure weathertight construction.
C. Flashing and Trim: Provide flashing and trim formed from same material as metal panels as required to seal against weather and to provide finished appearance. Locations include, but are not limited to, eaves, rakes, corners, bases, framed openings, ridges, fasciae, and fillers. Finish flashing and trim with same finish system as adjacent metal panels.
D. Gutters and Downspouts: Formed from same material as roof panels according to SMACNA's "Architectural Sheet Metal Manual." Finish to match roof fascia and rake trim.
F. Panel Fasteners: Self-tapping screws designed to withstand design loads.
G. Panel Sealants: Provide sealant type recommended by manufacturer that are compatible with panel materials, are nonstaining, and do not damage panel finish.
1. Sealant Tape: Pressure-sensitive, 100 percent solids, gray polyisobutylene compound sealant tape with release-paper backing; 1/2 inch (13 mm) wide and 1/8 inch (3 mm) thick.
2. Joint Sealant: ASTM C920; as recommended in writing by metal panel manufacturer.
3. Butyl-Rubber-Based, Solvent-Release Sealant: ASTM C1311.
2.5 FABRICATION
A. Fabricate and finish metal panels and accessories at the factory, by manufacturer's standard procedures and processes, as necessary to fulfill indicated performance requirements demonstrated by laboratory testing. Comply with indicated profiles and with dimensional and structural requirements.
B. On-Site Fabrication: Subject to compliance with requirements of this Section, metal panels may be fabricated on-site using UL-certified, portable roll-forming equipment if panels are of same profile and warranted by manufacturer to be equal to factory-formed panels. Fabricate according to equipment manufacturer's written instructions and to comply with details shown.
C. Provide panel profile, including major ribs and intermediate stiffening ribs, if any, for full length of panel.
D. Fabricate metal panel joints with factory-installed captive gaskets or separator strips that provide a weathertight seal and prevent metal-to-metal contact, and that minimize noise from movements.
E. Sheet Metal Flashing and Trim: Fabricate flashing and trim to comply with manufacturer's recommendations and recommendations in SMACNA's "Architectural Sheet Metal Manual" that apply to design, dimensions, metal, and other characteristics of item indicated.
2.6 FINISHES
A. Panels and Accessories:
1. Two-Coat Fluoropolymer: AAMA 621 or AAMA 2605. Fluoropolymer finish containing not less than 70 percent polyvinylidene fluoride (PVDF) resin by weight in color coat.
2. Three-Coat Fluoropolymer: AAMA 621 or AAMA 2605. Fluoropolymer finish containing not less than 70 percent polyvinylidene fluoride (PVDF) resin by weight in both color coat and clear topcoat.
3. Siliconized Polyester: Epoxy primer and silicone-modified, polyester-enamel topcoat; with a dry film thickness of not less than 0.2 mil (0.005 mm) for primer and 0.8 mil (0.02 mm) for topcoat.
4. Concealed Finish: White or light-colored acrylic or polyester backer finish.
PART 3 - EXECUTION
3.1 PREPARATION
A. Miscellaneous Supports: Install subframing, furring, and other miscellaneous panel support members and anchorages according to ASTM C754 and metal panel manufacturer's written recommendations.
3.2 INSTALLATION OF UNDERLAYMENT
A. Self-Adhering Sheet Underlayment: Apply primer if required by manufacturer. Comply with temperature restrictions of underlayment manufacturer for installation. Apply at locations indicated on Drawings, wrinkle free, in shingle fashion to shed water, and with end laps of not less than 6 inches (152 mm) staggered 24 inches (610 mm) between courses. Overlap side edges not less than 3-1/2 inches (90 mm). Roll laps with roller. Cover underlayment within 14 days.
1. Apply over the entire roof surface.
D. Flashings: Install flashings to cover underlayment to comply with requirements specified in Section 076200 "Sheet Metal Flashing and Trim."
3.3 INSTALLATION OF STANDING-SEAM METAL ROOF PANELS
A. Standing-Seam Metal Roof Panel Installation: Fasten metal roof panels to supports with concealed clips at each standing-seam joint at location, spacing, and with fasteners recommended in writing by manufacturer.
1. Install clips to supports with self-tapping fasteners.
2. Install pressure plates at locations indicated in manufacturer's written installation instructions.
3. Snap Joint: Nest standing seams and fasten together by interlocking and completely engaging factory-applied sealant.
4. Seamed Joint: Crimp standing seams with manufacturer-approved, motorized seamer tool so clip, metal roof panel, and factory-applied sealant are completely engaged.
5. Watertight Installation:
a. Apply a continuous ribbon of sealant or tape to seal joints of metal panels, using sealant or tape as recommend in writing by manufacturer as needed to make panels watertight.
b. Provide sealant or tape between panels and protruding equipment, vents, and accessories.
c. At panel splices, nest panels with minimum 6-inch (152-mm) end lap, sealed with sealant and fastened together by interlocking clamping plates.
B. Accessory Installation: Install accessories with positive anchorage to building and weathertight mounting, and provide for thermal expansion. Coordinate installation with flashings and other components.
C. Flashing and Trim: Comply with performance requirements, manufacturer's written installation instructions, and SMACNA's "Architectural Sheet Metal Manual." Provide concealed fasteners where possible, and set units true to line and level as indicated. Install work with laps, joints, and seams that will be permanently watertight and weather resistant.
3.4 CLEANING AND PROTECTION
A. Remove temporary protective coverings and strippable films, if any, as metal panels are installed, unless otherwise indicated in manufacturer's written installation instructions. On completion of metal panel installation, clean finished surfaces as recommended by metal panel manufacturer.
Maintain in a clean condition during construction.
END OF SECTION 074113.1
SECTION 076200 - SHEET METAL FLASHING AND TRIM
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Manufactured reglets with counterflashing.
2. Formed roof-drainage sheet metal fabrications.
3. Formed low-slope roof sheet metal fabrications.
4. Formed steep-slope roof sheet metal fabrications.
5. Formed wall sheet metal fabrications.
1.7 WARRANTY
A. Special Warranty on Finishes: Manufacturer agrees to repair finish or replace sheet metal flashing and trim that shows evidence of deterioration of factory-applied finishes within specified warranty period.
1. Exposed Panel Finish: Deterioration includes, but is not limited to, the following:
a. Color fading more than 5 Delta E units when tested in accordance with
ASTM D2244.
b. Chalking in excess of a No. 8 rating when tested in accordance with ASTM D4214.
c. Cracking, checking, peeling, or failure of paint to adhere to bare metal.
2. Finish Warranty Period: 20 years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Sheet metal flashing and trim assemblies, including cleats, anchors, and fasteners, are to withstand wind loads, structural movement, thermally induced movement, and exposure to weather without failure due to defective manufacture, fabrication, installation, or other defects in construction.
Completed sheet metal flashing and trim are not to rattle, leak, or loosen, and are to remain watertight.
B. Sheet Metal Standard for Flashing and Trim: Comply with NRCA's "The NRCA Roofing Manual:
Architectural Metal Flashing, Condensation and Air Leakage Control, and Reroofing" and SMACNA's "Architectural Sheet Metal Manual" requirements for dimensions and profiles shown unless more stringent requirements are indicated.
C. Sheet Metal Standard for Copper: Comply with CDA's "Copper in Architecture Handbook."
Conform to dimensions and profiles shown unless more stringent requirements are…