Atch 1_SOW_York Rooftop Unit Replacement.docx

DOCX document 43 KB Posted

Attached to
Replace Rooftop AC Unit, Laurel, MD
Solicitation number
12639525R0023
Issued by

About this file

This document is a Statement of Work (SOW) for replacing a York rooftop air handling unit at the USDA Animal and Plant Health Inspection Service's National Center for Applied Plant Protection (NCAPP) in Laurel, MD. The project involves removing a 25-year-old 15-25 ton air-cooled packaged unit and installing a comparable replacement unit, with comprehensive scope including utility disconnection, equipment removal, new unit installation, ductwork modifications, electrical work, controls integration, and system commissioning.

The solicitation (12639525R0023) is set aside exclusively for small businesses under NAICS code 238220, with a small business size standard of $19 million and an estimated project value between $500,000 and $1 million. The work must be performed by EPA-certified technicians during normal business hours (Monday-Friday, 7:00 AM to 3:30 PM), with strict facility access requirements including valid identification, supervised site work, and potential coordination for after-hours activities. Key contacts include Contracting Officer Jim Roloff, Engineering Project Manager Toni Mitchell, and Facilities Operations Specialist Westley Hutchinson, all from USDA APHIS.

View the file

Other files

File Type Posted
RFIs 4.docx DOCX document
RFIs and Responses 3.docx DOCX document
Site visit sign-in sheet.pdf PDF
RFIs and Responses 2.docx DOCX document
RFIs and Responses.docx DOCX document
12639525R0023.pdf PDF
Atch 2_Federal Construction Wage Rates_PG County.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation 12639525R0023, Attachment 1 Statement of Work For York Rooftop Unit Replacement at NCAPP July 2025

1.0 Contract Project: YORK Rooftop Unit Replacement at NCAPP

2.0 Location: USDA APHIS PPQ FO

National Center for Applied Plant Protection
9901 Power Mill Rd.
Laurel, MD 20708

3.0 Project Background: USDA’s APHIS National Center for Applied Plant Protection, Plant facility (NCAPP), a.k.a. Building 580, performs research activities related to agricultural crop diseases and mitigation. The NCAPP campus comprises several buildings constructed at different times. The first buildings which make up the facility were the Headhouse and the Greenhouse connector that were built to serve the greenhouses. The Virology Laboratory was constructed in 1986. The addition of the high-security building to the north of the Virology Laboratory and the plant inspection station and breezeway leading to the headhouse were constructed in 1999.

We have a York DR180 rooftop unit, an air-cooled packaged unit with capacities ranging from 15 to 25 nominal tons, supplying conditioned air to the Plant Inspection Station and Plant Pathogen Confirmatory Diagnostics Laboratory. It’s 25 years old and has exceeded its operational life. The scope of this project is to replace the RTU with a unit of comparable performance.

4.0 Project Scope:

4.1 Removal of Existing Unit: This includes not limited to disconnecting utilities (electrical, gas, refrigerant, etc.), removing the old unit from the roof and disposing of it properly. site-specific conditions, such as roof access, crane placement, and any potential obstacles.

4.2 Installation of New Unit: Including setting the new unit on the roof (potentially on a new or existing curb), connecting utilities, and ensuring proper sealing and weatherproofing of connections. Equipment should be comparable with size, capacity, tonnage, airflow, heating cooling etc.

4.3 Building Codes and Standards: International Building Code, local codes and industry standards (e.g., ASHRAE).

4.4 Safety Requirements: Safety procedures, including lockout/tagout procedures, fall protection, and personal protective equipment.

4.5 Duct Work Modifications: Modifying existing ductwork to connect to the new AHU or installing new ductwork, including connections to supply and return vents.

4.6 Electrical Work: Disconnecting and reconnecting wiring, potentially installing new electrical components (e.g., disconnect switches, wiring), and ensuring proper grounding.

4.7 Controls Integration: Ensuring integrating the new AHU with existing building automation systems with BACnet capabilities and working with current BAS contractor.

4.8 Refrigerant Piping: If applicable, this includes connecting refrigerant lines, potentially using existing building penetrations, and ensuring proper insulation of the lines.

4.9 Testing and Commissioning: Testing the new AHU to ensure it meets performance requirements (e.g., airflow, temperature, pressure) and commissioning it with the manufacturer's representative.

4.10 Training: Providing training to building staff on the operation and maintenance of the new AHU.

4.10 Warranty: Specifying the warranty period for the new AHU and its components.

Contractors must comply with applicable codes, environmental regulations in the State of Maryland and local ordinances.

· All work shall be performed in accordance with all applicable State and Local codes and standards.

· All work to be performed by EPA certified technicians and executed in a professional workman like manner.

· All equipment and material installed on this project shall be new and unused unless otherwise noted.

· All work to be performed during normal business hours, Monday through Friday, unless otherwise noted.

5.0 Project Contacts:

5.1 Contracting Officer (CO):
Jim Roloff
USDA, APHIS, Contracting
250 Marquette Ave
Minneapolis, MN 55401
Tel. No.: 612-590-7603
Email: James.G.Roloff@usda.gov
5.2Engineering Project Manager (EPM):
Toni T Mitchell
USDA, APHIS, ASD, ESB
5601 Sunyside Ave, Room 3-2401
Beltsville, MD 20705
Tel. No.: (301) 252-4333
E-mail: Toni.T.Mitchell@usda.gov
5.3APHIS PPQ Facilities Operations Specialist (FOS):
Westley Hutchinson

USDA, APHIS, PPQ, FO

Bldg. 580, BARC-EAST Beltsville, MD 20705 Tel. No.: (301) 313-9256 Email: Wesley.Hutchinson@usda.gov

6.0 Facility Security and Safety Requirements:

In addition to this SOW, Bldg. 580, BARC-EAST is a restricted facility.

· Work Hours are Monday through Friday from 7:00 AM to 3:30 PM. All work outside of the day mentioned and hours shall be approved by the Facilities Operations Specialist in writing, prior to entering the facility. This includes work during Federal holidays.

· Some of this work will be required working after 3:30, the Contractor is to provide a schedule for those days to coordinate with the Facility Operations Specialist.

· All Contractors shall have a valid picture identification such as a driver’s license or a State identification card.

· All vehicles shall have proper insurance and registration for entering the facility.

· All Contractors working at the facility shall remain in the project site under the supervision of a qualified job site superintendent. Anyone found outside of the determined construction area will be removed from the facility and not allowed to return.

· All Contractors shall provide temporary and portable restroom facilities for their employees if the project has a duration of over three working days.