AB24115 Bradford County Courthouse M DSS.pdf
PDF 3 MB Posted
- Attached to
- Bradford County Courthouse Renovation
- Solicitation number
- 145686
- Issued by
- Broward County, Florida
About this file
Bradford County Courthouse Renovation - Mechanical Documentation
This document set comprises mechanical design and specification sheets for the interior renovation of the Bradford County Courthouse located at 945 N Temple Avenue, Starke, Florida. The project, identified as AB24115, is being designed by Akin Brooks Engineering, Inc. and includes comprehensive HVAC system modifications across the first and second floors of the facility. The scope of work encompasses demolition of existing diffusers, exhaust grilles, return grilles, and specified ductwork; installation of new supply diffusers, return air grilles, and exhaust grilles with reconnection to existing ductwork where applicable; and complete testing, adjusting, and balancing of all mechanical systems. The mechanical work is governed by the Florida Building Code (8th Edition, 2023), Florida Fire Prevention Code, NFPA standards, and industry standards including ASHRAE 62.1, SMACNA, and AMCA specifications. The project is issued at 100% construction documents status as of February 27, 2026, with a drawing date of March 2, 2026.
The specifications detail extensive requirements for metal ductwork fabrication and installation, requiring compliance with SMACNA HVAC duct construction standards and achieving air-tight systems with leakage rates not exceeding 3% for low-pressure systems and 1% for systems rated over 3" W.G. Flexible ductwork is limited to maximum lengths of 6 feet with R-6 insulation minimum. All ductwork shall be externally insulated with 2.2 inches of fiberglass blanket insulation achieving R-6 minimum installed value. Test and balance tolerances require supply air, return air, and outdoor air quantities to be balanced within 5% of design values, with exhaust fans balanced within 10% of design. The contractor is responsible for pre-construction testing of existing equipment (AC-1, AC-2, and exhaust systems), submission of shop drawings for ductwork layout and coordination with structural elements, and completion of pressure testing and duct leakage verification prior to system operation. Additional requirements include vibration isolation for all units, access panels for non-accessible construction, fire damper installation where systems penetrate fire-rated assemblies, and comprehensive as-built documentation on contractor field sets of drawings.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL LEGEND
MD
G
F
FS
S
D
H
T
M
M
M
XXX - ###
S
SUPPLY DIFFUSER
RETURN GRILLE
EXHAUST GRILLE
RECTANGULAR ELBOW - MITERED - WITH TURNING VANES
RECTANGULAR ELBOW - MITERED
RECTANGULAR CROSS
RECTANGULAR TEE
ROUND CROSS
ROUND TEE
ROUND ELBOW - 1D
ROUND ELBOW - 1.5D
ROUND ELBOW - 2D
ROUND TAKEOFF WITH DAMPER - CONICAL
ROUND TAKEOFF WITH DAMPER
MOTORIZED DAMPER
GRAVITY DAMPER
FIRE DAMPER
FIRE & SMOKE DAMPER
SMOKE DAMPER
DUCT-MOUNTED SMOKE DETECTOR W/ ACCESS PANEL
ROOM HUMIDISTAT. MOUNT TOP AT 48" AFF
ROOM THERMOSTAT - TEMPERATURE & HUMIDITY. MOUNT
TOP AT 48" AFF
AIRTROL FITTING
AUTOMATIC AIR VENT WITH VALVE
AUTOMATIC BALANCING VALVE
BACKFLOW PREVENTER
VALVE. SEE SPECIFICATIONS FOR TYPE.
CALIBRATED BALANCING VALVE
CHECK VALVE
CONCENTRIC REDUCER
ECCENTRIC REDUCER
FILL VALVE
FLEXIBLE PIPE CONNECTION
PRESSURE GAUGE
PRESSURE OR TEMPERATURE TEST PORT
INLINE STRAINER
INLINE STRAINER WITH BLOWDOWN VALVE
WITH THREADED CONNECTION AND CAP
PLUG VALVE
PRESSURE REDUCING VALVE
RELIEF VALVE
SPEED CONTROLLER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
THERMOMETER
THERMOMETER WELL
UNION; DIELECTRIC WATERWAY (SEE SPECIFICATIONS)
VENTURI FLOW METER
DOOR GRILLE
WATER METER
CONNECT TO EXISTING
UNIT SYMBOL WITH UNIT NUMBER
SA
RA
EA
OA
SA
RA
EA
OA
SA
RA
EA
OA
SUPPLY AIR
RETURN AIR
EXHAUST
OUTSIDE AIR
NEW WORK EXISTING DEMOLITION
DUCT LEGEND
GENERAL NOTES
THE FOLLOWING NOTES ARE TO DEMONSTRATE MINIMUM MECHANICAL CODE COMPLIANCE ONLY. CONTRACTOR IS RESPONSIBLE FOR THE FULL WRITTEN SPECIFICATIONS. IF ANY INCONSISTENCIES ARE PRESENT, THE FULL WRITTEN
SPECIFICATIONS PREVAIL.
AIR DISTRIBUTION:
1. VERIFY COLLAR SIZES ON ALL EQUIPMENT INLETS AND OUTLETS. TRANSITION DUCTWORK AS NECESSARY. EXTERNALLY INSULATE TRANSITIONS AT EQUIPMENT CONNECTIONS.
2. PROVIDE DUCT FLEX CONNECTIONS FOR ALL UNITS. EXTERNALLY INSULATE FLEXIBLE CONNECTIONS.
3. ALL EXHAUST DUCTWORK RUNOUTS SHALL BE RIGID DUCT.
4. DUCT SIZES ARE SHEET METAL SIZES. NO DUCTWORK SHALL RUN PARALLEL WITH AND OVER WALLS.
5. CONTRACTOR SHALL VERIFY CLEARANCE SPACE AVAILABLE, OFFSETS REQUIRED, STRUCTURAL OPENINGS, AND WORK BY OTHER TRADES PRIOR TO FABRICATION OF DUCTWORK. SUBMIT SHOP DRAWINGS ON DUCTWORK LAYOUT.
COORDINATE WITH ROOF TRUSSES/STRUCTURE. PRESSURE TEST ALL DUCTWORK FOR LEAKS. SEE SPECIFICATIONS. RETURN AND EXHAUST DUCT SHALL BE TESTED UNDER NEGATIVE PRESSURE.
EQUIPMENT:
1. PROVIDE FULL SIZE COPPER CONDENSATE DRAINS FROM ALL UNITS TO DISPOSAL POINT INDICATED ON THE DRAWINGS.
2. PROVIDE A TRAP ON ALL CONDENSATE DRAIN OUTLETS. SLOPE ALL CONDENSATE DRAIN PIPING -1/8" INCH PER FOOT.
3. CONTRACTOR SHALL INSTALL ALL EQUIPMENT, PIPING, AND DUCTWORK SUCH THAT MANUFACTURER'S RECOMMENDED CLEARANCES ARE MET FOR ALL ACCESS PANELS, MOTORS, FANS, BELTS, FILTERS AND AIR INTAKES.
4. PROVIDE VIBRATION ISOLATORS FOR ALL UNITS. SEE SPECIFICATIONS AND DETAILS.
5. PROVIDE ACCESS PANELS IN ALL NON-ACCESSIBLE CONSTRUCTIONS (INCLUDING CEILING, WALLS, ETC) SIZED AND LOCATED AS REQUIRED TO PROVIDE PROPER SERVICE ACCESS IN ACCORDANCE WITH THE MANUFACTURERS
RECOMMENDATION FOR ALL HVAC EQUIPMENT INCLUDING DAMPERS AND VALVES.
6. ALL HVAC EQUIPMENT TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND UNDER SUPERVISION OF MANUFACTURER'S REPRESENTATIVE.
CONTROLS:
1. MAINTAIN A MINIMUM OF 3'-6" SEPARATION FROM THE HVAC CONTROL WIRING AND OTHER DATA, TV, OR PHONE WIRING TO PREVENT ANY INTERFERENCE.
2. ALL LOW VOLTAGE CONTROL WIRING SHALL COMPLY WITH SPEC AND IN ACCORDANCE WITH ELECTRICAL SPEC REQUIREMENTS.
3. PROVIDE ALL SOFTWARE, PROGRAMMING, GRAPHICS, AND RELATED INTERFACE TO MONITOR THE HVAC SYSTEM VIA INTERNET LOGIN.
GENERAL:
1. PRIOR TO COMMENCING ANY WORK, THE CONTRACTOR SHALL SATISFY HIMSELF AS TO THE ACCURACY OF ALL DATA AS INDICATED IN THESE PLANS AND SPECIFICATIONS AND/OR AS PROVIDED BY THE OWNER. SHOULD THE CONTRACTOR DISCOVER ANY INACCURACIES, ERRORS, OR OMISSIONS IN THE DATA, HE SHALL IMMEDIATELY NOTIFY THE ARCHITECT/ENGINEER IN ORDER THAT PROPER ADJUSTMENTS CAN BE ANTICIPATED AND ORDERED.
2. COMMENCEMENT BY THE CONTRACTOR OF ANY WORK SHALL BE HELD AS AN ACCEPTANCE OF THE DATA BY HIM AFTER WHICH TIME THE CONTRACTOR HAS NO CLAIM AGAINST THE OWNER RESULTING FROM ALLEGED ERRORS, OMISSIONS, OR INACCURACIES OF THE SAID DATA.
3. ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND COMPLETED IN A FIRST-CLASS WORKMANLIKE MANNER AND IN ACCORDANCE WITH THE BEST MODERN METHODS AND PRACTICE. ANY MATERIALS INSTALLED WHICH DO NOT PRESENT AN ORDERLY AND REASONABLY NEAT AND/OR WORKMANLIKE APPEARANCE, OR DO NOT ALLOW ADEQUATE SPACE FOR MAINTENANCE, SHALL BE REMOVED AND REPLACED WHEN SO DIRECTED BY THE
ARCHITECT/ENGINEER.
4. IT IS THE CONTRACTOR'S RESPONSIBILITY TO SEE THAT ALL EQUIPMENT AND DEVICES THAT MAY REQUIRE MAINTENANCE AND OPERATION ARE MADE EASILY ACCESSIBLE, REGARDLESS OF THE DIAGRAMMATIC LOCATION SHOWN ON
THE DRAWINGS.
5. THE CONTRACTOR SHALL PROTECT EQUIPMENT AND MATERIAL AT ALL TIMES. HE SHALL REPLACE ALL EQUIPMENT AND MATERIAL WHICH ARE DAMAGED AS A RESULT OF INADEQUATE PROTECTION.
6. THOROUGHLY CLEAN ALL EXPOSED PARTS OF APPARATUS AND EQUIPMENT AND REMOVE ALL OIL AND GREASE SPOTS. REPAINT OR TOUCH UP AS REQUIRED TO LOOK LIKE NEW. DURING PROGRESS OF WORK, CONTRACTOR IS TO
CAREFULLY CLEAN UP AND LEAVE PREMISES AND ALL PORTIONS OF BUILDING FREE FROM DEBRIS AND IN A CLEAN AND SAFE CONDITION.
7. DURING THE PROGRESS OF THE WORK, THE CONTRACTOR SHALL RECORD ON THEIR FIELD SET OF DRAWINGS (AS-BUILTS) THE EXACT LOCATION, AS INSTALLED, OF ALL PIPING, DUCTWORK, EQUIPMENT, AND OTHER SYSTEMS WHICH
ARE NOT INSTALLED EXACTLY AS SHOWN ON THE CONTRACT DOCUMENTS.
GENERAL
1. THE WORK COVERED BY THIS DIVISION CONSISTS OF PROVIDING ALL LABOR, EQUIPMENT AND MATERIALS AND PERFORMING ALL OPERATIONS NECESSARY FOR THE INSTALLATION OF THE MECHANICAL WORK AS HEREIN CALLED
FOR AND SHOWN ON THE DRAWINGS.
CODES
1. ALL WORK UNDER DIVISION 23 SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE CODES LISTED HEREIN. THE DESIGN HAS BEEN BASED ON THE REQUIREMENTS OF THESE CODES; AND WHILE IT IS NOT THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THAT ALL WORK CALLED FOR COMPLIES WITH THESE CODES, HE SHALL BE RESPONSIBLE FOR CALLING TO THE ARCHITECT/ENGINEER'S ATTENTION ANY DRAWINGS OR SPECIFICATIONS THAT ARE NOT IN CONFORMANCE WITH THESE OR OTHER CODES PRIOR TO ORDERING EQUIPMENT OR INSTALLING WORK.
2. COMPLY WITH REGULATIONS AND CODES OF UTILITY SUPPLIERS.
3. WHERE NO SPECIFIC METHOD OR FORM OF CONSTRUCTION IS CALLED FOR IN THE CONTRACT DOCUMENTS, THE
CONTRACTOR SHALL COMPLY WITH CODE REQUIREMENTS WHEN CARRYING OUT SUCH WORK.
4. WHERE CODE CONFLICT EXISTS, GENERALLY THE MOST RESTRICTIVE REQUIREMENT APPLIES. COMPLY WITH
CURRENT CODE EDITION, UNLESS NOTED.
5. ADDITIONAL CODES OR STANDARDS APPLYING TO A SPECIFIC PART OF THE WORK MAY BE INCLUDED IN THAT
SECTION.
6. THE FOLLOWING CODES GOVERN THE WORK:
A. FLORIDA BUILDING CODE - BUILDING - 8TH EDITION (2023).
B. FLORIDA BUILDING CODE - MECHANICAL - 8TH EDITION (2023).
C. FLORIDA BUILDING CODE - ENERGY CONSERVATION - 8TH EDITION (2023).
D. FLORIDA BUILDING CODE - TEST PROTOCOLS FOR HIGH VELOCITY HURRICANE ZONES - 8TH EDITION (2023).
E. FLORIDA FIRE PREVENTION CODE - 8TH EDITION (2023).
a. UNIFORM FIRE CODE (NFPA 1) - 2021 FLORIDA EDITION
b. LIFE SAFETY CODE (NFPA 101) - 2021 FLORIDA EDITION
F. NATIONAL ELECTRIC CODE (NFPA 70) - 2020.
G. STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS (NFPA 90A).
a. 2015 IN ACCORDANCE WITH FBC - MECHANICAL - EIGHTH EDITION (2023)
b. 2021 IN ACCORDANCE WITH FAC 69A-3.012 STANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION
AND OTHER STANDARDS ADOPTED.
H. VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY (ASHRAE 62.1) - 2019
STANDARDS
1. ALL DIVISION 23 MATERIALS, INSTALLATION AND SYSTEMS SHALL MEET THE REQUIREMENTS OF THE FOLLOWING STANDARDS, INCLUDING THE LATEST ADDENDA AND AMENDMENTS, TO THE EXTENT REFERENCED:
A. UNDERWRITERS' LABORATORIES (UL)
B. AMERICAN NATIONAL STANDARDS INSTITUTION (ANSI)
C. AMERICAN SOCIETY OF TESTING MATERIALS (ASTM)
D. NATIONAL FIRE PROTECTION (NFPA)
E. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
F. AIR CONDITIONING AND REFRIGERATION INSTITUTE (ARI)
G. SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION (SMACNA)
H. AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR CONDITIONING ENGINEERS (ASHRAE)
I. AIR MOVEMENT AND CONTROL ASSOCIATION (AMCA)
J. STANDARD FOR SMOKE CONTROL SYSTEMS (NFPA 92) – 2018
K. STANDARDS OF THE HYDRONIC INSTITUTE (IBR)
CODES & STANDARDS
ABBREVIATIONS
(UNABRIDGED)
A AMPS; AREA
AAV AUTOMATIC AIR VENT
ABV CLG ABOVE FINISHED CEILING
AC AIR CONDITIONING UNIT
ACH AIR CHANGE PER HOUR
AFF ABOVE FINISHED FLOOR
AH ATOMIZING HUMIDIFIER
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AL ALUMINUM
AM AIRFLOW MONITOR
AMS AIRFLOW MEASURING STATION
AO ANALOG OUTPUT
AP ACCESS PANEL
AS AIR SEPARATOR
BD BALANCING DAMPER
BFF BELOW FINISHED FLOOR
BFP BACKFLOW PREVENTER
BTU BRITISH THERMAL UNITS
BTUH BTU PER HOUR
B BOILER
C CONDENSATE
CAC CONTROL AIR COMPRESSOR
CB CHILLED BEAM
CD CEILING DIFFUSER
CF CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CBWP CHILLED BEAM WATER PUMP
CBWS CHILLED BEAM WATER SUPPLY
CBWR CHILLED BEAM WATER RETURN
CH CHILLER
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CO CLEANOUT
CR CONDENSATE RETURN (STEAM)
CSR CURRENT SENSING RELAY
CS CURRENT SENSING (AMPS)
CT COOLING TOWER; COMPRESSION TANK
CU CONDENSING UNIT; COPPER
CV COEFFICIENT OF VALVE
DB DRY BULB
DC DUST COLLECTOR
DDC DIRECT DIGITAL CONTROLS
DEFL DEFLECTION
DG DOOR GRILLE
DI DIGITAL INPUT
DIA DIAMETER
DO DIGITAL OUTPUT
DS DUCT SILENCER
DTG DOOR TRANSFER GRILLE
DTW DUAL TEMPER WATER
DTWR DUAL TEMPER WATER RETURN
DTWS DUAL TEMPER WATER SUPPLY
EA EACH
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EG EXHAUST GRILLE
EH EXHAUST HOOD
ENT ENTERING
ER EXHAUST REGISTER
ESP EXTERNAL STATIC PRESSURE
EV EXHAUST VALVE
EWT ENTERING WATER TEMPERATURE
EXST,X, EX EXISTING
EXH EXHAUST
°F DEGREES FAHRENHEIT
FBC FLORIDA BUILDING CODE
FCU FAN COIL UNIT
FD FIRE DAMPER, FLOOR DRAIN
FEV FUME EXHAUST VALVE
FG FILTER GRILLE
FH FUME HOOD
FMS FLOW MEASURING STATION
FO FLAT OVAL
FPM FEET PER MINUTE
FRP FIBERGLASS REINFORCED PLASTIC
FSC FAN SPEED CONTROLLER
FT FEET
FT WG FEET OF WATER, GAUGE
FTU FAN TERMINAL UNIT
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GEV GENERAL EXHAUST VALVE
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HG HOT GAS
HHW HEATING HOT WATER
HHP HEATING HOT WATER PUMP
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HP HEAT PUMP; HORSEPOWER
HPS HEAT PRESSURE SYSTEM
HR HOUR
HX HEAT EXCHANGER
ID INSIDE DIAMETER
IN. WG INCHES OF WATER, GAUGE
KW KILOWATTS
KWH KILOWATT HOUR
LAT LEAVING AIR TEMPERATURE
LB POUND
LD LINEAR DIFFUSER
LPS LOW PRESSURE STEAM
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSANDS OF BTU'S
MCF THOUSANDS OF CUBIC FEET
MD MOTORIZED DAMPER
MIN MINUTE; MINIMUM
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN, NUMBER
NTS NOT TO SCALE
OA OUTDOOR AIR
OAL OUTDOOR AIR LOUVER
OC ON CENTER
OD OUTSIDE DIAMETER
P PUMP
PCW PROCESS COOLING WATER
PCWP PROCESS COOLING WATER PUMP
PCWR PROCESS COOLING WATER RETURN
PCWS PROCESS COOLING WATER SUPPLY
PH PHASE
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PVC POLYVINYL CHLORIDE
R RADIUS
RA RETURN AIR
RD ROUND DIFFUSER
RAG RETURN AIR GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RL REFRIGERANT LIQUID
RP REDUCED PRESSURE
RPM REVOLUTIONS PER MINUTE
RAR RETURN AIR REGISTER
RS REFRIGERANT SUCTION
RV ROOF VENT
SA SUPPLY AIR
SAR, SR SUPPLY AIR REGISTER
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DAMPER
SF SQUARE FEET, SUPPLY FAN
SG SOFFIT GRILLE
SIM SIMILAR
SP STATIC PRESSURE
SPEC SPECIFICATION
SR SIDEWALL REGISTER
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STM STEAM
SV SUPPLY VALVE
TEMP TEMPERATURE
TG TRANSFER GRILLE; TEMPERATURE GAUGE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UC UNDERCUT DOOR - 3/4"
UG UNDERGROUND
UH UNIT HEATER
V VOLTS
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VFM VENTURI FLOW METER
VLV VALVE
VRF VARIABLE REFRIGERANT FLOW
VRV VARIABLE REFRIGERANT VOLUME
VVU VARIABLE VOLUME UNIT
WB WET BULB
WPD WATER PRESSURE DROP
AIR DISTRIBUTION SIZING
SUPPLY DIFFUSERS RETURN GRILLES/REGISTERS
CFM RANGE
NOMINAL DUCT
CONNECTION SIZE
0-120
125-250
255-380
385-550
555-740
8ø
6ø
10ø
12ø
14ø
16ø750-1000
CFM RANGE
NOMINAL DUCT
CONNECTION SIZE
0-175
180-300
305-450
455-650
655-900
10ø
8ø
12ø
14ø
16ø
18ø905-1200
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
H E
A
R C
H
IT
E C
T 'S
O R
T
N
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
D
S
P E
C
IF
IC
A
T
IO
N S
C O
M P
L Y
W
IT
H
T H
E A
P P
L
IC
A B
M
IN
IM
U M
B U
IL
D
G
C
O D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E T
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
I
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 3/2/2026 4:43:48 PM
MECHANICAL LEGEND,
ABBREVIATIONS, CODES AND
STANDARDS
100% CONSTRUCTION
DOCUMENTS
PJD DLB
M001
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
REVISIONS
NO: DATE: REF: BY:
eleen DLB Stamp
T
T
T
A
B
C
2 4 5 6 7
C
VAV-11
VAV-12
S.T.-1 S.T.-2
AC-1
AHU-1
VAV-5
VAV-14VAV-9
VAV-10
1 1
3 3
VAULT BACK OF HOUSE
143A
BOOKS/RECORDS
LOBBY
CONFERENCE
IT ROOM
CORRIDOR
139A
OFFICE
148L
OFFICE
148G
OFFICE
148F
OFFICE
148E
OFFICE
143T
STAIR
ELECTRIC
ADA TOILET
148H
SMALL OFFICE
148I
STORAGE
148J
MENS
WOMENS
ELEVATOR
CUSTODIAL
VSTIBULE
VESTIBULE
CORRIDOR
Room
Room
Room
VESTIBULE
KITCHEN
CLERKS OFFICE
OFFICE
VESTIBULE
148A
STORAGE
148B
STORAGE
148C
Room
Room
Room
TOILET
Room
Room
Room
Room
Room
Room
Room
TOILET
Room
Room
Room
AC-2
KEY NOTES
1. DEMOLISH ALL DIFFUSERS AND EXHAUST / RETURN GRILLES IN PROJECT
AREA.
2. DUCT RUNOUTS TO DIFFUSERS AND RETURN / EXHAUST GRILLES SHALL
BE LEFT EXISTING TO REMAIN FOR CONNECTION TO NEW DIFFUSERS /
GRILLES TO THE GREATEST EXTENT POSSIBLE UNLESS OTHERWISE
NOTED.
3. DEMOLISH DUCTWORK AS SHOWN.
4. REMOVE AND RETAIN THERMOSTATS DURING DEMOLITION.
5. DEMOLISH DUCTWORK AS SHOWN, CAP AND SEAL OPENING.
SHEET NOTES
A. MECHANICAL EQUIPMENT/ DUCTWORK SIZES, LOCATION, AND LAYOUT
SHOWN FROM EXISTING PLANS AND MAY NOT REFLECT EXACT AS-BUILT
CONDITIONS. CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND
REPORT ANY SIGNIFICANT DEVIATIONS PRIOR TO START OF DEMOLITION.
HVAC PRETEST DIRECTIONS
A. CONTRACTOR SHALL SUBMIT THE RESULTS OF PRE-TEST TO ENGINEER
OF RECORD PRIOR TO START OF ANY CONSTRUCTION.
B. AC-1 & AC-2
a. RECORD CFM, SP, AND DISCHARGE TEMP AT FULL COOL.
b. RECORD CFM, SP, AND DISCHARGE TEMP AT FULL HEAT.
c. RECORD AIRFLOW AT EACH DIFFUSER CONNECTED TO UNIT.
C. RETURN GRILLES
a. RECORD AIRFLOW AT RETURN GRILLES. WHEN RECORDING RETURN
AIRFLOW, ENSURE ALL DOORS IN THE SPACE ARE SHUT.
D. EXHAUST SYSTEM
a. RECORD CFM AT EACH EXHAUST GRILLE IN PROJECT AREA.
b. RECORD ASSOCIATED EXHAUST FAN TOTAL AIRFLOW, SP, EQUIPMENT NAMEPLATE, AND CONDITION IN REPORT.
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 3/2/2026 4:43:52 PM
MECHANICAL FIRST FLOOR PLAN -
DEMOLITION
100% CONSTRUCTION
DOCUMENTS
PJD DLB
M111
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 MECHANICAL FIRST FLOOR PLAN - DEMOLITION
REVISIONS
NO: DATE: REF: BY:
NOT IN PROJECT SCOPE
T T T
TTT
T
T
T
T
T
A
B
C
2 4 5 6 7
JURY ROOM
JURY ROOM
TOILET
TOILET
PRISONER DETENTION
PRISONER DETENTION
CIRCUIT JUDGE JUDICIAL ASSISTANT
TOILET
Unoccupied
Unoccupied
CIRCUIT JUDGE
CIRCUIT JUDGE JUDICIAL ASSISTANT
TOILET
HEARING ROOM
OFFICE
VISITING JUDGE
LACTATION ROOM
JURY ROOM
203A
TOILET
TOILET
COURTROOM
203B
COORIDOR
PUBLIC
203C
SECRETARY
JUDICIAL HEARING OFFICER
ELEVATOR
CUSTODIAL
WOMENS
MENS
CORRIDOR
DEPUTY'S ROOM
DEPUTY'S ROOM
NORTH COURTROOM
SOUTH COURTROOM
COURT REPORTER
COURT REPORTER
OFFICE
OFFICE
217OFFICE
OFFICE / RECEPTION
HALL
WAITING
STORAGE
VAULT
FILES
COUNTY JUDGE
LIBRARY
COUNTY JUDGE
HEARING ROOM
Unoccupied
Unoccupied
TOILET
STORAGE
STAFF
TOILET
Unoccupied
Unoccupied
TOILET
TOILET
VAV-44
VAV-28
VAV-36
VAV-53
VAV-21VAV-22
VAV-51 VAV-50 VAV-49 VAV-48
VAV-38
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 3/2/2026 4:43:55 PM
MECHANICAL SECOND FLOOR
PLAN - DEMOLITION
100% CONSTRUCTION
DOCUMENTS
PJD DLB
M112
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
REVISIONS
NO: DATE: REF: BY:
N
SCALE: 1/8" = 1'-0"
1 MECHANICAL SECOND FLOOR PLAN - DEMOLITION
KEY NOTES
1. DEMOLISH ALL DIFFUSERS AND EXHAUST / RETURN GRILLES IN PROJECT
AREA.
2. DEMOLISH DUCTWORK, RUNOUTS, AND FLEX CONNECTIONS FOR
DIFFUSERS/GRILLES AS REQUIRED TO TRANSISTION TO NEW
DIFFUSERS/GRILLES.
3. REMOVE AND RETAIN THERMOSTAT FOR REINSTALLATION.
SHEET NOTES
A. DUCTWORK AND DIFFUSER LAYOUT AND QTY ARE TAKEN FROM EXISTING
DRAWINGS AND MAY NOT REFLECT EXACT AS-BUILT CONDITIONS.
CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND REPORT ANY
SIGNIFICANT DEVIATIONS PRIOR TO START OF DEMOLITION.
B. AHU-2 SERVING 2ND FLOOR IS LOCATED IN ROOFTOP PENTHOUSE.
NOT IN PROJECT SCOPE
HVAC PRETEST DIRECTIONS
A. CONTRACTOR SHALL SUBMIT THE RESULTS OF PRE-TEST TO ENGINEER
OF RECORD PRIOR TO START OF ANY CONSTRUCTION.
B. EXHAUST SYSTEM
a. RECORD CFM AT EACH EXHAUST GRILLE IN PROJECT AREA.
b. RECORD ASSOCIATED EXHAUST FAN TOTAL AIRFLOW, SP, EQUIPMENT NAMEPLATE, AND CONDITION IN REPORT.
T
T
T
A
B
C
2 4 5 6 7
NOT IN PROJECT SCOPE
1 1
BOOKS/RECORDS
LOBBY
VAV-5
VAV-10
VAV-11
VAV-12
AC-1
AHU-1
10x12 SA 10x12 SA x1
S
A
4-2408 CD-1
130CFM EA
2408 CD-1
150CFM
2408 CD
150CFM EA
x1
S
A
16x12 SA 10x10 SA x1
S
A x1
S
A
8x6 EA
12x12 EG 75CFM 8x4 EA
8x4 EA
12x12 EG
75CFM
4-36X2 LD
150CFM EA
12x12 EG
75CFM
8x4 EA
STORAGE
148J
SMALL OFFICE
148I
OFFICE
148L
OFFICE
148G
OFFICE
148F
OFFICE
148E
OFFICE
143T
CORRIDOR
148M
STAIR
ELECTRIC
VAULT BACK OF HOUSE
143A
Room
Room
Room
CORRIDOR
139A
TOILET
TOILET
STORAGE
148B
STORAGE
148C
VESTIBULE
148A
OFFICE
CLERKS OFFICE
KITCHEN
Room
Room
Room
VESTIBULE
CORRIDOR
WOMENS
MENS
ELEVATOR
CUSTODIAL
VSTIBULE
VESTIBULE
CORRIDOR
Room
Room
Room
Room
Room
Room
Room
Room
Room
CORRIDOR
2408 CD
200CFM2408 CD
125CFM
2408 CD
125CFM
2408 CD
125CFM
4-2406 CD
100CFM EA
2406 CD-1
100CFM
250CFM
2408 CD
75CFM
2406 CD
50CFM
2406 CD
30CFM
2406 CD-1
50CFM
10-2408 CD
200CFM EA
2-2416 RAR-1
750CFM EA
750CFM
2412 FRR
500CFM
ADA TOILET
148H
1208 CD
200CFM
1208 CD
200CFM
12X12 EG
300CFM
12X12 EG
200CFM
12x8 EA x1
S
A x1
S
A
16x16 SA x8
S A x8
S A
12x8 SA
12x8 SA x1
S
A
22x12 SA 16x12 SA 12x12 SA 10x10 SA
24x24 RA
8x
E A
WORK ROOM
AC-2
UC
16x16 RA
F
RETURN UP TO CEILING 16X24 OA
INTAKE LOUVER
EX 11 SQ FT RETURN
AIR OPENING IN WALL
RG
RG
RG
F
18x18 DTG
18x18 DTG18x18 DTG
UC
UC
UC
UC
CAP
UC
UCUC
UC
2410 TG
200CFM
24X24RAR-1
600CFM
14x14 RA x1
R
A
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 3/2/2026 4:43:57 PM
MECHANICAL FIRST FLOOR PLAN -
NEW WORK
100% CONSTRUCTION
DOCUMENTS
M211
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 MECHCANICAL FIRST FLOOR PLAN - NEW WORK REVISIONS
NO: DATE: REF: BY:
KEY NOTES
1. PROVIDE ALL NEW DIFFUSERS AND EXHAUST / RETURN GRILLES IN
PROJECT AREA. RECONNECT TO EXISTING DUCTWORK AS INDICATED.
FLEXIBLE DUCT RUNS SHALL NOT EXCEED 8'-0".
2. EXISTING FILTERED RETURN IN CEILING. PROVIDE NEW GRILLE AND
FILTER.
3. REINSTALL THERMOSTAT REMOVED DURING DEMOLITION.
4. CONTRACTOR SHALL FIX SAGGING AND PINCHED VAV BOX INLET
DUCTWORK ALL THE WAY BACK TO MAIN TAKEOFF TO ENSURE SMOOTH
AIRFLOW. WITH NO SHARP BENDS OR KINKS IN FLEXIBLE DUCT.
5. ADJUST BAS SETPOINT FOR VAV MAX CFM SETPOINT AS DESCRIBED IN
TAB DIRECTIONS.
SHEET NOTES
A. MECHANICAL EQUIPMENT/ DUCTWORK SIZES, LOCATION, AND LAYOUT
SHOWN FROM EXISTING PLANS AND MAY NOT REFLECT EXACT AS-BUILT
CONDITIONS. CONTRACTOR SHALL VERIFY FIELD CONDITIONS AS
REQUIRED PRIOR TO COMMENCEMENT OF NEW WORK.
B. THE PROJECT AREA UTILIZES AN EXISTING RETURN AIR PLENUM IN THE
MAIN CORRIDORS. ALL NEW WORK MATERIALS ABOVE CEILING SHALL BE
PLENUM RATED.
C. IF PRETEST OF EXHAUST SYSTEM REVEALS THAT EXISTING EQUIPMENT
WILL NOT SATISFY CODE MINIMUM REQUIREMENTS, EOR SHALL ISSUE
FIELD ORDER TO UPGRADE THE EXHAUST SYSTEM.
TEST AND BALANCE DIRECTIONS
A. SEE SPECIFICATIONF OR FULL TAB DIRECTIONS.
B. VAV BOX TOTALS SHALL BE BALANCED TO EXISTING SCHEDULED
VALUES.
C. BALANCE AHU-1 OA SETPOINT TO 1,100 CFM.
D. BALANCE AC-1 OA SETPOINT TO 150 CFM.
E. BALANCE VAV-11 MAX CFM SETPOINT TO 670 CFM.
F. BALANCE VAV-12 MAX CFM SETPOIN TO 600 CFM.
T T TT
T
T
T
T
T
A
B
C
2 4 5 6 7
C
JURY ROOM
JURY ROOM
TOILET
TOILET
PRISONER DETENTION
PRISONER DETENTION
CIRCUIT JUDGE JUDICIAL ASSISTANT
TOILET
Unoccupied
Unoccupied
CIRCUIT JUDGE
CIRCUIT JUDGE JUDICIAL ASSISTANT
TOILET
HEARING ROOM
OFFICE
VISITING JUDGE
LACTATION ROOM
JURY ROOM
203A
TOILET
TOILET
COURTROOM
203B
COORIDOR
PUBLIC
203C
SECRETARY
JUDICIAL HEARING OFFICER
ELEVATOR
CUSTODIAL
WOMENS
MENS
CORRIDOR
DEPUTY'S ROOM
DEPUTY'S ROOM
NORTH COURTROOM
SOUTH COURTROOM
COURT REPORTER
COURT REPORTER
OFFICE
OFFICE
217OFFICE
OFFICE / RECEPTION
HALL
WAITING
STORAGE
VAULT
FILES
COUNTY JUDGE
LIBRARY
COUNTY JUDGE
HEARING ROOM
Unoccupied
Unoccupied
TOILET
STORAGE
STAFF
TOILET
Unoccupied
Unoccupied
TOILET
TOILET
2412CD
550 CFM
2412 CD
550CFM
2410 CD
350 CFM
2410 CD
300 CFM
2410 CD
300 CFM
2410 CD
370 CFM
12X12 EG
70CFM
12X12 EG
70CFM
12X12 EG
70CFM
12X12 EG
70CFM
6-2412 CD
400CFM EA
24x24 RG
370 CFM
24x24 RG
300 CFM
24x24 RG
300 CFM
24x24 RG
350 CFM
24x24 RAG
500 CFM
24x24 RAG
500 CFM
24X24 EG
300 CFM
24X24 EG
250 CFM
2408 CD
200 CFM
6-2412 CD
500CFM EA
4-24X24 RAG
750CFM EA
3-24X24 RAG
800CFM EA
VAV-22
VAV-21
VAV-51 VAV-50 VAV-49 VAV-48
VAV-28
VAV-44
2408 CD
220 CFM
VAV-36
VAV-38
VAV-53
2406 CD
150CFM
2406 CD
150CFM
250CFM220CFM 200CFM
12X12 EG
70CFM
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 3/2/2026 4:43:57 PM
MECHANICAL SECOND FLOOR
PLAN - NEW WORK
100% CONSTRUCTION
DOCUMENTS
PJD DLB
M212
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
REVISIONS
NO: DATE: REF: BY:
NOT TO SCALE
1 MECHANICAL SECOND FLOOR PLAN - NEW WORK
KEY NOTES
1. PROVIDE ALL NEW DIFFUSERS AND EXHAUST / RETURN GRILLES IN
PROJECT AREA AS SHOWN. RECONNECT TO EXISTING DUCTWORK.
FLEXIBLE DUCT RUNS SHALL NOT EXCEED 8'-0"; EXHAUST DUCT SHALL
BE HARD DUCTED.
2. REINSTALL THERMOSTAT REMOVED DURING DEMOLITION.
3. BALANCE DIFFUSERS TO PRE-TEST RECORDED VALUES.
SHEET NOTES
A. EXISTING MECHANICAL DUCTWORK SIZES NOT PROVIDED DUE TO LACK OF AVAILABLE
INFORMATION ON AS-BUILT DOCUMENTS. CONTRACTOR SHALL VERIFY DUCT SIZES AS
NECESSARY PRIOR TO ORDERING MATERIALS FOR TAKEOFFS TO ENSURE
COMPATABILITY.
B. THE PROJECT AREA UTILIZES AN EXISTING RETURN AIR PLENUM. ALL NEW WORK
MATERIALS ABOVE CEILING SHALL BE PLENUM RATED.
C. AHU-2 SERVING THE 2ND FLOOR IS EXISTING TO REMAIN AND LOCATED IN MECHANICAL
ROOM ON ROOF.
D. IF PRETEST OF EXHAUST SYSTEM REVEALS THAT EXISTING EQUIPMENT WILL NOT
SATISFY CODE MINIMUM REQUIREMENTS, EOR SHALL ISSUE FIELD ORDER TO UPGRADE
THE EXHAUST SYSTEM.
TEST AND BALANCE DIRECTIONS
A. BALANCE ALL DIFFUSERS TO CFM VALUES INDICATED.
B. VAV BOX TOTALS SHALL BE BALANCED TO EXISTING SCHEDULED VALUES.
C. BALANCE EXHAUST GRILLES TO CFM INDICATED. IF AIRFLOW CANNOT BE
SATISFIED, CONTACT EOR IMMEDIATELY.
D. BALANCE AHU-2 OA SETPOINT TO 3,500 CFM.
MAIN DUCT
FINISHED CEILING
NOTES:
1. DETAIL IS FOR CONCEALED DUCT. WHERE EXPOSED, DUCT RUNOUTS SHALL BE DOUBLE WALL HARD DUCT ALL THE
WAY TO DIFFUSER/GRILLE.
2. PROVIDE ADAPTER WITH SIDE CONNECTION WHERE OBSTRUCTIONS DO NOT ALLOW CONNECTION TO TOP. IF SIDE
ADAPTERS ARE NEEDED AT DIFFUSER/GRILLE, NOTIFY ENGINEER.
3. FOR CEILING DIFFUSERS, FLEX DUCT SHALL BE FULL SIZE OF DIFFUSER NECK.
BALANCING DAMPER IN ALL
DUCT RUNOUTS (THIS MAY BE INTEGRAL
TO SPIN-IN). PROVIDE STANDOFF HANDLE
FOR INSULATED DUCTS.
PROVIDE
FLEXMASTER
FLEXRIGHT 90 DEG
ELBOW SUPPORTS
AND INSTALL PER
MANUFACTURER
SPEC.
SUPPLY DIFFUSERS TO BE
FACTORY INSULATED
ROUND SHEET METAL DUCT SHALL MATCH
DIFFUSER NECK SIZE AND BE INSULATED AS
REQUIRED TO MATCH MAIN DUCT
CONICAL SPIN-IN FITTING
IF CONICAL SPIN-IN CANNOT FIT,
USE SMACNA 45° RECTANGULAR
WITH TRANSITION TO ROUND
CONICAL SPIN-IN FITTING
6'-0" MAXIMUM FLEX LENGTH
PROVIDE SUPPORT STRAPS UP TO
STRUCTURER AS NECESSARY TO ELIMINATE
SAGGING AND PINCHING OF FLEX DUCT
MAIN DUCT
W/4 45°
W
(4"MIN)
4W
PROVIDE STANDOFF
ON INSULATED DUCTS
MIN LENGTH = 6X MIN LENGTH = 6X
X X
H1 H1
H2
SHEET METAL DUCT W/
2" WRAP INSULATION PLUS
1-1/2" CLEAR ALL SIDES
B E
A M
H E
IG
H
T B
O T
T O
M O
F B
E A
M /J
O
IS
T
B O
B /B
O J)
FIN. CEILING HT
FIN. FLOOR
B O
T T
O M
O F
D U
C T
B
O D
FREE AREA OF DUCT AT EASEMENT SHALL
NOT BE LESS THAN 80% OF DUCT FULL FREE
AREA. INCREASE WIDTH IF REQUIRED
FULL RADIUS ELBOW HALF RADIUS ELBOW
W
1.0 X W1.5 X W
NOTES:
1. DIMENSIONS 'A' AND 'B' MUST BE EQUAL ON SQUARE ELBOWS, UNLESS OTHERWISE SHOWN ON
DRAWINGS.
2. FULL RADIUS ELBOW SHALL BE USED AS THE STANDARD. HALF RADIUS ELBOWS SHALL ONLY BE
PERMITTED WHERE FULL RADIUS ELBOWS WILL NOT FIT. MECHANICAL CONTRACTOR SHALL
OBTAIN WRITTEN APPROVAL FROM ENGINEER PRIOR TO INSTALLATION OF HALF RADIUS ELBOWS.
W
B
A
MAINTAIN SAME DIMENSIONS
SQUARE ELBOW WITH TURNING VANES
60" MAX
1" MIN
50" DIA. MAX.24" DIA. MAX.
LOAD RATED
FASTENERS
HANGER
BAND OF
SAME SIZE
AS HANGER
STRAP
HANGER STRAPS
SCREWS MAY BE OMITTED IF
HANGER LOOPS
SCREWS
EXPANSION SHIELDS
CONCRETE ANCHORS
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 3/2/2026 4:43:58 PM
MECHANICAL DETAILS AND
SPECIFICATIONS
100% CONSTRUCTION
DOCUMENTS
PJD DLB
M301
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
REVISIONS
NO: DATE: REF: BY:
NOT TO SCALE
1 DUCT RUNOUT TO DIFFUSERS AND GRILLES
NOT TO SCALE
2 BRANCH DUCT TAKEOFF DETAIL
NOT TO SCALE
3 DUCT EASEMENT DETAIL
NOT TO SCALE
4 DUCT ELBOW DETAIL
NOT TO SCALE
5 DUCT HANGER DETAILS
1. GENERAL MECHANICAL:
A. GENERAL
a. THE WORK COVERED BY THIS DIVISION CONSISTS OF PROVIDING ALL LABOR, EQUIPMENT AND MATERIALS AND PERFORMING ALL OPERATIONS NECESSARY FOR THE INSTALLATION OF THE MECHANICAL WORK AS HEREIN CALLED FOR AND SHOWN ON THE DRAWINGS. REVIEW ALL OTHER CONTRACT DOCUMENTS TO BE AWARE OF CONDITIONS AFFECTING WORK HEREIN. PRIOR TO COMMENCING WORK, THE CONTRACTOR SHALL BE SATISFIED AS TO THE ACCURACY OF ALL DATA INDICATED ON THE DRAWINGS AND/OR PROVIDED BY THE OWNER. SHOULD THE CONTRACTOR DISCOVER ANY INACCURACIES, ERRORS, OR OMISSIONS IN THE DATA, CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER. COMMENCEMENT OF WORK BY THE CONTRACTOR SHALL BE HELD AS AN ACCEPTANCE OF THE DATA BY HIM AFTER WHICH TIME THE CONTRACTOR HAS NO CLAIM AGAINST THE OWNER RESULTING FROM ALLEGED ERRORS, OMISSIONS, OR INACCURACIES OF THE SAID DATA. MATERIALS DELIVERED TO SITE SHALL BE INSPECTED FOR DAMAGE, UNLOADED, AND STORED WITH A MINIMUM OF HANDLING. ALL MATERIAL SHALL BE STORED TO PROVIDE PROTECTION FROM THE WEATHER AND ACCIDENTAL DAMAGE.
ALL WORKERS UNDER THIS SECTION MUST OPERATE WITHIN AND MAINTAIN A CLEAN AND SAFE WORKING ENVIRONMENT. GENERAL CLEANING REQUIREMENTS SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR. ALL SAFETY PROTOCOLS ESTABLISHED BY THE GENERAL CONTRACTOR SHALL BE STRICTLY ADHERED TO. REPORT ANY
DISCOVERED SAFETY CONCERNS WITH THE PROJECT SUPERINTENDENTS.
B. PRODUCTS
a. EQUIPMENT AND MATERIALS SHALL BE NEW AND THE MOST SUITABLE GRADE FOR THE PURPOSE INTENDED. WHERE PRACTICAL, ALL THE COMPONENTS SHALL BE PRODUCTS OF
A SINGLE MANUFACTURER IN ORDER TO PROVIDE PROPER COORDINATION AND RESPONSIBILITY. CATALOG NUMBERS AND MODEL NUMBERS INDICATED IN THE DRAWINGS AND SPECIFICATIONS ARE USED AS A GUIDE IN THE SELECTION OF THE EQUIPMENT AND ARE ONLY LISTED FOR THE CONTRACTOR'S CONVENIENCE. THE CONTRACTOR SHALL DETERMINE THE ACTUAL MODEL NUMBERS FOR ORDERING EQUIPMENT AND MATERIALS IN ACCORDANCE WITH THE WRITTEN DESCRIPTION OF EACH ITEM AND WITH THE INTENT
OF THE DRAWINGS AND SPECIFICATIONS.
C. SHOP DRAWING SUBMITTAL
a. SUBMIT PRODUCT DATA FOR DIFFUSERS. SUBMIT MATERIALS AND METHODS FOR DUCTWORK AND INSULATION.
D. EXECUTION
a. ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND COMPLETED IN A FIRST-CLASS WORKMANLIKE MANNER AND IN ACCORDANCE WITH THE BEST MODERN METHODS AND
PRACTICE. ATHE CONTRACTOR SHALL BE RESPONSIBLE FOR FULL COORDINATION OF THE MECHANICAL SYSTEMS WITH SHOP DRAWINGS OF THE BUILDING CONSTRUCTION SO THE PROPER OPENINGS AND SLEEVES OR SUPPORTS ARE PROVIDED FOR PIPING, DUCTWORK, OR OTHER EQUIPMENT PASSING THROUGH SLABS OR WALLS.
b. ALL CONNECTIONS TO FIXTURES AND EQUIPMENT SHOWN ON THE DRAWINGS SHALL BE CONSIDERED DIAGRAMMATIC UNLESS OTHERWISE INDICATED BY A SPECIFIC DETAIL ON THE DRAWINGS. THE ACTUAL CONNECTIONS SHALL BE MADE TO FULLY SUIT THE REQUIREMENTS OF EACH CASE AND ADEQUATELY PROVIDE FOR SERVICING. START OF WORK
SHALL BE CONSTRUED AS ACCEPTANCE OF SUITABILITY OF WORK OF OTHERS
2. HVAC METAL DUCTWORK
A. GENERAL
a. ALL SHEET METAL DUCTWORK SHALL COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE" FOR FABRICATION AND INSTALLATION OF METAL DUCTWORK. COMPLY WITH NFPA 90A "STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS”. FLEXIBLE DUCTWORK SHALL MEET THE
REQUIREMENTS OF UL-181.
b. APPROVAL SUBMITTALS:
• DUCTWORK, SEALANTS, ADHESIVES, FLEXIBLE DUCT, SPIN-IN FITTINGS
B. PRODUCTS
a. MATERIALS:
• GALVANIZED SHEET STEEL: COMPLY WITH ASTM A 653, LOCKFORMING QUALITY; WITH G 90 ZINC COATING IN ACCORDANCE WITH ASTM A 525; AND MILL PHOSPHATIZED FOR EXPOSED LOCATIONS. STAMP GAUGE AND MANUFACTURER'S IDENTIFICATION ON EACH SHEET. BREAK SHEETS SO THAT IDENTIFICATION IS EXPOSED.
• SUPPORTS: EXCEPT AS OTHERWISE INDICATED, PROVIDE HOT-DIPPED GALVANIZED STEEL FASTENERS, ANCHORS, RODS, STRAPS, TRIM AND ANGLES FOR SUPPORT OF
DUCTWORK.
• FLEXIBLE DUCTS: PROVIDE WITH R-VALUE OF R-6 FOR CONNECTION OF SUPPLY AIR DEVICES IS ACCEPTABLE ONLY WHERE SHOWN ON THE DRAWINGS. PROVIDE WITH REINFORCED METALIZED POLYESTER JACKET THAT IS TEAR AND PUNCTURE RESISTANT, AIRTIGHT INNER CORE WITH NO FIBERGLASS EROSION IN THE AIR STREAM AND AN ENCAPSULATED WIRE HELIX. FLEXIBLE DUCTWORK SHALL HAVE A RECOMMENDED OPERATING PRESSURE OF 6" W.G. FOR SIZES 4" THROUGH 12" DIAMETER AND 4" W.G. FOR SIZES 14" THROUGH 20" DIAMETER. ALL DIAMETERS SHALL BE SUITABLE FOR A NEGATIVE OPERATING PRESSURE OF 0.75" W.G. FLEXIBLE DUCTWORK SHALL MEET THE REQUIREMENTS OF UL-181, FBC MECHANICAL, SBCC, NFPA 90A AND NFPA 90B. ACCEPTABLE MANUFACTURERS: ATCO 36, FLEXMASTER 8M-R6, AND THERMAFLEX M-KE R6.
EXECUTION.
• SPIN-IN FITTINGS: PROVIDE ROUND BRANCH RUN-OUTS AS FOLLOWS. SUPPLY AIR DIFFUSER CONNECTIONS SHALL BE CONICAL WITH DAMPER AND ONE INCH HIGH
INSULATION STAND-OFF EQUAL TO CROWN 3200 DS OR FLEXMASTER CBD-BO.
b. DUCTWORK:
• FOR DUCT ROUTING, LOCATE DUCTWORK RUNS, EXCEPT AS OTHERWISE INDICATED, VERTICALLY AND HORIZONTALLY.COORDINATE LAYOUT WITH STRUCTURE AND LIGHTING
LAYOUTS AND SIMILAR FINISHED WORK. WHERE DUCTS PASS THROUGH FIRE-RATED FLOORS, WALLS, OR PARTITIONS, PROVIDE FIRESTOPPING BETWEEN DUCT AND SUBSTRATE. INSTALLING CONTRACTORS SHALL PROVIDE ALL SPECIALTIES INCLUDING DAMPERS, ACCESS DOORS, AND FLEX CONNECTORS AS REQUIRED TO SUPPORT A
COMPLETE AND FUNCTIONAL INSTALLATION.
c. SHOP FABRICATION:
• SHOP FABRICATE DUCTWORK IN 4, 8, 10 OR 12-FT LENGTHS WHERE POSSIBLE. PREASSEMBLE WORK IN SHOP TO GREATEST EXTENT POSSIBLE, SO AS TO MINIMIZE FIELD
ASSEMBLY OF SYSTEMS.
• LIMIT ANGULAR TAPERS TO 30° FOR CONTRACTING TAPERS AND 20° FOR EXPANDING TAPERS.
d. FACTORY-FABRICATED LOW PRESSURE DUCTWORK (MAXIMUM 2" W.G.):
• MATERIAL: GALVANIZED SHEET STEEL COMPLYING WITH ASTM A 527, LOCKFORMING QUALITY, WITH ASTM A 525, G90 ZINC COATING, MILL PHOSPHATIZED.
• GAUGE: 28-GAUGE MINIMUM FOR ROUND DUCTS AND FITTINGS, 4" THROUGH 8" DIAMETER. 26-GAUGE MINIMUM 9" THROUGH 14", 24-GAUGE MINIMUM 15" THROUGH 26"..
• ACCEPTABLE MANUFACTURERS: SEMCO MFG., INC., UNITED SHEET METAL DIV., UNITED MCGILL CORP, OR APPROVED EQUAL
C. EXECUTION
a. METAL DUCTWORK:
• ASSEMBLE AND INSTALL DUCTWORK IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES WHICH WILL ACHIEVE AIR-TIGHT (5% LEAKAGE FOR SYSTEMS RATED 3" AND UNDER; 1% FOR SYSTEMS RATED OVER 3") AND NOISELESS (NO OBJECTIONABLE NOISE) SYSTEMS, CAPABLE OF PERFORMING EACH INDICATED SERVICE. INSTALL EACH RUN WITH MINIMUM NUMBER OF JOINTS. ALIGN DUCTWORK ACCURATELY AT CONNECTIONS, WITHIN _" MISALIGNMENT TOLERANCE AND WITH INTERNAL SURFACES SMOOTH.
SUPPORT DUCTS RIGIDLY WITH SUITABLE TIES, BRACES, HANGERS AND ANCHORS OF TYPE WHICH WILL HOLD DUCTS TRUE-TO-SHAPE AND TO PREVENT BUCKLING.
• ROUTE DUCTWORK RUNS, EXCEPT AS OTHERWISE INDICATED, VERTICALLY AND HORIZONTALLY. AVOID DIAGONAL RUNS WHEREVER POSSIBLE. LOCATE RUNS AS INDICATED BY DIAGRAMS, DETAILS AND NOTATIONS OR, IF NOT OTHERWISE INDICATED, RUN DUCTWORK IN SHORTEST ROUTE WHICH DOES NOT OBSTRUCT USEABLE SPACE OR BLOCK ACCESS FOR SERVICING BUILDING AND ITS EQUIPMENT. HOLD DUCTS CLOSE TO WALLS, OVERHEAD CONSTRUCTION, COLUMNS, AND OTHER STRUCTURAL AND PERMANENT
ENCLOSURE ELEMENTS OF BUILDING.
b. FLEXIBLE DUCT:
• MAXIMUM LENGTH: FOR ANY DUCT RUN USING FLEXIBLE DUCTWORK, DO NOT EXCEED 6'-0" EXTENDED LENGTH. FLEXIBLE DUCT SHALL ONLY BE ALLOWED AS DETAILED ON
THE DRAWINGS. MINIMUM LENGTH: FOR ANY DUCT RUN USING FLEXIBLE DUCTWORK, USE A MINIMUM OF 3’-0” EXTENDED LENGTH SECTION.
• INSTALL IN ACCORDANCE WITH SECTION III OF SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE". SUPPORT FLEXIBLE DUCTS TO ELIMINATE
PINCHING AND KINKING WHICH WOULD RESTRICT FLOW. BENDS SHALL BE MADE WITH AT LEAST ONE DUCT DIAMETER.
• DOWNSTREAM OF VAV BOXES: PEEL BACK INSULATION AND SLIDE THE INNER CORE OVER THE SPIN-IN OR DIFFUSER NECK, SEAL WITH DUCT SEALANT AND INSTALL PANDUIT
STRAP TIGHTLY. SLIDE INSULATION BACK OVER THE INNER CORE AND SECURELY TAPE THE INSULATION OUTER JACKET.
c. LEAKAGE TESTS: AFTER EACH DUCT SYSTEM IS COMPLETED, TEST FOR DUCT LEAKAGE IN ACCORDANCE WITH SECTIONS 3 AND 5 OF THE SMACNA HVAC AIR DUCT LEAKAGE TEST
MANUAL. TEST PRESSURE SHALL BE EQUAL TO PRESSURE CLASS OF DUCT, LESS 0.5" STATIC PRESSURE. REPAIR LEAKS AND REPEAT TESTS UNTIL TOTAL LEAKAGE IS LESS THAN 3% OF SYSTEM DESIGN AIR FLOW FOR LOW PRESSURE SYSTEMS AND LESS THAN 1% FOR SYSTEMS RATED OVER 3".
3. EXTERIOR INSULATION FOR DUCTWORK
A. APPROVAL SUBMITTALS: SUBMIT PRODUCT DATA FOR INSULATION, COVERINGS, ADHESIVES, SEALERS
B. PRODUCTS
a. ACCEPTABLE MANUFACTURERS: KNAUF, OWENS-CORNING, JOHNS MANVILLE, CERTAIN TEED
b. FLAME/SMOKE RATING: PROVIDE COMPOSITE MECHANICAL INSULATION (INSULATION, COVERINGS, SEALERS, MASTIC, AND ADHESIVE) WITH A FLAME SPREAD RATING OF 25 OR
LESS, AND A SMOKE-DEVELOPED RATING OF 50 OR LESS AS TESTED BY ANSI/ASTM 84.
c. FLEXIBLE FIBERGLASS INSULATION: ASTM C553, TYPE I, CLASS B-3 (TEMPERATURE LESS THAN 350°F). DUCT WRAP SHALL BE 0.75 PCF DENSITY WITH UL RATED ALUMINUM FOIL
VAPOR BARRIER (FSK).
d. GENERAL PURPOSE MASTIC: BENJAMIN FOSTER 35-00 SERIES, CHILDERS CP-10, OR APPROVED EQUAL. THE FINAL SELECTION OF THIS PRODUCT FOR THE SPECIFIC APPLICATION
INDICATED IS THE RESPONSIBILITY OF THE INSULATION SUPPLIER. THE INSULATION SYSTEM MUST MEET THE SPECIFIED APPLICATION.
e. VAPOR BARRIER SEALANT: BENJAMIN FOSTER 30-65, CHILDERS CP-34, OR APPROVED EQUAL. PROVIDE "LOW ODOR" TYPE. PROVIDE WATER-BASED PRODUCT. THE FINAL
SELECTION OF THIS PRODUCT FOR THE SPECIFIC APPLICATION INDICATED IS THE RESPONSIBILITY OF THE INSULATION SUPPLIER. THE INSULATION SYSTEM MUST MEET THE
SPECIFIED APPLICATION.
f. ADHESIVE: BENJAMIN FOSTER 85-60, CHILDERS CP-82, CHILDERS CP-127, OR APPROVED EQUAL. PROVIDE WATER-BASED PRODUCT. THE FINAL SELECTION OF THIS PRODUCT FOR THE SPECIFIC APPLICATION INDICATED IS THE RESPONSIBILITY OF THE INSULATION SUPPLIER. THE INSULATION SYSTEM MUST MEET THE SPECIFIED APPLICATION.
g. FIBER-GLAS MESH: 10X10 MESH. FOSTER MASTAFAB, CHIL GLASS #10 OR EQUAL.
C. EXECUTION
a. INSTALLATION OF INSULATION:
• CLEAN AND DRY DUCTWORK PRIOR TO INSULATING. WRAP INSULATION SHALL EXTEND MINIMUM OF 6" OVER CONNECTION TO EXISTING INTERIOR LINED DUCTWORK.
• ADHERE INSULATION TO DUCT WITH 50 PERCENT COVERAGE USING APPROVED INSULATION ADHESIVE APPLIED IN 6-INCH WIDE SWATHS WITH 6-INCH SPACES BETWEEN
SWATHS. ADDITIONALLY SECURE INSULATION WITH PERFORATED PINS AND TUFF-BOND OR BY SELF-STICKING PINS WITH A 3/8" SELF-TAPPING SCREW. SPACE ON 12-INCH CENTERS AND 3 INCHES FROM ALL EDGES. DUCTS UP THROUGH 24" WIDE ONLY REQUIRE ONE ROW OF PINS. DUCTS OVER 24" WIDE SHALL HAVE PINS SPACED AS
DESCRIBED HEREIN.
• APPLY OPEN MESH GLASS FABRIC EMBEDDED IN VAPOR BARRIER MASTIC. THEN APPLY A SECOND COAT OF GENERAL PURPOSE MASTIC WITH ALUMINUM GREY COLOR. THIS
FINISH SHALL BE COMPLETE OVER ALL RIGID INSULATION.
• INSULATE ALL SUPPLY AND RETURN DUCTWORK ABOVE CEILINGS, IN CHASES, OR ELSEWHERE WITH 2.2" THICK FIBERGLASS BLANKET INSULATION WITH VAPOR BARRIER
(INSTALLED R-VALUE OF 6.0 MINIMUM).
4. GRILLES, REGISTERS, AND CEILING DIFFUSERS
A. GENERAL
a. APPROVAL SUBMITTALS: SUBMIT MANUFACTURER'S TECHNICAL PRODUCT DATA FOR AIR OUTLETS AND INLETS INDICATING CONSTRUCTION, FINISH, AND MOUNTING.
• DIFFUSERS
• RETURN GRILLES
b. O&M DATA SUBMITTALS: SUBMIT CLEANING INSTRUCTIONS FOR FINISHES AND SPARE PARTS LISTS. INCLUDE THIS DATA AND A COPY OF APPROVAL SUBMITTALS IN O&M MANUAL.
B. PRODUCTS
a. PERFORMANCE: PROVIDE GRILLES, REGISTERS AND CEILING DIFFUSERS THAT HAVE, AS MINIMUM, TEMPERATURE AND VELOCITY TRAVERSES, THROW AND DROP, AND NOISE
CRITERIA RATINGS FOR EACH SIZE DEVICE EQUAL TO THE BASIS OF DESIGN.
b. CEILING AND WALL COMPATIBILITY: PROVIDE GRILLES, REGISTERS AND DIFFUSERS WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT WALL AND CEILING SYSTEMS, AND THAT ARE SPECIFICALLY MANUFACTURED TO FIT INTO CEILING MODULE OR WALL WITH ACCURATE FIT AND ADEQUATE SUPPORT.
c. APPEARANCE: ALL GRILLES AND REGISTERS SHALL BE STEEL CONSTRUCTION, UNLESS OTHERWISE NOTED, WITH UNIFORM MATCHING APPEARANCE FOR EACH TYPE OF OUTLET.
CEILING MOUNTED GRILLES AND REGISTERS SHALL BE SET TO BE SIGHT TIGHT FROM THE PREDOMINANT EXPOSURE.
d. FINISH: ALL CEILING MOUNTED GRILLES, REGISTERS, AND DIFFUSERS SHALL BE FINISHED WITH BAKED WHITE ENAMEL UNLESS OTHERWISE SPECIFIED.
e. ACCEPTABLE MANUFACTURERS: TITUS, METAL AIRE, PRICE
f. SQUARE CEILING DIFFUSERS (CD)
• PROVIDE DIFFUSER AS SPECIFIED ON PLANS. ALTERNATE DIFFUSERS FROM TITUS OR METAL AIRE MAY BE CONSIDERED IF THEY SATISFY PERFORMANCE AND SIZE REQUIREMENTS FOR APPLICATION. PROVIDE LAY-IN PANEL AS REQUIRED. BASIS OF DESIGN IS PRICE SCD/SCDA.
• DIFFUSER BACK SHALL BE FACTORY INSULATED.
g. LINEAR DIFFUSER (LD)
• PROVIDE LINEAR SUPPLY SLOT DIFFUSERS WITH FULL 180 DEGREE ADJUSTABLE AIR PATTERN AND COMPLETE FLOW CONTROL INCLUDING BLANK OFF. THEY SHALL HAVE 3 X 3/4" WIDTH SLOTS; INDIVIDUALLY ADJUSTABLE THROW PATTERN, AND SLOPED SHOULDER PLENUM. PROVIDE JOINING AND ALIGNMENT STRIPS, END CAPS, MITRED CORNERS, AND FRAME TYPE SUITABLE FOR CEILING INSTALLATION. PROVIDE INSULATED PLENUMS FOR SUPPLY DIFFUSERS. BOD IS PRICE SDS W/ SDA PLENUM. COORDINATE
INSTALLATION FRAME/TRIM OPTIONS WITH ARCHITECT PRIOR TO PURCHASE.
h. TRANSFER GRILLE (TG)
• PROVIDE RETURN REGISTERS WITH ONE SET OF 1/2" SPACED, 45 DEGREE FIXED LOUVERS, PARALLEL TO THE LONG DIMENSION. BASIS OF DESIGN: TITUS 350 FL OR
METALAIRE RH, PRICE 630.
i. FILTERED RETURN AIR REGISTERS (FRR)
• PROVIDE FILTER RETURN GRILLES WITH ONE SET OF 45 DEGREE, FIXED LOUVERS, PARALLEL TO THE LONG DIMENSION. PROVIDE FRAME AND HINGED CORE WITH PROVISION
FOR ONE INCH THICK FILTERS. TITUS 350FF OR METALAIRE RHEF, PRICE 630FF.
j. RETURN AIR GRILLE / EXHAUST AIR GRILLE (RAG / EG)
• PROVIDE RETURN GRILLES WITH ONE SET OF 1/2" SPACED, 45 DEGREE FIXED LOUVERS, PARALLEL TO THE LONG DIMENSION WITH SCREWDRIVER OPERATED LOUVER. BASIS
OF DESIGN: PRICE 630 OR APPROVED EQUAL.
MECHANICAL SPECIFICATIONS
5. DUCTWORK ACCESSORIES
A. CODES AND STANDARDS
a. SMACNA COMPLIANCE: COMPLY WITH APPLICABLE PORTIONS OF BOTH SMACNA "HVAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE" AND "FIRE, SMOKE AND
RADIATION DAMPER INSTALLATION GUIDE FOR HVAC SYSTEMS" .
b. UL COMPLIANCE: CONSTRUCT, TEST, AND LABEL FIRE DAMPERS IN ACCORDANCE WITH UL STANDARD 555 "FIRE DAMPERS AND CEILING DAMPERS". CONSTRUCT, TEST AND LABEL SMOKE DAMPERS IN ACCORDANCE WITH UL STANDARD 555S "LEAKAGE RATED DAMPERS FOR USE IN SMOKE CONTROL SYSTEMS" .
c. NFPA COMPLIANCE: COMPLY WITH APPLICABLE PROVISIONS OF NFPA 90A "AIR CONDITIONING AND VENTILATING SYSTEMS" PERTAINING TO INSTALLATION OF DUCTWORK
ACCESSORIES.
B. PRODUCTS
a. APPROVAL SUBMITTALS
• LOW PRESSURE MANUAL DAMPERS
• FIRE DAMPERS
b. MANUAL DAMPERS
• LOW PRESSURE MANUAL DAMPERS: PROVIDE 16 GAUGE DAMPERS OF SINGLE-BLADE TYPE (12" MAXIMUM BLADE WIDTH) OR MULTIBLADE TYPE. DAMPER BLADES TO BE
GANG-OPERATED FROM A SINGLE SHAFT WITH NYLON OR BALL BEARINGS ON EACH END. PROVIDE INDEXED LOCKING QUADRANT. PARALLEL OR OPPOSED BLADE STYLE IS ACCEPTABLE. PROVIDE 2" STANDOFF ON LOCKING QUADRANT FOR EXTERNALLY INSULATED DUCT
c. FIRE DAMPERS
• FIRE DAMPERS: PROVIDE CURTAIN TYPE FIRE DAMPERS, UL CLASSIFIED AND LABELED PER UL 555, OF TYPES AND SIZES INDICATED. CONSTRUCT CASINGS AND BLADES
OF GALVANIZED STEEL. DAMPER SHALL NOT RESTRICT DUCT FREE AREA WHEN OPEN. DAMPERS SHALL BE RATED FOR DYNAMIC CLOSURE UNDER FLOW AND PRESSURE.
PROVIDE SLEEVES AND MOUNTING ANGLES. PROVIDE FUSIBLE LINK RATED AT 160 TO 165° F UNLESS OTHERWISE INDICATED. PROVIDE DAMPER WITH POSITIVE LOCK IN
CLOSED POSITION. ALL DAMPERS SHALL BE SPRING ACTIVATED. BASIS OF DESIGN:
• 1-1/2 HR: RUSKIN IBD2 - STYLE B FOR RECTANGULAR, STYLE CR FOR ROUND, STYLE CO FOR OVAL.
• 1-1/2 HR: RUSKIN IBDT FOR TRANSFER GRILLES IN NARROW PARTITIONS.
• 3 HR: RUSKIN IBD23 - STYLE B FOR RECTANGULAR, STYLE CR FOR ROUND, STYLE CO FOR OVAL.
d. ACCEPTABLE MANUFACTURERS
• AIR BALANCE, INC., AMERICAN WARNING & VENTILATING, ARROW LOUVER AND DAMPER, PENN VENTILATOR CO., RUSKIN MFG. CO., GREENHECK
C. EXECUTION
a. FIRE DAMPERS
• NOTIFY ENGINEER AT LEAST 48 HOURS IN ADVANCE OF CEILING INSTALLATION OR CHASE CLOSURE SO THAT COMPLETE [FIRE DAMPER] INSTALLATION CAN BE OBSERVED.
A COPY OF THE MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS SHALL BE AVAILABLE AT THE SITE.
• OPERATE INSTALLED DUCTWORK ACCESSORIES TO DEMONSTRATE COMPLIANCE WITH REQUIREMENTS. TEST FOR AIR LEAKAGE WHILE SYSTEM IS OPERATING. REPAIR OR REPLACE FAULTY ACCESSORIES AS REQUIRED TO OBTAIN PROPER OPERATION AND LEAKPROOF PERFORMANCE.
6. TEST AND BALANCING
A. AIRFLOW TOLERANCES
a. AIRFLOW MEASUREMENT: AIRFLOW MEASUREMENTS FOR AIR HANDLING UNITS (AHU), EXHAUST FANS (EF) AND VAV BOXES SHALL BE OBTAINED BY DUCT TRAVERSE AND REPORTED IN THE TAB REPORT WITH THE [[INDICATED BAS READING FROM AHU OR EF FLOW RINGS AND] VAV BOX CONTROLLER READINGS FOR COMPARISON. THE LOCATION OF THE TRAVERSE SHALL BE INDICATED ON A SKETCH INCLUDED IN THE TAB REPORT. IF AIRFLOW IS DETERMINED BY ANY OTHER MEANS THAN A TRAVERSE (I.E., SUM OF OUTLETS, OR OTHER INDIRECT METHOD) IT SHALL BE CLEARLY STATED IN THE TAB REPORT. ORGANIZE TAB REPORT CONTEMPORANEOUS DATA SO THAT THE FOLLOWING CAN BE READILY
CHECKED:
• COMPARISON OF ACTUAL CFM TO DESIGN CFM AND PERCENT VARIANCE.
• COMPARISON OF SUPPLY AIR CFM TO RETURN PLUS OUTDOOR AIR CFM.
• COMPARISON OF EACH AHU SUPPLY AIR CFM TO THE SUM OF ITS TERMINALS.
• COMPARISON OF EACH TERMINAL (SUCH AS VAV BOX OR SUPPLY VALVE) TOTAL CFM TO THE SUM OF THE OUTLETS FOR THE TERMINAL.
• COMPARISON OF EACH EF CFM TO THE SUM OF THE INLETS FOR THE EF.
• COMPARISON OF TOTAL OUTDOOR AIR CFM TO TOTAL CONDITIONED EXHAUST CFM FOR EACH ZONE, FLOOR, OR AHU AS APPLICABLE. PROVIDE AN INDICATION OF THE NET
POSITIVE OR NEGATIVE CFM FOR THAT ZONE, FLOOR, OR AHU.
b. AIR HANDLING: THE SUPPLY AIR, RETURN AIR AND OUTDOOR AIR QUANTITIES SHALL BE BALANCED WITHIN ±5% OF DESIGN VALUES.
• BALANCE DUAL DUCT SYSTEMS WITH ALL AIR THROUGH THE COLD DECK. RECHECK FOR NOISE LEVEL IN OCCUPIED SPACES AT 50% BYPASS.
• SET DAMPERS, VOLUME CONTROLS AND FAN SPEEDS TO OBTAIN SPECIFIED AIR DELIVERY WITH MINIMUM NOISE LEVEL AND MINIMUM ENERGY USE. REBALANCE AS REQUIRED
TO ACCOMPLISH THIS. SIMULATE FULLY LOADED FILTERS DURING TEST.
c. EXHAUST FANS: THE EXHAUST FAN QUANTITIES SHALL BE SET AS REQUIRED TO MAINTAIN THE DESIGN EXHAUST TERMINAL FLOWS WITHIN ±5% OF DESIGN VALUES. IF NO EXHAUST
TERMINALS EXIST, EXHAUST FAN AIR QUANTITIES SHALL BE BALANCED WITHIN ± 10% OF DESIGN VALUES.
• STATIC PRESSURE MEASUREMENT: STATIC PRESSURE (SP) MEASUREMENTS FOR EFS SHALL BE OBTAINED AT BOTH SUCTION AND DISCHARGE SO THAT TOTAL STATIC
PRESSURE (TSP) CAN BE REPORTED. PLOT DESIGN CFM AND SP ON FAN CURVE AND INCLUDE IN TAB REPORT. IN ADDITION, THE STATIC PRESSURE DROP ACROSS EACH COMPONENT OF THE EQUIPMENT (SUCH AS COILS, FILTERS, ETC.) SHALL BE REPORTED AND SHOWN ON A SKETCH INCLUDED IN THE TAB REPORT. ORGANIZE TAB REPORT
CONTEMPORANEOUS DATA SO THAT THE FOLLOWING CAN BE READILY CHECKED
d. TERMINAL UNITS: THE AIR QUANTITIES ASSOCIATED WITH VAV BOXES AND OTHER TERMINAL UNITS SHALL BE BALANCED WITHIN ±5% OF DESIGN VALUES.
e. CEILING DIFFUSERS, SUPPLY REGISTERS, RETURN AND EXHAUST INLETS: BALANCE TO AN AIR QUANTITY WITHIN ±10% OF THE DESIGN VALUES. WHERE THE DRAWINGS INDICATE A
DESIGN PRESSURE DIFFERENTIAL FOR THE ROOM, AIR QUANTITIES SHALL BE FURTHER ADJUSTED TO A MORE RESTRICTIVE TOLERANCE AS REQUIRED TO ESTABLISH THE
PRESSURE DIFFERENTIAL.
• SET GRILLE DEFLECTIONS AS NOTED ON PLANS. MODIFY DEFLECTIONS IF REQUIRED TO ELIMINATE DRAFTS OR OBJECTIONABLE AIR MOVEMENT. RECORD AIR TERMINAL
VELOCITY AFTER COMPLETION OF BALANCE WORK. RECORD FINAL GRILLE AND REGISTER DEFLECTION SETTINGS IF DIFFERENT FROM THAT SPECIFIED ON CONTRACT
DRAWINGS.
B. TEMPERATURE TOLERANCES
1. AIR HANDLING TEMPERATURES: THE CONTROLLED TEMPERATURES AT AHUS SHALL BE VERIFIED TO BE UNDER CONTROL WITHIN ± 1°F OF DESIGN VALUES.
2. ROOM TEMPERATURES: BALANCE SYSTEMS AND CONTROLS WITHIN ±2°F OF INDICATED SETTINGS.
C. APPROVAL SUBMITTALS
a. SUBMIT THE NAME OF THE PROPOSED TEST AND BALANCE COMPANY FOR THE ENGINEER'S APPROVAL WITHIN THIRTY (30) DAYS AFTER AWARDING OF CONTRACT.
b. SUBMIT PROJECT SPECIFIC TAB FORMS SHOWING HOW REQUIREMENTS OF THIS SECTION WILL BE DOCUMENTED.
D. PRODUCTS
a. PATCHING MATERIALS
• EXCEPT AS OTHERWISE INDICATED, USE SAME PRODUCTS AS USED BY ORIGINAL INSTALLER FOR PATCHING HOLES IN INSULATION, DUCTWORK AND HOUSINGS WHICH HAVE BEEN CUT OR DRILLED FOR TEST PURPOSES, INCLUDING ACCESS FOR TEST INSTRUMENTS, ATTACHING JIGS, AND SIMILAR PURPOSES.
b. TEST INSTRUMENTS
• UTILIZE TEST INSTRUMENTS AND EQUIPMENT OF THE TYPE, PRECISION, AND CAPACITY AS RECOMMENDED IN THE REFERENCED STANDARD. ALL INSTRUMENTS SHALL BE IN
GOOD CONDITION AND SHALL HAVE BEEN CALIBRATED WITHIN THE PREVIOUS SIX (6) MONTHS (OR MORE RECENTLY IF REQUIRED BY STANDARD).
E. EXECUTION
a. TEST, ADJUST AND BALANCE SYSTEMS DURING SUMMER SEASON FOR AIR CONDITIONING SYSTEMS AND DURING WINTER SEASON FOR HEATING SYSTEMS, INCLUDING AT LEAST A PERIOD OF OPERATION AT OUTSIDE CONDITIONS WITHIN 5°F WET BULB TEMPERATURE OF MAXIMUM SUMMER DESIGN CONDITION, AND WITHIN 10°F DRY BULB TEMPERATURE OF MINIMUM WINTER DESIGN CONDITION. WHEN SEASONAL OPERATION DOES NOT PERMIT MEASURING FINAL TEMPERATURES, THEN TAKE FINAL TEMPERATURE READINGS WHEN
SEASONAL OPERATION DOES PERMIT.
b. THE CONTRACTOR SHALL RETURN FOR A CHANGE OF SEASONS TEST AT NO ADDITIONAL COST TO THE OWNER AND SUBMIT THE REVISED TAB REPORT.
c. PUNCH LIST: PREPARE A DEFICIENCY (PUNCH)LIST FOR THE CONTRACTOR WITH A COPY TO THE ENGINEER THAT LISTS ALL ITEMS THAT ARE INCORRECTLY INSTALLED OR ARE
FUNCTIONING IMPROPERLY. PROVIDE A RETEST AFTER ALL ITEMS ARE CORRECTED.
d. PREPARE TAB REPORT OF TEST RESULTS, INCLUDING INSTRUMENTATION CALIBRATION REPORTS, IN FORMAT RECOMMENDED BY APPLICABLE STANDARDS, MODIFIED AS REQUIRED
TO INCLUDE ALL DATA LISTED HEREIN.
e. MARK EQUIPMENT SETTINGS, INCLUDING DAMPER CONTROL POSITIONS, VALVE INDICATORS, FAN SPEED CONTROL LEVERS, AND SIMILAR CONTROLS AND DEVICES, TO SHOW FINAL
SETTINGS AT COMPLETION OF TAB WORK. PROVIDE MARKINGS WITH PAINT OR OTHER SUITABLE PERMANENT IDENTIFICATION MATERIALS.
f. INCLUDE IN THE TAB REPORT RECOMMENDATIONS FOR CORRECTING UNSATISFACTORY MECHANICAL PERFORMANCES WHEN SYSTEM CANNOT BE SUCCESSFULLY BALANCED.
F. NAMEPLATE DATA
a. COMPLETE NAMEPLATE DATA FOR ALL EQUIPMENT.
b. MOTOR DATA TO INCLUDE HORSEPOWER, PHASE, VOLTAGE, RPM, FULL LOAD NAMEPLATE CURRENT, FUSE RATING IN DISCONNECT SWITCH, NUMBER OR MANUFACTURER'S SIZE
DESIGNATION, AND AMPERE RATING OF OVERCURRENT AND LOW VOLTAGE PROTECTION DEVICES IN STARTERS.
| Sheets |
| M001 - MECHANICAL LEGEND, ABBREVIATIONS, CODES AND STANDARDS |
| M111 - MECHANICAL FIRST FLOOR PLAN - DEMOLITION |
| M112 - MECHANICAL SECOND FLOOR PLAN - DEMOLITION |
| M211 - MECHANICAL FIRST FLOOR PLAN - NEW WORK |
| M212 - MECHANICAL SECOND FLOOR PLAN - NEW WORK |
| M301 - MECHANICAL DETAILS AND SPECIFICATIONS |
| 2026-03-02T17:12:24-0500 | |
| David Brooks |
| 2026-03-02T17:12:38-0500 | |
| David Brooks |
| 2026-03-02T17:12:42-0500 | |
| David Brooks |
| 2026-03-02T17:12:48-0500 | |
| David Brooks |
| 2026-03-02T17:12:50-0500 | |
| David Brooks |
| 2026-03-02T17:12:51-0500 | |
| David Brooks |
File details come from the government source that posted it. Updated .