Attachment 2 Drawings SXHT 16-1104.pdf

PDF 3 MB Posted

Attached to
Repair Backup Generator Building 423, Patrick Space Force Base, Fl Federal contract opportunity
Solicitation number
FA252122B0010
Issued by
Department of the Air Force Space Command

About this file

This solicitation is for a firm-fixed-price construction contract to provide labor, equipment and materials to remove and replace an existing generator and circuitry supplying power to a command post building at Patrick Space Force Base in Florida. The contractor must furnish a complete and usable facility in accordance with the project drawings and specifications. The requirement is a set-aside for women-owned small businesses between $250,000 and $500,000. Funds are presently unavailable and the government's obligation is contingent on appropriated funds availability, with no liability until notice of such availability is confirmed in writing.

View the file

Other files for this federal contract opportunity

Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATE R

O

AD

A1A

ACCESS ROAD

REDSTONE ROAD

RECREATION ROAD

U N

KN

O

W N

CONTROL ROAD

UNKNOWN

CONTROL ROAD

UNKNOWN

U N

KN

O

W N

ACCESS ROAD

ACCESS ROAD

PEQUOT TRAIL

ACCESS R

OAD

FO

RE

CA

ST

L

AN

E

ATLAS AVENUE

FA

LC

O N

AV

EN

UE

SOUTH TECH ROAD

COUGAR RUN

SANDOLLAR COVE

ENDEAVOR ROAD

ACCESS ROAD

TI

TA

N

RO

AD

PORPOISE COVE

TU

SK

EG

EE

A

IR

M

EN

D

RI

VE

UN

KN

O W

N

SP

AC

EL

IF

T

AV

EN

UE

O M

AL

LE

Y

DR

ACCESS ROAD

NORTH DRIVE

N C

O C

LU

B SO

U

TH

PAR

KIN

G

UTE TRAIL

SEQUOIA TRAIL

JAGUAR AVENUE

DUSKY RUN

PHARMACY DRIVE

ACCESS ROAD

PANTHER RUN

DE

LT

A

DR

IV

E

SHOSHONI TRAIL

C

AN

IN

E

D R

IV

E

JUPITER STREET

ACCESS ROAD THUNDER LANE

THOR STREET

EDWARD H. WHITE II

JUPITER STREET

CHALLENGER STREET

MATADOR STREET

BREAKERS LANE

PERSHING PLACE

RE

SC

UE

R

O

AD

RELAY STATION ROAD

MACE ROAD

SATURN ROAD

6TH HOLE SUNSET BLVD

GR

EE

NS

KE

EP

ER

L

AN

E

STATE ROAD 404

STATE ROAD 404 (ONRAMP)

AC

CE

SS

R

O

AD

AC

C

ESS R

O

AD

H

ABITAT R

U N

C O

N

TR

O L

R O

AD

RI

VE

RS

ID

E

TR

AI

L

R

IVER

SID

E TR

AIL

UNKNOWN

UN

KN

O W

N

SO

U

TH

P

AT

R

IC

K

D R

IV

E

ACCESS ROAD

ACCESS ROAD

SCHOOL AVENUE

SC

H

O O

L AVEN

U

E

C O

N

TR

O L

R O

AD

C

O N

TR

O

L R

O

AD

W

ES

T

TE

C H

R O

AD

JUPITER STREET

M

AINTENANCE ROAD

COYOTE RUN

COYOTE RUN

ACCESS ROAD

IROQUIS TRAIL

IROQUIS TRAIL

BEAR RUN

BEAR RUN

ALLIGATOR RUN

ALLIGATOR RUN

U N

KN

O

W N

MINUTEMAN STREET

RE

SC

UE

R

O

AD

R

ES

C U

E R

O

AD

R

EE

F C

O U

R T

UNKNOWN

CONTROL ROAD

CONTROL ROAD

SO

U

TH

P

AT

R

IC

K

D R

IV

E

SO

U

TH

PATR

IC

K D

R

IVE

ANVIL ROAD

ANVIL ROAD

ACCCESS ROAD

RESCUE ROAD

R

ES

C U

E R

O

AD

AC

C

ES

S

R O

AD

AC

C

ES

S

R O

AD

AC

CE

SS

R

O

AD

AC

C

ES

S

R O

AD

U N

KN

O

W N

EDWARD H. WHITE II

MINUTEMAN STREET

BASE OPERATIONS:

COMMUNICATIONS:

PROJECT MANAGER:

CHIEF, ENGINEERING FLIGHT:

USER:

SAFETY:

SECURITY FORCES:

ATO:

OTHER:

ENVIRONMENTAL:

FIRE:

A P P R O V E D

SXHT 16-1104

REPAIR/REPLACE COMMAND

POST GENERATOR, B423

PATRICK SPACE FORCE BASE (PSFB)

MELBOURNE, FLORIDA

A

B

2 3

C

D

1 2 3

4 5 6

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

R

EV

IE

W

ED

B

Y:

4 5

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

SHEET

IDENTIFICATION

C

D

A

B

U

SS

F

TH

C

IV

IL

E N

G

IN

EE

R

S Q

U

AD

R O

N , P

SF

B, F L

C O

N

TR

AC

T

N O

FA

-1 8-

D -0

TR

AC

ES

TE

C H

N

IC

AL

R

AN

G

E

AR

C H

IT

EC

T

EN

G

IN

EE

R

IN

G

SE

R

VI

C

ES

N el so nE ng in ee ri ng C o.

rh od es b rit o

A

R

C

H

I T

E

S

AA

D

AT

E:

AS

B

U

IL

T D

AT

E:

D

EL

IV

ER

Y N

O

PR

O

JE

C

T N

U M

BE

R

N

EL

SO

N

EN

G

IN

EE

R

IN

G

/2

1/

C . J

O D

H

AN

R . S

AN

TO

S

B.

K

O

LA

K P.

E.

SX

H

T

-1

SX

H

T

-1

R

EP

AI

R

/R

EP

LA

C

E C

O M

M

AN

D P

O

ST

G

EN

ER

AT

O R

, B

S.R. A1A

PINEDA CAUSWAY

SOUTH GATE (PERSONNEL ONLY)

TRUCK DELIVERY ONLY

EAST GATE (PERSONNEL ONLY)

BUILDING 535-45TH CES

BUILDING 423-CONTRACTING OFFICER

TALLAHASSEE

JACKSONVILLE

ORLANDO

TAMPA PATRICK SPACE FORCE BASE

MIAMI

ATLANTIC OCEAN

GOLF COURSE

BANANA RIVER

STATE OF FLORIDA

SCALE: N.T.S.

EDWARD H. WHITE ST

MINUTEMAN ST

FA

LC

O N

AV

E.

PROJECT LOCATION

PERMIT(S)/ENVIRONMENTAL AND SLD 45 ACTIONS

REQUIRED PRIOR TO CONSTRUCTION

ERP/STORMWATER

ERP/WETLANDS/DREDGE & FILL

FDEP/DRINKING WATER

FDEP/DOM. WASTE WATER ARCHEO./HISTORICAL

SURVEY/WILDLIFE

SLD 45 RISK ASSESSMENT

NONE

FDEP/IND. WASTE WATER

IRP

FDEP/FUEL TANK

NOI/SWPPP

ASBESTOS

HEAVY METALS

YES NO

LEAD

PCB

NOT

VERIFIEDHAZARDOUS MATERIALS

NOTE: IF IT IS SUSPECTED THAT ANY HAZARDOUS MATERIAL NOT

IDENTIFIED ON THESE DRAWINGS IS REQUIRED TO BE DISTURBED IN

ORDER TO PERFORM THE CONTRACT WORK, LEAVE MATERIAL

UNDISTURBED AND IMMEDIATELY INFORM THE CONTRACTING OFFICER.

G-001

C O

VE

R

S H

EE

T

DRAWING INDEX

DRAWING NO. SHEET TITLE

G-001 COVER SHEET

G-101 FIRST FLOOR COMPOSITE PLAN

G-102 THIRD FLOOR COMPOSITE PLAN

E-001 ELECTRICAL GENERAL NOTES

E-101 FIRST FLOOR GENERATOR ROOM - ENLARGED POWER PLANS

E-102 THIRD FLOOR ROOM C310 - ENLARGED POWER PLANS

E-501 ELECTRICAL DETAILS

E-601 PARTIAL SINGLE-LINE DIAGRAM AND PANEL SCHEDULES

1 3 4 5 6 7 8 9 10 21 22

W

V

U

T

S

R

Q

P

M

L

K

J

H

G

F

E

D

C

B

A

2 11 12 13 14 15 16 17 19 2018 A

B

2 3

C

D

1 2 3

4 5 6

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

R

EV

IE

W

ED

B

Y:

4 5

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

SHEET

IDENTIFICATION

C

D

A

B

U

SS

F

TH

C

IV

IL

E N

G

IN

EE

R

S Q

U

AD

R O

N , P

SF

B, F L

C O

N

TR

AC

T

N O

FA

-1 8-

D -0

TR

AC

ES

TE

C H

N

IC

AL

R

AN

G

E

AR

C H

IT

EC

T

EN

G

IN

EE

R

IN

G

SE

R

VI

C

ES

N el so nE ng in ee ri ng C o.

rh od es b rit

D

AT

E:

AS

B

U

IL

T D

AT

E:

D

EL

IV

ER

Y N

O

PR

O

JE

C

T N

U M

BE

R

N

EL

SO

N

EN

G

IN

EE

R

IN

G

/2

1/

C . J

O D

H

AN

R . S

AN

TO

S

B.

K

O

LA

K P.

E.

SX

H

T

-1

SX

H

T

-1

R

EP

AI

R

/R

EP

LA

C

E C

O M

M

AN

D P

O

ST

G

EN

ER

AT

O R

, B

SCALE IN FEET

GRAPHIC SCALE

0 4 8 16

3/32"=1'-0"

SCALE:

FIRST FLOOR COMPOSITE PLAN

3/32" = 1'-0"

E-101 A

FI

R

ST

F

LO

O

R C

O M

PO

SI

TE

P

LA

N

G-101

E-101 B

N

1 3 4 5 6 7 8 9 10 21 22

W

V

U

T

S

R

Q

P

M

L

K

J

H

G

F

E

D

C

B

A

11 12 13 14 15 16 17 19 2018

A

B

2 3

C

D

1 2 3

4 5 6

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

R

EV

IE

W

ED

B

Y:

4 5

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

SHEET

IDENTIFICATION

C

D

A

B

U

SS

F

TH

C

IV

IL

E N

G

IN

EE

R

S Q

U

AD

R O

N , P

SF

B, F L

C O

N

TR

AC

T

N O

FA

-1 8-

D -0

TR

AC

ES

TE

C H

N

IC

AL

R

AN

G

E

AR

C H

IT

EC

T

EN

G

IN

EE

R

IN

G

SE

R

VI

C

ES

N el so nE ng in ee ri ng C o.

rh od es b rit

D

AT

E:

AS

B

U

IL

T D

AT

E:

D

EL

IV

ER

Y N

O

PR

O

JE

C

T N

U M

BE

R

N

EL

SO

N

EN

G

IN

EE

R

IN

G

/2

1/

C . J

O D

H

AN

R . S

AN

TO

S

B.

K

O

LA

K P.

E.

SX

H

T

-1

SX

H

T

-1

R

EP

AI

R

/R

EP

LA

C

E C

O M

M

AN

D P

O

ST

G

EN

ER

AT

O R

, B

SCALE IN FEET

GRAPHIC SCALE

0 4 8 16

3/32"=1'-0"

SCALE:

THIRD FLOOR COMPOSITE PLAN

3/32" = 1'-0"

E-102 C

TH

IR

D F

LO

O

R C

O M

PO

SI

TE

P

LA

N

G-102

E-102 D

N

ELECTRICAL SYMBOL LEGEND:

INDICATES HOME RUN CIRCUIT. TEXT BEFORE "/" INDICATES SOURCE DESIGNATION. TEXT

AFTER "/" INDICATES CIRCUIT NUMBER

DISCONNECT SWITCH, NON-FUSED NUMBER INDICATES SWITCH SIZE.

ELECTRICAL PANEL

ENCLOSED CIRCUIT BREAKER

120V, 20A, NEMA 5-20R RECEPTACLE

TRANSFORMER (ONE-LINE DIAGRAM)

CIRCUIT BREAKER (ONE-LINE DIAGRAM)

DEMOLITION

CONDUCTOR

JUNCTION BOX/SPLICE BOX

DOUBLE THROW SWITCH

AUTOMATIC TRANSFER SWITCH

FIRE ALARM TERMINAL CABINET

APPLIES TO ALL ELECTRICAL SHEETS

(XX)-(XXX)

ELECTRICAL GENERAL NOTES:

A

B

2 3

C

D

1 2 3

4 5 6

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

R

EV

IE

W

ED

B

Y:

4 5

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

SHEET

IDENTIFICATION

C

D

A

B

U

SS

F

TH

C

IV

IL

E N

G

IN

EE

R

S Q

U

AD

R O

N , P

SF

B, F L

C O

N

TR

AC

T

N O

FA

-1 8-

D -0

TR

AC

ES

TE

C H

N

IC

AL

R

AN

G

E

AR

C H

IT

EC

T

EN

G

IN

EE

R

IN

G

SE

R

VI

C

ES

N el so nE ng in ee ri ng C o.

rh od es b rit

D

AT

E:

AS

B

U

IL

T D

AT

E:

D

EL

IV

ER

Y N

O

PR

O

JE

C

T N

U M

BE

R

N

EL

SO

N

EN

G

IN

EE

R

IN

G

/2

1/

C . J

O D

H

AN

R . S

AN

TO

S

B.

K

O

LA

K P.

E.

SX

H

T

-1

SX

H

T

-1

R

EP

AI

R

/R

EP

LA

C

E C

O M

M

AN

D P

O

ST

G

EN

ER

AT

O R

, B

EL

EC

TR

IC

AL

G

EN

ER

AL

N

O

TE

S

E-001

CODE COMPLIANCE CRITERIA:

29 CFR 1926 OSHA STANDARDS FOR CONSTRUCTION

NFPA 70 NATIONAL ELECTRICAL CODE

IEE C.2 NATIONAL ELECTRICAL SAFETY CODE

NFPA 70E STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE

UFC 3-501-01 UNIFIED FACILITIES CRITERIA, ELECTRICAL ENGINEERING

AFI 32-1062 AIR FORCE INSTRUCTION, ELECTRICAL SYSTEMS, POWER PLANTS AND GENERATORS

UFC 3-460-01 DESIGN: PETROLEUM FUEL FACILITIES

1. ALL CONSTRUCTION WILL BE GOVERNED BY THE PLANS, SPECIFICATIONS, AND

ALL APPLICABLE BUILDING AND SAFETY CODES, LAWS, AND ORDINANCES.

2. ALL ELECTRICAL CONSTRUCTION/INSTALLATION WILL BE IN ACCORDANCE

WITH THE LATEST REVISION NFPA 70, NFPA 780, 70E, AND UFC 3-501-01.

3. DE-ENERGIZE ALL ITEMS TO BE DEMOLISHED OR REMOVED. PERFORM

LOCKOUT/TAGOUT IN ACCORDANCE WITH OSHA 29 CFR 1910.147, THE LATEST

REVISION OF NFPA 70E, AND PSFB REQUIREMENTS.

4. LOCATIONS OF ALL ELECTRICAL EQUIPMENT ARE APPROXIMATE AND MAY BE

RELOCATED TO AN APPROVED LOCATION. FIELD VERIFY ALL LOCATIONS AND

SPACING. CONTACT CONTRACTING OFFICER PRIOR TO ANY FIELD CHANGES.

5. INSTALL FURNISH, AND PROVIDE ARE ALL DEFINED TO INCLUDE ALL

NECESSARY MATERIALS AND INSTALLATION BY THE CONTRACTOR. ALL

INSTALLATION, SERVICES, AND MATERIALS ARE TO BE PROVIDED BY THE

CONTRACTOR UNLESS SPECIFICALLY INDICATED OTHERWISE IN THE

CONTRACT AND CONSTRUCTION DOCUMENTS.

6. CONTRACTOR MUST BE FAMILIAR WITH THE SITE, THE WORK REQUIRED, THE

CUSTOMER'S WORK PROCEDURES, AND ALL OTHER CONDITIONS THAT MAY

AFFECT THE SUCCESSFUL COMPLETION OF THE JOB PRIOR TO

COMMENCEMENT OF WORK.

7. CONTRACTOR MUST TAKE NECESSARY PRECAUTIONS AND PROVIDE

PROTECTION AS REQUIRED TO PRESERVE THE CONDITION OF EXISTING

UTILITIES, EQUIPMENT, FURNISHING, AND SURFACES NOT INDICATED FOR

REMOVAL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO WORK AROUND THE

EXISTING CONDITIONS TO ACCOMPLISH THE WORK.

8. ALL SPECIFIC MATERIALS AND PRODUCTS IDENTIFIED IN THE PLANS ARE

INCLUDED AS THE BASIS OF DESIGN. CONTRACTOR MAY SUBMIT EQUIVALENT

PRODUCTS IN COMPLIANCE WITH THE PROJECT SPECIFICATIONS FOR

APPROVAL INSTEAD OF THOSE IDENTIFIED.

9. SEAL ALL WALL PENETRATIONS RESULTING FROM THE WORK WITH UL RATED

AND APPROVED SEALANT TO MATCH EXISTING WALL ASSEMBLY FIRE RATING.

10. ALL NEW EXTERIOR CONDUITS, INCLUDING CONDUIT THROUGH WALL

PENETRATIONS, ARE TO BE RGS. FINAL CONNECTIONS TO EXTERIOR

EQUIPMENT MAY BE MADE WITH LIQUID-TIGHT FLEXIBLE METAL CONDUIT.

11. ALL NEW INTERIOR CONDUIT MAY BE EMT, BUT EMT MAY NOT PENETRATE

WALLS.

12. ALL NEW CONDUIT MUST BE MINIMUM 3/4 INCH.

13. ALL NEW LOW VOLTAGE POWER CONDUCTORS MUST BE COPPER WITH

INSULATION TYPE TYPE THHN-THWN2 UNLESS SPECIFIED OTHERWISE.

14. REPAIR INTERIOR AND EXTERIOR FINISHES THAT ARE DIRECTLY IMPACTED BY

WORK, TO MATCH EXISTING TO THE GREATEST EXTENT POSSIBLE.

15. ENSURE ALL MODIFIED AND NEW PANELBOARDS RECEIVE NEW, TYPED PANEL

SCHEDULES REFLECTING AS-BUILD CONDITIONS. INSTALL PANEL SCHEDULES

ON THE INSIDE OF THE PANEL DOOR OR IN A SIMILAR CONSPICUOUS

LOCATION.

16. REFER TO PANEL SCHEDULES SINGLE LINE DIAGRAM ON SHEET E-601 FOR

BRANCH CIRCUIT AND FEEDER CONDUIT AND CONDUCTOR INFORMATION.

17. CONTRACTOR MUST TRANSPORT, DELIVER, PROCESS, AND TURN-IN

GENERATOR TO JACKSONVILLE FL DLA/DRMO.

18. CONTRACTOR MUST PROVIDE THEIR OWN RAISED FLOOR TILE PULLER(S) AND

PROVIDE THE GOVERNMENT WITH A NEW RAISED TILE PULLER UPON

COMPLETION OF THE PROJECT.

ABBREVIATIONS:

A AMPERES

AWG AMERICAN WIRE GAUGE

BICSI BUILDING INDUSTRY CONSULTING SERVICE INTERNATIONAL

CAT CATEGORY

CB CIRCUIT BREAKER

CCSFS CAPE CANAVERAL SPACE FORCE STATION

CKT CIRCUIT

DS DISCONNECT SWITCH

ECB ENCLOSED CIRCUIT BREAKER

EMT ELECTRICAL METALLIC TUBING

FACP FIRE ALARM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

GND GROUND

KAIC THOUSAND AMPERES INTERRUPTING CAPACITY

KCMIL THOUSAND CIRCULAR MILS

KV KILOVOLT

KVA KILOVOLT-AMPERE

MCA MAXIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

PH PHASE

RGS RIGID GALVANIZED STEEL

SCH SCHEDULE

SWGR SWITCHGEAR

THHN THERMOPLASTIC HIGH HEAT-RESISTANT NYLON-COATED

THWN THERMOPLASTIC HIGH WATER-RESISTANT NYLON-COATED

U UNIT

UFC UNIFIED FACILITIES CRITERIA

UTL UTILITY

VAC VOLTS ALTERNATING CURRENT

W WATT

XFMR TRANSFORMER

PANEL COMP RM-208V-120V

FED FROM

PANEL HH-3

1. SUPPLY AND INSTALL MELAMINE PLASTIC/ PHELONIC NAMEPLATES LABELS SHOWN BELOW

2. LABELS SHALL BE PROVIDED WITH A BLACK BACKGROUND AND WHITE LETTERS.

3. LABELS SHALL BE AFFIXED TO EQUIPMENT VIA SCREWS/ ADHESIVE (ADEQUATE FOR OUTDOOR INSTALLATIONS).

4. LABEL EXAMPLES BY EQUIPMENT TYPE SHOWN BELOW.

EQUIPMENT LABELING:

ECB

J

FATC

DTS

ATS

8 9 10

F

E

D

C

J ATS

T

8 9 10

F

E

D

C

J

T

ATS

D

/S

FA

TC

D /S

J

A

B

2 3

C

D

1 2 3

4 5 6

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

R

EV

IE

W

ED

B

Y:

4 5

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

SHEET

IDENTIFICATION

C

D

A

B

U

SS

F

TH

C

IV

IL

E N

G

IN

EE

R

S Q

U

AD

R O

N , P

SF

B, F L

C O

N

TR

AC

T

N O

FA

-1 8-

D -0

TR

AC

ES

TE

C H

N

IC

AL

R

AN

G

E

AR

C H

IT

EC

T

EN

G

IN

EE

R

IN

G

SE

R

VI

C

ES

N el so nE ng in ee ri ng C o.

rh od es b rit

D

AT

E:

AS

B

U

IL

T D

AT

E:

D

EL

IV

ER

Y N

O

PR

O

JE

C

T N

U M

BE

R

N

EL

SO

N

EN

G

IN

EE

R

IN

G

/2

1/

C . J

O D

H

AN

R . S

AN

TO

S

B.

K

O

LA

K P.

E.

SX

H

T

-1

SX

H

T

-1

R

EP

AI

R

/R

EP

LA

C

E C

O M

M

AN

D P

O

ST

G

EN

ER

AT

O R

, B

SCALE IN FEET

GRAPHIC SCALE

0 1 2 4

3/8"=1'-0"

E

SCALE:

FIRST FLOOR GENERATOR ROOM - ENLARGED POWER DEMOLITION PLAN

3/8" = 1'-0" A

G-101

FI

R

ST

F

LO

O

R G

EN

ER

AT

O

R R

O O

M

EN

LA

R G

ED

P

O W

ER

P

LA

N

S

E-101

GENERATOR

ROOM

EXISTING DISCONNECT

SWITCHES

EXISTING JUNCTION BOX "JB-1"

EXISTING ATS

EXISTING

GENERATOR

EXISTING FUEL TANK

EXISTING AIR INTAKE LOUVER

SCALE:

FIRST FLOOR GENERATOR ROOM - ENLARGED POWER PLAN

3/8" = 1'-0" B

G-101

GENERATOR

ROOM

EXISTING FUEL TANK

EXISTING AIR INTAKE LOUVER

N

N

1. REFER TO GENERAL NOTES, ABBREVIATIONS, AND LEGEND ON SHEET E-001.

2. REFER TO SINGLE LINE DIAGRAM AND PANEL SCHEDULE ON SHEET E-601 FOR SYSTEM

CONFIGURATION AND CABLE AND CONDUIT INFORMATION.

3. SURFACE MOUNT ALL NEW CONDUIT. EXISTING CONDUIT MAY BE REUSED PROVIDED IT MEETS

TECHNICAL REQUIREMENTS OF THIS DESIGN.

1. DEMOLISH EXISTING GENERATOR INCLUDING EXHAUST SYSTEM, AND FUEL LINES TO EXTENT

REQUIRED FOR NEW INSTALLATION. RETAIN EXISTING POWER AND CONTROL CONDUIT AND

WIRING FROM EXISTING JUNCTION BOX "JB-1" BACK TO COMMAND POST ATS. RETAIN ALL

EXISTING EARTH GROUNDING CONDUCTORS FOR REUSE.

2. DEMOLISH EXISTING WEATHER STATION/COMPUTER ROOM ATS AND THREE EXISTING

SWITCHES CONFIGURED FOR BYPASS OPERATION. DEMOLISH CONDUITS AND CONDUCTORS

BACK TO GENERATOR AND TRANSFORMER SECONDARY SWITCH.

3. DEMOLISH EXISTING CONDUIT TO WALL PENETRATION. REMOVE CONDUCTOR AND PRESERVE

EXISTING 2-1/2 INCH RGS RUN FROM WALL PENETRATION TO MECHANICAL ROOM 3MECH1 FOR

REUSE.

4. DEMOLISH EXISTING 60A FUSED DISCONNECT SWITCH, METER, AND 25KVA TRANSFORMER.

DEMOLISH EXISTING SERVICE FEEDERS AND CONDUIT BACK TO UNIT SUBSTATION SECONDARY

BUS ENCLOSURE.

5. DEMOLISH EXISTING DISCONNECT SWITCH AND CONDUIT TO WALL PENETRATION. REMOVE

CONDUCTOR AND PRESERVE EXISTING 2-1/2 INCH RGS RUN FROM WALL PENETRATION TO

MECHANICAL ROOM 3MECH1.

6. INSTALL A NEW, MINIMUM 150KW, 480VAC, STANDBY DIESEL GENERATOR. COORDINATE

LOCATION WITH EXISTING CHILLED WATER LINES, AIR INTAKE LOUVER AND CONTAINMENT CURB

STRUCTURE. EXTEND EXISTING FUEL LINES AS REQUIRED TO SUPPLY NEW GENERATOR.

7. INSTALL NEW 45KVA, 480-208/120VAC, DRY-TYPE TRANSFORMER TO FEED EXISTING COMMAND

POST. INSTALL NEW CONDUIT AND CONDUCTOR FROM NEW GENERATOR OUTPUT BREAKER TO

FEED NEW TRANSFORMER. RECONFIGURE EXISTING COMMAND POST ATS FEEDER

CONDUCTORS AND CONDUIT TO NEW TRANSFORMER SECONDARY TO REFEED COMMAND POST

ATS ALTERNATE SOURCE. INSTALL #6 AWG GROUND FROM TRANSFORMER "COMMAND POST"

X0 CONNECTION TO FACILITY STRUCTURAL STEEL.

8. INSTALL NEW 150A, 3P, 208/120VAC, 18KAIC ENCLOSED CIRCUIT BREAKER "COMMAND POST ECB"

IN NEMA 1 ENCLOSURE TO PROVIDE SECONDARY PROTECTION FOR "COMMAND POST" XFMR.

9. INSTALL NEW 175A, 3P, 30KAIC CIRCUIT BREAKER IN EXISTING SQUARE D SWITCHBOARD TO

FEED NORMAL SOURCE OF NEW COMPUTER ROOM ATS.

10. INSTALL QTY 2 NEW 200A, 600VAC, 3P, HEAVY DUTY DISCONNECT SWITCHES IN NEMA 1

ENCLOSURE. FUSE AS IDENTIFIED ON SHEET E-601. FEED BOTH NEW DISCONNECT SWITCHES

FROM GENERATOR OUTPUT BREAKER. ONE DISCONNECT SWITCH WILL FEED NEW COMPUTER

ROOM ATS AND THE OTHER WILL PROVIDE LOAD BANK CONNECTION POINT FOR GENERATOR

TESTING.

11. INSTALL NEW 225A, 480VAC, 4P "COMP ROOM" ATS. FEED NORMAL SOURCE FROM NEW

BREAKER IN EXISTING MAIN SWITCHBOARD AND ALTERNATE SOURCE FROM NEW DOUBLE

THROW SWITCH LOAD 1.

12. INSTALL ALL NEW ELECTRICAL EQUIPMENT ON NEW FIELD FABRICATED STRUT FRAME. REFER

TO DETAIL ON SHEET E-501 FOR ADDITIONAL FRAME CONSTRUCTION INFORMATION.

13. INSTALL NEW 208/120VAC, 100A BUS, 60A MCB, 10KAIC, 3PH, 4W, SERVICE RATED, SURFACE

MOUNTED PANELBOARD "GEN PNL". CONNECT BATTERY CHARGER, CONTROL PANEL HEATER,

JACKET HEATER, AND ALTERNATOR HEATER TO NEW PANEL. SIZE GENERATOR CIRCUITS IN

ACCORDANCE WITH GENERATOR MANUFACTURER INSTRUCTIONS.

14. REUSE 2-1/2 INCH RGS RUN FROM WALL PENETRATION TO MECHANICAL ROOM 3MECH1 TO

REFEED ECB HH-3. REFER TO SHEET E-102 FOR CONNECTION TO ECB HH-3.

15. INSTALL 1 INCH CONDUIT FROM GENERATOR CONTROL PANEL TO EXISTING FATC FOR FUTURE

CONNECTION TO FACP. CONNECTION TO FACP TO BE PERFORMED BY OTHERS.

16. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL FUEL SYSTEM VALVES, FITTINGS, AND

SAFETIES AS REQUIRED BY THE GENERATOR MANUFACTURER, UFC 3-460-01, AND

SPECIFICATION 33 57 55.

17. INSTALL NEW 12 X 12 X 6 INCH NEMA 1 JUNCTION BOX AND TAP GENERATOR FEEDER TO FEED

NEW DISCONNECT SWITCHES IN ACCORDANCE WITH NEC 240.21 USING INSULATED

MECHANICAL LUGS.

FLAG NOTES:

SPECIFIC NOTES:

EXISTING MAIN

SWITCHBOARD

EXISTING 60A

DISCONNECT SWITCH

EXISTING 25

KVA XFMR

EXISTING MAIN

SWITCHBOARD

SCALE:

GENERATOR ROOM SOUTH WALL

NTS

E

EXISTING JUNCTION BOX

EXISTING DISCONNECT SWITCHES

EXISTING OVERHEAD

JUNCTION BOX

EXISTING UNIT SUBSTATION

SECONDARY BUS TAP

ENCLOSURE

EXISTING UNIT SUBSTATION

TRANSFORMER AND

PRIMARY SWITCH

TO DISCONNECT SWITCH IN

THIRD FLOOR MECHANICAL

ROOM 3MECH1 SHEET E-102

TO DISCONNECT SWITCH IN

THIRD FLOOR MECHANICAL

ROOM 3MECH1 SHEET E-102

EXISTING UNIT SUBSTATION

SECONDARY BUS TAP

ENCLOSURE

EXISTING UNIT SUBSTATION

TRANSFORMER AND

PRIMARY SWITCH

TO ECB IN THIRD FLOOR

MECHANICAL ROOM

3MECH1 SHEET E-102

TO COMMAND POST

FUTURE LOAD BANK CONNECTION

TO COMMAND POST

E-501

EXISTING 100A

DISCONNECT SWITCH

EXISTING JUNCTION

BOX "JB-1"

WEATHER

STATION/COMPUTER

ROOM ATS

G

F

E D

3 4

E

J

ECB

ECB

T

T

G

F

E D

3 4

E

J

T

ECB

T

T

A

B

2 3

C

D

1 2 3

4 5 6

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

R

EV

IE

W

ED

B

Y:

4 5

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

SHEET

IDENTIFICATION

C

D

A

B

U

SS

F

TH

C

IV

IL

E N

G

IN

EE

R

S Q

U

AD

R O

N , P

SF

B, F L

C O

N

TR

AC

T

N O

FA

-1 8-

D -0

TR

AC

ES

TE

C H

N

IC

AL

R

AN

G

E

AR

C H

IT

EC

T

EN

G

IN

EE

R

IN

G

SE

R

VI

C

ES

N el so nE ng in ee ri ng C o.

rh od es b rit

D

AT

E:

AS

B

U

IL

T D

AT

E:

D

EL

IV

ER

Y N

O

PR

O

JE

C

T N

U M

BE

R

N

EL

SO

N

EN

G

IN

EE

R

IN

G

/2

1/

C . J

O D

H

AN

R . S

AN

TO

S

B.

K

O

LA

K P.

E.

SX

H

T

-1

SX

H

T

-1

R

EP

AI

R

/R

EP

LA

C

E C

O M

M

AN

D P

O

ST

G

EN

ER

AT

O R

, B

SCALE IN FEET

GRAPHIC SCALE

0 1 2 4

3/8"=1'-0"

F

N

SCALE:

THIRD FLOOR ROOM C310 - ENLARGED POWER DEMOLITION PLAN

3/8" = 1'-0" C

G-102

TH

IR

D F

LO

O

R R

O O

M C

- E N

LA

R

G

ED

P O

W

ER

P

LA

N S

E-102

SERVER ROOM

C310D

MECHANICAL ROOM

3MECH1

EXISTING

RACK

EXISTING

RACK

EXISTING

RACK

EXISTING

RACK

EXISTING

VAULT ON

PALLET

EXISTIN

G

U

PS

EXISTING JUNCTION BOX

EXISTING DISCONNECT

SWITCH

45KVA PANEL H1

TRANSFORMER

EXISTING

PANEL H1

EXISTING

PANEL H2

EXISTING

PP-1

PANEL CR #2

PANEL CR #1

SCALE:

THIRD FLOOR ROOM C310 - ENLARGED POWER INSTALLATION PLAN

3/8" = 1'-0" D

G-102

SERVER ROOM

C310D

MECHANICAL ROOM

3MECH1

EXISTIN

G

U

PS

EXISTING JUNCTION BOX

EXISTING

PANEL H1

EXISTING

PANEL H2

EXISTING

PP-1

PANEL CR #2

N

EXISTIN

G

D

ATA

AIR

E D

AP4 C

R

AC

D

X U N

IT

(C

R

AC

-2)

EXISTIN

G

C R

AC

/C

R

AH

U N

IT

(C

R

AC

-1)

PANEL HH-3

EXISTIN

G

D

ATA

AIR

E D

AP4 C

R

AC

D

X U N

IT

(C

R

AC

-2)

EXISTIN

G

C R

AC

/C

R

AH

U N

IT

(C

R

AC

-1)

PANEL

HH-3

XFMR COMP RM

PANEL COMP RM

SCALE:

MECHANICAL ROOM 3MECH1 WEST WALL

NTS

F

1. REFER TO GENERAL NOTES, ABBREVIATIONS, AND LEGEND ON SHEET E-001.

2. REFER TO SINGLE LINE DIAGRAM AND PANEL SCHEDULE ON SHEET E-601 FOR SYSTEM

CONFIGURATION AND CABLE AND CONDUIT INFORMATION.

3. SURFACE MOUNT ALL NEW CONDUIT. EXISTING CONDUIT MAY BE REUSED PROVIDED IT

MEETS TECHNICAL REQUIREMENTS OF THIS DESIGN.

4. RECEPTACLE COUNT IS IS BASED ON USER PROVIDED INFORMATION. SPECIFIC

LOCATIONS TO BE COORDINATED WITH USER.

1. DEMOLISH ECB INCLUDING CONDUIT TO WALL PENETRATION. REMOVE CONDUCTOR AND

PRESERVE EXISTING 2-1/2 INCH RGS RUN FROM WALL PENETRATION TO SWITCHBOARD

ROOM ON FIRST FLOOR.

2. DEMOLISH DISCONNECT SWITCH INCLUDING CONDUIT AND CONDUCTOR FEEDING

EXISTING 75KVA TRANSFORMER. REMOVE CONDUCTOR AND PRESERVE EXISTING 2-1/2

INCH RGS RUN FROM WALL PENETRATION TO SWITCHBOARD ROOM ON FIRST FLOOR

FOR REUSE.

3. DEMOLISH CONDUIT AND CONDUCTORS FEEDING ECB HH-3 BACK TO PANEL PP-1.

4. DISCONNECT ALL EXISTING CIRCUITS AND DEMOLISH EXISTING PANEL CR#1. RELOCATE

CIRCUITS FEEDING UNDERFLOOR CLUSTER RECEPTACLES TO NEW PANEL "COMP ROOM"

AND REMAINING FACILITY CIRCUITS TO EXISTING PANEL CR#2.

5. PROVIDE 175A, 3P, 18KAIC CIRCUIT BREAKER IN PANEL "HH-3" TO SUPPLY NEW "COMP RM

XFMR".

6. INSTALL NEW 112.5 KVA 480VAC TO 208/120 DRY TYPE TRANSFORMER "COMP RM".

INSTALL #1/0 AWG GROUND FROM TRANSFORMER "COMP RM" X0 CONNECTION TO

FACILITY STRUCTURAL STEEL.

7. INSTALL NEW, SURFACE MOUNTED, BOTTOM FED, 208V/120VAC, 400A, 3PH, 4W, 10KAIC,

PANELBOARD "COMP RM" IN NEMA 1 ENCLOSURE IN ROOM C-310. FEED NEW PANEL

FROM XFMR "COMP RM". FIELD LOCATE PANEL TO ENSURE MINIMUM 36 INCHES OF

CLEAR SPACE IS MAINTAINED IN FRONT.

8. RELOCATE AND REFEED APPROXIMATELY QTY 20 EXISTING UNDERFLOOR CLUSTER

RECEPTACLE CIRCUITS FROM PANELS CR#1 AND CR#2 FROM NEW PANEL COMP RM.

CONTRACTOR TO FIELD VERIFY EXACT QUANTITY OF CIRCUITS.

9. RELOCATE AND REFEED ALL OTHER CIRCUITS THAT ARE NOT UNDERFLOOR CLUSTER

RECEPTACLE CIRCUITS IN PANEL CR#1 FROM PANEL CR#2.

10. REFEED PANEL CR#2 FROM EXISTING 150A, 3P BREAKER IN PANEL CR-DP THAT

PREVIOUSLY FED PANEL CR#1.

11. A TOTAL OF 32 NEMA L5-20R RECEPTACLES ARE REQUIRED TO SUPPORT USER SUPPLIED

CLUSTER EQUIPMENT. INSTALL 12 NEW RECEPTACLES UNDER EXISTING RAISED FLOOR

SYSTEM AND RECIRCUIT 20 EXISTING RECEPTACLES FROM EXISTING PANEL CR2 IN

ROOM 3MECH1 AND EXISTING PANEL CR#1 TO NEW PANEL COMP ROOM. DESIGNATED

RECEPTACLES ARE REQUIRED TO BE LOCATED JUST UNDERNEATH THE INTENDED

EQUIPMENT. CONTRACTOR MUST COORDINATE FINAL LOCATION OF RECEPTACLES WITH

END-USER.

12. PROVIDE 125A, 3P, 18 KAIC CIRCUIT BREAKER IN PNL PP1 TO REFEED EXISTING 75KVA

COMPUTER ROOM TRANSFORMER.

13. RE-USE 2-1/2 INCH RGS RUN FROM FIRST FLOOR SWITCHBOARD ROOM TO FEED ECB

HH-3 FROM NEW "COMP ROOM" ATS.

FLAG NOTES:

SPECIFIC NOTES:

EXISTING ENCLOSED

CIRCUIT BREAKER

45KVA PANEL H1

TRANSFORMER

(COMP RM)-(5)

(COMP RM)-(3)

(COMP RM)-(1)

(COMP RM)-(9)

(COMP RM)-(19)

(COMP RM)-(7)

(COMP RM)-(11)

(COMP RM)-(15)

(COMP RM)-(17)

(COMP RM)-(21)

(COMP RM)-(2)

(COMP RM)-(6)

(COMP RM)-(10)

(COMP RM)-(14)

(COMP RM)-(18)

(COMP RM)-(22)

(COMP RM)-(26)

(COMP RM)-(27)

(COMP RM)-(30)

(COMP RM)-(25)

(COMP RM)-(23)

(COMP RM)-(4)

(COMP RM)-(8)

(COMP RM)-(12)

(COMP RM)-(16)

(COMP RM)-(20)

(COMP RM)-(24)

(COMP RM)-(28)

(COMP RM)-(29)

(COMP RM)-(13)

DISCONNECT SWITCH

DISCONNECT SWITCH

ECB HH-3ECB HH-3

EXISTING PANEL

CR-DP

EXISTING PANEL

CR-DP

EXISTING NW RISER TAP BOX EXISTING NW RISER TAP BOX

EXISTING 75KVA

COMPUTER ROOM

TRANSFORMER

EXISTING 75KVA

COMPUTER ROOM

TRANSFORMER

FROM FIRST FLOOR

SWITCHBOARD ROOM

SHEET E-101

(COMP RM)-(32)

(COMP RM)-(31)

FROM 100A DISCONNECT

SWITCH IN FIRST FLOOR

SWITCHBOARD ROOM

SHEET E-101

FROM 60A DISCONNECT

SWITCH IN FIRST FLOOR

GENERATOR ROOM

SHEET E-101

B

2 3

C

D

1 2 3

4 5 6

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

R

EV

IE

W

ED

B

Y:

4 5

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

SHEET

IDENTIFICATION

C

D

A

B

U

SS

F

TH

C

IV

IL

E N

G

IN

EE

R

S Q

U

AD

R O

N , P

SF

B, F L

C O

N

TR

AC

T

N O

FA

-1 8-

D -0

TR

AC

ES

TE

C H

N

IC

AL

R

AN

G

E

AR

C H

IT

EC

T

EN

G

IN

EE

R

IN

G

SE

R

VI

C

ES

N el so nE ng in ee ri ng C o.

rh od es b rit

D

AT

E:

AS

B

U

IL

T D

AT

E:

D

EL

IV

ER

Y N

O

PR

O

JE

C

T N

U M

BE

R

N

EL

SO

N

EN

G

IN

EE

R

IN

G

/2

1/

C . J

O D

H

AN

R . S

AN

TO

S

B.

K

O

LA

K P.

E.

SX

H

T

-1

SX

H

T

-1

R

EP

AI

R

/R

EP

LA

C

E C

O M

M

AN

D P

O

ST

G

EN

ER

AT

O R

, B

E-501

EL

EC

TR

IC

AL

D

ET

AI

LS

GRAPHIC SCALE

SCALE IN FEET

0 0.5 1 2

1 1/2"=1'-0"

TRANSFORMER

SCALE:

TYPICAL FIELD FABRICATED FRAME DETAIL

1 1/2" = 1'-0"

E-101

FRONT VIEW SIDE VIEW

NOTES:

1. DETAIL IS INTENDED TO SHOW TYPICAL FRAME CONSTRUCTION FOR VARIOUS TYPES OF

EQUIPMENT AND IS NOT REPRESENTATIVE OF ANY SPECIFIC INSTALLATION LOCATION.

2. FOR EXTERIOR APPLICATIONS USE 316 STAINLESS STEEL STRUT AND STRUT ACCESSORIES.

ELECTRICAL

PANEL

CONCRETE PAD

ATTACH BRACE AT VERTICAL SUPPORT COLUMN MID

HEIGHT USING UNISTRUT PART P1354AW AND 1/2

INCH DIAMETER HOT DIP GALVANIZED STEEL BOLTS

BRACE ACH VERTICAL SUPPORT COLUMN

USING HOT DIP GALVANIZED STEEL,

12-GAUGE, 1-5/8 INCH STRUT

ATTACH BRACE AT CONCRETE PAD

USING UNISTRUT PART P1354AW

AND 1/2 INCH DIAMETER HOT DIP

GALVANIZED STEEL, CONCRETE

EPOXY ANCHORS WITH A MINIMUM

5 INCH EMBEDMENT DEPTH

FOR INTERIOR INSTALLATIONS STRUT

MAY BE ATTACHED TO BUILDING

STRUCTURE WHERE PRACTICAL

2'-0" MIN

FASTEN EQUIPMENT TO HORIZONTAL

CHANNELS USING 1/4 INCH DIAMETER

HOT DIP GALVANIZED STEEL BOLTS.

QUANTITY OF FASTENERS SHALL BE IN

ACCORDANCE WITH MANUFACTURER

PROVIDED MOUNTING POINTS, BUT IN

NO CASE LESS THAN A QUANTITY OF

FOUR (4) PER PIECE OF EQUIPMENT

HOT DIP GALVANIZED STEEL 12-GAUGE,

BACK-TO-BACK 1-5/8 INCH STRUT

VERTICAL SUPPORT COLUMN SPACED

MINIMUM OF 36-INCHES AND A

MAXIMUM OF 60-INCHES O.C. AS

REQUIRED FOR EQUIPMENT

INSTALLATION

HOT DIP GALVANIZED STEEL DOUBLE

CHANNEL POST BASE, UNISTRUT PART

P2073ASQ OR EQUIVALENT. MOUNT

BASE TO CONCRETE PAD USING 1/2 INCH

DIAMETER, HOT DIP GALVANIZED STEEL,

CONCRETE EPOXY ANCHORS WITH

MINIMUM 5 INCH EMBEDMENT DEPTH

MAXIMUM HEIGHT OF FIELD FABRICATED

STRUCTURES IS BE 72 INCHES UNLESS

OTHERWISE NOTED

HOT DIP GALVANIZED STEEL 12-GAUGE

1-5/8 INCH FULL LENGTH HORIZONTAL

CHANNEL SUPPORT SPACED VERTICALLY

ON FRONT AND BACK OF FRAME AS

REQUIRED FOR EQUIPMENT TO BE

INSTALLED. CONNECT SUPPORTS TO

VERTICAL COLUMNS USING HOT DIP

GALVANIZED STEEL BRACKETS

MANUFACTURED FOR SUCH PURPOSE.

PROVIDE ADDITIONAL HORIZONTAL

CHANNELS AS REQUIRED TO SUPPORT

CONDUIT INSTALLATION.

CONCRETE PAD

AUTOMATIC

TRANSFER

SWITCH

1. REFER TO GENERAL NOTES, ABBREVIATIONS, AND LEGEND ON SHEET E-001.

2. REFER TO SINGLE LINE DIAGRAM AND PANEL SCHEDULE ON SHEET E-601 FOR

SYSTEM CONFIGURATION AND CABLE AND CONDUIT INFORMATION.

GENERAL NOTES:

ENCLOSED

CIRCUIT

BREAKER

DISCONNECT

SWITCH

DISCONNECT

SWITCH

JUNCTION

BOX

B

2 3

C

D

1 2 3

4 5 6

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

R

EV

IE

W

ED

B

Y:

4 5

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

AP

PR

SHEET

IDENTIFICATION

C

D

A

B

U

SS

F

TH

C

IV

IL

E N

G

IN

EE

R

S Q

U

AD

R O

N , P

SF

B, F L

C O

N

TR

AC

T

N O

FA

-1 8-

D -0

TR

AC

ES

TE

C H

N

IC

AL

R

AN

G

E

AR

C H

IT

EC

T

EN

G

IN

EE

R

IN

G

SE

R

VI

C

ES

N el so nE ng in ee ri ng C o.

rh od es b rit

D

AT

E:

AS

B

U

IL

T D

AT

E:

D

EL

IV

ER

Y N

O

PR

O

JE

C

T N

U M

BE

R

N

EL

SO

N

EN

G

IN

EE

R

IN

G

/2

1/

C . J

O D

H

AN

R . S

AN

TO

S

B.

K

O

LA

K P.

E.

SX

H

T

-1

SX

H

T

-1

R

EP

AI

R

/R

EP

LA

C

E C

O M

M

AN

D P

O

ST

G

EN

ER

AT

O R

, B

E-601

PA

R

TI

AL

S

IN

G

LE

-L

IN

E D

IA

G

R

AM

A N

D P

AN

EL

S C

H

ED

U

LE

S

1. CRAC 2 IS REDUNDANT TO CRAC 1. LOADS WILL NOT OPERATE AT THE SAME

TIME AND ARE CONSIDERED NON-COINCIDENTAL IN ACCORDANCE WITH NEC

ARTICLE 220.83.

2. PROVIDE A RENTAL 20 KW, 208/120V GENERATOR, CABLES, AND FUEL FOR A

MINIMUM OF 24 HOURS TO PROVIDE STANDBY POWER IN THE EVENT OF A

UTILITY POWER FAILURE TO THE COMMAND POST. PROVIDE GENERATOR

VENDOR SERVICE TO SUPPORT GENERATOR TESTING AND OPERATION.

3. TAP CONDUCTOR LENGTH SHOULD NOT BE MORE THAN 10 LINEAR FEET IN

ACCORDANCE WITH NEC ARTICLE 240.21(B).

FLAG NOTES:

EXISTING HH-3 PANEL

NEW COMP RM PANEL

EXISTING PP-1 PANEL

COMP ROOM ATS

480VAC

225A

4-POLE

EN

L

G

GENERATOR B423

480VAC

150KW

3PH 3W

MSB

480/277VAC

1000A

3PH 4W 1000A

3P

PARTIAL SINGLE LINE

175A 3P

FROM UTILITY

TRANSFORMER

COMP

RM

400A

208/120VAC

PANEL

175A 3P

70A 3P

TO COMMAND POST

COMMAND

POST

ECB

208/120VAC

150A

3PH 4W

CONDUIT AND WIRE SCHEDULE

ID NEW/EXISTING

CABLE

TYPE

CIRCUIT

VOLTAGE

NO. OF

PARALLEL

SET

PHASE

QUAN-SIZE PER

SET

NEUTRAL

SIZE PER

SET

GND

SIZE PER

SET

CND TRADE

SIZE

(INCHES) NOTES

1 NEW THWN 480 1 3-#2/0 N/A #6 2"

2 NEW THWN 480 1 3-#2/0 N/A #6 2 1/2"

5 NEW 480 N/A #8 1"

6 NEW THWN

4 NEW THWN 208/120 3-500 KCMIL 500 KCMIL #3 3 1/2"

208/120 3-#1/0 #1/0 #6 2"

7 EXISTING EXIST 208/120 EXISTING EXISTING EXIST EXISTING

THWN

3 SEE NOTE THWN 480 1 3-#4/0 N/A #4 2"

EXISTING

3-#4

175A 3P

175A 3P

ECB HH-3

480VAC

18KAIC

225A

3PH 3W

225A 3P

PANEL HH-3

480VAC

18KAIC

225A

3PH 3W

EXISTING CONDUIT WITH NEW WIRE

GEN PNL

208/120VAC

10KAIC

100A

3PH 4W

8 NEW THWN 208/120 3-#4 #4 #8 1 1/2"1

CAPPED 4-INCH

RGS CONDUIT

NIPPLE FOR

FUTURE LOAD

BANK CONNECTIONS

PANEL NAME HH-3 MAIN BREAKER 175 AMP

TYPE MCB Cu BUS 225 AMP

VOLTAGE 480VAC MINIMUM AIC RATING 18 KA FED FROM: 75KVA TRANSFORMER SXHT003310

TR

IP

A M

PS

PO

LE

S

DESIGNATION WIRE

N

EU

TR

A

L

G N

D

C O

N D

K

VA

C A

TE

G

O R

Y

N O

PH

A

SE

A

PH

A

SE

B

PH

A

SE

C

N O

C A

TE

G

O R

Y

K

VA

C O

N D

G N

D

N

EU

TR

A

L

WIRE DESIGNATION

PO

LE

S

TR

IP

A M

PS

45 3 CRAC-2 #8 - #10 1"

11.4 M 1 15.0 2 M 3.6

3/4" #12 - #12 CRAC 1 3 1511.4 M 3 15.0 4 M 3.6

11.4 M 5 15.0 6 M 3.6

175 3 COMP RM XFMR #2/0 - #6 2"

37.5 G 7 37.5 8

37.5 G 9 37.5 10

37.5 G 11 37.5 12

13 0.0 14 15 0.0 16 17 0.0 18

* 3 SPD * * * *

0.0 G 19 0.0 20

0.0 G 21 0.0 22

0.0 G 23 0.0 24

TOTAL 52.47 52.47 52.47 TOTAL CONNECTED LOAD 157.40 KVA

DEMAND KVA

R RECEPTACLE<10KW 100% 0.0 DEMAND 199.57 AMPS

R RECEPTACLE >10KW 50% 0.0

L LIGHTS 125% 0.0

G GENERAL EQUIPMENT 100% 112.5 NOTES: 1. NEW CIRCUITS NOTED IN BOLD TEXT

H HEATER 125% 0.0 2. PROVIDE NEW, TYPED PANEL SCHEDULE.

M MOTORS LESS LARGEST 100% 10.8 3. PROVIDE PANEL WITH TYPE 2 CATEGORY B SPD SIZE CIRCUIT M LARGEST MOTOR 125% 42.6 BREAKER AND WIRING IN ACCORDANCE WITH SPD MANUFACTURER'S

TOTAL 165.9 RECOMMENDATIONS.

PANEL NAME COMP RM MAIN BREAKER 350 AMP

TYPE MCB Cu BUS 400 AMP

VOLTAGE 208/120VAC MINIMUM AIC RATING 18 KA FED FROM: PANEL HH-3

TR

IP

A M

PS

PO

LE

S

DESIGNATION WIRE

N

EU

TR

A

L

G N

D

C O

N D

K

VA

C A

TE

G

O R

Y

N O

PH

A

SE

A

PH

A

SE

B

PH

A

SE

C

N O

C A

TE

G

O R

Y

K

VA

C O

N D

G N

D

N

EU

TR

A

L

WIRE DESIGNATION

PO

LE

S

TR

IP

A M

PS

20 1 SELR9-1 3-#12 #12 #12 3/4" 2.4 G 1 4.8 2 G 2.4 3/4" #12 #12 3-#12 SELR6-1 1 20 20 1 SELR9-2 3-#12 #12 #12 3/4" 2.4 G 3 4.8 4 G 2.4 3/4" #12 #12 3-#12 SELR6-2 1 20 20 1 SELR9-3 3-#12 #12 #12 3/4" 2.4 G 5 4.8 6 G 2.4 3/4" #12 #12 3-#12 SELR6-3 1 20 20 1 SELR9-4 3-#12 #12 #12 3/4" 2.4 G 7 4.8 8 G 2.4 3/4" #12 #12 3-#12 SELR6-4 1 20 20 1 SELR9-5 3-#12 #12 #12 3/4" 2.4 G 9 4.8 10 G 2.4 3/4" #12 #12 3-#12 SELR8-1 1 20 20 1 SELR4-1 3-#12 #12 #12 3/4" 2.4 G 11 4.8 12 G 2.4 3/4" #12 #12 3-#12 SELR8-2 1 20 20 1 SELR4-2 3-#12 #12 #12 3/4" 2.4 G 13 4.8 14 G 2.4 3/4" #12 #12 3-#12 SELR8-3 1 20 20 1 SELR4-3 3-#12 #12 #12 3/4" 2.4 G 15 4.8 16 G 2.4 3/4" #12 #12 3-#12 SELR8-4 1 20 20 1 SERL11-1 3-#12 #12 #12 3/4" 2.4 G 17 4.8 18 G 2.4 3/4" #12 #12 3-#12 SELR7-1 1 20 20 1 SERL11-2 3-#12 #12 #12 3/4" 2.4 G 19 4.8 20 G 2.4 3/4" #12 #12 3-#12 SELR7-2 1 20 20 1 SERL11-3 3-#12 #12 #12 3/4" 2.4 G 21 4.8 22 G 2.4 3/4" #12 #12 3-#12 SELR7-3 1 20 20 1 SERL11-4 3-#12 #12 #12 3/4" 2.4 G 23 4.8 24 G 2.4 3/4" #12 #12 3-#12 SELR7-4 1 20 20 1 SERL11-5 3-#12 #12 #12 3/4" 2.4 G 25 4.8 26 G 2.4 3/4" #12 #12 3-#12 SERL10-1 1 20 20 1 SERL11-6 3-#12 #12 #12 3/4" 2.4 G 27 4.8 28 G 2.4 3/4" #12 #12 3-#12 SERL10-2 1 20 20 1 SERL10-5 3-#12 #12 #12 3/4" 2.4 G 29 4.8 30 G 2.4 3/4" #12 #12 3-#12 SERL10-3 1 20 20 1 SERL10-6 3-#12 #12 #12 3/4" 2.4 G 31 4.8 32 G 2.4 3/4" #12 #12 3-#12 SERL10-4 1 20

33 0.0 34 35 0.0 36

* 3 SPD * * 31.0 *

0.0 G 37 0.0 38

0.0 G 39 0.0 40

0.0 G 41 0.0 42

TOTAL 28.80 24.00 24.00 TOTAL CONNECTED LOAD 76.80 KVA

DEMAND KVA

R RECEPTACLE<10KW 100% 0.0 DEMAND 213.18 AMPS

R RECEPTACLE >10KW 50% 0.0

L LIGHTS 125% 0.0

G GENERAL EQUIPMENT 100% 76.8 NOTES: 1. PROVIDE NEW, TYPED PANEL SCHEDULE.

H HEATER 125% 0.0 2. PROVIDE PANEL WITH TYPE 2 CATEGORY B SPD SIZE CIRCUIT

M MOTORS LESS LARGEST 100% 0.0 BREAKER AND WIRING IN ACCORDANCE WITH SPD MANUFACTURER'S

M LARGEST MOTOR 125% 0.0 RECOMMENDATIONS.

TOTAL 76.8

PANEL NAME PP-1 MAIN BREAKER 225 AMP

TYPE MCB Cu BUS 225 AMP

VOLTAGE 480/277VAC MINIMUM AIC RATING 15 KA FED FROM: MSB

TR

IP

A M

PS

PO

LE

S

DESIGNATION WIRE

N

EU

TR

A

L

G N

D

C O

N D

K

VA

C A

TE

G

O R

Y

N O

PH

A

SE

A

PH

A

SE

B

PH

A

SE

C

N O

C A

TE

G

O R

Y

K

VA

C O

N D

G N

D

N

EU

TR

A

L

WIRE DESIGNATION

PO

LE

S

TR

IP

A M

PS

60 3 PT-1 45KVA XFMR 3-#4 - #10 1"

8.3 G 1 14.5 2 G 6.2

3/4" #10 - 3-#6 CT-NW 30KVA XFMR 3 458.3 G 3 14.5 4 G 6.2

8.3 G 5 14.5 6 G 6.2

20 3 AHU-1A, 3MECH1 3-#12 - #12 3/4"

2.8 M 7 5.5 8 H 2.8

3/4" #12 - 3-#12 DUCT HEATER DH-1 3 202.8 M 9 5.5 10 H 2.8

2.8 M 11 5.5 12 H 2.8

13 25.0 14 G 25.0

1-1/2" #6 - 3-#1 75 KVA XFMR 3 12515 25.0 16 G 25.0

17 25.0 18 G 25.0 19 0.0 20 21 0.0 22 23 0.0 24 25 0.0 26 27 0.0 28 29 0.0 30 31 0.0 32 33 0.0 34 35 0.0 36 37 0.0 38 39 0.0 40 41 0.0 42

TOTAL 45.09 45.09 45.09 TOTAL CONNECTED LOAD 135.28 KVA

DEMAND KVA

R RECEPTACLE<10KW 100% 0.0 DEMAND 167.71 AMPS

R RECEPTACLE >10KW 50% 0.0

L LIGHTS 125% 0.0

G GENERAL EQUIPMENT 100% 118.6 NOTES: 1. NEW CIRCUITS NOTED IN BOLD TEXT.

H HEATER 125% 10.4 2. LOAD INFORMATION FOR EXISTING CIRCUIT CALCULATED

M MOTORS LESS LARGEST 100% 0.0 AT 50% OF BREAKER CAPACITY.

M LARGEST MOTOR 125% 10.4 3. INSTALL NEW 125A, 3P, BREAKER IN CIRCUIT NOTED IN

TOTAL 139.4 BOLD TEXT.

INSTALL NEW 12 X 12 X 6 INCH NEMA 1

JUNCTION BOX AND TAP FEEDERS IN

ACCORDANCE WITH NEC 240.21 USING

INSULATED MECHANICAL LUGS.

Sheets and Views
G-001 COVER SHEET
G-101 FIRST FLOOR COMPOSITE PLAN
G-102 THIRD FLOOR COMPOSITE PLAN
E-001 ELECTRICAL GENERAL NOTES
E-101 FIRST FLOOR GENERATOR ROOM - ENLARGED POWER PLANS
E-102 THIRD FLOOR ROOM C310 - ENLARGED POWER PLANS
E-501 ELECTRICAL DETAILS
E-601 PARTIAL SINGLE-LINE DIAGRAM AND PANEL SCHEDULES

File details come from the government source that posted it. Updated .