Addendum_No.2_with_Attachments.pdf
PDF 872 KB Posted
- Solicitation number
- RFQ 25-718
- Issued by
- Volusia County, Orlando City, Florida
About this file
The documents are a series of fire extinguisher inspection and maintenance reports from Pye-Barker Fire & Safety for New Smyrna Beach Utilities, covering multiple facilities located in New Smyrna Beach, Florida. The reports document annual fire extinguisher inspections conducted on September 23, 2024, at various utility sites including the main commission building, water reclaim facility, water treatment facility, generation site, substation, and other locations. Each report includes a comprehensive itemized list of fire extinguishers at each site, detailing their manufacturer, size, agent type, serial number, manufacturing date, and maintenance status.
The inspection reports consistently show no deficiencies were found during the surveys. Fire extinguishers were assessed for proper size, accessibility, mounting, and overall condition. Most extinguishers are ABC-type (multi-purpose) with sizes ranging from 2.5 to 20 pounds, manufactured by brands including Ansul, Amerex, Buckeye, and Badger. The reports indicate that all units were either recently inspected or will have their next six-year maintenance (6YM) or hydrostatic testing due by September 2030. The consistent use of a standardized reporting format and thorough documentation suggests a comprehensive, systematic approach to fire safety equipment maintenance across New Smyrna Beach Utilities' various facilities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| BID_TAB_25-718.xlsx | XLSX spreadsheet | |
| RFQ_25-718_Addendum_1.pdf | ||
| 25-718_Fire_Extinguisher_Inspections_&_Service_8-14-25.pdf | ||
| 25-718_Fire_Extinguisher_Inspections_&_Service_8-14-25.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NEW SMYRNA BEACH UTILITIES
200 CANAL STREET
P.O. BOX 100
NEW SMYRNA BEACH, FL 32170-010
RFQ 25-718
Fire Extinguisher Inspections & Maintenance
Page 1 RFQ 25-718 Fire Extinguisher & Maintenance Addendum No 2
DATE: 9-3-25
RE: RFQ 25-718 ADDENDUM NO. 02
To prospective vendors:
New Smyrna Beach Utilities is issuing the following addendum. As such it becomes an integral part of the proposal and must be acknowledged by the return of this signed form, with your proposal form, acknowledging receipt of the addendum.
1. Regarding the pricing for some of the recharges, we haven’t really come across some of the sizes such as 6#, 8#, 16#, 18#, and 31# ABC’s as well as a 15# BC. Can you please clarify how many of those you have? I have attached the previous vendor's inspection reports to clarify.
2. On the second page of the pricing sheets, there is an Other category with a line item of Special.
What specifically do you mean by Special? I don’t see that any of our extinguishers would qualify as special (like a class D Fire Extinguisher). Please enter N/A on that line. See attachment listed Special
A Copy of This Signed Form Must Accompany Your Proposal
Acknowledgment of Receipt of Addenda No. 2
Company_______________________________________
Title___________________________________________
Signature_______________________________________
9/23/2024
1046PZ@pyebarkerfs.com
Bobby
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
200 Canal St FL
9046347100
Jacksonville FL 32256
386-424-3176
SERVICE TICKET:
STREET CITY STATE
8475 Western Way Ste 110
Nsb Utilities Commission 32168-7006
Pye-Barker Fire & Safety
PHONEBUILDING CONTACT
New Smyrna Beach
ST00268087
Please see the attached reports. If there are any questions, please reach out to the above office.
Download your Report at:
Signed Signed
Inspector: Building Contact:
Title:
9/23/2024 9/23/2024
Matt Tegenkamp Bobby https://customer.pyebarkerfire.com
Licenses:
Jacksonville: FED22-000076 / FED20-000005 / EF00001197 - Tampa: FPI18-000123 12259 W.
Hillsborough Ave. Unit 101, Tampa, FL 33635
ST00268087Service Ticket No. :
0000038663
Equipment Location :
Frequency :
: 32168-700632168-7006
Inspection Contract No. :
Phone 386-424-3176
200 Canal St
State
Address :
386-424-3176
Phone
State
Address Nsb Utilities CommissionOwner
FIRE EXTINGUISHER ITEMIZED
Nsb Utilities Commission
Zip
200 Canal St Property :
ST00268087
New Smyrna Beach New Smyrna BeachCity
Date :
Service Ticket No. :
9/23/2024
FL
Zip
FL
City
Annual
PO No. :
None found at time of inspection.
DEFICIENCIES
BUILDING SURVEY
General Questions What is the frequency of this service? Annual
**Does the customer have the proper size and type of fire extinguishers? Yes
Are extinguishers accessible in case of emergency? Yes
**Are all extinguishers securely mounted at the proper height? Yes
Are extinguisher locator signs recommended? No
Are protective covers or cabinets recommended for any or all extinguishers? No
Were any units serviced during this inspection/maintenance? Yes
**Are there any other deficiencies? No
Mfg DateManufacturer
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassInspectionD58895709 Upstairs Elev Lobby 1 /ABC09/2017 5 /Amerex 09/2023 /
PassInspectionH15558391322 Hall /ABC09/2022 5 /Ansul / /
PassInspectionF52560690314 /ABC09/2019 5 /Ansul 06/2022 /
PassInspectionB03630928Back Printer /ABC09/2016 5 /Badger 09/2022 /
PassInspectionPE6901842nd Offices /ABC09/1997 5 /Badger 09/2022 /
PassInspectionB05961436Bathrooms /ABC09/2016 5 /Badger 09/2022 /
PassInspectionC98455502Kitchen /ABC09/2017 5 /Badger 09/2023 /
Fire Extinguisher Itemized Page 2 of 4
• 8475 Western Way Ste 110 • Jacksonville FL • 32256
Mfg DateManufacturer
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassInspectionTF317016It Room /ABC09/2002 5 /Badger 09/2023 /
PassInspectionVP356789Roof Elev Rm /ABC09/2003 10 /Badger 09/2023 /
PassInspectionD01683835Tunnel /Water09/2017 2.5 /Amerex 09/2023 /
PassInspectionF52560715Tunnel /ABC09/2019 5 /Ansul / /
PassInspectionZD554239Tunnel /ABC09/2007 5 /Buckeye 09/2023 /
PassInspectionZD554255Tunnel /ABC09/2007 5 /Ansul 09/2023 /
PassNewI277Server Room /ABCN/A 11 09/2030Ansul / /
PassHydroXk09206Hall 209 /ABCN/A 5 09/2030Ansul N/A /
PassHydro223 /ABCN/A 5 09/2030Ansul N/A /
PassInspectionB09456199216 /ABC09/2016 5 /Amerex 08/2022 /
PassInspectionC667432Elev Lobby 2nd /ABC09/2009 5 /Buckeye 09/2022 /
PassHydroElev Lobby /ABCN/A 5 09/2030Ansul N/A /
PassInspection KM00537478121 /ABC09/1992 5 /Buckeye 09/2020 /
PassHydroXl929838118 /ABCN/A 5 09/2030Amerex / /
PassInspectionZD554245Offices /ABC09/2007 5 /Ansul 09/2023 /
PassInspectionF83488416103 /ABC09/2019 5 /Ansul / /
PassHydroWl020806Exit Door /ABCN/A 5 09/2030Amerex / /
PassInspectionM522517Exit By Stairs /ABC09/2009 5 /Ansul 09/2023 /
PassInspectionZD554125109 /ABC09/2007 5 /Ansul 09/2023 /
PassInspectionSP898673 Hall To Maintenance /ABC09/2001 5 /Buckeye 09/2023 /
PassInspectionB80054486Maintenance /ABC09/2017 10 /Badger 09/2023 /
PassInspectionAZ589459Maintenance /ABC09/2012 5 /Ansul 08/2021 /
PassHydroHo9068965Drive Thru /ABCN/A 5 09/2030Buckeye N/A /
PassInspectionF72490846Vehicles /ABC09/2019 2.5 /Ansul / /
PassInspectionE88644333Vehicles /ABC09/2019 2.5 /Kidde / /
PassInspectionH07973824Vehicles /ABC09/2022 2.5 /Other / /
PassInspectionC328922Vehicles /ABC09/2009 2.5 /Ansul 06/2021 /
PassInspectionF72490844Vehicles /ABC09/2019 2.5 /Amerex / /
PassInspectionE88644309Vehicles /ABC09/2019 2.5 /Kidde / /
PassHydroE76830535Vehicles /ABCN/A 2.5 09/2030Other / /
PassHydroH07973836Vehicles /ABCN/A 2.5 09/2030Other / /
PassHydroE74094793Vehicles /ABCN/A 2.5 09/2030Amerex N/A /
PassHydroXG89518Vehicles /ABCN/A 2.5 09/2030Amerex N/A /
PassInspectionH90566952Vehicles /ABC09/2023 2.5 /Ansul / /
PassHydroE74094811 Upstairs Elev Lobby 42 /ABCN/A 2.5 09/2030Amerex N/A /
Fire Extinguisher Itemized Page 3 of 4
This report was reviewed with: Pye-Barker Fire & Safety
SIGNATURE
Bobby
DateDate
Signature
9/23/2024
Matt Tegenkamp
9/23/2024:
:Technician
Signature
Print Name
Fire Extinguisher Itemized Page 4 of 4
9/4/2024
Bobby
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
2495 Boat Ramp FL
9046347100
Jacksonville FL 32256
386-424-3176
SERVICE TICKET:
STREET CITY STATE
8475 Western Way Ste 110
New Smyrna Utilities Fleet Maintenance Facility
32168
Pye-Barker Fire & Safety
PHONEBUILDING CONTACT
New Smyrna Beach
ST00268092
Please see the attached reports. If there are any questions, please reach out to the above office.
Download your Report at:
Signed Signed
Inspector: Building Contact:
Title:
9/4/2024 9/4/2024
Matt Tegenkamp Bobby https://customer.pyebarkerfire.com
Licenses:
ST00268092Service Ticket No. :
0000038677
Equipment Location :
Frequency :
: 32168-700632168
Inspection Contract No. :
Phone 386-424-3176
2495 Boat Ramp
State
Address :
3864243176
Phone
State
Address Nsb Utilities CommissionOwner
FIRE EXTINGUISHER ITEMIZED
New Smyrna Utilities Fleet
Zip
200 Canal St Property :
ST00268092
New Smyrna Beach New Smyrna BeachCity
Date :
Service Ticket No. :
9/4/2024
FL
Zip
FL
City
Annual
PO No. :
None found at time of inspection.
DEFICIENCIES
BUILDING SURVEY
General Questions What is the frequency of this service? Annual
**Does the customer have the proper size and type of fire extinguishers? Yes
Are extinguishers accessible in case of emergency? Yes
**Are all extinguishers securely mounted at the proper height? Yes
Are extinguisher locator signs recommended? No
Are protective covers or cabinets recommended for any or all extinguishers? No
Were any units serviced during this inspection/maintenance? No
**Are there any other deficiencies? No
Mfg DateManufacturer
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassInspectionF72739567Shop 1 /ABC09/2019 10 /Ansul 09/2021 /
PassInspectionL615170Shop 2 /ABC09/2009 10 /Amerex 09/2023 /
PassInspectionC89938096Shop Stairs /ABC09/2017 10 /Amerex 09/2023 /
PassInspectionWU02678Upstairs /ABC09/2004 5 /Ansul 09/2023 /
PassInspectionW260223Breakroom /ABC09/2010 5 /Buckeye 09/2023 /
PassInspectionZ937521Shop 6 /CO211/2007 15 /Ansul 01/2023 /
PassNewI25641633Spare /ABC09/2024 5 09/2030Ansul / /
Fire Extinguisher Itemized Page 2 of 3
ST00268092Service Ticket No. :
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
This report was reviewed with: Pye-Barker Fire & Safety
SIGNATURE
Bobby
DateDate
Signature
9/4/2024
Matt Tegenkamp
9/4/2024:
:Technician
Signature
Print Name
Fire Extinguisher Itemized Page 3 of 3
9/4/2024
Bobby
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
1000 Field St FL
9046347100
Jacksonville FL 32256
386-424-3176
SERVICE TICKET:
STREET CITY STATE
8475 Western Way Ste 110
New Smyrna Utilities Generation Site
32168-7278
Pye-Barker Fire & Safety
PHONEBUILDING CONTACT
New Smyrna Beach
ST00268175
Please see the attached reports. If there are any questions, please reach out to the above office.
Download your Report at:
Signed Signed
Inspector: Building Contact:
Title:
9/4/2024 9/4/2024
Matt Tegenkamp Bobby https://customer.pyebarkerfire.com
Licenses:
ST00268175Service Ticket No. :
0000039827
Equipment Location :
Frequency :
: 32168-700632168-7278
Inspection Contract No. :
Phone 386-424-3176
1000 Field St
State
Address :
3864243176
Phone
State
Address Nsb Utilities CommissionOwner
FIRE EXTINGUISHER ITEMIZED
New Smyrna Utilities Generation Site
Zip
200 Canal St Property :
ST00268175
New Smyrna Beach New Smyrna BeachCity
Date :
Service Ticket No. :
9/4/2024
FL
Zip
FL
City
Annual
PO No. :
None found at time of inspection.
DEFICIENCIES
BUILDING SURVEY
General Questions What is the frequency of this service? Annual
**Does the customer have the proper size and type of fire extinguishers? Yes
Are extinguishers accessible in case of emergency? Yes
**Are all extinguishers securely mounted at the proper height? Yes
Are extinguisher locator signs recommended? No
Are protective covers or cabinets recommended for any or all extinguishers? No
Were any units serviced during this inspection/maintenance? Yes
**Are there any other deficiencies? No
Mfg DateManufacturer
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassHydroZ384379Generator B 1 09/2029CO203/2019 15 /Buckeye / /
PassNewI30112169Generations /ABCN/A 20 09/2030Ansul / N/A
PassInspectionG34464729Generator B 3 /CO201/2021 10 /Amerex / /
PassHydroI360972585Generator A 09/2029CO2N/A 10 /Buckeye / /
PassHydroAa81699Generator A 09/2029CO2N/A 15 /Buckeye / /
PassNewI21276511Crates /ABC03/2012 10 09/2030Ansul N/A /
PassInspectionH00074419Crates /ABC09/2021 10 /Ansul / /
ST00268175Service Ticket No. :
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassNewI30113212Generator B 8 /Purple KN/A 20 09/2030Ansul / /
PassInspectionCrates 1 /ABCN/A 10 N/AAnsul / /
PassInspectionCrates 2 /ABCN/A 10 N/AAnsul / /
PassHydroPl080706Crates 3 /ABCN/A 10 09/2030Ansul / /
This report was reviewed with: Pye-Barker Fire & Safety
SIGNATURE
Bobby
DateDate
Signature
9/4/2024
Matt Tegenkamp
9/4/2024:
:Technician
Signature
Print Name
10/25/2024
Bobby
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
1151 Field St FL
9046347100
Jacksonville FL 32256
3864243176
SERVICE TICKET:
STREET CITY STATE
8475 Western Way Ste 110
New Smyrna Utilities Substation
32168-7281
Pye-Barker Fire & Safety
PHONEBUILDING CONTACT
New Smyrna Beach
ST00322497
Please see the attached reports. If there are any questions, please reach out to the above office.
Download your Report at:
Signed Signed
Inspector: Building Contact:
Title:
10/25/2024 10/25/2024
Matt Tegenkamp Bobby https://customer.pyebarkerfire.com
Licenses:
ST00322497Service Ticket No. :
Equipment Location :
Frequency :
: 32168-728132168-7281
Inspection Contract No. :
Phone 3864243176
1151 Field St
State
Address :
3864243176
Phone
State
Address
Substations
New Smyrna Utilities SubstationOwner
Fire Extinguisher Summary Report
New Smyrna Utilities Substation
Zip
1151 Field St Property :
ST00322497
New Smyrna Beach New Smyrna BeachCity
Date :
Service Ticket No. :
10/25/2024
FL
Zip
FL
City
Annual
PO No. :
None found at time of inspection.
DEFICIENCIES
BUILDING SURVEY
General Questions What is the frequency of this service? Service Call
**Does the customer have the proper size and type of fire extinguishers? Yes
Are extinguishers accessible in case of emergency? Yes
**Are all extinguishers securely mounted at the proper height? Yes
Are extinguisher locator signs recommended? No
Are protective covers or cabinets recommended for any or all extinguishers? No
Were any units serviced during this inspection/maintenance? Yes
**Are there any other deficiencies? No
COMMON UNITS
Common Extinguishers Serviced
10# ABC 1
20# ABC 5
10# CO2 6
11# Halotron 1
TOTAL UNITS
Total Units Serviced Enter the total number of units 13
Fire Extinguisher Summary Report Page 2 of 3
ST00322497Service Ticket No. :
SIGNATURE
Bobby
DateDate
Signature
10/25/2024
Matt Tegenkamp
10/25/2024:
:Technician
Signature
Print Name
Fire Extinguisher Summary Report Page 3 of 3
Bobby
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
1151 Field St FL
9046347100
Jacksonville FL 32256
386-424-3176
SERVICE TICKET:
STREET CITY STATE
8475 Western Way Ste 110
New Smyrna Utilities 32168-7281
Pye-Barker Fire & Safety
PHONEBUILDING CONTACT
New Smyrna Beach
ST00268103
Please see the attached reports. If there are any questions, please reach out to the above office.
Download your Report at:
Signed Signed
Inspector: Building Contact:
Title:
9/23/2024 9/23/2024
Matt Tegenkamp Bobby https://customer.pyebarkerfire.com
Licenses:
ST00268103Service Ticket No. :
0000038725
Equipment Location :
Frequency :
: 32168-700632168-7281
Inspection Contract No. :
Phone 386-424-3176
1151 Field St
State
Address :
3864243176
Phone
State
Address Nsb Utilities CommissionOwner
FIRE EXTINGUISHER ITEMIZED
New Smyrna Utilities
Zip
200 Canal St Property :
ST00268103
New Smyrna Beach New Smyrna BeachCity
Date :
Service Ticket No. :
9/23/2024
FL
Zip
FL
City
Annual
PO No. :
None found at time of inspection.
DEFICIENCIES
BUILDING SURVEY
General Questions What is the frequency of this service? Annual
**Does the customer have the proper size and type of fire extinguishers? Yes
Are extinguishers accessible in case of emergency? Yes
**Are all extinguishers securely mounted at the proper height? Yes
Are extinguisher locator signs recommended? No
Are protective covers or cabinets recommended for any or all extinguishers? No
Were any units serviced during this inspection/maintenance? Yes
**Are there any other deficiencies? No
Mfg DateManufacturer
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassHydroC99269345Barn 1 /ABCN/A 10 09/2030Ansul / /
PassInspectionH21698323Barn 2 /ABC09/2022 10 /Ansul / /
PassInspectionPC613112Barn 3 /ABC09/1997 20 /Badger 09/2023 /
PassInspectionH08483831Barn 4 /Purple K09/2022 10 /Amerex / /
PassHydroXh961059Shop Building /ABCN/A 10 09/2030Amerex / /
PassHydroShop Building /ABCN/A 10 09/2030Ansul / /
PassHydroShop Building /ABCN/A 10 09/2030Ansul / /
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassInspectionC93634024Shop Building /ABC09/2017 10 /Ansul 06/2022 /
PassInspectionC825625Shop Building /ABC09/2009 10 /Buckeye 07/2021 /
PassHydroZp705159Shop Building /ABCN/A 5 09/2030Ansul / /
PassHydroZp656575Shop Building /ABCN/A 5 09/2030Buckeye N/A /
PassHydroFo6905711Barn 12 /ABCN/A 5 09/2030Buckeye / /
PassHydroE94263952Shop Office /ABCN/A 5 /Ansul N/A /
PassHydroShop Building /ABCN/A 5 09/2030Buckeye N/A /
PassHydroShop Office /ABCN/A 5 09/2030Amerex / /
PassNewI27702826Shop Office /HalotronN/A 5 09/2030Amerex / /
Pass Missing or Not
Accessible
BA431721
Substation Yard /ABC09/2012 20 /Kidde 07/2018 /
Pass Missing or Not
Accessible Y433387Substation /CO205/2002 15 /Amerex 12/2019 /
Pass Missing or Not
Accessible A95702236Substation /ABC09/2015 10 /Buckeye 05/2018 /
Pass Missing or Not
Accessible BN513904Substation /ABC09/2013 10 /Ansul 12/2019 /
Pass Missing or Not
Accessible F48136800
Substation Yard /ABC09/2018 20 /Amerex / /
Pass Missing or Not
Accessible E95724592Barn 22 /ABC09/2018 20 /Ansul / /
Pass Missing or Not
Accessible
AB564953
Schoolway Substation /ABC09/2010 20 /Badger 06/2018 /
Pass Missing or Not
Accessible
AC290140
Schoolway Substation /CO209/2014 15 /Buckeye 07/2019 /
Pass Missing or Not
Accessible
XD965002
Schoolway Substation /ABC09/2005 10 /Buckeye 09/2023 /
Pass Missing or Not
Accessible F48136797
Airport Substation /ABC09/2018 20 /Amerex / /
Pass Missing or Not
Accessible F55248823
Airport Substation /ABCN/A 20 /Ansul / /
Pass Missing or Not
Accessible F72654920
Airport Substation /ABC09/2019 20 /Ansul / /
Pass Missing or Not
Accessible
ZD554249
Airport Substation /ABC09/2007 5 /Ansul 09/2023 /
PassNewI31251056Vehicles 1 /ABC09/2020 5 09/2030Ansul / /
PassHydroVehicles 2 /ABCN/A 2.5 09/2030Ansul / /
PassInspectionWS080228Vehicles 3 /ABC09/2004 5 /Badger 09/2022 /
PassInspectionF63788348Vehicles 4 /ABC09/2019 5 /Amerex / /
PassInspectionF46632413Vehicles 5 /ABC09/2019 5 /Other / /
PassInspectionG45503451Vehicles 6 /ABC09/2021 5 /Amerex / /
PassInspectionG44403430Vehicle 16 /ABC09/2021 5 /Amerex / /
PassInspectionE88644310Vehicles 8 /ABC09/2019 2.5 /Kidde / /
PassInspectionH07973820Vehicles 9 /ABC09/2022 2.5 /Other / /
PassHydroH03969587Vehicles 10 /ABCN/A 2.5 09/2030Other / /
PassInspectionE88644334Vehicles 11 /ABC09/2019 2.5 /Kidde / /
PassInspectionF99303702Vehicles 12 /ABC09/2020 2.5 /Kidde / /
PassInspectionH90566893Vehicles 13 /ABC09/2023 2.5 /Ansul / /
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassInspectionXE474787Vehicles 14 /ABC09/2005 5 /Amerex 09/2023 /
PassInspectionZD554190Vehicles 15 /ABC09/2007 5 /Ansul 09/2023 /
PassInspectionAH200658Vehicle 16 /ABC09/2011 5 /Buckeye 09/2023 /
PassNewI25625455Fuel Tank /Purple KN/A 20 09/2030Ansul / /
This report was reviewed with: Pye-Barker Fire & Safety
SIGNATURE
Bobby
DateDate
Signature
9/23/2024
Matt Tegenkamp
9/23/2024:
:Technician
Signature
Print Name bobby
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
413 Smith St FL
9046347100
Jacksonville FL 32256
386-424-3176
SERVICE TICKET:
STREET CITY STATE
8475 Western Way Ste 110
New Smyrna Utilities 32168-7351
Pye-Barker Fire & Safety
PHONEBUILDING CONTACT
New Smyrna Beach
ST00268088
Please see the attached reports. If there are any questions, please reach out to the above office.
Download your Report at:
Signed Signed
Inspector: Building Contact:
Title:
9/23/2024 9/23/2024
Matt Tegenkamp bobby https://customer.pyebarkerfire.com
Licenses:
ST00268088Service Ticket No. :
0000038664
Equipment Location :
Frequency :
: 32168-700632168-7351
Inspection Contract No. :
Phone 386-424-3176
413 Smith St
State
Address :
3864243176
Phone
State
Address Nsb Utilities CommissionOwner
FIRE EXTINGUISHER ITEMIZED
New Smyrna Utilities
Zip
200 Canal St Property :
ST00268088
New Smyrna Beach New Smyrna BeachCity
Date :
Service Ticket No. :
9/23/2024
FL
Zip
FL
City
Annual
PO No. :
None found at time of inspection.
DEFICIENCIES
BUILDING SURVEY
General Questions What is the frequency of this service? Annual
**Does the customer have the proper size and type of fire extinguishers? N/A
Are extinguishers accessible in case of emergency? N/A
**Are all extinguishers securely mounted at the proper height? N/A
Are extinguisher locator signs recommended? N/A
Are protective covers or cabinets recommended for any or all extinguishers? N/A
Were any units serviced during this inspection/maintenance? Yes
**Are there any other deficiencies? No
Mfg DateManufacturer
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassHydrocg691207Shop 1 /ABCN/A 5 09/2030Ansul N/A /
PassHydrorf872982Office /ABCN/A 5 09/2030Buckeye N/A /
PassInspectione94709568Break Room /ABCN/A 5 /Ansul 09/2022 /
PassInspectionF72490825Shop 4 /ABC09/2019 2.5 /Ansul / /
PassInspectionH09036405Pump House /ABC09/2022 10 /Ansul / /
PassInspectionF72739571Pump House /ABC09/2019 10 /Ansul / /
PassInspectionB13368822Pump House /ABC09/2016 10 /Badger 09/2023 /
ST00268088Service Ticket No. :
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassInspectionWL81141Pump House /ABC09/2004 10 /Badger 07/2022 /
PassInspectionG20440248Vehicles 1 /ABC09/2020 5 /Other / /
PassInspectionZJ949721Vehicles 2 /ABC09/2008 5 /Kidde 07/2022 /
PassHydroVehicles 3 /ABCN/A 2.5 09/2030Buckeye / /
PassInspectionE88677946Vehicles 4 /ABC09/2019 2.5 /Kidde / /
PassInspectionE88801029Vehicles 5 /ABC09/2019 2.5 /Kidde / /
PassInspectionF82490828Vehicles 6 /ABC09/2019 2.5 /Ansul / /
PassHydroE76839948Vehicles 7 /ABCN/A 2.5 09/2030Other / /
PassHydroE87814639Vehicles 8 /ABCN/A 2.5 09/2030Kidde / /
PassHydroE72923631Vehicles 9 /ABCN/A 2.5 09/2030Kidde / /
PassInspectionE88645330Vehicles 10 /ABC09/2019 2.5 /Kidde / /
PassInspectionE76830537Vehicles 11 /ABC09/2019 2.5 /Other / /
PassInspectionE88734624Vehicles 12 /ABC09/2019 2.5 /Kidde / /
PassInspectionE88787612Vehicles 13 /ABC09/2019 2.5 /Kidde / /
PassInspectionF72490827Vehicles 14 /ABC09/2019 2.5 /Ansul / /
PassInspectionE88740590Vehicles 15 /ABC09/2019 2.5 /Kidde / /
PassInspectionE84466420Vehicles 16 /ABC09/2020 2.5 /Kidde / /
PassInspectionH13699088Vehicles 17 /ABC09/2022 20 /Amerex / /
PassHydroH90566914Vehicles 18 /ABCN/A 2.5 09/2030Ansul / /
PassInspectionH90566868Vehicles 19 /ABC09/2023 2.5 /Ansul / /
PassHydroH90566962Vehicles 20 /ABCN/A 2.5 09/2030Ansul / /
This report was reviewed with: Pye-Barker Fire & Safety
SIGNATURE
bobby
DateDate
Signature
9/23/2024
Matt Tegenkamp
9/23/2024:
:Technician
Signature
Print Name
Bobby
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
3119 State Road 44 FL
9046347100
Jacksonville FL 32256
386-424-3176
SERVICE TICKET:
STREET CITY STATE
8475 Western Way Ste 110
New Smyrna Utilities Water Reclaim Facility &
32168-8880
Pye-Barker Fire & Safety
PHONEBUILDING CONTACT
New Smyrna Beach
ST00268091
Please see the attached reports. If there are any questions, please reach out to the above office.
Download your Report at:
Signed Signed
Inspector: Building Contact:
Title:
9/23/2024 9/23/2024
Matt Tegenkamp Bobby https://customer.pyebarkerfire.com
Licenses:
ST00268091Service Ticket No. :
0000038675
Equipment Location :
Frequency :
: 32168-700632168-8880
Inspection Contract No. :
Phone 386-424-3176
3119 State Road 44
State
Address :
3864243176
Phone
State
Address Nsb Utilities CommissionOwner
FIRE EXTINGUISHER ITEMIZED
New Smyrna Utilities Water Reclaim
Zip
200 Canal St Property :
ST00268091
New Smyrna Beach New Smyrna BeachCity
Date :
Service Ticket No. :
9/23/2024
FL
Zip
FL
3129 State Road 44 City
Annual
PO No. :
None found at time of inspection.
DEFICIENCIES
BUILDING SURVEY
General Questions What is the frequency of this service? Annual
**Does the customer have the proper size and type of fire extinguishers? N/A
Are extinguishers accessible in case of emergency? N/A
**Are all extinguishers securely mounted at the proper height? N/A
Are extinguisher locator signs recommended? N/A
Are protective covers or cabinets recommended for any or all extinguishers? N/A
Were any units serviced during this inspection/maintenance? Yes
**Are there any other deficiencies? No
Mfg DateManufacturer
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassInspectionC328675 Maintenance Building /ABC09/2009 2.5 /Ansul 08/2021 /
PassInspectionF52675731 Maintenance Building /ABC09/2019 10 /Ansul 09/2021 /
PassInspectionH15448372 Maintenance Building /ABC09/2022 5 /Ansul / /
PassInspectionX533410 Maintenance Building /ABC09/2010 10 /Ansul 08/2023 /
PassHydroF56048100 Maintenance Building 09/2029CO2N/A 10 N/AAmerex / /
PassInspectionH00074524Water Plant /ABC09/2022 10 /Ansul / /
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassNewF75730054 Sodium Hypochlorite 09/2029
Water MistN/A 2.5 /Amerex / /
PassInspectionF48127831 Sodium Hypochlorite /
Water Mist09/2018 2.5 /Amerex / /
PassHydroC38655400Air Compressor /ABCN/A 2.5 09/2030Amerex N/A /
PassInspectionH00074411Electrical /ABC09/2021 10 /Ansul / /
PassHydroE82709050South Electrical /ABCN/A 5 09/2030Amerex N/A /
PassInspectionC90987314South Electrical /Purple K09/2017 20 /Amerex 09/2023 /
PassInspectionH21698303Wrf Shop /ABC09/2022 10 /Ansul / /
PassInspectionWK967947Printer /ABC09/2004 5 /Ansul 08/2022 /
PassNewI31251104Main Lab /ABCN/A 5 09/2030Ansul / /
PassInspectionSZ547744Lobby /ABC09/2002 5 /Ansul 06/2022 /
PassInspectionY648899Hedend /CO209/2004 10 /Buckeye 08/2019 /
PassInspectionAB536303Hedend /CO209/2010 15 /Amerex 08/2019 /
PassInspectionF58489989 Power Substation Yard /ABC09/2019 20 /Badger / /
PassInspectionF58410171 Power Substation
/CO209/2019 10 /Amerex / /
PassInspectionF58410169 Power Substation
/CO209/2019 10 /Amerex / /
PassInspectionF58410137 Power Substation
/CO209/2019 10 /Amerex / /
PassInspectionF58410143 Power Substation
/CO209/2019 5 /Amerex / /
PassNewI3011985 Power Substation Yard /ABCN/A 20 09/2030Badger 09/2030 /
PassInspectionF72739561 Boat Ramp N Causeway /ABC09/2019 10 /Ansul 08/2019 /
PassNewF31251038Vehicles 1 /ABCN/A 5 09/2030Ansul N/A /
PassNewI31251131Vehicles 2 /ABCN/A 5 09/2030Ansul / /
PassInspectionF70832801Vehicles 3 /ABC09/2020 5 /Kidde / /
PassInspectionH00072151Vehicles 4 /ABC09/2021 5 /Ansul / /
PassInspectionF65749708Vehicles 5 /ABC09/2019 5 /Buckeye / /
PassHydroG10049675Vehicles 6 /ABCN/A 2.5 09/2030Kidde / /
PassHydroE94274025Vehicles 7 /ABCN/A 5 09/2030Ansul N/A /
PassInspectionI01424423Vehicles 8 /ABC09/2023 5 /Ansul / /
PassInspectionI01424416Vehicles 9 /ABC09/2023 5 /Ansul / /
PassHydroC99982861Vehicles 10 /ABCN/A 5 09/2030Ansul / /
PassNewY648499Data Center 1 /HalotronN/A 5 09/2030Amerex / /
PassNewI27977317Data Center 2 /HalotronN/A 11 09/2030Amerex / /
PassNewI28698440Data Center 3 /Purple KN/A 20 09/2030Amerex / /
SIGNATURE
Bobby
DateDate
Signature
9/23/2024
Matt Tegenkamp
9/23/2024:
:Technician
Signature
Print Name
Bobby
ZIP
SERVICE DATE:
Report Cover Page
BUILDING
2640 Paige Ave FL
9046347100
Jacksonville FL 32256
386-424-3176
SERVICE TICKET:
STREET CITY STATE
8475 Western Way Ste 110
New Smyrna Utilities Water Treatment Facility
32168-7006
Pye-Barker Fire & Safety
PHONEBUILDING CONTACT
New Smyrna Beach
ST00268089
Please see the attached reports. If there are any questions, please reach out to the above office.
Download your Report at:
Signed Signed
Inspector: Building Contact:
Title:
9/23/2024 9/23/2024
Matt Tegenkamp Bobby https://customer.pyebarkerfire.com
Licenses:
ST00268089Service Ticket No. :
0000038665
Equipment Location :
Frequency :
: 32168-700632168-7006
Inspection Contract No. :
Phone 386-424-3176
2640 Paige Ave
State
Address :
3864243176
Phone
State
Address Nsb Utilities CommissionOwner
FIRE EXTINGUISHER ITEMIZED
New Smyrna Utilities Water
Zip
200 Canal St Property :
ST00268089
New Smyrna Beach New Smyrna BeachCity
Date :
Service Ticket No. :
9/23/2024
FL
Zip
FL
City
Annual
PO No. :
None found at time of inspection.
DEFICIENCIES
BUILDING SURVEY
General Questions What is the frequency of this service? Annual
**Does the customer have the proper size and type of fire extinguishers? N/A
Are extinguishers accessible in case of emergency? N/A
**Are all extinguishers securely mounted at the proper height? N/A
Are extinguisher locator signs recommended? N/A
Are protective covers or cabinets recommended for any or all extinguishers? N/A
Were any units serviced during this inspection/maintenance? Yes
**Are there any other deficiencies? No
Mfg DateManufacturer
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassNewLime Room 1 09/2029CO2N/A 10 /Ansul / /
PassHydroVky47629 Sodium Silicofluoride /ABCN/A 5 09/2030Buckeye N/A /
PassInspectionL614606Barn /ABC07/2009 10 /Amerex 05/2022 /
PassHydroYa 524110Barn /ABCN/A 10 09/2030Ansul / /
PassHydroE75970658Barn /ABCN/A 10 09/2030Amerex / /
PassInspectionB81569964Barn /ABC07/2016 5 /Ansul 08/2022 /
PassHydroV669827Pump House /ABCN/A 10 09/2030Amerex / /
ST00268089Service Ticket No. :
FIRE EXTINGUISHER LIST
Size Agent Type
Maintenance Performed
Unit Results Serial
Number Next 6YM
Due Next Hydro
Due Location Last 6YM
Date Last Hydro
PassInspectionS172760Pump House /ABC07/2010 10 /Buckeye / /
PassInspectionBX003726Generator /ABC07/2013 5 /Badger 06/2019 /
PassInspectionD00049927Outside Gps /Purple K07/2017 20 /Amerex 09/2023 /
PassHydroD0195737 Breathing Apparatus /ABCN/A 5 09/2030Buckeye / /
PassInspectionYF571530Lockers /ABC07/2006 10 /Buckeye 09/2023 /
PassHydroVp664524Office /ABCN/A 5 09/2030Buckeye / /
PassInspectionD57553073Breakroom /ABC07/2017 5 /Amerex 09/2023 /
PassHydroYk550924Pipe Galley /ABCN/A 5 09/2030Amerex / /
PassInspectionF65749699Wtp Operations /ABC07/2019 5 /Buckeye / /
PassInspectionAC589482 South Beach Pump House /CO209/2013 15 /Amerex 01/2019 /
PassInspectionSG853695Taps 3rd Ave /ABC07/2001 10 /Amerex 07/2019 /
PassHydroC239121Well 10 /ABCN/A 5 09/2030Buckeye / /
PassHydroXf872949Well 14 /ABCN/A 5 09/2030Buckeye / /
PassInspectionF52560666Well 12 /ABC09/2019 5 /Ansul / /
PassInspectionG02825735Vehicles 4 /ABC09/2021 5 /Badger 09/2023 /
PassInspectionSG631556Vehicles 5 /ABC09/2001 5 /Badger 09/2023 /
PassInspectionYY110820Vehicles 6 /ABC09/2007 5 /Amerex 09/2023 /
PassHydroDo6905754Office 1 /ABCN/A 5 09/2030Amerex / /
PassHydro62140022Office 2 /ABCN/A 5 09/2030Amerex / /
PassHydroAb630381Office 3 /ABCN/A 5 09/2030Amerex / /
PassHydroYk327749Office 4 /ABCN/A 5 09/2030Amerex / /
This report was reviewed with: Pye-Barker Fire & Safety
SIGNATURE
Bobby
DateDate
Signature
9/23/2024
Matt Tegenkamp
9/23/2024:
:Technician
Signature
Print Name
| RFQ 25-718 Addendum 2.pdf |
| Special |
| FIre Extinguisher COB 23 Sept 2024 |
| Fire Extinguisher Fleet 05 Sept 2024 |
| Fire Extinguisher Generations 05 Sept 2024 |
| Fire Extinguisher Substations 25 Oct 2024 |
| Fire Extinguisher T&D 23 Sept 2024 |
| Pye Barker Smith Street Annual Inspection |
| Pye Barker WRF Annual Inspections |
| Pye Barker WTP Annual Inspection |