Attachment 11 - NAVFAC MIDLANT PWD-Maine - ICS Standard.pdf
PDF 2 MB Posted
- Attached to
- B238 Renovations Federal contract opportunity
- Solicitation number
- N4008520B2533
About this file
This document provides standards for an integrated control system (ICS) network. It outlines naming conventions, configuration standards, and graphical user interface guidelines for points, objects, stations, alarms, histories and other aspects of an ICS. Specific standards are provided for IP and BACNET addressing, point facets including data types, equipment and station naming formats, alarm and history extensions, prohibited special characters, and user access. Appendices include lists of standard point names, equipment types, and examples of graphical user interfaces. The document aims to maintain consistency across ICS installations for various buildings and facilities of the Naval Facilities Engineering Command Mid-Atlantic Public Works Department in Maine.
The related federal contract opportunity is a solicitation to repair and renovate spaces in Building B238, including demolition and construction of a break room and renovation of a training room, cafeteria, locker room and work spaces. Issued by the Naval Facilities Engineering Command, the period of performance is 280 days from award. The solicitation number is N4008520B2533 and the project name is B238 Renovations.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 1419 BID RESULTS N4008520B2533 B238.pdf | ||
| Amendment 0001 - Mirror Spec.pdf | ||
| N4008520B2533 Amendment 0001 Released.pdf | ||
| Amendment 0001 - Gov Responses to RFIs.pdf | ||
| Attachment 6 - Drawings B238 3-21-2020 DF.pdf | ||
| Attachment 1 - Bid Form 2-28-20.pdf | ||
| Attachment 5 - Submittal Register 3-10-20.XLS | XLS spreadsheet | |
| Attachment 8 - B238-ISRL 3-4-20.XLSX | XLSX spreadsheet | |
| Attachment 6 - Drawings B238 3-21-2020 DF JR.pdf | ||
| Attachment 10 - UFC Telecommunications Requirements.pdf | ||
| B238 - Scope of Work IH DBB_Rev 20-21 4-8-20.pdf | ||
| N4008520B2533 B238 Renovations - Released.pdf | ||
| Attachment 4 -Furniture SOW 3-6-20.pdf | ||
| Attachment 9 - PNSY Local Electrical Standard - Rev C.pdf | ||
| Attachment 2 and 3 - Div 1 and Technical Specifications.pdf | ||
| Attachment 7 - eOMSI WORKBOOK REV 6 3-3-2020.xlsx | XLSX spreadsheet |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 1
NAVFAC MIDLANT PWD-Maine
ICS Standard
1. GENERAL
2. NETWORK ADDRESSING
2.1. IP
2.2. BACNET
3. POINT AND OBJECT CONFIGURATION
3.1. POINT AND EQUIPMENT NAMING
3.2. POINT FACETS
3.2.1. INTEGERS
3.2.2. ONE DECIMAL
3.2.3. TWO DECIMALS
3.2.4. THREE DECIMALS
3.2.5. BOOLEAN VALUES
3.2.6. ENUMERATED VALUES
3.3. NIAGARA STATION NAMING
3.3.2. LOCATION EXAMPLES
3.3.3. BUILDING PREFIX EXAMPLES
3.3.4. BUILDING NUMBERS
3.3.7. STATION NAME EXAMPLES
3.4. ALARMS
3.4.1. EXTENSION CONFIGURATION
3.5. HISTORIES
3.5.1. NAMING
3.5.1.2. BUILDING PREFIX EXAMPLES
3.5.1.3. BUILDING NUMBER
3.5.1.4. EQUIPMENT TYPE
3.5.1.5. EQUIPMENT INSTANCE
3.5.1.6. POINT NAME
3.5.1.7. HISTORY NAMING EXAMPLES
3.6. SPECIAL CHARACTERS
Attachment 11
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 2
4. GRAPHICAL USER INTERFACE
4.3. EXPORT TAGS
5. USER ACCESS
5.1. EXISTING INSTALLATIONS
5.2. NEW INSTALLATIONS
6. APPENDICES
6.1. STANDARD POINT NAMING CONVENTION LIST
6.2. STANDARD EQUIPMENT NAMING CONVENTION LIST
6.3. GRAPHICAL USER INTERFACE EXAMPLES
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 3
1. GENERAL
1.1. JACE version shall be newest released version of Niagara that is compatible with the existing
Niagara Supervisor in Building 374 (ECC).
2. NETWORK ADDRESSING
2.1. IP
2.1.1. All IP addresses on the ICS network shall be provided by NAVFAC. Submit request for all IP devices to contracting officer.
2.1.2. All IP devices shall be networked to allow IP communication directly from Building 374 ECC.
2.2. BACNET
2.2.1. All BACnet instances and network numbers shall be provided by NAVFAC. Submit request for all BACnet addressing information to contracting officer.
3. POINT AND OBJECT CONFIGURATION
3.1. POINT AND EQUIPMENT NAMING
3.1.1. Assign all points on the ICS network a name from the naming convention list. The point description should match the intended operation of the ICS point being named.
Intermediate logic points used for calculations within the JACE do not need a standard name. The point containing the final result of the logic should be standard however. See
Appendix 6.1 and 6.2 for point and equipment list.
3.1.2. In the event that no applicable point name exists for an ICS point, the contractor shall use the following guidelines to create a new point name:
3.1.2.1. Contractor shall RFI point names recommendations for any points that do not seem to fit into the naming convention.
3.1.2.2. No special characters including spaces, hyphens and periods shall be used. See section
3.6 SPECIAL CHARACTERS.
3.1.2.3. Use CamelCase instead of spaces in point names.
3.1.2.4. In some circumstances, certain equipment and station names may use underscores instead of spaces with NAVFAC PWD-Maine HVAC Action Team approval.
3.1.2.5. If there are multiple points for a piece of equipment that require the same point name prefix the point name with a brief descriptor such as “North”. The point will become
“NorthZoneTemp”. If there are multiple NorthZoneTemp points in a single point folder they shall be numbered like: “NorthZoneTemp2”.
3.1.3. Multiple pieces of equipment under one controller shall use folders to separate the different pieces of equipment into logical devices. This will allow the use of the normal naming convention rules as well as graphic templates, history naming etc.
3.2. POINT FACETS
3.2.1. INTEGERS
Minutes (min)
Seconds (s)
Cubic feet per minute (cfm)
Parts per million (ppm)
Number of equipment running
Zones calling for heat
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 4
Cooling stages active
3.2.2. ONE DECIMAL
Temperature (°F)
Humidity (%RH) Pounds per square inch (psi) Hours (hr) Pounds per hour (lb/hr) Voltage (V) Amps (A) Power factor (pf) Frequency (Hz) Kilowatts (kW) Kilowatt hours (kW-hr) Gallons (gal) Gallons per hour (gal/min) Pounds per hour (lb/hr)
3.2.3. TWO DECIMALS
Inches of Water Column (in/wc) used for duct static pressure
3.2.4. THREE DECIMALS
Inches of Water Column (in/wc) used for building pressure
3.2.5. BOOLEAN VALUES
Equipment Commands and Statuses (On/Off) Valve and Damper Commands and Statuses (Open/Closed) Occupancy (Occupied/Unoccupied) Alarms, Faults and Failures (Normal/Alarm)
3.2.5.1. Equipment specific values can be used
3.2.5.2. Avoid all capitals letters
3.2.5.3. Avoid using special characters
3.2.6. ENUMERATED VALUES
3.2.6.1. Equipment specific values can be used
3.2.6.2. Avoid all capitals letters
3.2.6.3. Avoid using special characters
3.3. NIAGARA STATION NAMING
3.3.1. Name shall be in the format: “[LOCATION]_[BUILDING PREFIX][BUILDING NUMBER]”.
3.3.2. LOCATION EXAMPLES
PNSY
CUTLER
QUINCY
SYRACUSE
3.3.3. BUILDING PREFIX EXAMPLES
“B” (Building)
“H” (Housing)
“DD” (Dry Dock)
“NOSC” (Naval Operation Support Center)
3.3.4. BUILDING NUMBERS
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 5
3.3.4.1. All buildings shall use a 3 digit number keeping leading zeroes. Since there are minimal dry dock numbers they shall use 2 digits.
3.3.5. No spaces shall be used. Use an underscore (_) between the location and building prefix.
3.3.6. If there are multiple buildings served by one JACE, the station shall indicate this by listing the buildings separated by underscores.
3.3.7. STATION NAME EXAMPLES
PNSY_B043
PNSY_B153_B170_B170A
PNSY_DD01
CUTLER_B001
QUINCY_B001
3.4. ALARMS
3.4.1. EXTENSION CONFIGURATION
3.4.1.1. SOURCE NAME
3.4.1.1.1. Utilize bformat so the when viewed in the alarm console, the alarm is annunciated with a source name similar to the last part of the history names.
For example:
VAV01_ZoneTemp
HotWaterSystem_PriHWSupplyTemp
3.4.1.1.2. This allows the operator to understand what system and what point is in alarm.
3.4.1.2. MESSAGE TEXT
3.4.1.2.1. The message text shall include some basics about the alarm. This can be generic based on the type of alarm the extension it is.
3.4.2. ALARM CLASSES
3.4.2.1. The three alarm classes that are to be used are:
3.4.2.1.1. Notification. Designated for non-critical alarms.
3.4.2.1.2. System. Designated for system-type alarms such as controllers offline (if not deemed critical).
3.4.2.1.3. Critical. Designated for alarms for anything that was thought to be of critical nature.
3.4.2.2. In the supervisor station, the alarm classes are brought into the station and appended with the JACE station prefix. This allows the supervisor station to organize the alarm consoles by both by the different alarm classes and by the buildings. The building name in the supervisor alarm class is what determines what building the alarm is coming from. This prefix is required since the alarm name will only display the equipment name with no building designation.
3.5. HISTORIES
3.5.1. NAMING
3.5.1.1. Name shall be in the format: “[BUILDING PREFIX][BUILDING NUMBER]_[EQUIPMENT
TYPE][EQUIPMENT INSTANCE]_[POINT NAME]”.
3.5.1.2. BUILDING PREFIX EXAMPLES
“B” (Building)
“H” (Housing)
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 6
“DD” (Dry Dock)
“NOSC” (Naval Operation Support Center)
3.5.1.3. BUILDING NUMBER
3.5.1.3.1. All buildings shall use a 3 digit number keeping leading zeroes. Since there are minimal dry dock numbers they shall use 2 digits.
3.5.1.4. EQUIPMENT TYPE
3.5.1.4.1. As listed in the Point and Equipment Naming Convention List.
3.5.1.5. EQUIPMENT INSTANCE
3.5.1.5.1. The number (or letter) used to uniquely identify the piece of equipment
3.5.1.6. POINT NAME
3.5.1.6.1. Shall be the same as the parent object.
3.5.1.6.2. No spaces shall be used. Use an underscore (_) building number and equipment type and also between equipment instance and point name.
3.5.1.7. HISTORY NAMING EXAMPLES
B153_HotWaterSystem_PriHWSupplyTemp
B156_JACE_Module1_OutsideAirTemp
B170A_ARU01_ReturnAirTemp
B059_VAV05_BoxFlow
DD01_DH01_ZoneTemp
3.5.1.8. The history names should be the same under both the JACE and as imported into the
Niagara Supervisor.
3.5.2. EXTENSION CONFIGURATION
3.5.2.1. History extensions shall reside within the JACE. The history shall be setup to import its data at least once every 24 hours.
3.5.2.2. Numeric points shall use interval trends set at 10 minutes. Boolean and Enumerated histories shall be set for Change of Value (COV).
3.6. SPECIAL CHARACTERS
3.6.1. The Niagara framework does not allow certain characters to be used in naming objects. If illegal characters are used, Niagara will use an escape sequence to replace the illegal character. An example is that the hyphen would be replaced with “$2d”. Although the display name of the object will show the hyphen, the ord of the object will contain the $2d.
The history name will also contain $2d which makes browsing through the history points list more difficult for an operator. The extra characters also count towards the history name maximum character count. Approved characters are A-Z, 0-9, and underscore (_).
4. GRAPHICAL USER INTERFACE
4.1. Graphics shall maintain the same look and feel as existing ICS graphics. See Appendix 6.3 for graphic user interface examples.
4.2. Graphics shall use standard pallets and should not require any special licenses to use.
4.3. EXPORT TAGS
4.3.1. Niagara export tag architecture shall be used.
4.3.2. Graphics shall be created in the building’s supervisor controller and then exported through the join process into the existing Niagara server in Building 374 (ECC).
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 7
4.3.3. The intent is to give a technician complete local access to the building graphics while the technician in troubleshooting from inside the building. The local building graphics would also be programmatically replicated in the Niagara Supervisor in Building 374 (ECC).
4.3.4. The Join process shall only be initiated after approval from NAVFAC PWD-Maine ICS System
Admin.
5. USER ACCESS
5.1. EXISTING INSTALLATIONS
5.1.1. A contractor performing new work on an existing JACE or the Niagara Supervisor shall have a temporary user created for them to use. Usernames will be assigned uniquely per individual. No group names or sharing of names is allowed. Coordinate users with NAVFAC
PWD-Maine ICS System Admin.
5.2. NEW INSTALLATIONS
5.2.1. Any new JACE installation shall be setup similar to the other JACEs installed on the ICS network.
5.2.2. The Admin superuser, all platform users, and the passphrase shall be turned over before the system can be turned over to the government.
5.2.3. Credentials shall be given to the contracting official of the project on CD.
5.2.4. The JACE shall be setup to receive network users from the Niagara Supervisor in Building
374. Coordinate user roles and prototypes with NAVFAC PWD-Maine ICS System Admin.
Join profile shall be setup. A pre-configured join profile is available upon request.
5.2.5. The station Admin superuser will not be a network user and shall be left in the JACE.
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 8
6. APPENDICES
6.1. STANDARD POINT NAMING CONVENTION LIST
Point Name Description Writable Read Only Alarm Trend Schedule Global
AlarmCode Equipment Alarm Code x x
AlarmReset Alarm Reset x
BalancerClgCmd Balancer Cool Override Command x x
BalancerCmd Balancer Override Command x
BalancerHtgCmd Balancer Heat Override Command x x
BoilerAlarm Boiler General Alarm x x
BoilerCmd Boiler Command x x
BoilerLockout Boiler Lockout Alarm x x
BoilerReturnWaterTemp Boiler Return Water Temperature x x
BoilerReturnWaterTemp Boiler Return Water Temperature x x
BoilerSig Boiler Signal x x
BoilerStatus Boiler Run Status x x
BoilerSupplyWaterTemp Boiler Supply Water Temperature x x
BoxFlow VAV Box Flow CFM x x
BoxKFactor VAV Box K-Factor x
BoxSizeSqFt VAV Box Size Square Footage x
BypassDamper Bypass Damper Command x x
BypassDamperStatus Bypass Damper Status x x
CallForCool Zone/Unit Call For Cool x x x
CallForHeat Zone/Unit Call For Heat x x x
ChilledWaterValve Chilled Water Valve Command x x
ChilledWaterValveStatus Chilled Water Valve Status x x
ChillerAlarm Chiller General Alarm x x
ChillerCapacity Current Chiller Capacity x x
ChillerCmd Chiller Command x x
ChillerLockout Chiller Lockout Alarm x x
ChillerSig Chiller Signal x x
ChillerStatus Chiller Run Status x x
CHWOAEnableSp Chilled Water System Outside Air Enable Setpoint x
ClgSupplyFan Cooling Supply Fan Command x x
ClStagesOn Number Of Cooling Stages On x x
CO2Sensor CO2 Sensor x x x
CO2SensorAverage Average CO2 Sensor Calculation x x x
CO2Sp CO2 Setpoint x
CommunicationState Network Communication State x x x
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 9
Point Name Description Writable Read Only Alarm Trend Schedule Global
ContinuousFanMode Continuous Fan Mode Configuration x
CoolDownSetpoint Cool Down Mode Setponit x
CoolLckOutSp Cooling Lockout Setpoint x
CoolLoad Cool Load x x
CoolStage1 Cooling Stage 1 Command x
CoolStage2 Cooling Stage 2 Command x
CUHValve Cabinet Unit Heat Valve Command x x
CWBypassValve Condenser Water Bypass Valve Command x x
CWBypassValveStatus Condenser Water Bypass Valve Status x x
CWPump Condenser Water Pump Command x x
CWPumpAmps Condenser Water Pump Amps x x
CWPumpFailure Condenser Water Pump Failure x x
CWPumpStatus Condenser Water Pump Status x x
CWPumpVFDAmps Condenser Water Pump VFD Amps x x
CWPumpVFDCmd Condenser Water Pump VFD Command x x
CWPumpVFDFault Condenser Water Pump VFD Fault x x
CWPumpVFDFb Condenser Water Pump VFD Feedback x x
CWPumpVFDHOA Condenser Water Pump VFD HOA Status x x
CWPumpVFDHz Condenser Water Pump VFD Hertz x x
CWPumpVFDKw Condenser Water Pump VFD Kw Reading x x
CWPumpVFDKwh Condenser Water Pump VFD KWH Accumulation x x
CWPumpVFDReady Condenser Water Pump VFD Drive Ready x x
CWPumpVFDReset Condenser Water Pump VFD Fault Reset x
CWPumpVFDRpm Condenser Water Pump
VFD RPM
x x
CWPumpVFDSpd Condenser Water Pump VFD Speed Command x x
CWPumpVFDStatus Condenser Water Pump VFD Status x x
DamperPosition Damper Position x x
DefrostSp Defrost Setpoint x
DefrostStatus Defrost Status x x
Dewpoint Dewpoint Reading x x x
DewpointAlarm Dewpoint Alarm x x
DewpointSp Dewpoint Setpoint x
DHWSteamValve Domestic Hot Water Steam Valve x x
DHWSupplyTemp Domestic Hot Water Supply Temperature x x x
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 10
DHWSupplyTempSp Domestic Hot Water Supply Temperature Setpoint x
DmprRevRot Damper Polarity Configuration x
DuctStatic Duct Static Pressure x x x
EconAvail Economizer Mode Availibility x x
EconDamper Economizer Damper Command x x
EconDamperStatus Economizer Damper Status x x
EconEnable Economizer Enable Network Command x x
EconEnaSp Economizer Enable Setpoint x
EconMinPosSp Minimum Economizer Damper Position Setpoint x
Economizer Economizer Command x x
EffBoilerSp Effective Boiler Setpoint x x
EffBoxFlowSp Effective Box Flow CFM Setpoint x
EffChillerSp Effective Chiller Setpoint x x
EffCoolSp Effective Cool Setpoint x x
EffHeatSp Effective Heat Setpoint x x
EffOcc Effective Occupancy Status x
EffPriHWSupplyTempSp Effective Primary Hot Water Supply Temperature Setpoint x x
EffSetpoint Effective Setpoint x
EffSupplyAirTempSp Effective Supply Air Temp Setpoint x x
EUHCmd Electric Unit Heater Command x x
ExhaustAirDamper Exhaust Air Damper Command x x
ExhaustAirDamperStatus Exhaust Air Damper Status x x
ExhaustAirFlow Exhaust Air Flow Reading x x
ExhaustAirFlowCal Exhaust Air Flow Calibration Factor x
ExhaustAirTemp Exhaust Air Temperature x x
ExhaustFan Exhaust Fan Command x x
ExhaustFanAmps Exhaust Fan Amps x x
ExhaustFanCFMSp Exhaust Fan CFM Setpoint x
ExhaustFanFailure ExhaustFanFailure x x
ExhaustFanOffsetSp Exhaust Fan Offset Setpoint x
ExhaustFanStatus Exhaust Fan Status x x
ExhaustFanVFDAmps Exhaust Fan VFD Amps x x
ExhaustFanVFDCmd Exhaust Fan VFD Command x x
ExhaustFanVFDFault Exhaust Fan VFD Fault x x
ExhaustFanVFDFb Exhaust Fan VFD Feedback x x
ExhaustFanVFDHOA Exhaust Fan VFD HOA Status x x
ExhaustFanVFDHz Exhaust Fan VFD Hertz x x
ExhaustFanVFDKw Exhaust Fan VFD Kw Reading x x
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 11
ExhaustFanVFDKwh Exhaust Fan VFD KWH Accumulation x x
ExhaustFanVFDReady Exhaust Fan VFD Drive Ready x x
ExhaustFanVFDReset Exhaust Fan VFD Fault Reset x
ExhaustFanVFDRpm Exhaust Fan VFD RPM x x
ExhaustFanVFDSpd Exhaust Fan VFD Speed Command x x
ExhaustFanVFDStatus Exhaust Fan VFD Status x x
FaceBypassDamper Face and Bypasss Damper x x
FaceBypassDamperStatus Face and Bypasss Damper Status x x
FanCmd Fan Command x x
FanFailureAlarm Fan Failure Alarm x x
FanSpeedConfig Fan Speed Configuration x
FanStatus Fan Status x x
FilterStatus Filter Status x x
FilterStatusReset Filter Status Reset Command x
FinalFilterStatus Final-Filter Status x x
FrzStatAlarmAuto Freezestat Alarm with Auto Reset x x
FrzStatAlarmManual Freezestat Alarm with Manual Reset x x
FrzStatHeatSp The position the heat will go to on Freezestat Trip x
FTRValve Finned Tube Radiation Valve Command x x
GeneralAlarm General Equipment Alarm Indicator x x
HeatLckOutSp Heating Lockout Setpoint x
HeatLoad Heat Load x x
HeatStage1 Heating Stage 1 Command x
HeatStage2 Heating Stage 2 Command x
HeatWheelCmd Heat Wheel Command x x
HeatWheelSp Heat Wheel Command Setpoint x
HeatWheelSpd Heat Wheel Speed Command x x
HiTempAlarm High Temperature Alarm x x
HotWaterValve Hot Water Valve Command x x
HtgSupplyFan Cooling Supply Fan Command x x
HtStagesOn Number Of Heating Stages On x x
HWSOAEnableSp Hot Water System Outside Air Enable Setpoint x
HXEnteringTemp Heat Exchanger Entering Temperature x x
HXLeavingTemp Heat Exchanger Leaving Temperature x x
InManualState Controller In Manual Status x x
LeadCompressor Lead Compressor Designation x
LocalSp Local Tstat Setpoint x x
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 12
LoTempAlarm Low Temperature Alarm x x
MaxCO2Sp Maximum CO2 Setpoint x
MaxFlowSp Maximum Flow CFM Setpoint x
MaxHeatFlowSp Maximum Heating CFM Setpoint x
MaxHeatSp Maximum Heat Setpoint x
MaxOADamperPosSp Maxmum Outside Air Damper Position Setpoint x
MaxResetPriHWOASp Maximum Primary Hot Water Reset Outside Air Setpoint x
MaxResetPriHWSp Maximum Primary Hot Water Reset Setpoint x
MaxResetSupplyAirOASp Maximum Supply Air Temp Outside Air Reset Setpoint x
MaxResetSupplyAirRASp Maximum Supply Air Temp Return Air Reset Setpoint x
MaxResetSupplyAirSp Maxmimum Supply Air Temp Reset Setpoint x
MaxWallModSp Maximum Wall Module Setpoint x
MinCO2Sp Minimum CO2 Setpoint x
MinCoolSp Minimum Cooling Flow CFM Setpoint x
MinFlowSp Minimum Flow CFM Setpoint x
MinHeatFlowSp Minimum Heating CFM Setpoint x
MinOADamperPosSp Minimum Outside Air Damper Position Setpoint x
MinOAFlowSp Minimum Outside Air Flow Setpoint x
MinResetPriHWOASp Minimum Primary Hot Water Reset Outside Air Setpoint x
MinResetPriHWSp Minimum Primary Hot Water Reset Setpoint x
MinResetSupplyAirOASp Minimum Supply Air Temp Outside Air Reset Setpoint x
MinResetSupplyAirRASp Minimum Supply Air Temp Return Air Reset Setpoint x
MinResetSupplyAirSp Minimum Supply Air Temp Reset Setpoint x
MinWallModSp Minimum Wall Module Setpoint x
MixedAirDamper Mixed Air Damper Command x x
MixedAirDamperStatus Mixed Air Damper Status x x
MixedAirTemp Mixed Air Temperature x x
MixedAirTempLLSp Mixed Air Temperature Low Limit Setpoint x
NetLockoutCool Network Command to Lockout Cool x x
NetLockoutHeat Network Command to Lockout Heat x x
NetOccCommand Network Occupancy Command x x
NetOutsideAirCO2 Network Outside Air CO2 x x
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 13
NetOutsideAirEnth Network Outside Air Enthalpy x x
NetOutsideAirRH Network Outside Air RH x x
NetOutsideAirTemp Network Outside Air Temp x x
NetUnitCmd Network Unit Command x x
OccupiedCoolSp Occupied Cool Setpoint x
OccupiedHeatSp Occupied Heat Setpoint x
OccupiedHeatSpOffset Occupied Heat Setpoint Offset x
OccupiedSp Occupied Setpoint x
OccupiedSpHiLim Occupied Setpoint High Limit Setpoint x
OccupiedSpLoLim Occupied Setpoint Low Limit Setpoint x
OSCommand Optimal Start Command x x
OutsideAirCO2 Outside Air CO2 x x
OutsideAirDamper Outside Air Damper Command x x
OutsideAirDamperStatus Outside Air Damper Status x x
OutsideAirDewpoint Outside Air Dewpoint x x
OutsideAirEnth Outside Air Enthalpy x x
OutsideAirFlowCal Outside Air Flow Calibration Factor x
OutsideAirIsoDamper Outside Air Isolation Damper Command x x
OutsideAirIsoDamperStatus Outside Air Isolation Damper Status x x
OutsideAirRH Outside Air RH x x
OutsideAirTemp Outside Air Temp x x
PanelTemp Panel Temperature x
PBOverrideSp Tstat Pushbutton Override Duration Setpoint x
PBOverrideStatus Pushbutton Override Status x x
PreFilterStatus Pre-Filter Status x x
Pri13SteamValve Primary 1/3 Steam Valve Command x x
Pri23SteamValve Primary 2/3 Steam Valve Command x x
PriCHWBypassValve Primary Chilled Water Loop Water Bypass Valve Command x x
PriCHWBypassValveStatus Primary Chilled Water Loop Water Bypass Valve Status x x
PriCHWPump Primary Loop Chilled Water Pump Command x x
PriCHWPumpAmps Primary Loop Chilled Water Pump Amps x x
PriCHWPumpFailure Primary Chilled Water Loop Pump Failure x x
PriCHWPumpStatus Primary Loop Chilled Water Pump Status x x
PriCHWPumpVFDAmps Primary Loop Chilled Water Pump VFD Amps x x
PriCHWPumpVFDCmd Primary Loop Chilled Water Pump VFD Command x x
PriCHWPumpVFDFault Primary Loop Chilled Water Pump VFD Fault
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 14
PriCHWPumpVFDFb Primary Loop Chilled Water Pump VFD Feedback x x
PriCHWPumpVFDHOA Primary Loop Chilled Water Pump VFD HOA Status x x
PriCHWPumpVFDHz Primary Loop Chilled Water Pump VFD Hertz x x
PriCHWPumpVFDKw Primary Loop Chilled Water Pump VFD Kw Reading x x
PriCHWPumpVFDKwh Primary Loop Chilled Water Pump VFD KWH Accumulation x x
PriCHWPumpVFDReady Primary Loop Chilled Water Pump VFD Drive Ready x x
PriCHWPumpVFDReset Primary Loop Chilled Water Pump VFD Fault Reset x
PriCHWPumpVFDRpm Primary Loop Chilled Water Pump VFD RPM x x
PriCHWPumpVFDSpd Primary Loop Chilled Water Pump VFD Speed Command x x
PriCHWPumpVFDStatus Primary Loop Chilled Water Pump VFD Status x x
PriHWBypassValve Primary Hot Water Loop Water Bypass Valve Command x x
PriHWBypassValveStatus Primary Hot Water Loop Water Bypass Valve Status x x
PriHWDiffPress Primary Hot Water Differential Pressure x x
PriHWDiffPressSp Primary Hot Water Differential Pressure Setpoint x
PriHWFlow Primary Hot Water Flow Switch x x
PriHWLeadPump Primary Hot Water Lead Pump x x
PriHWPump Primary Loop Hot Water Pump Command x x
PriHWPumpAmps Primary Loop Hot Water Pump Ampsvalve x x
PriHWPumpFailure Primary Hot Water Loop Pump Failure x x
PriHWPumpStatus Primary Loop Hot Water Pump Status x x
PriHWPumpVFDAmps Primary Loop Hot Water Pump VFD Amps x x
PriHWPumpVFDCmd Primary Loop Hot Water Pump VFD Command x x
PriHWPumpVFDFault Primary Loop Hot Water Pump VFD Fault x x
PriHWPumpVFDFb Primary Loop Hot Water Pump VFD Feedback x x
PriHWPumpVFDHOA Primary Loop Hot Water Pump VFD HOA Status x x
PriHWPumpVFDHz Primary Loop Hot Water Pump VFD Hertz x x
PriHWPumpVFDKw Primary Loop Hot Water Pump VFD Kw Reading x x
PriHWPumpVFDKwh Primary Loop Hot Water Pump VFD KWH Accumulation x x
PriHWPumpVFDReady Primary Loop Hot Water Pump VFD Drive Ready
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 15
PriHWPumpVFDReset Primary Loop Hot Water Pump VFD Fault Reset x
PriHWPumpVFDRpm Primary Loop Hot Water Pump VFD RPM x x
PriHWPumpVFDSpd Primary Loop Hot Water Pump VFD Speed Command x x
PriHWPumpVFDStatus Primary Loop Hot Water Pump VFD Status x x
PriHWReturnTemp Primary Hot Water Return Temp x x
PriHWSupplySp Primary Hot Water Supply Setpoint x
PriHWSupplyTemp Primary Hot Water Supply Temp x x
RadiantValve Radiant Valve Command x x
ReheatStage1 Reheat Stage 1 x x
ReheatStage2 Reheat Stage 2 x x
ReheatValve Reheat Valve Command x x
ReheatValveStatus Reheat Valve Status x x
ReturnAirCO2 Return Air CO2 Sensor x x
ReturnAirDuctStaticPress Return Duct Static Pressure x x
ReturnAirEnthalpy Return Air Enthalpy x x
ReturnAirFlow Return Air Flow Reading x x
ReturnAirHumidity Return Air Humidity x x
ReturnAirSmokeDetAlarm Return Air Smoke Detector Alarm x x
ReturnAirTemp Return Air Temperatature x x
ReturnFan Return Fan Command x x
ReturnFanAmps Return Fan Amps x x
ReturnFanCFMSp Return Fan CFM Setpoint x
ReturnFanFailure ReturnFanFailure x x
ReturnFanStatus Return Fan Status x x
ReturnFanVFDAmps Return Fan VFD Amps x x
ReturnFanVFDFault Return Fan VFD Fault x x
ReturnFanVFDFb Return Fan VFD Feedback x x
ReturnFanVFDHOA Return Fan VFD HOA Status x x
ReturnFanVFDHz Return Fan VFD Hertz x x
ReturnFanVFDKw Return Fan VFD Kw Reading x x
ReturnFanVFDKwh Return Fan VFD KWH Accumulation x x
ReturnFanVFDReady Return Fan VFD Drive Ready x x
ReturnFanVFDReset Return Fan VFD Fault Reset x
ReturnFanVFDRpm Return Fan VFD RPM x x
ReturnFanVFDStatus Return Fan VFD Status x x
ReturntAirCO2 Return Air CO2 x x
Safeties System Safeties x
Sec13SteamValve Secondary 1/3 Steam Valve Command x x
Sec23SteamValve Secondary 2/3 Steam Valve Command
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 16
SecCHWBypassValve Secondary Chilled Water Loop Water Bypass Valve Command x x
SecCHWBypassValveStatus Secondary Chilled Water Loop Water Bypass Valve Status x x
SecCHWPump Secondary Loop Chilled Water Pump Command x x
SecCHWPumpAmps Secondary Loop Chilled Water Pump Amps x x
SecCHWPumpFailure Secondary Chilled Water Loop Pump Failure x x
SecCHWPumpStatus Secondary Loop Chilled Water Pump Status x x
SecCHWPumpVFDAmps Secondary Loop Chilled Water Pump VFD Amps x x
SecCHWPumpVFDCmd Secondary Loop Chilled Water Pump VFD Command x x
SecCHWPumpVFDFault Secondary Loop Chilled Water Pump VFD Fault x x
SecCHWPumpVFDFb Secondary Loop Chilled Water Pump VFD Feedback x x
SecCHWPumpVFDHOA Secondary Loop Chilled Water Pump VFD HOA Status x x
SecCHWPumpVFDHz Secondary Loop Chilled Water Pump VFD Hertz x x
SecCHWPumpVFDKw Secondary Loop Chilled Water Pump VFD Kw Reading x x
SecCHWPumpVFDKwh Secondary Loop Chilled Water Pump VFD KWH Accumulation x x
SecCHWPumpVFDReady Secondary Loop Chilled Water Pump VFD Drive Ready x x
SecCHWPumpVFDReset Secondary Loop Chilled Water Pump VFD Fault Reset x
SecCHWPumpVFDRpm Secondary Loop Chilled Water Pump VFD RPM x x
SecCHWPumpVFDSpd Secondary Loop Chilled Water Pump VFD Speed Command x x
SecCHWPumpVFDStatus Secondary Loop Chilled Water Pump VFD Status x x
SecHWBypassValve Secondary Hot Water Loop Water Bypass Valve Command x x
SecHWBypassValveStatus Secondary Hot Water Loop Water Bypass Valve Status x x
SecHWPump Secondary Loop Hot Water Pump Command x x
SecHWPumpAmps Secondary Loop Hot Water Pump Amps x x
SecHWPumpFailure Secondary Hot Water Loop Pump Failure x x
SecHWPumpStatus Secondary Loop Hot Water Pump Status x x
SecHWPumpVFDAmps Secondary Loop Hot Water Pump VFD Amps x x
SecHWPumpVFDCmd Secondary Loop Hot Water Pump VFD Command
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 17
SecHWPumpVFDFault Secondary Loop Hot Water Pump VFD Fault x x
SecHWPumpVFDFb Secondary Loop Hot Water Pump VFD Feedback x x
SecHWPumpVFDHOA Secondary Loop Hot Water Pump VFD HOA Status x x
SecHWPumpVFDHz Secondary Loop Hot Water Pump VFD Hertz x x
SecHWPumpVFDKw Secondary Loop Hot Water Pump VFD Kw Reading x x
SecHWPumpVFDKwh Secondary Loop Hot Water Pump VFD KWH Accumulation x x
SecHWPumpVFDReady Secondary Loop Hot Water Pump VFD Drive Ready x x
SecHWPumpVFDReset Secondary Loop Hot Water Pump VFD Fault Reset x
SecHWPumpVFDRpm Secondary Loop Hot Water Pump VFD RPM x x
SecHWPumpVFDSpd Secondary Loop Hot Water Pump VFD Speed Command x x
SecHWPumpVFDStatus Secondary Loop Hot Water Pump VFD Status x x
SetpointDiff The temperature change required for heating/cooling to start x
SmokeDetAlarm Smoke Detector Alarm x x
StandbyCoolSp Standby Cool Setpoint x
StandbyHeatSp Standby Heat Setpoint x
StatusMode Unit Status Mode x
SteamValve Steam Valve Command x x
SupplyAirDuctStaticPress Supply Duct Static Pressure x x
SupplyAirDuctStaticPressSp Supply Duct Static Pressure Setpoint x
SupplyAirFlow Supply Air Flow Reading x x
SupplyAirHiLimitPress Supply Air Hi-Limit Pressure Alarm x x
SupplyAirRH Supply Air Relative Humidity x x
SupplyAirSmokeDetAlarm Supply Air Smoke Detector Alarm x x
SupplyAirTemp Supply Air Temperature x x x
SupplyAirTemperingSp Supply Air Temperature Setpoint x
SupplyFan Supply Fan Command x x
SupplyFanAmps Supply Fan Amps x x
SupplyFanCFMSp Supply Fan CFM Setpoint x
SupplyFanFailure Supply Fan Failure x x
SupplyFanStatus Supply Fan Status x x
SupplyFanVFDAmps Supply Fan VFD Amps x x
SupplyFanVFDCmd Supply Fan VFD Command x x
SupplyFanVFDFault Supply Fan VFD Fault x x
SupplyFanVFDFb Supply Fan VFD Feedback x x
SupplyFanVFDHOA Supply Fan VFD HOA Status x x
SupplyFanVFDHz Supply Fan VFD Hertz x x
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 18
SupplyFanVFDKw Supply Fan VFD Kw Reading x x
SupplyFanVFDKwh Supply Fan VFD KWH Accumulation x x
SupplyFanVFDReady Supply Fan VFD Drive Ready x x
SupplyFanVFDReset Supply Fan VFD Fault Reset x
SupplyFanVFDRpm Supply Fan VFD RPM x x
SupplyFanVFDSpd Supply Fan VFD Speed Command x x
SupplyFanVFDStatus Supply Fan VFD Status x x
SystemEnable Master System Enable (Maintenance Switch) x
TerminalLoad Terminal Load x
TerminalLoadAverage Average Load from Associated Terminals x
UHCmd Unit Heater Command x x
UHValve Unit Heater Valve Command x x
UnoccupiedCoolCall Unoccupied Call for Cool x x
UnoccupiedCoolSp Unoccupied Cool Setpoint x
UnoccupiedHeatCall Unoccupied Call for Heat x x
UnoccupiedHeatSp Unoccupied Heat Setpoint x
WarmUpSetpoint Warmup Mode Setponit x
ZoneCO2 Zone CO2 x
ZoneRH Zone Relative Humidity x x
ZoneTemp Zone Temperature x x x
ZoneTempAverage Average Zone Temperature x x
ZoneTstatCallForHeat Zone Tstat Calling for Heat x x
6.2. STANDARD EQUIPMENT NAMING CONVENTION LIST
Equipment Name Description
AC AC Unit
ACCU Air Cooled Condensing Unit
AHU Air Handler Unit
BLR Boiler
CRACU Computer Room AC Unit
CUH Cabinet Unit Heater
DC Dust Collector
DH Dehumidifier
EnergyMeter Energy Meter
FCU Fan Coil Unit
FTR Finned Tube Radiation
HC Heating Coil
HRU Heat Recovery Unit
HX Heat Exchanger
MAU Makeup Air Unit
RTU Roof Top Unit
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 19
UH Unit Heater
6.3. GRAPHICAL USER INTERFACE EXAMPLES
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 20
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 21
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 22
20180717 - NAVFAC MIDLANT PWD-Maine – ICS Standard 23
| 1. GENERAL |
| 2. NETWORK ADDRESSING |
| 2.1. IP |
| 2.2. BACNET |
| 3. POINT AND OBJECT CONFIGURATION |
| 3.1. POINT AND EQUIPMENT NAMING |
| 3.2. POINT FACETS |
| 3.2.1. INTEGERS |
| 3.2.2. ONE DECIMAL |
| 3.2.3. TWO DECIMALS |
| 3.2.4. THREE DECIMALS |
| 3.2.5. BOOLEAN VALUES |
| 3.2.6. ENUMERATED VALUES |
| 3.3. NIAGARA STATION NAMING |
| 3.3.2. LOCATION EXAMPLES |
| 3.3.3. BUILDING PREFIX EXAMPLES |
| 3.3.4. BUILDING NUMBERS |
| 3.3.7. STATION NAME EXAMPLES |
| 3.4. ALARMS |
| 3.4.1. EXTENSION CONFIGURATION |
| 3.5. HISTORIES |
| 3.5.1. NAMING |
| 3.5.1.2. BUILDING PREFIX EXAMPLES |
| 3.5.1.3. BUILDING NUMBER |
| 3.5.1.4. EQUIPMENT TYPE |
| 3.5.1.5. EQUIPMENT INSTANCE |
| 3.5.1.6. POINT NAME |
| 3.5.1.7. HISTORY NAMING EXAMPLES |
3.6. SPECIAL CHARACTERS
| 4. GRAPHICAL USER INTERFACE |
| 4.3. EXPORT TAGS |
| 5. USER ACCESS |
| 5.1. EXISTING INSTALLATIONS |
| 5.2. NEW INSTALLATIONS |
| 6. APPENDICES |
| 6.1. STANDARD POINT NAMING CONVENTION LIST |
| 6.2. STANDARD EQUIPMENT NAMING CONVENTION LIST |
| 6.3. GRAPHICAL USER INTERFACE EXAMPLES |