Attachment_6_-_Walkin_Refrigerator_and_Freezer_Specifications.pdf
PDF 13 KB Posted
- Attached to
- Multiple Construction Projects - Pine Knot Job Corps Center Federal contract opportunity
- Solicitation number
- AG-82A7-S-17-0051
About this file
Attachment 6
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SF-30_Amend_000002_-_AG-82A7-S-17-0051.pdf | ||
| A13_Q&A_5.22.2017.pdf | ||
| Attachment_10_-_BuildingDescs_PineKnot-FireAlarm.pdf | ||
| A13_Q&A_4.28.2017.docx | DOCX document | |
| SF-30_Amendment_000001_-_AG-82A7-S-17-0051.pdf | ||
| Attachment_9_-_Proposal_Submission_Package.pdf | ||
| Attachment_3_-_Project_Specifications_-_Misc._Building_Exterior_Repairs.pdf | ||
| Attachment_2_-_Drawings_-_Culinary_Arts_Buildout.pdf | ||
| Attachment_5_-_Project_Specifications_and_Drawing_-_Fire_Detection_System.pdf | ||
| Attachment_1_-_Project_Specifications_-_Culinary_Arts_Buildout.pdf | ||
| Attachment_8_-_DB_-_Pine_Knot_-_Building.pdf | ||
| Solicitation_-_AG-82A7-S-17-0051.pdf | ||
| Attachment_4_-_Drawing_-_Misc._Building_Exterior_Repairs.pdf | ||
| Attachment_7_-_DB_-_Pine_Knot_-_Residential.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment 6
Pine Knot CCC
Walk-in Refrigerator and Freezer Replacement
Statement of Work
The Center requires total removal and replacement of the existing Master Built model #C-5131 commercial/institutional grade walk-in refrigerator and freezer.
Prepare area as specified by manufacturer and provide all new commercial/institutional grade walk-in refrigerator and freezer components for 7’-9” wide x 13’-6” length x 7’-6” high refrigerator and 7’-9” wide x 13’-6” length x 7’-6” high freezer, . Included are floor, walls, ceiling, doors, seals, insulation, and all mechanical equipment sized appropriately to maintain proper temps per industry standards.
Minimum requirements:
General: Contractor to verify dimensions of existing space and determine size and configuration, and confirm refrigeration units are sized property for cooling requirements and ambient conditions. Provide layout plan and equipment selection to Contracting Officer prior to ordering components. Walk-in refrigerator and freezer shall be constructed of prefab panels and field assembled in place.
Wall/Ceiling panel construction: minimum 26 gauge metal with foam insulation, R-32 minimum
Floor: Heavy duty structural floor, designed to support a distributed load of at least 5000 pounds. Similar construction to wall panel, with diamond tread
Doors: 36” x 78” left hand hinged, standard duty, heavy duty threshold
Thermometer: dial-type showing temperature in Fahrenheit
Refrigerator condensing unit: Hermetic type compressor, 0.75 HP, 208-230 voltage, R-404A refrigerant, designed to operate at 100F ambient temperature at compressor.
Refrigerator evaporator coil: 115 voltage, R-404A refrigerant
Freezer condensing unit: Hermetic type compressor, 2 HP, 208-230 voltage, R-404A refrigerant, designed to operate at 100F ambient temperature at compressor
Freezer evaporator coil: 208-230 voltage, R-404A refrigerant
Warranty: 1 year, with 4 year extended warranty on compressor