Attach 3_ Tech Specs DIV 26 1659482.pdf
PDF 76 KB Posted
- Attached to
- Replace Power Plant UPS Federal contract opportunity
- Solicitation number
- N4008520B2527
About this file
This technical specification document outlines requirements for replacing an uninterruptible power supply (UPS) system at the Portsmouth Naval Shipyard. The project requires providing all labor, equipment, materials, transportation, and supervision to install a new UPS. The specification details the system components, operational modes, technical requirements, and performance testing for the UPS. It also addresses installation procedures and commissioning activities. Key information includes specifications for a redundant UPS system rated at 30kVA to support data processing equipment loads. The system is to include batteries capable of delivering 125% of rated load for 45 minutes. The Navy's Naval Facilities Engineering Command is the contracting agency.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attach 2_ PNSYDIV1 Specs 1282019.pdf | ||
| Attach 8_ Electrical Systems and Construction Standards PNSY.pdf | ||
| Attach 4_ Submittal Reg 1659482.pdf | ||
| Attach 1_ Bid Form 1659482.pdf | ||
| Attach 6_ eOMSI WORKBOOK 1659482 REPLACE POWER PLANT UPS.pdf | ||
| N40085-20-B-2527.pdf | ||
| Attach 5 1659482_B72_DBB Replace Power Plant UPS drawings signed.pdf | ||
| Attach 7_ ISRL 1659482 REPLACE POWER PLANT UPS.pdf | ||
| encl a-SOW Replace Power Plant UPS B72 1659482.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 26 33 53 Page 1
SECTION TABLE OF CONTENTS
DIVISION 26 - ELECTRICAL
SECTION 26 33 53
STATIC UNINTERRUPTIBLE POWER SUPPLY (UPS)
05/19
PART 1 GENERAL
1.1 REFERENCES
1.2 DEFINITIONS
1.3 SUBMITTALS
1.4 OPERATION AND MAINTENANCE MANUALS
1.4.1 Additions to UPS Operation and Maintenance Manuals
1.5 QUALITY ASSURANCE
1.5.1 UPS Drawings
1.5.2 UPS Installation
1.5.3 Work Plan
1.5.4 Performance Test Plan
1.5.5 Performance Test Report
1.5.6 Regulatory Requirements
1.5.6.1 Reference Standard Compliance
1.5.7 Standard Products
1.5.7.1 Material and Equipment Manufacturing Date
1.6 DELIVERY AND STORAGE
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
2.2 MODES OF OPERATION
2.2.1 Normal
2.2.2 Battery - Emergency Operation (Loss or deviation of AC Input Power)
2.2.3 Failure of AC Input Power to Return
2.2.4 Recharge
2.2.5 Transfer to Static Bypass AC Power Source
2.2.6 Transfer to Inverter
2.2.7 Off-Battery (Battery Maintenance)
2.3 GENERAL UPS SYSTEM COMPONENTS AND FABRICATION
2.3.1 Semiconductor Fusing
2.3.2 EMI/RFI Protection
2.3.3 Internal Wiring
2.3.4 Internal Assembly
2.3.5 Cable Lugs and Terminations
2.3.5.1 Cable Lugs
2.3.5.2 Terminations
2.3.6 Cabinets
2.3.6.1 Cabinet Finish
2.3.6.2 Factory Applied Finish
2.3.6.3 Drawout Assemblies
2.3.7 Manufacturer's Nameplates
2.3.8 Field Fabricated Nameplates
2.3.9 Safety
2.3.9.1 Remote Emergency Power Off (REPO) Switch
SECTION 26 33 53 Page 2
2.4 TECHNICAL REQUIREMENTS UPS SYSTEM RATINGS
2.4.1 UPS SYSTEM LOAD PROFILE
2.4.2 System Requirements
2.4.3 Battery Capacity
2.4.4 Static Switch
2.4.5 Short Circuit Withstand Rating
2.4.6 AC Input
2.4.7 AC Output
2.4.8 Transient Response
2.4.8.1 Voltage Transients
2.4.8.2 Frequency
2.5 UPS MODULE
2.5.1 General Description
2.5.1.1 Interchangeability
2.5.1.2 Rectifier/Charger Unit
2.5.1.2.1 Input Protective Device
2.5.1.2.2 Power Walk-In
2.5.1.2.3 Sizing
2.5.1.2.4 AC Input Current Limiting
2.5.1.2.5 Battery Charging Current
2.5.1.2.6 DC Ripple (Output Filter)
2.5.1.2.7 Battery Isolation Protective Device
2.5.2 Inverter Unit
2.5.2.1 Output Protective Device
2.5.2.2 Output Transformer
2.5.3 External Protection
2.5.4 Internal Protection
2.5.5 Battery Protection
2.5.6 Parallel Operation
2.6 STATIC BYPASS TRANSFER CIRCUIT
2.6.1 Construction
2.6.2 Automatic Uninterrupted Transfer
2.6.3 Interrupted Transfer
2.6.4 Manual Load Transfer
2.6.5 Automatic Uninterrupted Forward Transfer
2.6.6 Forced Transfer
2.6.7 Overload Ratings
2.6.8 System Protection
2.7 DISPLAY,CONTROLS AND ALARMS
2.7.1 Module Meters
2.7.1.1 Meter Construction
2.7.2 Module Controls
2.7.3 Module or System Alarm Indicators
2.7.4 Module Emergency OFF Button
2.8 REMOTE MONITORING PANEL
2.8.1 Audible Alarm
2.9 COMMUNICATIONS AND DATA ACQUISITION
2.9.1 Emergency Control Contacts
2.10 TEMPERATURE CONTROL
2.10.1 General
2.10.2 Blower Power Source
2.10.3 Temperature Sensors
2.11 BATTERY SYSTEM
2.11.1 General
2.11.2 Battery Cabinet
2.11.3 Battery Rack
SECTION 26 33 53 Page 3
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Control Cable
3.1.2 Grounding
3.1.2.1 Grounding Conductor Title
3.1.2.2 Separately Derived
3.1.3 UPS Output Conductors
3.1.4 DC Power Conductors
3.1.5 Conduit Entries
3.1.6 Battery Rack Assembly
3.1.7 Battery Cabinet Assembly
3.1.8 Battery Installation
3.2 FIELD QUALITY CONTROL
3.2.1 Installation Preparation
3.2.2 Initial Inspection and Tests
3.2.3 Performance Tests
3.2.3.1 UPS Unit Performance Tests
3.3 DEMONSTRATION
3.3.1 Instructing Government Personnel
3.4 FINAL ADJUSTMENTS
3.5 NAMEPLATE MOUNTING
-- End of Section Table of Contents --
SECTION 26 33 53
STATIC UNINTERRUPTIBLE POWER SUPPLY (UPS)
05/19
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2017; Errata 2017) Standard for
Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17)
National Electrical Code
NFPA 70E (2018; TIA 18-1; TIA 81-2) Standard for
Electrical Safety in the Workplace
UNDERWRITERS LABORATORIES (UL)
UL 1778 (2014; Reprint Sep 2017) UL Standard for Safety Uninterruptible Power Systems
1.2 DEFINITIONS
SECTION 26 33 53 Page 4
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in
IEEE 100.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation.
SD-1 Shop Drawings
UPS Drawings; G
UPS Installation; G
SD-2 Test Reports
Work Plan; G
SD-3 Manufacturer's Field Reports
Initial Inspection and Tests; G
Performance Tests; G
Performance Test Plan; G
Performance Test Report; G
SD-4 Operation and Maintenance Data
UPS Operation and Maintenance; G
SD-5 Closeout Submittals
Installation; G
1.4 OPERATION AND MAINTENANCE MANUALS
1.4.1 Additions to UPS Operation and Maintenance Manuals
In addition to requirements of above SD include the followings on the actual UPS system provided:
a. An outline drawing, front, top, and side views.
b. Prices for spare parts and supply list.
c. Routine and field acceptance test reports.
d. Date of Purchase.
e. Corrective maintenance procedures.
1.5 QUALITY ASSURANCE
The manufacturer must have a documented quality assurance program including:
a. Inspections of incoming parts, modular assemblies and final product.
SECTION 26 33 53 Page 5
b. Final test procedure for the product including proof of performance specifications.
c. The on-site test procedure includes an inspection of controls and indicators after installation of the equipment.
d. Equipment shall be UL Listed.
1.5.1 UPS Drawings
Drawings are to include the following: Detail drawings consisting of a complete list of equipment and materials, manufacturer's descriptive and technical literature, battery sizing calculations per IEEE 485, installation instructions, single-line diagrams, elevations, layout drawings, and details required to demonstrate that the system has been coordinated and will function properly as a unit.
a. One-line diagram.
b. Outline drawings including front elevation, section views, footprints, and overall dimensions.
c. Manufacturer's descriptive and technical literature.
d. Markings and NEMA nameplate data.
e. Battery sizing calculations per IEEE 485.
f. Wiring and control diagrams with terminals identified, and indicating prewired interconnections between items of equipment and interconnection between the items.
g. Complete list of materials and equipment covering major components.
Ensure the bill of material and the schematic have a direct correlation between items in order to easily identify the various components.
h. Details required to demonstrate that the system has been coordinated and will function properly as a unit.
1.5.2 UPS Installation
Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation. Wiring diagrams are to identify circuit terminals and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment. Drawings are to indicate adequate clearance for operation, maintenance, and replacement of operating equipment devices. Submittals include the nameplate data, size, and capacity. Submittals also include applicable federal, military, industry, and technical society publication references.
1.5.3 Work Plan
Submit schedules of dates for installation, field tests, and operator training for the UPS system.
SECTION 26 33 53 Page 6
1.5.4 Performance Test Plan
Submit test plans and procedures at least 15 calendar days prior to the start of field tests. Provide detailed description and dates and times scheduled for performance of tests, and detailed description of test procedures and setups of the tests to be conducted to ensure the UPS meets the performance specification.
1.5.5 Performance Test Report
Submit report of test results as specified by paragraph entitled "Performance Tests" within 15 calendar days after completion of tests.
Field test reports are to be signed by an official authorized to certify on behalf of the UPS manufacturer that the system meets specified requirements in accordance with the requirements set forth in paragraph entitled "Performance Tests". Provide test reports in in booklet form tabulating measurements performed, upon completion and testing of the installed system. Reports are to state the Contractor's name and address, the name of the project and location, and list the specific requirements which are being certified.
1.5.6 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.5.8.1 Reference Standard Compliance
Where equipment or materials are specified to conform to industry and technical society reference standards of the organizations such as American National Standards Institute (ANSI), American Society for Testing and Materials (ASTM), National Electrical Manufacturers Association (NEMA), Underwriters Laboratories (UL), and Association of Edison Illuminating Companies (AEIC), submit proof of such compliance. The label or listing by the specified organization will be acceptable evidence of compliance.
1.5.9 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
SECTION 26 33 53 Page 7
d. The service organization is to be, in the opinion of the Contracting
Officer, reasonably convenient to the site.
e. Provide new parts and materials comprising the UPS system from the current manufacture, of a high grade and free of defects and imperfections, and has not been in prior service except as required during aging and factory testing.
1.5.9.1 Material and Equipment Manufacturing Date
Products manufactured more than 6 months prior to date of delivery to site are not acceptable.
1.6 DELIVERY AND STORAGE
Protect equipment placed in storage from humidity and temperature variations, moisture, water intrusion, dirt, airborne corrosives, or other contaminants.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide continuous duty, three-phase, solid state, on-line double conversion reverse transfer static UPS(s). The UPS by means of solid state conversion techniques, must provide continuous regulated AC power to its output terminals, while operating from an input power source, cabinet or rack-mounted direct current (DC) storage battery or other approved means. The performance of the UPS must not be degraded when operating without a system battery, provided the input AC source is within tolerance. Provide an UPS system that conforms to UL 1778 and consists of UPS module, battery system, battery protective device, static bypass transfer switch, controls and monitoring, system protective devices, means of isolating the UPS system from the critical load, and remote monitoring interfaces. Connect input ac power the normal source ac input of the UPS module. Connect alternate power source bypass. Connect battery to the dc input of the UPS module through the battery protective device. The following configuration is used:
2.1.1 Redundant System.
(1) Split Bus System. Provide two parallel redundant systems that may be operated separately or through a tie breaker for increased redundancy. Each UPS system on either side of the split bus is able to support the total critical load.
2.2 MODES OF OPERATION
2.2.1 Normal
The UPS module rectifier/charger must convert the incoming ac input power to dc power for the inverter and for float charging the battery. The inverter continuously converts the dc power to ac power to supply the critical load. The inverter output must synchronize with the bypass ac power source, provided that the bypass ac power source is within the specified voltage and frequency range.
2.2.2 Battery - Emergency Operation (Loss or deviation of AC Input Power)
Whenever the ac input power source deviates from the specified tolerances
SECTION 26 33 53 Page 8 including complete failure, the inverter must draw power from the battery system and supply AC power to the critical load without any interruption or switching transient. The battery system must supply power to the inverter for the specified protection time or until return of ac input source. Provide an audible alarm to indicate the UPS is on battery and provide provisions for a remote alarm signal to be sent via the communication network and a relay output, allowing startup of a secondary power source or orderly shutdown of the critical load.
2.2.3 Failure of AC Input Power to Return
If the ac input power fails to return before the battery voltage reaches the discharge limit, then the UPS system must disconnect from the critical load to safeguard the battery.
2.2.4 Recharge
Upon restoration of normal power to the UPS unit, the input converter and output inverter must simultaneously recharge the batteries and provide regulated power to the critical load.
2.2.5 Transfer to Static Bypass AC Power Source
When the UPS controller senses an overload, two or more inverter shutdown signals or degradation of the inverter output, the static bypass switch automatically transfers the critical load from the inverter output to the bypass ac power source without an interruption of power only if the connected load exceeds the capacity of the remaining on-line modules. If the static bypass ac power source is outside of specified tolerance limits, the UPS and the critical load shut down. Transfer to static bypass can also be done manually (requested bypass). Transfer to bypass does not take place under these conditions: 100% stepload; and, loss or return of input power, momentary sags, surges or spikes on the input to the UPS.
2.2.6 Transfer to Inverter
Provide a static bypass switch that is capable of automatically transferring the load back to the inverter output after the inverter overload condition has returned to normal conditions. Transfer only occurs once the two sources are synchronized. UPS system logic is to monitor the number of retransfer's within any one-hour period and is to allow 1 to 3 transfers in order to prevent cyclical transfers caused by overloads.
2.2.7 Off-Battery (Battery Maintenance)
Provide a battery protective device which disconnects the battery from the rectifier/charger and inverter for maintenance. The device may be located external to the UPS cabinet. The UPS module continues to function and meet the performance criteria specified except for the battery back-up time function.
2.3 GENERAL UPS SYSTEM COMPONENTS AND FABRICATION
2.3.1 Semiconductor Fusing
Protect power semiconductors with fast-acting fuses to prevent cascaded or sequential semiconductor failures. Bolt fuses at both ends to bus bars to ensure mechanical and electrical integrity. Indicator lamp or display panel denoting blown fuse conditions must be readily observable by the operator without removing panels or opening cabinet doors.
SECTION 26 33 53 Page 9
2.3.2 EMI/RFI Protection
Provide an UPS that complies with and is labeled compliant, with FCC Part 15, Subclass B, Class A.
2.3.3 Internal Wiring
Wiring practices, materials, and coding must be in accordance with the requirements of NFPA 70, OSHA, UL 1778, and other applicable standards.
Protect wire runs in a manner which separates power and control wiring.
Provide control cabling that is at least No. 16 AWG extra-flexible stranded copper. Logic-circuit wiring may be smaller. Provide ribbon cables that are at least minimum No. 22 AWG. Provide control wiring with permanently attached wire numbers.
2.3.4 Internal Assembly
The printed circuit board (PCB) subassemblies are to be mounted in pull-out swing-out trays where feasible. Provide cable connections to the trays that are sufficiently long to allow easy access to all components.
Where not feasible to mount PCB subassemblies in pull-out or swing-out trays, then mount them firmly mounted inside the enclosure. Monitor every PCB subassembly. Include self-test and diagnostic circuitry in the logic circuits such that a fault can be isolated down to the PCB subassembly level. When used, control logic cards are to have test points or logic indicators on the front edge of the control logic card and be labeled.
2.3.5 Cable Lugs and Terminations
2.3.5.1 Cable Lugs
Provide appropriate compression type lugs or pre-drilled bus bars on all ac and dc power connections to the UPS system and battery as required.
Aluminum or bare copper cable lugs are not suitable.
2.3.5.2 Terminations
Supply terminals for making power and control connections. Provide terminal block for field wiring terminals. Provide terminal blocks that are the heavy-duty, strap-screw type or screw terminals that are integrated into removable plugs. Locate terminal blocks for field wiring in one place in each module. Extend control wiring to the terminal block location. Any terminal point is limited to land a maximum of two wires.
Where control wiring is attached to the same point as power wiring, Provide a separate terminal where control wiring is attached to the same point as power wiring. If bus duct is used, provide bus stubs where bus duct enters cabinets.
2.3.6 Cabinets
Install the UPS system in cabinets of heavy-duty structure meeting the NEMA PE 1 standards for floor mounting. Provide a structurally adequate UPS module that can be forklift handled and lifted. Cabinets shall be secured to the floor. Provide the UPS module cabinet with hinged and key lockable doors on the front only and with assemblies and components accessible from the front. Provide dead-front construction behind the door for those UPS module cabinets that are not lockable.
Operating controls are to be located outside the locked doors. Install input, output, and battery cables through the top or bottom of the cabinet.
SECTION 26 33 53 Page 10
2.3.6.1 Cabinet Finish
Provide an equipment cabinet that is cleaned, primed and painted in the manufacturer's standard colors, in accordance with accepted industry standards. Cabinets are to be labeled in accordance with NFPA 70 and
NFPA 70E.
2.3.6.2 Factory Applied Finish
Provide electrical equipment with a factory-applied painting systems which, as a minimum, meets the requirements of NEMA 250 corrosion-resistance test.
2.3.7 Manufacturer's Nameplates
Provide a nameplate for each item of equipment bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.3.8 Field Fabricated Nameplates
ASTM D709. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified or as indicated on the drawings. Provide an inscription on each nameplate that identifies the name of the item, calculated short circuit rating with date, and source of power e.g. 'Panel A in Electrical Room 103'. Provide nameplates that are made of melamine plastic, 3 mm 0.125 inch thick, black with white center core. Provide the nameplate with a surface that is matte finished and that has square corners. Accurately align lettering and engrave into the core.
Provide nameplates that are at least 25 by 65 mm 1.0 by 2.5 inches with a minimum lettering size of 6.35 mm 0.25 inch high normal block style.
2.3.9 Safety
Provide UPS with instruction plates including warnings and cautions, suitably located, and describing any special or important procedures to be followed in operating and servicing the equipment. Provide control panel displays, which also provide warning messages prior to performing a critical function.
2.3.9.1 Maintenance Isolation
All energized terminals, both AC and DC, and control voltage exposed points are to be insulated or enclosed to ensure the safety of maintenance personnel. Provide the system with the ability to isolate the static switch to enable repair when the UPS is bypassed.
2.3.9.2 Remote Emergency Power Off (REPO) Switch
Provide a remote emergency power off switch that is separate from the UPS. Provide a red, pushbutton with a cover with a label indicating "UPS Emergency Power Off". The switch disconnects all breakers or contactors including battery, input, output, and bypass breakers when activated.
2.4 TECHNICAL REQUIREMENTS UPS SYSTEM RATINGS
Unless stated otherwise, the parameters listed are under full output load over the range of0.9 lagging power factor to 0.9 leading power factor, with batteries fully charged and floating on the dc bus and with nominal input voltage.
SECTION 26 33 53 Page 11
2.4.1 UPS SYSTEM LOAD PROFILE
Provide an UPS system that is compatible with the load characteristics defined in the LOAD PROFILE below and load configuration. The UPS system is to provide compensation for UPS/load interaction problems resulting from nonlinear loads or transformer and motor inrush.
LOAD PROFILE
Type of load:
Data processing equipment. Size of load: 30 KVA, 120 voltage, 0.9 power factor.
Load switching pattern: unswitched.
Steady-state characteristics: 0.9 lagging power factor.
2.4.2 System Requirements
The UPS is to support and maintain full battery charging under the following conditions: indicated environmental conditions, AC input voltage range, air filters blocked up to 50% and a single failed fan. The UPS size and configuration is indicated below.
The parallel system is sized for 30 kVA per each UPS.
2.4.3 Battery Capacity
Discharge time to end voltage: 45 minutes, at 25 degrees C 77 degrees F. Provide a battery that is capable of delivering 125 percent of full rated UPS kW load at 0.9 power factor at initial start-up.
2.4.4 Static Switch
70 amperes (continuous duty)
2.4.5 Short Circuit Withstand Rating
Braced for at least 35,000 amperes symmetrical interrupting capacity.
2.4.6 AC Input
a. Voltage 480 volts line-to-line.
b. Number of phases: Three-phase + ground configuration.
c. Voltage Range: Plus 10 percent, minus 15 percent nominal (no battery discharge), without affecting battery float voltage or output voltage.
d. Frequency: 60 Hz, plus or minus 5 percent.
e. Power walk-in: 20 percent to 100 percent input current over 10 to 15 seconds.
f. Total harmonic current distortion (THD) reflected into the primary line: 10 percent maximum at full load.
g. Sub-cycle magnetizing inrush: 2 to 3 times full load current for
SECTION 26 33 53 Page 12 modules without an isolation transformer.
h. Input surge protection: per IEEE C62.41.1 and IEEE C62.41.2, meeting IEEE C62.41 requirement of Category B3 6kV, 100k Hz ring wave and 6kV, combined wave.
i. Input power factor: Lagging from 1-100 percent load.
2.4.7 AC Output
a. Voltage 480 volts line-to-line prior to transformer.
b. Number of phases: Three-phase + ground configuration.
c. Voltage regulation:
(1) Balanced load: Plus or minus 1.0 percent.
(2) 50 percent load imbalance, phase-to-phase: Plus or minus 2 percent.
(3) 100 percent load imbalance, phase-to-phase Plus or minus 3 percent.
(4) Voltage drift: Plus or minus 1 percent over any 30 day interval (or length of test) at stated ambient conditions found in paragraph Environmental Conditions.
d. Voltage adjustment: Plus or minus 5 percent.
e. Frequency: 60 Hz.
f. Frequency regulation: Plus or minus 0.1 percent, when on internal oscillator. Internal oscillator is to be temperature compensated.
g. Frequency drift: Plus or minus 0.1 percent over any 24 hour interval (or length of test) at stated ambient conditions when on internal oscillator.
h. Harmonic content (RMS voltage): Provide a system that meets the following voltage THD levels: maximum of 4% RMS total, 2 percent total with 100 percent on any single harmonic (linear load) and 5 percent RMS total for up to 100 percent nonlinear load.
i. Load power factor operating range (without derating): 0.9 leading to
0.9 lagging.
j. Phase angle displacement/imbalance:
(1) Balanced load: 120 degrees plus or minus 0.5 degree of bypass input.
(2) 50 percent load imbalance phase-to-phase: 120 degrees plus or minus 3 degrees of input.
k. Inverter overload capability (at full voltage with plus or minus 2 percent regulation) (excluding battery):
(1) 125 percent load for 10 minutes.
(2) 150 percent load for 60 seconds.
(3) Fault clearing. Provide an UPS that is able to maintain output
SECTION 26 33 53 Page 13 current during a fault condition for 20 cycles if bypass is unavailable or 1 cycle with bypass available. If the fault is not cleared and a bypass is available, the UPS is to transfer to bypass without interruption to clear the fault.
l. Bypass Overload Capability.
150 percent load for 15 seconds.
2.4.8 Transient Response
2.4.8.1 Voltage Transients
a. 100 percent load step: Plus or minus 5 percent.
b. Loss or return of ac input: Plus or minus [1][5] percent.
c. Automatic transfer of load from UPS to bypass: Plus or minus 1 percent.
d. Manual retransfer of load from bypass to UPS: Plus or minus 5 percent.
e. Response time: Recovery to 1 percent of nominal within 20 milliseconds where there was a maximum deviation from nominal system output of volts plus or minus 5 percent.
2.4.8.2 Frequency
a. Transients: Plus or minus 0.6 Hz maximum.
b. Slew Rate: under all conditions of operation, provide 0.4 to 1.0 Hz per second.
2.5 UPS MODULE
Rectifier/charger unit is to minimize ripple current and voltage supplied to the battery; the ripple voltage into the battery is not to exceed 1 percent RMS of the float voltage. Ensure the AC ripple voltage of the rectifier DC output does not exceed 0.5 percent of the float voltage.
2.5.2 General Description
UPS module consists of a rectifier/charger unit and a 3-phase inverter unit with their associated transformers, synchronizing equipment, protective devices, surge suppression, and accessories as required for operation.
2.5.2.1 Interchangeability
The subassemblies in one UPS module are to be interchangeable with the corresponding modules within the same UPS, and from one UPS system to another of identical systems.
2.5.2.2 Rectifier/Charger Unit
Provide a solid state rectifier/charger unit that converts alternating current to direct current, and provides regulated direct current to the dc bus, supplying power to the inverter and charging the battery plant.
2.5.2.2.1 Input Protective Device
SECTION 26 33 53 Page 14
Provide the rectifier/charger unit with an input protective device. Size the protective device to accept simultaneously the full-rated load and the battery recharge current. Provide a protective device that is capable of shunt tripping and has an amperes symmetrical interrupting rating of 35,000. Provide the protective device with an under-voltage release to open automatically when the control voltage is lost.
2.5.2.2.3 Power Walk-In
Protect the rectifier/charger unit with a power walk-in feature such that when ac power is returned to the ac input bus, the total initial power requirement will not exceed 20 percent of the rated full load current.
This demand is to gradually increase to 100 percent of the rated full load current plus the battery charging current over the specified time interval.
2.5.2.2.4 Sizing
Size the rectifier/charger unit for the following two simultaneous operating conditions:
a. Supplying the full rated load current to the inverter.
b. Recharging a fully-discharged battery to 90 percent of rated ampere-hour capacity within ten times the discharge time after normal ac power is restored.
2.5.2.2.5 AC Input Current Limiting
Provide a circuit on the rectifier/charger to limit AC input current to an adjustable level of 100 percent to 125 percent with a factory setting at 100 percent.
2.5.2.2.6 Battery Charging Current
a. Primary current limiting: Battery-charging current is to be voltage regulated and current limited. Provide a separately adjustable battery-charging current limit that is adjustable from 1 percent to 20 percent of the maximum discharge current. Set the limit at the factory to 10 percent. After the battery is recharged, the rectifier/charger unit maintains the battery at full float charge until the next operation under input power failure. Battery charger is capable of providing equalizing charge to the battery.
2.5.2.2.7 DC Ripple (Output Filter)
Rectifier/charger unit is to minimize ripple current and voltage supplied to the battery; the ripple voltage into the battery is not to exceed 1 percent RMS of the float voltage. Ensure the AC ripple voltage of the rectifier DC output does not exceed 0.5 percent of the float voltage.
2.5.2.2.9 Battery Isolation Protective Device
Provide the module or external battery system with a dc protective device to isolate the module from the battery system. The protective device size and interrupting rating are as required by system capacity and is to incorporate the trip required by circuit design. Provide the protective device with a provision for locking in the "off" position.
2.5.3 Inverter Unit
Provide a solid-state inverter with sinusoidal output deriving its power from the dc bus (rectifier or battery source) and providing ac power within specified limits to the critical load. Inverter is to utilize
SECTION 26 33 53 Page 15 microprocessor controlled solid state Pulse Width Modulation (PWM) controlled insulated gate bipolar transistor (IGBT) power transistor technology to shape the ac output.
Provide an inverter that is able to sustain an overload as specified across its output terminals. The inverter is to remain on and continue to operate within rated parameters, with inverse-time overload shutdown protection. If the overload condition persists beyond the rated parameters of the inverter, the load is to be transferred to the bypass source where the inverter disconnects automatically from the critical load bus. If the bypass source is not available and the overload/fault condition continues, the inverter is to current limit for the time as determined by the manufacturer and then shut down to protect the internal components.
2.5.3.1 Output Protective Device
Provide an output protective device that is capable of opening on an applied control signal and has the proper frame size and trip rating to supply overload current as specified. Provide the external output protective device with provision for locking in the "off" position. The inverter output protective device works in conjunction with the bypass protective device for both manual and automatic load transfers to and from bypass power.
2.5.4 External Protection
Provide the UPS module with built-in self-protection against undervoltage, overvoltage, overcurrent and surges introduced on the ac input source and/or the bypass source. Provide the UPS with built-in self-protection against overvoltage and voltage surges introduced at the output terminals by paralleled sources, load switching, or circuit breaker operation in the critical load distribution system.
2.5.5 Internal Protection
Provide the UPS module with the ability to be self-protected against overcurrent, sudden changes in output load and short circuits at the output terminals. Provide the UPS module with output reverse power detection which causes the module to be disconnected from the critical load bus when output reverse power is present. Provide the UPS module with built-in protection against permanent damage to itself and the connected load for predictable types of failure within itself and the connected load. At the end of battery discharge limit, the module shuts down without damage to internal components.
2.5.6 Battery Protection
Provide the inverter with monitoring and controls circuits to protect the battery system from damage due to excessive discharge. Inverter shutdown is be initiated when the battery has reached the end of discharge voltage. Manufacturer is to calculate the end-of-discharge voltage and automatically adjusted for partial load conditions to allow extended operation without damaging the battery. Automatic shutdown based on discharge time is not acceptable.
2.5.8 Parallel Operation
For parallel operation, ensure the protection system has control logic capable of isolating only the faulted module, and does not shut down the entire UPS system upon a fault in one module. Open protective devices are
SECTION 26 33 53 Page 16 to be indicated by an alarm and indicator light.
2.6 STATIC BYPASS TRANSFER CIRCUIT
Provide the control logic with an automatic transfer circuit that senses the status of the inverter logic signals and alarm conditions and provides an uninterrupted transfer of the load to the static bypass ac power source, without exceeding the transient limits specified herein, during times when maintenance is required, when a malfunction occurs in the UPS or when an external overload condition occurs. The static bypass transfer circuit is to be used to connect the input bypass ac power source to the critical load when required. Provide the static bypass transfer circuit with the following features:
2.6.1 Construction
Provide a static with a continuous duty rating of at least 100 percent of the UPS output rating. Provide a static bypass transfer circuit as an integral part of the UPS that consists of a static switch, made up of two reverse-paralleled SCRs (silicon-controlled rectifiers) per phase conductor, and a bypass protective device, made up of a circuit breaker and fuses. The bypass protective device is to be in series with the static switch. The inverter output protective device disconnects and isolates the inverter from the bypass transfer circuit.
2.6.2 Automatic Uninterrupted Transfer
The static bypass transfer switch automatically causes the bypass ac power source to assume the critical load without interruption when the bypass control logic senses one of the following conditions and the UPS inverter output is synchronized to the bypass ac power source:
a. Inverter overload exceeds unit's rating.
b. Battery protection period is expired and bypass is available.
c. System failure.
d. Inverter output undervoltage or overvoltage.
2.6.3 Interrupted Transfer
If an overload occurs and the UPS inverter output is not synchronized to the bypass ac power source, the UPS inverter output current-limits for 200 milliseconds minimum. The inverter then turns off and an interrupted transfer to the bypass ac power source is made.
If the bypass ac power source is beyond the conditions stated below, an interrupted transfer is made upon detection of a fault condition:
a. Bypass voltage greater than plus or minus 10 percent from the UPS rated output voltage.
b. Bypass frequency greater than plus or minus 0.5 Hz from the UPS rated output frequency.
c. Phase differential of ac bypass voltage to UPS output voltage greater than plus or minus 3 degrees.
2.6.4 Manual Load Transfer
SECTION 26 33 53 Page 17
It must be possible to make a manually-initiated static transfer from the system status and control panel by turning the UPS inverter off or by initiating it through the UPS display interface. The transfer is to make-before-break utilizing the UPS output and system bypass circuit breakers. Do not use the static switch for manual transfer unless there isn't a parallel by-pass circuit breaker or contactor.
2.6.5 Automatic Uninterrupted Forward Transfer
Automatic transfer of the load back to the inverter is to take place when the transfer was caused by an overload and only after the load has returned to a level within the inverter souse. Provide the ability to allow 1 to 3 transfers within any one-hour period to prevent cyclical transfers caused by overloads.
2.6.6 Forced Transfer
Provide control logic circuitry with the means of making a forced or reverse transfer of the static bypass transfer circuit on an interrupted basis. Minimum interruption is 200 milliseconds when the UPS inverter is not synchronized to the bypass ac power source.
2.6.7 Overload Ratings
The static bypass transfer switch is to withstand the following overload conditions:
a. 1000 percent of UPS output rating for one cycle.
b. 125 percent of UPS output rating for 1 minute.
2.6.8 System Protection
Incorporate into the static bypass circuit back-feed protection per UL 1778.
To achieve back-feed protection, provide a back-feed protection breaker/mechanical contactor upstream and in series with the bypass switch that is controlled by the UPS/static switch, to open immediately upon sensing a condition where back-feeding of the static switch by any source connected to the critical output bus of the system is occurring.
2.7 DISPLAY, CONTROLS AND ALARMS
Provide the UPS module with a microprocessor-controlled display unit located on the hinged door on the front of the system. Provide a LCD color alphanumeric display that operated by touchscreen to access the various information. Controls, meters, alarms and indicators for operation of the UPS module are to be on this panel. Provide a menu driven graphical user interface for browsing the screens. All three-phases of three-phase parameters are to be displayed simultaneously.
2.7.1 Meter Construction
Display alphanumeric parameters based on true RMS metering with 2 percent accuracy at full scale (minimum 4 significant digits) at the display panel.
2.7.2 Module Controls
Provide a module or equivalent features via touchscreen with the following controls:
SECTION 26 33 53 Page 18
a. Silence audible alarm.
b. Display or set the date and time.
c. Adjust setpoints on various alarms.
d. Alarm test/reset pushbutton.
e. Battery protective device trip pushbutton.
f. Emergency off pushbutton, with guard. Provide a hard-wired pushbutton even if touchscreen system is provided.
g. DC voltage adjustment potentiometer, with locking guard or AC output voltage adjustment potentiometer. Provide potentiometer that is accessible only by authorized personnel.
h. Control power off switch.
i. Transfer load to and from static bypass circuit.
j. Display control pushbuttons: up, down, select.
2.7.3 Module or System Alarm Indicators
Provide the module with indicators for the following alarm items. Any one of these conditions is to turn on an audible alarm and the appropriate summary indicator. The system is to register each new alarm without affecting any previous alarm. Provide a processor that time-date stamps each event.
a. Input ac power source failure.
b. Input protective device open.
c. Input power out of tolerance.
d. Overload.
e. Overload shutdown.
f. DC overvoltage/shutdown.
g. DC ground fault.
h. Low battery.
i. Battery discharged.
j. Battery protective device open.
k. Blower fan failure or overtemperature.
l. Overtemperature shutdown.
m. Hardware shutdown.
n. Equipment overtemperature.
o. Fuse blown with annunciation..
SECTION 26 33 53 Page 19
p. Control power failure.
q. Charger off/problem.
r. Inverter fault/off.
s. Emergency power off.
t. External shutdown (Remote Emergency Power Off) activated.
u. Output protective device open.
v. Operating on internal oscillator
w. UPS on battery
x. Critical load on static bypass.
y. Static bypass transfer switch disabled/failure.
z. Inverter output overvoltage.
aa. Inverter output undervoltage.
bb. Inverter output overfrequency.
cc. Inverter output underfrequency.
dd. Bypass source overvoltage.
ee. Bypass source undervoltage.
ff. Bypass source overfrequency.
gg. Bypass source underfrequency.
hh. Bypass source to inverter out of synchronization.
2.7.4 Module Emergency OFF Button
Provide an emergency off pushbutton with a protective cover. Pressing the emergency off button causes the module input, output, and battery circuit breakers or contactors to open, completely isolating the UPS system from sources of power and transfer of the load to bypass.
System Mimic Panel
Provide a mimic panel in the format of a single-line diagram that graphically depicts whether the load is supplied from the inverter, bypass, or battery. Provide on status on the following:
a. Module on-line, one per UPS module.
b. UPS output protective device status, one for closed (red), one for open (green), and one for withdrawn (amber).
c. Static bypass protective device status, one for closed (red), one for open (green), and one for withdrawn (amber).
d. Static switch status, one for connected (red), and one for
SECTION 26 33 53 Page 20 disconnected (green).
e. Status on the AC input circuit breaker, battery circuit breaker, and inverter circuit breaker. Connected (red) and disconnected (green).
2.7.5 Audible Alarm
Any single indicator turns on the audible alarm. An audible alarm test/reset button and lamp test/reset button is to be included. The alarm on the module is not affected nor reset by the reset button.
2.8 COMMUNICATIONS AND DATA ACQUISITION
Provide an IP communications and data acquisition port. This port allows the system parameters, status, alarm indication and control panel functions specified to be remotely monitored and controlled.
2.8 TEMPERATURE CONTROL
2.9.1 General
Ensure cabinet and enclosure ventilation is adequate to operate the components within their ratings. Forced-air cooled rectifier, inverter, and control unit will be acceptable. If UPS input power is lost, then the cooling fans are to continue to operate. Provide redundancy that ensures failure of one fan or associated circuit breaker does not cause an overheat condition. Cooling air is to enter the lower front of the cabinets and exhaust at the top. Provide visual and audible alarms on the control panel that indicate blower power failure. Provide replaceable filters on air inlets, which may be located on the inside of the cabinet doors and are easily accessible for replacement.
2.9.2 Blower Power Source
Provide a blower power source that is internally derived from the output side of UPS module, with automatic transfer arrangement.
2.9.3 Temperature Sensors
Provide temperature sensors to monitor the air temperature. Provide a sensor or sensors to monitor the temperature of rectifier and inverter heat sinks. Provide separate sensors to monitor the transformer temperature. Provide critical equipment over-temperature indication that starts a timer that shuts down the UPS system if the temperature does not return below the setpoint level recommended by the UPS manufacturer.
2.11 BATTERY SYSTEM
2.11.1 Battery Cabinet
Furnish the battery pack assembly in a battery cabinet matching the UPS cabinet. Design the battery cabinet to allow for checking the torque on the connections in the battery system and to provide adequate access for annual housekeeping chores. Provide an external wiring interface through the bottom or top of the assembly. Provide a high temperature alarm that annunciates detection of high temperature within the battery cabinet.
2.11.2 Battery Rack
Provide a suitable number of racks to fit the room layout shown for the
SECTION 26 33 53 Page 21 number of batteries provided. Provide a steel battery rack that is protected with electrolyte-resistant paint. Ship the battery rack unassembled with all necessary hardware for assembly. Provide each rack with a complete set with bus bars to accommodate cables from UPS module.
Provide bus bar connectors for battery-to-battery connections and high-flex multi-stranded copper cable (ASTM B173 stranding class H) with proper cable supports for connecting top row of batteries to bottom row of batteries at rack ends. Cut end sections to length to prevent wasting floor space.
3.1 INSTALLATION
Conform electrical installations to IEEE C2, NFPA 70, and to requirements specified herein. Provide new equipment and materials unless indicated or specified otherwise. Set the UPS system in place that is wired and connected in accordance with the approved shop drawings and manufacturer's instructions.
3.1.1 Control Cable
Install UPS control wiring in individual separate rigid steel conduits, unless connections are made between side by side matching cabinets of UPS.
Tag control wires with numeric identification tags corresponding to the terminal strip location to where the wires are connected. In addition to manufacturer's requirements, provide four additional spare conductors between UPS module and remote alarm panel in same conduit. When routing control cables inside UPS module, maintain a minimum 155 mm 6 inches separation from power cables.
3.1.2 Grounding
3.1.2.1 Grounding Conductor Title
Provide a separate grounding conductor that is separate from the electrical system neutral conductor in feeder and branch circuits. Ground battery racks and battery breaker cabinets with a separate equipment grounding conductor to the UPS cabinet.
3.1.2.2 Separately Derived
If not part of a listed power supply for a data-processing room, comply with NFPA 70 requirements for connecting to grounding electrodes and for bonding to building steel.
3.1.3 UPS Output Conductors
Isolate the UPS output conductors from the UPS cabinet to the critical load panels and from other conductors by installing in separate conduit.
3.1.4 DC Power Conductors
When installed in conduits, place dc power conductors from the UPS cabinet to the battery circuit breaker such that each conduit contains an equal number of positive and negative conductors, for example, two positive and two negative conductors in each conduit. Size conductor for a maximum of 2 percent voltage drop at full discharge.
3.1.6 Conduit Entries
Ensure conduit entries use the available conduit areas shown on manufacturer's installation drawings. Do not make conduit entries through
SECTION 26 33 53 Page 22 the front, side or rear panels of the UPS.
3.1.7 Battery Rack Assembly
Battery racks are typically shipped dismantled in separate rail, frame, and brace packages. Ensure that manufacturer furnished assembly hardware is used to assemble battery racks. Conform battery rack installation to the manufacturer's instructions.
3.1.9 Battery Installation
Conform battery cabinet installation to the manufacturer's instructions.
3.2 FIELD QUALITY CONTROL
Notify the Contracting Officer in writing at least 30 calendar days prior to completion of the UPS system installation. At this time the Contractor, will schedule the UPS manufacturer's technical representative to inspect the completed installation. Provide instruction for activity personnel by the UPS technical representative as specified in paragraph titled
"DEMONSTRATION".
3.2.1 Installation Preparation
Completely install the following items by the Contractor and be operational prior to the arrival of the UPS representative for inspection, unit start-up and testing:
a. Ventilation equipment in the UPS and battery cabinets.
b. Battery cabinets and cells.
c. Battery connections including cell-to-cell, tier-to-tier, and rack-to-rack connections, with correct polarity;
d. DC power and control connections between UPS and battery circuit breaker, with correct polarity;
e. DC power connection between battery circuit breaker and battery, with correct polarity;
f. Clockwise phase rotation of ac power connections;
g. AC power to rectifier input bus;
h. AC power to UPS bypass input bus;
i. AC power to UPS maintenance bypass circuit breaker;
j. AC power from UPS output to UPS maintenance bypass output circuit breaker;
k. Remote monitors and control wiring;
l. UPS system and battery system properly
o. Clean and vacuum UPS and battery room floors, battery cells, and UPS equipment, both inside and outside
3.2.2 Initial Inspection and Tests
SECTION 26 33 53 Page 23
The UPS technical representative and the Contracting Officer, in the presence of the Contractor, will inspect the completed installation. The Contractor is responsible to correct construction or installation deficiencies as directed. Perform acceptance checks in accordance with the manufacturer's recommendations and include the following visual and mechanical inspections, performed in accordance with NETA ATS.
a. UPS Unit visual and mechanical inspection
(1) Compare equipment nameplate data with drawings, specifications and approved shop drawings.
(2) Inspect physical and mechanical condition. Inspect doors, panels, and sections for paint, dents, scratches, fit, and missing hardware. Inspect the displays for scratches, dark pixels or uneven brightness.
(3) Inspect anchorage, alignment, grounding, and required clearances.
(4) Verify that fuse sizes and types correspond to drawings.
(5) Verify the unit is clean inside and out.
(6) Test all electrical and mechanical interlock systems for correct operation and sequencing.
(7) Inspect bolted electrical connections for high resistance using one of the following methods:
(a) Use a low-resistance ohmmeter.
(b) Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method.
(c) Perform thermographic survey.
(8) Verify operation of forced ventilation.
(9) Verify that vents are clear and new clean filters are installed.
(10) Inspect batteries and chargers according to requirements in
NETA ATS
b. UPS Batteries visual and mechanical inspection
(1) Compare equipment nameplate data with drawings, specifications and approved shop drawings.
(2) Inspect physical and mechanical condition. Inspect doors, panels, and sections for paint, dents, scratches, fit, and missing hardware. Inspect the displays for scratches, dark pixels or uneven brightness.
(3) Inspect anchorage, alignment, grounding, and…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .