Building Descriptions Date: 05/18/2016Center : Pine Knot (00320) Page: 12 of 114

Building: 0009 - CENTER MAINTENANCE

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

Drywall Wood Paneling

Wood Unit - Wood Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

None

Double Hung - Vinyl Frame; Double Glazing;

Acoustical Tile Gypsum Board Plywood

Exhaust Ventilation

Windows6.

Floors1. Asbestos: Yes

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Two Goodman gas fired packaged units heat and cool the entire building. One unit is model GPG 12240701a, with a gas heat input of 69,000 BTUH. The other is Goodman PGB 0361001B, with a rated gas heat input of 92,000 BTUH.

Comments:

HVAC

Heat1.

Gas-Fired Furnace

Single Duct None Electric Mechanical None Entire Building

Ventilation2.

Ceilings

Page: 13 of 114

Building: 0009 - CENTER MAINTENANCE

There is a 30 gallon electric water heater, Richmond model 6K30-2.Comments:

Cast-Iron None None

Electric Water Cooler Lavatory Sink Urinal Water Closet (Tank)

Gas (Natural)

None None ABC Type Fire Extinguisher

Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank located at the northwest side of the building via underground cable and terminated in the 200A main branch panelboard with 200A main circuit breaker (MCB).

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Packaged Direct

Expansion (Air Source)

Single Duct None Electric Mechanical None Entire Building

Incandescent Comments: The exterior building-mounted light fixtures are controlled by a photocell.

Main Branch Panel 120/208V, 1-Phase, 3 Wire Branch Panel Only Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Cooling is provided by the same units that provide heating. The model numbers are given under heating.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1.

3. Air Conditioning

LIGHTING

Page: 14 of 114

Building: 0009 - CENTER MAINTENANCE

FIRE ALARM

Comments: The fire alarm control panel is by Cerberus-Pyrotronics. This panel is located in the maintenance office.

Comments: The building is connected to the LAN. The public address system is not connected and therefore is not operational.

Audible Alarm Control Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System None None None

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Conference Rooms

Toilets

Storage Rooms

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Emergency Exit

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

Interior Lighting2.

Emergency /Exit Lighting3. Number of Deficiencies = 2

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No NoNo

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

Type Location N/A N/A

CARBON MONOXIDE DETECTION

Detection Required No

Number of Deficiencies = 0

IMPAIRMENT

Potentially Impaired

DOL Responded

DOL Determination

Potential Impaired Comments DOL Determination Discussion/Comments

Page: 31 of 114

Building: 0014 - GYMNASIUM/RECREATION HALL

INTERIOR FINISH

Carpet Ceramic Tile Concrete Rubberized Athletic Flooring Vinyl Tile

Drywall Wood Paneling

Metal Unit - Metal Frame Wood Unit - Wood Frame

VERTICAL CIRCULATION

Metal Stairs Wood Stairs (2 Interior) Comments: The building has two interior wood stairs and one exterior metal fire escape stair.

Sliding - Aluminum Frame; Double Glazing;

Acoustical Tile Exposed Structure Gypsum Board

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 2

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

The gym is served by two Trane packaged units located in the rear of the gym. One unit is Trane model YCH180B3LOHB and the other unit is Trane model YCH240BBLOJB.

First floor recreation areas are served by two Trane gas fired furnaces. One is model number TXC049C4HPD0 and one is model number TXC037C4HPC0.

Second floor recreation areas are served by two electric furnaces. One unit is a Trane model TWE120A300 and the other unit is a Maytag model B5BMX60K-C.

Comments:

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Packaged

Gas-Fired Furnace

Electric Resistance

Single Duct

Single Duct

Single Duct

None

None

None

Electric

Electric

Electric

Mechanical

Mechanical

Mechanical

None

None

None

Gymnasium

Recreation Area

Recreation Area

Page: 32 of 114

Building: 0014 - GYMNASIUM/RECREATION HALL

Mechanical

Mechanical

Restroom

Kiln Area

Comments: The kilns are served by a dedicated exhaust hood.

Domestic hot water is provided by a Richmond model 6E30-2 electric water heater.Comments:

Cast Iron None None

Electric Water Cooler Lavatory Shower Urinal Water Closet (Flush Valve)

Gas (Natural)

None None ABC Type Fire Extinguisher

Ventilation Area Served

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Source)

Packaged Direct

Expansion (Air Source)

Single Duct

Single Duct

Refrigerant

None

Electric

Electric

Mechanical

Mechanical

None

None

Recreation Area

Gymnasium

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Exhaust Ventilation

The four furnaces are paired with outdoor air cooled condensing units. The condensing units are as follows: Trane 2TTA0036A300A, Trane TTA120A300FA, Trane TTA090A300FA and Maytag

MSH4BD060K.

The gym is served by two packaged units located outside. Data on the units is listed under heating.

Comments:

Comments:

Ventilation2.

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

Page: 33 of 114

Building: 0014 - GYMNASIUM/RECREATION HALL

Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank located at the northeast side of the building via overhead cable to an 800A main distribution panelboard (MDP) with 800A main circuit breaker (MCB) located in the electrical room.

FIRE ALARM

Comments: The fire alarm control panel is a Cerberus-Pyrotronics. This panel is located in the main lobby.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution.

High Intensity Discharge (HID) Comments: Building-mounted light fixtures are controlled by astronomical time clock located in the electrical room.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

High Intensity Discharge (HID)

T8 - Fluorescent

T8 - Fluorescent

Offices

Equipment Rooms (Elec/Mech)

Toilets

Storage Rooms

Vocational

Gymnasium

Locker Room

Recreation

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches

Emergency Exit

Number of Deficiencies = 1

ELECTRICAL SERVICES Number of Deficiencies = 6

Exterior Lighting1.

Interior Lighting2. Number of Deficiencies = 1

Emergency /Exit Lighting3. Number of Deficiencies = 3

Type Location N/A N/A

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required No

Number of Deficiencies = 0

Page: 60 of 114

Building: 0057 - KING HALL DORMITORY (MALE)

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

Ceramic Tile Drywall Painted CMU

Metal Unit - Metal Frame Wood Unit - Metal Frame

Mechanical Toilet/Shower

Comments: The attic houses the following air handlers : Trane TWE030P130B0, mfg 10/2002; International Comfort FSM46000A, mfg date Oct 2010; Goodman ARUF486016CA

Ventilation Area Served

VERTICAL CIRCULATION

Exterior Concrete Stairs Ramp

Double Hung - Wood Frame; Double Glazing;

Acoustical Tile Gypsum Board

Exhaust Ventilation

Windows6.

Floors1. Asbestos: Yes

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 1

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Three Trane model TWE series split system heat pumps serve the dorm. A Norodyne model B2BM030K-B heat pump serves the lower level. The three outdoor units for the dorm are as follows:

Trane model 2TWA 0030A300AB, Tappan model N4H360GHB400, and International Comfort Products model X131076544. The outdoor unit for the lower level is a Tempstar E110600250, mfg date Feb 2011.

Comments:

HVAC

Heat1.

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Ventilation2. Number of Deficiencies = 1

Page: 61 of 114

Building: 0057 - KING HALL DORMITORY (MALE)

There are two 120 gallon each electric hot water heaters. One is a Rheem model EGS18-120-G and the other is a Bradford White model MII120-18-3SF-39.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Service Sink Shower Urinal Water Closet (Flush Valve)

None

None None ABC Type Fire Extinguisher

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Cooling for the dorm is provided by three split system heat pumps. Cooling for the lower level is provided by one split system heat pump. Data on the units is provided under "Heating".

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Number of Deficiencies = 1FIRE PROTECTION

Page: 62 of 114

Building: 0057 - KING HALL DORMITORY (MALE)

Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the northwest side of the building, via a 600A pole-mounted main circuit breaker. From this circuit breaker the electrical service is routed to the building via underground cable and terminated in the 600A main panelboard with 600A main circuit breaker (MCB). The service equipment is located in the electrical/mechanical room.

FIRE ALARM

Comments: The fire alarm control panel is a Siemens FS-250. This panel is located in the RA office.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution.

High Intensity Discharge (HID) Comments: Building-mounted lighting is controlled by photocell and an astronomical time clock located in the electrical/mechanical room.

T8 - Fluorescent

T8 - Fluorescent

Compact Fluorescent

T8 - Fluorescent

Compact Fluorescent

T8 - Fluorescent

T12 - Fluorescent

T8 - Fluorescent

Offices

Corridors & Stairs

Equipment Rooms (Elec/Mech)

Toilets

Storage Rooms

Housing Lounge

Shower

Sleeping Rooms

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Panelboard 120/240V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches

Emergency Exit

Number of Deficiencies = 2

ELECTRICAL SERVICES Number of Deficiencies = 1

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3. Number of Deficiencies = 2

Type Location None None

There is no plausible means by which harmful levels of CO could enter sleeping rooms.

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required

Page: 65 of 114

Building: 0059 - PERKINS DORMITORY (MALE)

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

Ceramic Tile Drywall Painted CMU

Metal Unit - Metal Frame Wood Unit - Metal Frame

Mechanical Toilet/Shower

Ventilation Area Served

VERTICAL CIRCULATION

Concrete Stairs Ramp

Double Hung - Wood Frame; Double Glazing;

Gypsum Board Plaster

Exhaust Ventilation

Number of Deficiencies = 1

Number of Deficiencies = 1

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 1

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heating is provided by three split system heat pumps. The indoor units are Trane model

TWEO060A100EL.

Comments:

HVAC

Heat1.

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Page: 66 of 114

Building: 0059 - PERKINS DORMITORY (MALE)

Domestic hot water is provided by two Bradford White model MII120-183SF39 120 gallon electric water heaters.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Shower Sink Urinal Water Closet (Flush Valve)

None

None None ABC Type Fire Extinguisher

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Outdoor units are Trane model 2TWA0060A3000AB, and Goodman CPLJ48-1B plus International Comfort Product model X12147111, mfg date Aprilo 2012.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Page: 67 of 114

Building: 0059 - PERKINS DORMITORY (MALE)

Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the west side of the building, via a 600A pole-mounted main circuit breaker. From this circuit breaker the electrical service is routed to the building via underground cable and terminated in the 600A main panelboard with 600A main circuit breaker (MCB). The service equipment is located in the electrical/mechanical room.

FIRE ALARM

Comments: The fire alarm control panel is a Simens FS-250. This panel is located in the RA office.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution.

High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Compact Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Corridors & Stairs

Equipment Rooms (Elec/Mech)

Toilets

Storage Rooms

Housing Lounge

Shower

Sleeping Rooms

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Panelboard 120/240V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches

Emergency Exit

Number of Deficiencies = 2

ELECTRICAL SERVICES Number of Deficiencies = 1

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3.

Type Location None None

There is no plausible means by which harmful levels of CO could enter sleeping rooms.

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required

Page: 70 of 114

Building: 0060 - WASHINGTON DORMITORY (MALE)

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

Ceramic Tile Drywall Painted CMU

Wood Unit - Metal Frame

Mechanical Toilet/Shower

Ventilation Area Served

VERTICAL CIRCULATION

Ramp

Double Hung - Wood Frame; Double Glazing;

Gypsum Board Plaster

Exhaust Ventilation

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 2

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heating is provided by three split system heat pumps. The outdoor units are two Trane model 2TWA0060A3000AB, and one International Comfort Products model N4H330AHB300. Indoor units are two Trane TWE036PBOBO and one International Comfort Products model FSM4P3000A1.

Comments:

HVAC

Heat1.

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Page: 71 of 114

Building: 0060 - WASHINGTON DORMITORY (MALE)

Domestic hot water is provided by two 120 gallon electric water heaters. One water heater is a Bradford White model MII120-18-35F-39 and the other is a Richmond Perfect model ES-TES120- 18G.

Comments:

Cast Iron None None

Electric Water Cooler Hose Bibb Lavatory Service Sink Shower Urinal Water Closet (Flush Valve)

None

None None ABC Type Fire Extinguisher

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Cooling is provided by three split system heat pumps, data for which is provided under heating.Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Page: 72 of 114

Building: 0060 - WASHINGTON DORMITORY (MALE)

Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the west side of the building, via a 600A pole-mounted main circuit breaker. From this circuit breaker the electrical service is routed to the building via underground cable and terminated in the 600A main panelboard with 600A main lugs only (MLO). The service equipment is located in the electrical/mechanical room.

FIRE ALARM

Comments: The fire alarm control panel is a Siemens FS-250. This panel is located in the RA office.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution.

High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Incandescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Corridors & Stairs

Equipment Rooms (Elec/Mech)

Storage Rooms

Laundry Room

Housing Lounge

Shower

Sleeping Rooms

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Panelboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches

Emergency Exit

ELECTRICAL SERVICES Number of Deficiencies = 2

Exterior Lighting1. Number of Deficiencies = 2

Interior Lighting2.

Emergency /Exit Lighting3. Number of Deficiencies = 2

Type Location None None

There is no plausible means by which harmful levels of CO could enter sleeping rooms.

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required

Page: 98 of 114

Building: 0074 - FORESTRY

INTERIOR FINISH

Concrete Vinyl Tile

Drywall

Metal Unit - Metal Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

Concrete Stairs

Fixed - Aluminum Frame; Double Glazing;

Acoustical Tile Gypsum Board

Exhaust Ventilation

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

The inside unit is a Goodman model A42-15. The unit is located in the attic.Comments:

HVAC

Heat1.

Split Heat Pump (Air

Source)

Electric Resistance

Single Duct

Unit Heater

Refrigerant

None

Electric

Electric

Mechanical

Natural

None

None

Entire Building

Shop Area

Page: 99 of 114

Building: 0074 - FORESTRY

Domestic hot water is provided by a Richmond Perfect model 6E30-2 30-gallon water heater.Comments:

PVC None None

Electric Water Cooler Lavatory Sink Urinal Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the south side of the building, via a 400A pole-mounted disconnect switch. From this distribution panelboard the electrical service is routed to the building via underground cable and terminated in the 400A panelboard with 300A main circuit breaker (MCB).

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Split Heat Pump (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.

Main Branch Panel 120/208V, 1-Phase, 3 Wire Branch Panel Only Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

The outside unit is a Goodman model CPKJ36-1AB.Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Number of Deficiencies = 1FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1. Number of Deficiencies = 1

Page: 100 of 114

Building: 0074 - FORESTRY

FIRE ALARM

Comments: The fire alarm control panel is a Simplex DS 9400I. This panel is located in the storage room.

Comments: The building is connected to the LAN.

Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System None None TV with VCR

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

T12 - Fluorescent

T12 - Fluorescent

T12 - Fluorescent

T12 - Fluorescent

Offices

Toilets

Storage Rooms

Vocational

Area Recommended Recorded Light Type

None Battery Backup

Emergency Exit

Number of Deficiencies = 1

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

Interior Lighting2.

Emergency /Exit Lighting3. Number of Deficiencies = 2

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No N/ANo

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

Type Location N/A N/A

CARBON MONOXIDE DETECTION

Detection Required No

Number of Deficiencies = 0

IMPAIRMENT

Potentially Impaired

DOL Responded

DOL Determination

Potential Impaired Comments DOL Determination Discussion/Comments

Page: 107 of 114

Building: 0076 - STUDENT ACTIVITY CENTER

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

Ceramic Tile Drywall

Wood Units - Metal Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

Concrete Stairs Metal Stairs Ramp Comments: The metal stairs pull down for attic access.

Fixed - Aluminum Frame; Double Glazing; Sliding - Aluminum Frame; Double Glazing;

Acoustical Tile Gypsum Board

Exhaust Ventilation

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heating is provided by two gas-fired furnaces located in the attic. One serves the common areas, and one serves the offices. The furnaces are Lennox Pulse model CH22-65-1 and model CH23-65-1.

Comments:

HVAC

Heat1.

Gas-Fired Furnace

Single Duct None Electric Mechanical None Entire Building

Page: 108 of 114

Building: 0076 - STUDENT ACTIVITY CENTER

Domestic hot water is provided by a 20-gallon electric water heater.Comments:

PVC None None

Electric Water Cooler Lavatory Sink Urinal Water Closet (Flush Valve)

Gas (Natural)

None None ABC Type Fire Extinguisher

Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the south side of the building, via a 400A pole-mounted disconnect switch. From this distribution panelboard the electrical service is routed to the building via underground cable and terminated in the 400A panelboard with 300A main circuit breaker (MCB).

Copper Copper Electric Building Water Softener No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Split Direct Expansion (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

Incandescent Comments: The exterior building-mounted light fixtures are controlled by a photocell.

Main Branch Panel 120/208V, 1-Phase, 3 Wire Branch Panel Only Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

The furnaces are provided with evaporator coils matched to Lennox outdoor air cooled condensing units. One is a model HS26-060-2P and and one is a model HS26-048-2P.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Number of Deficiencies = 1FIRE PROTECTION

ELECTRICAL SERVICES Number of Deficiencies = 1

Exterior Lighting1.

Page: 109 of 114

Building: 0076 - STUDENT ACTIVITY CENTER

FIRE ALARM

Comments: The fire alarm control panel is a Tyco-Maxis PS 2040FC. This panel is located in the residential manager's office.

Comments: The building is connected to the LAN.

Audible Alarm Control/Annunciator Panel Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System None None None

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

High Intensity Discharge (HID)

Offices

Corridors & Stairs

Lounges

Storage Rooms

Study Room

Area Recommended Recorded Light Type

None Battery Backup

Emergency Exit

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

Interior Lighting2.

Emergency /Exit Lighting3.

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No NoNo

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

Type Location N/A N/A

CARBON MONOXIDE DETECTION

Detection Required No

IMPAIRMENT

Page: 102 of 114

Building: 0075 - DISPENSARY

INTERIOR FINISH

Ceramic Tile Concrete Vinyl Tile

Drywall

Wood Unit - Metal Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

Metal Stairs Ramp Comments: The metal stairs pull down for attic access.

Fixed - Wood Frame; Double Glazing; Sliding - Wood Frame; Double Glazing;

Acoustical Tile Gypsum Board

Exhaust Ventilation

Number of Deficiencies = 1

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

The building is heated by three high efficiency gas furnaces located in the attic. All three furnaces are Trane model TXCO42HPCO.

Comments:

HVAC

Heat1.

Gas-Fired Furnace

Single Duct None Electric Mechanical None Entire Building

Ventilation2. Number of Deficiencies = 2

Page: 103 of 114

Building: 0075 - DISPENSARY

Domestic hot water is provided by a Richmond model TES85-18-G 80 gallon electric water heater.Comments:

Cast Iron None None

Electric Water Cooler Lavatory Shower/Bathtub Sink Water Closet (Flush Valve)

Gas (Natural)

Wet None ABC Type Fire Extinguisher

Comments: There is a sprinkler system in the attic of the building where the mechanical equipment is located.

Comments: Electrical service of 120/208V to the building is provided from a pole-mounted utility-owned transformer bank, located at the north side of the building, via a 400A pole-mounted disconnect switch. From this distribution panelboard the electrical service is routed to the building via underground cable and terminated in the 400A panelboard with 400A main circuit breaker (MCB).

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Split Direct Expansion (Air

Source)

Single Duct Refrigerant Electric Mechanical None Entire Building

High Intensity Discharge (HID) Comments: Building-mounted lighting are controlled by astronomical time clock located in the electrical room.

Main Distribution Panel 120/208V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

The three outside condensing units are Trane model TTB042D.Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES Number of Deficiencies = 2

Exterior Lighting1.

Page: 104 of 114

Building: 0075 - DISPENSARY

FIRE ALARM

Comments: The fire alarm control panel is a Fire Lite MS 2410B. This panel is located in the lobby.

Comments: The building is connected to the LAN. The public address system is not connected and therefore not operational.

Audible Alarm Control Panel Flow Switch Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System None None TV with VCR

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Corridors & Stairs

Equipment Rooms (Elec/Mech)

Reception

Toilets

Storage Rooms

Housing Lounge

Medical/Dental

Wards (Patient)

Area Recommended Recorded Light Type

Selected Lighting w/ Battery Battery Backup

Emergency Exit

Interior Lighting2.

Emergency /Exit Lighting3. Number of Deficiencies = 1

COMMUNICATION

Electric Water Gas No NoNo

BUILDING UTILITY METERING

Type Location None None

There is no plausible means by which harmful levels of CO could enter sleeping rooms.

CARBON MONOXIDE DETECTION

Detection Required

Page: 80 of 114

Building: 0066 - VOCATIONAL SHOPS

INTERIOR FINISH

Carpet Concrete Vinyl Tile

Drywall Painted CMU Wood Paneling

Metal Unit - Metal Frame

VERTICAL CIRCULATION

Concrete Stairs Wood Stairs Comments: There are two sets of wood stairs and one of them is walled off and is unusable. This was done to eliminate unauthorized entry. The lower floor has its own entrance and exit doors as does the upper floor. Currently there is no interface between the functions of the upper and lower floors that requires interior circulation.

Fixed - Aluminum Frame; Double Glazing;

Exposed Structure Gypsum Board Plaster

Number of Deficiencies = 2

Windows6.

Floors1. Asbestos: Yes

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Heating and cooling for the first floor is provided by through the wall heat pumps.

Offices and shop areas are heated by unit heaters.

Comments:

Comments:

HVAC

Heat1.

Packaged Heat Pump (Air

Source)

Electric Resistance

Through-The- Wall Unit

Unit Heater

None

None

Electric

Electric

Mechanical

Natural

None

None

Classrooms

Entire Building

Page: 81 of 114

Building: 0066 - VOCATIONAL SHOPS

Mechanical Restroom

Domestic hot water is provided by a Bradford White model M120V6S513 water heater.Comments:

PVC None None

Electric Water Cooler Fixed Emergency Eyewash Lavatory Urinal Water Closet (Flush Valve)

None

None None ABC Type Fire Extinguisher

Ventilation Area Served

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Packaged Direct

Expansion (Air Cooled)

Split Heat Pump (Air

Cooled)

Window Unit

Through-The- Wall Unit

None

None

Electric

Electric

Mechanical

Mechanical

None

None

Offices

Classrooms

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Exhaust Ventilation

Ventilation2.

System Type

Number of Deficiencies = 2

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation Area

Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

Page: 82 of 114

Building: 0066 - VOCATIONAL SHOPS

Comments: Electrical service of 120/240V to the building is provided from a pole-mounted utility-owned transformer bank, located at the north side of the building, via a 600A pole-mounted main distribution panel. From this distribution panelboard the electrical service is routed to the building via underground cable and terminated in the two 225A panelboard with 225A main circuit breaker (MCB0, and two 150A main lugs only panelboards.

FIRE ALARM

Comments: The fire alarm control panel is a Cerberus-Prytronics. This panel is located in the first-floor instructor office.

Comments: The public address system is not connected and therefore is not operational.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control Panel Heat Detector Manual Pull Station Smoke Detector Visual Alarm

Connected to Main System None None TV with VCR

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

High Intensity Discharge (HID) Comments: The exterior building-mounted light fixtures are controlled by a photocell.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Toilets

Storage Rooms

Classrooms

Vocational

Area Recommended Recorded Light Type

Battery Backup Battery Backup

Main Distribution Panel 120/240V, 1-Phase, 3 Wire Panelboard Receptacles, GFCI, Switches

Emergency Exit

ELECTRICAL SERVICES Number of Deficiencies = 4

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3. Number of Deficiencies = 1

COMMUNICATION

Type Location N/A N/A

CARBON MONOXIDE DETECTION

LIGHTING

Detection Required

Pages from 2015_00320_Final_Vol2_Part1
Pages from 2015_00320_Final_Vol2_Part1-2
Pages from 2015_00320_Final_Vol2_Part1-3
Pages from 2015_00320_Final_Vol2_Part1-4
Pages from 2015_00320_Final_Vol2_Part1-5
Pages from 2015_00320_Final_Vol2_Part1-6
Pages from 2015_00320_Final_Vol2_Part1-7
Pages from 2015_00320_Final_Vol2_Part1-8

File details come from the government source that posted it. Updated .