This document is a set of electrical construction drawings and specifications for an interior renovation project at the Bradford County Courthouse located at 945 North Temple Avenue, Starke, Florida 32091. The project, identified as AB24115, is prepared by Akin Brooks Engineering, Inc. and includes complete electrical system design for both first and second floors of the courthouse. The scope of work encompasses electrical demolition, power distribution, lighting design and controls, fire alarm system installation, communications systems, and access control integration. The drawings include detailed floor plans for demolition, power, lighting, fire alarm, and building systems across both floors, along with electrical specifications, legend, abbreviations, and standard details. The project documents are issued as 100% Construction Documents dated February 27, 2026, and include 13 drawing sheets (E001 through E501) covering legends, demolition plans, power and lighting plans, fire alarm plans, systems coordination, technical details, and lighting fixture schedules.
The electrical specifications require all work to comply with the 2023 Florida Building Code, 2020 National Electrical Code (NFPA 70), 2019 National Fire Alarm Code (NFPA 72), and 2023 Florida Fire Prevention Code. Materials and equipment must be UL listed, with specific approved manufacturers designated for switches, receptacles, and other devices including Hubbell, Leviton, and Pass & Seymour. The contractor is responsible for furnishing all labor, materials, and equipment for a complete electrical installation, with all work guaranteed against defects for one year from final acceptance and lamps guaranteed for 30 days. The design includes dimmable and non-dimmable lighting control systems using occupancy sensors, daylight sensors, and room controllers based on Wattstopper DLM equipment. Fire alarm systems shall utilize intelligent addressable devices with Simplex as the approved manufacturer. The specifications detail requirements for conduit sizing, grounding and bonding, device identification, circuit labeling, and comprehensive submittals including product data, shop drawings, operations and maintenance manuals, as-built drawings, and factory-authorized training for owner personnel.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A AMPS
AC ABOVE COUNTER
ACS ACCESS CONTROL SYSTEM
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AL ALUMINUM
ARCH ARCHITECT OR ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
ATU AIR TERMINAL UNIT
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BJ BONDING JUMPER
BKR CIRCUIT BREAKER
BLDG BUILDING
BOD BASIS OF DESIGN
C CONDUIT
C/B, CB CIRCUIT BREAKER
CL CURRENT LIMITING
C/L CENTERLINE
CLG CEILING
CKT CIRCUIT
CR CORD REEL
CT CURRENT TRANSFORMER
CU COPPER
DDC DIRECT DIGITAL CONTROL
DEMO DEMOLISH
DIV DIVISION
EC ELECTRICAL CONTRACTOR
EGC EQUIPMENT GROUNDING CONDUCTOR
ELCU EMERGENCY LIGHTING CONTROL UNIT
ELEC ELECTRICAL
EMGB ELECTRICAL MAIN GROUNDING BUSBAR
EF EXHAUST FAN
EX EXISTING TO REMAIN
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
FACP FIRE ALARM SYSTEM CONTROL PANEL
FA, F/A FIRE ALARM
FLA FULL LOAD AMPS
FLR FLOOR
FMC FLEXIBLE METAL CONDUIT
FSS FUSED SAFETY SWITCH
FU FUSE
FVNR FULL VOLTAGE NON-REVERSING
G GROUND (OR GFI FOR SUBSCRIPT)
GC GENERAL CONTRACTOR
GEC GROUNDING ELECTRODE CONDUCTOR
GF,GFI GROUND FAULT (INTERRUPTER)
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GTD GENERATOR TRANSFER DEVICE
HH HANDHOLE
HOA HAND-OFF-AUTOMATIC
HP HEAT PUMP OR HORSEPOWER
HVAC HEATING, VENTILATION & AIR-CONDITIONING
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
JB, JBOX JUNCTION BOX
K KILO
KAIC KILO-AMPERE INTERRUPTING CAPABILITY
KCMIL THOUSAND CIRCULAR MILS
LCP LIGHTING CONTROL PANEL
LTG LIGHTING
LFMC LIQUID TIGHT FLEXIBLE METAL CONDUIT
LV LOW VOLTAGE
MAX MAXIMUM
MC MECHANICAL CONTRCATOR
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MCE MAIN COMMUNICATIONS EQUIPMENT ROOM
MCM THOUSAND CIRCULAR MILS
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MNT MOUNTING HEIGHT
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
NAC NOTIFICATION APPLIANCE CIRCUIT
N1 NEMA 1
N3R NEMA 3R
N4X NEMA 4X
N/A, NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NESC NATIONAL ELECTRICAL SAFETY CODE
N, NEU NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
OC ON CENTER
OCPD OVERCURRENT PROTECTION DEVICE
OFOI OWNER FURNISHED OWNER INSTALLED
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OH OVERHEAD
OHE OVERHEAD ELECTRIC
OHP OVERHEAD PRIMARY
OHS OVERHEAD SECONDARY
P POLE OR PHASE
PBD PANELBOARD
PEM POWER ENERGY MONITOR
PF POWER FACTOR
PNL PANELBOARD
PQM POWER QUALITY METER
PT POTENTIAL TRANSFORMER
PWR POWER
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RGS RIGID GALVANIZED STEEL CONDUIT
RNC RIGID NON-METALLIC CONDUIT
RVSS REDUCED VOLTAGE SOLID STATE
SA SURGE ARRESTER
SCA SHORT CIRCUIT AMPS
SCCA SHORT CIRCUIT CURRENT RATING
SF SUPPLY FAN
SLC SIGNALING LINE CIRCUIT
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SS SAFETY SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOMMUNICATIONS BONDING BACKBONE
TCC TIME CURRENT CURVE
TR TELECOMMUNICATIONS ROOM
TGB TELECOMMUNICATIONS GROUND BUSBAR
TMGB TELECOMMUNICATIONS MAIN GROUND BUSBAR
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TX TRANSFORMER
TYP TYPICAL
UFR UNDERFLOOR RACEWAY
UG UNDERGROUND
UGE UNDERGROUND ELECTRIC
UGP UNDERGROUND PRIMARY
UGS UNDERGROUND SECONDARY
UL UNDERWRITERS' LABORATORIES
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VA VOLT-AMPERES
VAR VOLT-AMPERES REACTIVE
VAV VARIABLE AIR VOLUME UNIT
VFD VARIABLE FREQUENCY DRIVE
W WATTS OR WIRE
WAO WORK AREA OUTLET
WP WEATHERPROOF
WSR WITHSTAND RATING
XD EXISTING TO BE DEMOLISHED
XFMR TRANSFORMER
XP EXPLOSION PROOF
XR EXISTING TO BE RELOCATED
Φ PHASE
72° DEGREES
∆ DELTA
+ OHMS
OTHER INDUSTRY STANDARD ABBREVIATIONS MAY ALSO EXIST
ABBREVIATIONS
GENERAL
1. ALL WORK UNDER DIVISION 26 SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE CODES AND STANDARDS LISTED HEREIN. THE DESIGN HAS BEEN BASED ON THE REQUIREMENTS OF THESE CODES AND STANDARDS. WHILE IT IS NOT THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THAT ALL WORK CALLED FOR COMPLIES WITH THESE CODES AND STANDARDS, HE SHALL BE RESPONSIBLE FOR CALLING TO THE ENGINEER'S ATTENTION ANY DETAILS ON THE DRAWINGS AND/OR SPECIFICATIONS THAT ARE NOT IN CONFORMANCE WITH THESE OR OTHER CODES AND STANDARDS. CURRENT
ISSUE OF CODE APPLIES UNLESS SPECIFICALLY NOTED OTHERWISE.
2. COMPLY WITH REGULATIONS AND CODES OF SUPPLIERS OF UTILITIES.
3. WHERE NO SPECIFIC METHOD OR FORM OF CONSTRUCTION IS CALLED FOR IN THE CONTRACT DOCUMENTS, THE
CONTRACTOR SHALL COMPLY WITH CODE REQUIREMENTS WHEN CARRYING OUT SUCH WORK.
4. WHERE CODE CONFLICT EXISTS, GENERALLY THE MOST STRINGENT REQUIREMENT APPLIES.
5. CODES OR STANDARDS APPLYING TO A SPECIFIC PART OF THE WORK MAY BE INCLUDED IN THAT SPECIFICATION
SECTION.
6. ALL ELECTRICAL MATERIALS, INSTALLATION AND SYSTEMS SHALL MEET THE REQUIREMENTS OF THE LISTED
STANDARDS, INCLUDING THE LATEST ADDENDA AND AMENDMENTS.
CODES
1. FLORIDA BUILDING CODE (FBC)
A. BUILDING - 2023 8TH EDITION
B. TEST PROTOCOLS FOR HIGH VELOCITY HURRICANE ZONES - 2023 8TH EDITION
2. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
A. NATIONAL ELECTRIC CODE (NFPA 70) - 2020
B. NATIONAL FIRE ALARM CODE (NFPA 72) - 2019
3. FLORIDA FIRE PREVENTION CODE - 2023 8TH EDITION
A. FIRE CODE (NFPA 1) - 2021 FLORIDA EDITION
B. LIFE SAFETY CODE (NFPA 101) - 2021 FLORIDA EDITION
STANDARDS
1. AMERICAN NATIONAL STANDARD INSTITUTES (ANSI)
2. ILLUMINATING ENGINEERING SOCIETY (IES)
3. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
4. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATIONS (NEMA)
5. NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION (NECA)
6. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
7. OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
8. UNDERWRITER'S LABORATORIES, INC. (UL)
CODES & STANDARDS
LEGEND
J
E
JUNCTION BOX.
ELECTRICAL CONNECTION TO EQUIPMENT. VERIFY LOCATION WITH EQUIPMENT PROVIDER. SUBSCRIPT
INDICATES AS FOLLOWS:
AD - AUTOMATIC DOOR.
FV - FLUSH VALVE.
AF - AUTOMATIC FAUCET.
TP - TRAP PRIMER. COORDINATE WITH ACTUAL TRAP PRIMER BEING INSTALLED.
FF - FURNITURE FEED. COORDINATE LOCATION OF BOX WITH ACTUAL PLACEMENT OF FURNITURE. DO NOT LOCATE BOX BEHIND ANY PIECE OF FURNITURE. BOX SHALL BE ACCESSIBLE WITHOUT MOVING THE
FURNITURE.
MB - MOTORIZED BLINDS.
MS - MOTORIZED SCREEN.
MISCELLANEOUS
CIRCUIT RUN CONCEALED BELOW FLOOR, ABOVE CEILING OR IN WALL.
EMERGENCY POWER CIRCUIT RUN CONCEALED BELOW FLOOR, ABOVE CEILING OR IN WALL.
HOMERUN TO PANELBOARD. UNDERLINED TEXT INDICATES PANEL & CIRCUIT DESIGNATION.P-3
CIRCUITING
TYPICAL LIGHT FIXTURE SYMBOLS. SUBSCRIPTS AS FOLLOWS:
EM = EMERGENCY FIXTURE. PROVIDE BATTERY PACK WITH CONNECTION TO UNSWITCHED LEG.
a = ZONE OF CONTROL.
24/7 = ON CONTINUOUSLY FOR SECURITY (NOT SWITCHED).
H22 = BOLD & UNDERLINED TEXT IS THE FIXTURE TAG. SEE LIGHTING FIXTURE SCHEDULE.
TYPICAL NORMAL POWER LIGHT FIXTURE SYMBOLS (BLACK).
TYPICAL EMERGENCY POWER LIGHT FIXTURE SYMBOLS (RED).
a
DL H22
LIGHTING
EXISTING TO BE DEMOLISHED.
NEW WORK.
EXISTING TO REMAIN.
LINETYPES
TOGGLE SWITCH. MOUNT 48" AFF TO TOP UNLESS NOTED OTHERWISE. SUBSCRIPT INDICATES AS FOLLOWS:
3 - THREE-WAY LIGHTING SWITCH.
4 - FOUR-WAY LIGHTING SWITCH.
D - SLIDE DIMMER SWITCH WITH PRESET.
M - MANUAL MOTOR STARTER.
a,b - LETTER INDICATES ZONE OF CONTROL.
T - TIME DELAY LIGHT SWITCH FOR DELAYED OFF TO EXHAUST FAN.
DT - DIGITAL TIME SWITCH WITH AUDIBLE & "FLASH LIGHTING" ALERTS.
DUPLEX RECEPTACLE NEMA 5-20R. MOUNT 18" AFF UNLESS NOTED OTHERWISE. VERIFY DUPLEX MOUNTING REQUIREMENTS WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. ALL GFI DEVICES AND DEVICES IN DAMP AND WET LOCATIONS SHALL BE WEATHER-RESISTANT "WR" TYPE. SUBSCRIPT INDICATES AS FOLLOWS:
G - GROUND FAULT CIRCUIT INTERRUPTER TYPE, MOUNT UNCONCEALED (READILY ACCESSIBLE).
GCB - SERVING CB SHALL BE GFCI TYPE.
WP - GFCI DEVICE WITH CLEAR WEATHERPROOF (IN-USE) COVERPLATE. IN EXTERIOR LOCATIONS
MOUNT 30" AFG.
EWC - GFCI DEVICE, MOUNT UNCONCEALED (READILY ACCESSIBLE) UNDER OR ADJACENT TO EWC.
TV - COORDINATE RECEPTACLE LOCATION WITH A/V OUTLET.
84" - MOUNTING HEIGHT OF DEVICE AFF.
TYPICAL "STACKED" DEVICES. DEVICES ARE IN THE SAME PLAN LOCATION ON THE WALL BUT AT DIFFERENT
HEIGHTS. THIS IS SIMILAR FOR OTHER SYMBOLS AS WELL.
DUPLEX RECEPTACLE NEMA 5-20R. MOUNTED FACE DOWN IN CEILING (IN EXPOSED STRUCTURE CEILINGS, PENDANT MOUNT TO HEIGHT PER ARCHITECT/ENGINEER).
DUPLEX RECEPTACLE MOUNTED HIGHER THAN 18" (UNO, MOUNT 42" AFF OR 8" ABOVE COUNTER). VERIFY
COUNTER HEIGHT PRIOR TO ROUGH-IN.
SPECIAL NEMA TYPE RECEPTACLE, SUBSCRIPT INDICATES NEMA TYPE. VERIFY WITH EQUIPMENT BEING
SUPPLIED. MOUNTED 18" AFF, UNLESS NOTED OTHERWISE.
QUADRAPLEX RECEPTACLE (TWO NEMA 5-20R) MOUNTED 18" AFF UNLESS NOTED OTHERWISE.
UTILITY FLOOR BOX. TAG INDICATES TYPE. SEE DETAILS.
UTILITY FLOOR POKE-THRU. TAG INDICATES TYPE. SEE DETAILS.
6-30
GENERAL WIRING DEVICES
ELECTRICAL EQUIPMENT SUCH AS PANELBOARD, SWITCHBOARD, TRANSFORMER, ETC. TAG INDICATES TYPE
OR SPECIFIC ITEM.
POWER & DISTRIBUTION
WALL MOUNTED LIGHT CONTROL STATION. MOUNT 48" AFF TO TOP UNO. SUBSCRIPT (IF SHOWN) INDICATES ROOM NUMBER OF ROOM CONTROLLER IT IS ASSOCIATED WITH. LETTER/NUMBER INDICATES AS FOLLOWS:
S# - LOW VOLTAGE BUTTON SWITCH, # INDICATES QTY OF BUTTONS/ZONES. CONNECT TO ROOM
CONTROLLER IT IS ASSOCIATED WITH.
D# - LOW VOLTAGE BUTTON DIMMER SWITCH, # INDICATES QTY OF BUTTONS/ZONES. CONNECT TO
ROOM CONTROLLER IT IS ASSOCIATED WITH.
O# - LINE VOLTAGE OCCUPANCY SENSOR (DUAL TECHNOLOGY) SWITCH, # INDICATES QTY OF
BUTTONS/ZONES. PROGRAM FOR AUTO ON, AUTO OFF.
V# - LINE VOLTAGE VACANCY SENSOR (DUAL TECHNOLOGY) SWITCH, # INDICATES QTY OF
BUTTONS/ZONES. PROGRAM FOR MANUAL ON, AUTO OFF.
OD - LINE VOLTAGE OCCUPANCY SENSOR (DUAL TECHNOLOGY) SWITCH, 1-ZONE, 0-10V DIMMER.
PROGRAM FOR AUTO ON, AUTO OFF. (EQUIVALENT TO WATTSTOPPER DW-311).
PC - PHOTOCELL, WEATHERPROOF.
CEILING OR PENDANT MOUNTED LOW VOLTAGE 360° OCCUPANCY/VACANCY SENSOR. SUBSCRIPT (IF SHOWN) INDICATES ROOM NUMBER OF ROOM CONTROLLER IT IS ASSOCIATED WITH. CONNECT TO ROOM
CONTROLLER IT IS ASSOCIATED WITH.
CEILING OR PENDANT MOUNTED LOW VOLTAGE DAYLIGHT SENSOR. SUBSCRIPT (IF SHOWN) INDICATES ROOM NUMBER OF ROOM CONTROLLER IT IS ASSOCIATED WITH. CONNECT TO ROOM CONTROLLER IT IS
ASSOCIATED WITH.
ROOM CONTROLLER(S) DIMMABLE. SUBSCRIPT (IF SHOWN) INDICATES ROOM NUMBER IT IS ASSOCIATED WITH. CONNECT ALL LOW VOLTAGE LIGHTING CONTROL DEVICES IN SAME SPACE TO ROOM CONTROLLER, SEE ROOM CONTROLLER DIAGRAM.
ROOM CONTROLLER(S) NON-DIMMABLE. SUBSCRIPT (IF SHOWN) INDICATES ROOM NUMBER IT IS ASSOCIATED WITH. CONNECT ALL LOW VOLTAGE LIGHTING CONTROL DEVICES IN SAME SPACE TO ROOM
CONTROLLER, SEE ROOM CONTROLLER DIAGRAM.
INPUT/OUTPUT MODULE. CONNECT TO ROOM CONTROLLER IT IS ASSOCIATED WITH.
RD
S4
LIGHTING CONTROL
IO
RN103
ROUGH-IN FOR COMMUNICATIONS OUTLET (CO). MOUNT ON WALL AT 18" AFF UNLESS SUBSCRIPTED OTHERWISE. INCLUDE 1" EMT FROM ROUGH-IN BOX STUBBED ABOVE CEILING. TERMINATE WITH BUSHING
AND PROVIDE PULL STRING.
ROUGH-IN FOR COMMUNICATIONS OUTLET (CO) MOUNTED HIGHER THAN 18" (UNO, MOUNT 42" AFF OR 8" ABOVE COUNTER). INCLUDE 1" EMT FROM ROUGH-IN BOX STUBBED ABOVE CEILING. TERMINATE WITH
BUSHING AND PROVIDE PULL STRING.
ROUGH-IN FOR COMMUNICATIONS OUTLET MOUNTED FACE DOWN IN CEILING.
TELECOM
2P1A
KEY NOTE TAG. SEE KEY NOTES.
BOLD UNDERLINED TEXT ADJACENT TO PLAN SYMBOL INDICATES ELECTRICAL OR MECHANICAL EQUIPMENT IDENTIFICATION TAG. TYPICAL FOR PANELS, LIGHT FIXTURES, FLOORBOXES, TRANSFORMERS, AHUS, ETC.
FOR MECHANICAL EQUIPMENT IDENTIFICATION TAG SEE MECHANICAL EQUIPMENT ELECTRICAL SCHEDULE.
LEADER.
LEADER.
ANNOTATIONS
FACP FIRE ALARM CONTROL PANEL.
ADDRESSABLE RELAY. INTERFACE WITH LIGHTING TO TURN LIGHTING ON DURING ALARM.
NAC DEVICES:
WALL MOUNTED NOTIFICATION DEVICE. SPOKES INDICATE VISUAL, ARCS INDICATE AUDIO. MOUNT BOTTOM OF DEVICE AT 80" AFF (OR WITHIN 6" OF CEILING FOR CEILINGS BELOW 86"). ALL STROBES SHALL BE
SYNCHRONIZED. SUBSCRIPT INDICATES STROBE CANDELA RATING.
CEILING OR PENDANT MOUNTED NOTIFICATION DEVICE. SPOKES INDICATE VISUAL, ARCS INDICATE AUDIO.
SURFACE MOUNT IN DROP CELINGS, PENDANT MOUNT IN EXPOSED STRUCTURE CEILINGS. ALL STROBES
SHALL BE SYNCHRONIZED. SUBSCRIPT INDICATES STROBE CANDELA RATING.
FIRE ALARM
RL
75cd
F
75cd F
F
75cd
F
75cd F
F
CARD ACCESS DOOR. PROVIDE ALL ELECTRONICS REQUIRED FOR FULL ELECTRONIC ACCESS CONTROL OF
DOOR. CONNECT TO EXISTING SYSTEM. UPGRADE HEAD END AS REQUIRED.
SECURITY & ACCESS CONTROL
CR
1. GENERAL ELECTRICAL:
A. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE INSTALLATION OF A COMPLETE ELECTRICAL SYSTEM AS INDICATED WITHIN THESE DRAWINGS. ALL WORK SHALL BE INSTALLED IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES AND ORDINANCES AND WITH MANUFACTURER'S
RECOMMENDATIONS.
B. ALL WORK, MATERIALS AND EQUIPMENT SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE.
C. THE CONTRACTOR SHALL CAREFULLY EXAMINE THE ARCHITECTURAL, STRUCTURAL, ELECTRICAL AND MECHANICAL
DRAWINGS PRIOR TO SUBMITTING HIS BID. THE CONTRACTOR WILL BE REQUIRED TO FURNISH, INSTALL AND
CONNECT ALL ITEMS AS INDICATED ON THE DRAWINGS.
D. THE ARCHITECT/ENGINEER SHALL BE NOTIFIED OF ANY CONFLICTS, OR INTERFERENCES THAT OCCUR BETWEEN
INDIVIDUAL DRAWINGS.
E. ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED IN A NEAT, FIRST CLASS, WORKMANLIKE MANNER, TO THE
APPROVAL OF THE ARCHITECT/ENGINEER AND GOVERNING AUTHORITIES.
F. IN ADDITION TO THE MANUFACTURERS STANDARD GUARANTEES, THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT AND WORKMANSHIP AGAINST DEFECTS FOR ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE, AND SHALL CORRECT ANY DEFECTS AT NO ADDITIONAL COST TO THE OWNER. ALL LAMPS SHALL BE
GUARANTEED FOR 30 DAYS AFTER FINAL ACCEPTANCE.
G. THE LOADS SHOWN FOR APPLIANCES AND EQUIPMENT ARE BASED ON DESIGN INFORMATION. THE CONTRACTOR SHALL VERIFY ALL APPLIANCE LOADS PRIOR TO RUNNING THE CIRCUIT. THE MINIMUM CIRCUIT REQUIREMENTS SHALL BE BASED ON THE APPLIANCE NAMEPLATE VALUE OR CODE REQUIREMENTS, WHICHEVER IS MORE STRINGENT. ADDITIONAL COMPENSATION SHALL NOT BE ALLOWED FOR APPLIANCE MODIFICATIONS BY THE
CONTRACTOR.
2. APPROVAL SUBMITTALS & CLOSEOUTS:
A. PRIOR APPROVAL: PRIOR APPROVAL SHALL BE REQUIRED FOR ANY MANUFACTURER OTHER THAN THOSE LISTED FOR ALL SPECIFIED ITEMS IN THESE DRAWINGS. SUBMIT ALL REQUESTS FOR PRIOR APPROVAL 2 WEEKS PRIOR TO
BID OPENING. ENGINEER'S APPROVAL WILL BE IN THE FORM OF AN ADDENDUM.
B. APPROVAL SUBMITTALS:
a. PRODUCT DATA FOR ALL EQUIPMENT BEING PROVIDED FOR ENGINEER'S REVIEW.
b. SCALED SHOP DRAWINGS FOR THE FOLLOWING:
• FIRE ALARM FLOOR PLANS.
• LIGHTING CONTROL FLOOR PLANS.
C. O&M MANUALS: PROVIDE OPERATIONS AND MAINTENANCE MANUALS AT THE SUBSTANTIAL COMPLETION
INSPECTION.
D. AS-BUILTS: PROVIDE A MARKED-UP SET OF DRAWINGS FOR AS-BUILTS.
E. TRAINING: INCLUDE SUFFICIENT FACTORY AUTHORIZED TRAINING FOR OWNER PERSONNEL FOR SYSTEMS SUCH AS
FIRE ALARM, SECURITY, LIGHTING CONTROLS, ETC.
3. ALTERATIONS & ADDITIONS TO EXISTING WORK:
A. PROVIDE ALL NECESSARY ADDITIONS AND ALTERATIONS TO EXISTING WORK AS REQUIRED TO PROVIDE AND
MAINTAIN A COMPLETE AND PROPER ELECTRICAL INSTALLATION.
B. AS NECESSARY, RELOCATE EXISTING ELECTRICAL WORK (LIGHT FIXTURES, BOXES, CONDUIT, ETC.) SO OTHER
TRADES CAN PURSUE THEIR WORK.
C. MAINTAIN POWER TO EXISTING PORTIONS OF BUILDINGS FED FROM OR THROUGH AREA IN SCOPE OF THIS
CONTRACT.
D. COORDINATE ALL REQUIRED OUTAGES WITH OWNER.
E. PROVIDE ACCESS PANELS AS REQUIRED TO INSTALL AND MAINTAIN NEW WORK.
4. BASIC MATERIALS & METHODS:
A. ALL ELECTRICAL EQUIPMENT, DEVICES, ETC. SHALL BE UL LISTED.
B. ALL ELECTRICAL EQUIPMENT, DEVICES, ETC. LOCATED OUTDOORS SHALL BE WEATHERPROOF.
C. COORDINATE WITH OTHER TRADES AND STRUCTURE.
D. ALL DIMENSIONS TO DEVICES AFF SHALL BE TO CENTERLINE UNLESS NOTED OTHERWISE.
E. COORDINATE LOCATIONS OF ELECTRICAL EQUIPMENT, DEVICES, OUTLETS, FIXTURES, ETC., WITH ARCHITECTURAL
PLANS, ELEVATIONS AND REFLECTED CEILING PLANS PRIOR TO ROUGH-IN WORK.
5. WIRES & CABLES:
A. MC CABLE IS NOT ALLOWED.
B. NO SHARED NEUTRALS ON SINGLE PHASE CIRCUITS.
C. ALL LINE VOLTAGE WIRING SHALL BE COPPER WITH INSULATION SUITABLE FOR THE APPLICATION.
D. MINIMUM SIZE LINE VOLTAGE WIRES SHALL BE #12AWG.
E. INCREASE WIRE SIZE DUE TO VOLTAGE DROP AS FOLLOWS (DISTANCE MEASURED TO CENTER OF LOAD):
a. 120V 100’ - 150’: #10 AWG.
b. 120V 150’ - 200’: #8 AWG.
c. 120V > 200’: #6 AWG.
d. 277V > 150’: #10 AWG.
6. RACEWAYS & BOXES:
A. MINIMUM SIZE CONDUIT FOR ABOVE GROUND USE SHALL BE 1/2".
B. MINIMUM SIZE CONDUIT FOR BELOW GROUND USE SHALL BE 3/4".
C. THE CONDUIT MATERIAL SHALL BE AS FOLLOWS:
a. BELOW GRADE - RNC. ELBOWS >1-1/2" SHALL BE RGS.
b. RISER FROM 36" BELOW GRADE - RGS.
c. CONCEALED RISER FROM 36" BELOW GRADE - RNC.
d. ABOVE GRADE SUBJECT TO PHYSICAL ABUSE - RGS.
e. ABOVE GRADE NOT SUBJECT TO PHYSICAL ABUSE OR WEATHER - EMT.
f. INDOORS NOT SUBJECT TO PHYSICAL ABUSE - EMT.
g. FINAL CONDUIT CONNECTIONS TO VIBRATING EQUIPMENT (TRANSFORMERS, PUMPS, AIR HANDLERS, EXHAUST
FANS, WATER HEATERS, ETC) SHALL BE FLEXIBLE (MAX LENGTH 3 FEET).
D. CONDUIT FITTINGS SHALL BE AS FOLLOWS:
a. EMT - COMPRESSION/SET-SCREW STEEL, CONNECTORS SHALL HAVE WITH INSULATED THROATS.
b. RGS - THREADED GALVANIZED STEEL.
c. PVC - PVC APPROVED FOR THE USE.
d. FMC - ZINC-PLATED STEEL OR CADMIUM-PLATED MALLEABLE IRON SCREW TYPE WITH INSULATED THROAT.
e. LFMC - CADMIUM-PLATED MALLEABLE IRON OR STEEL COMPRESSION TYPE WITH INSULATED THROAT.
E. ALL OUTLET BOXES SHALL BE 4"X4"X1-1/2" DEEP MINIMUM (2-1/8" DEEP FOR TELCOM AND AV SYSTEM BOXES).
F. ELECTRICAL CONTRACTOR SHALL PROVIDE ADEQUATE AND PROPER SUPPORT FOR ALL ELECTRICAL OUTLETS, DEVICES, LIGHT FIXTURES, ETC. BUILT IN OR MOUNTED ON CEILINGS. NO OUTLET BOX, DEVICE, LIGHT FIXTURE, ETC.
SHALL BE SUPPORTED FROM ANY ACOUSTICAL CEILING TILE OR DRYWALL CEILINGS. PROVIDE METAL SUPPORTS THAT ARE MADE FOR USE WITH CEILING GRID SYSTEMS OR PROVIDE HANGERS FROM STRUCTURE ABOVE.
G. JUNCTION BOXES LOCATED ABOVE CEILING SHALL BE INSTALLED FACING DOWN AND SHALL BE ACCESSIBLE AFTER
INSTALLATION.
H. CONDUIT ROUTINGS AND DEVICE/EQUIPMENT LOCATIONS SHOWN ARE DIAGRAMMATIC ONLY, CONTRACTOR SHALL FIELD ROUTE AND LOCATE AS REQUIRED. CONDUIT ROUTINGS SHALL BE PARALLEL OR PERPENDICULAR TO
BUILDING LINES.
I. WALL OUTLETS SHALL NOT BE INSTALLED BACK TO BACK.
7. GROUNDING & BONDING:
A. PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS.
8. IDENTIFICATION:
A. EQUIPMENT:
a. PROVIDE ENGRAVED PHENOLIC LABELS FOR ALL PANELBOARDS, DISCONNECTS, SAFETY SWITCHES, TRANSFORMERS, ATSs, CABINETS, ETC. SEE DETAIL.
B. RACEWAYS:
a. PAINT THE RACEWAY SYSTEMS COUPLINGS AND BOX COVERS PER DETAIL ON DRAWINGS.
b. BRANCH CKT BOX COVERS: WRITE THE PANEL & CIRCUIT NUMBER (I.E. "LPA-CKT#34,36") USING "SHARPIE" PEN.
c. FEEDER BOX COVERS: WRITE TO AND FROM PANELS USING "SHARPIE" PEN.
C. DEVICES & DEVICE COVER PLATES:
a. DEVICES: WRITE PNL AND CKT ON DEVICE AND INSIDE BOX USING "SHARPIE" PEN SUCH THAT IT CAN BE READ
WITH COVER REMOVED.
b. COVERS: MACHINE PRINTED LABEL (CLEAR BACKGROUND WITH BLACK INK) WITH PNL & CKT NUMBER.
c. COVERS: ENGRAVED COVERPLATES WITH PNL & CKT NUMBER.
D. WIRING (FACTORY JACKET COLORS):
a. 208Y120V CIRCUITS: PHASE A: BLACK, PHASE B: RED, PHASE C: BLUE, NEUTRAL: WHITE, GROUNDING
CONDUCTOR: GREEN.
9. GENERAL WIRING DEVICES:
A. SWITCHES - SPECIFICATION GRADE, 20 AMP, 120/277 SHALL BE:
a. HUBBELL HBL1221.
b. LEVITON 1221-2.
c. P&S PS20AC.
B. RECEPTACLES - SPECIFICATION GRADE, 20 AMP, NEMA 5-20R. SHALL BE:
a. HUBBELL HBL5362.
b. LEVITON 5362.
c. P&S 5362A.
C. OTHER WIRING DEVICES NOT LISTED ABOVE SHALL BE SPECIFICATION GRADE.
D. COVER PLATES - NYLON.
E. SPECIAL RECEPTACLES - PER THE DRAWINGS, VERIFY WITH EQUIPMENT BEING SUPPLIED.
F. DEVICES AND COVER PLATES SHALL BE WHITE OR AS DIRECTED BY ARCHITECT/ENGINEER.
G. APPROVED MANUFACTURERS: HUBBELL, LEVITON, PASS & SEYMOUR.
10. CIRCUIT BREAKERS FOR EXISTING PANELBOARDS:
A. MATCH EXISTING KAIC, STYLE AND TYPE AS REQUIRED TO FIT.
B. PROVIDE ANY MOUTING HARDWARE AS REQUIRED.
11. LIGHTING:
A. SEE LIGHT FIXTURE SCHEDULE.
B. PROVIDE A 6'-0" MAXIMUM FLEXIBLE CONNECTION FROM EACH RECESSED LIGHTING FIXTURE TO JUNCTION BOX
ABOVE CEILING.
C. FOR FIXTURES IN LAY-IN CEILINGS, PROVIDE WIRE SUPPORTS AT OPPOSITE CORNERS OF FIXTURE SEPARATE
FROM LAY-IN CEILING WIRE SUPPORTS.
D. PROVIDE ALL 0-10V DIMMING WIRES AS REQUIRED.
12. FIRE ALARM SYSTEM:
A. SLC/INITIATING DEVICES & CIRCUITING:
a. ALL INITIATING DEVICES SHALL BE INTELLIGENT ADDRESSABLE DEVICES. PULL STATIONS SHALL BE SINGLE
ACTION TYPE, SMOKE DETECTORS SHALL BE PHOTOELECTRIC TYPE, DUCT SMOKE DETECTORS SHALL BE SAMPLE TUBE TYPE. PROVIDE REMOTE INDICATORS FOR ALL DUCT SMOKE DETECTORS NOT IN PLAIN SIGHT
FROM FLOOR LEVEL.
b. DO NOT LOAD ANY SLC CONTROLLER MORE THAN 75% OF ITS ALLOWABLE DEVICE LIMIT.
c. PULL STATIONS SHALL BE MOUNTED 48" AFF TO CENTER, STROBES SHALL BE MOUNTED 80" AFF TO BOTTOM OF
STROBE LENS OR MOUNTED TO THE CEILING (REFER TO FLOOR PLANS FOR LOCATIONS).
d. SLC CABLES SHALL BE #18AWG TWISTED PAIR MINIMUM.
B. NAC DEVICES & CIRCUITING:
a. DO NOT LOAD ANY NAC CONTROLLER MORE THAN 75% OF ITS ALLOWABLE CAPACITY.
b. NAC CABLES SHALL BE #14AWG MINIMUM.
c. WIRE NUTS SHALL NOT BE USED. ALL WIRES SHALL BE CONNECTED/TERMINATED VIA SCREW TERMINALS.
d. LABEL ALL WIRES IN JUNCTIONS AND AT TERMINATIONS.
C. GENERAL:
a. TAG ALL CIRCUITS IN CABINETS AND JUNCTION LOCATIONS.
b. ALL CABLES SHALL BE IN CONDUIT DEDICATED TO THE FIRE ALARM SYSTEM. MINIMUM SIZE IS 3/4".
c. ALL TERMINATIONS SHALL BE UNDER SCREW TERMINALS. WIRE NUTS SHALL NOT BE USED.
d. TEST, CERTIFY & DOCUMENT IN COMPLIANCE WITH NFPA 72.
D. APPROVED MANUFACTURERS: MATCH EXISTING - SIMPLEX.
SPECIFICATIONS 8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
H E
A
R C
H
IT
E C
T 'S
O R
T
N
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
D
S
P E
C
IF
IC
A
T
IO
N S
C O
M P
L Y
W
IT
H
T H
E A
P P
L
IC
A B
M
IN
IM
U M
B U
IL
D
G
C
O D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E T
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
I
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:20 PM
ELECTRICAL LEGEND,
ABBREVIATIONS, CODES AND
STANDARDS
100% CONSTRUCTION
DOCUMENTS
E001
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
REVISIONS
NO: DATE: REF: BY:
marka MRA PE Digital
B
C
2 4 5 6 7
C
ILA
ILC
CORRIDOR
LOBBY
WORK ROOM
CORRIDOR
139A
BOOKS/RECORDS
TOILET
CORRIDOR
148M
STAIR
ELECTRIC
OFFICE
143T
VESTIBULE
OFFICE
148E OFFICE
148F
OFFICE
148G
OFFICE
148L
CONFERENCE
STORAGE
148J
SMALL OFFICE
148I
ADA TOILET
148H
IT ROOM
WOMENS
VESTIBULE
ELEVATOR
VSTIBULE
MENS
CUSTODIAL
CORRIDOR
Room
Room
123 Room
CORRIDOR
Room
Room
KITCHEN
CLERKS OFFICE
Unoccupied
Unoccupied
STORAGE
148B
STORAGE
148C
VESTIBULE
148A
OFFICE
VAULT BACK OF HOUSE
143A
Room
Room
Room
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:21 PM
ELECTRICAL FIRST FLOOR PLAN -
DEMOLITION
100% CONSTRUCTION
DOCUMENTS
E111
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 ELECTRICAL FIRST FLOOR PLAN - DEMOLITION
REVISIONS
NO: DATE: REF: BY:
1. APPLIES TO ALL DEMO PLANS.
2. PROVIDE MATERIALS AND LABOR AS NECESSARY TO:
A. REMOVE ALL ELECTRICAL ITEMS INDICATED TO BE REMOVED OR
DEMOLISHED.
B. REMOVE, STORE, CLEAN, AND REINSTALL ALL ELECTRICAL ITEMS
INDICATED AS EXISTING TO BE RELOCATED OR REINSTALLED.
C. MAINTAIN IN SERVICE - TO THE ORIGINAL CONDITION, TO THE
SATISFACTION OF THE OWNER AND THE ENGINEER - ANY
ELECTRICAL ITEMS OUTSIDE OF THE RENOVATION AREA WHICH ARE
SERVED BY OR SUPPLIED BY ELECTRICAL ITEMS WITHIN THE
RENOVATION AREA.
D. PERFORM ELECTRICAL DEMOLITION NECESSARY TO ACCOMMODATE
ARCHITECTURAL WORK SPECIFIED ON DEMOLITION SHEET.
COORDINATE EXACT REQUIREMENTS WITH ARCHITECTURAL
DOCUMENTS AND FIELD CONDITIONS PRIOR TO BID.
E. REPAIR OR REPLACE - TO THE ORIGINAL CONDITION & TO THE
SATISFACTION OF THE OWNER AND THE ENGINEER - ANY EXISTING
DEVICES, FINISHES, SURFACES, OR EQUIPMENT TO REMAIN WHICH
IS DAMAGED DURING DEMOLITION OR CONSTRUCTION WITH NO
CHANGE TO THE CONTRACT AMOUNT OR TIME SCHEDULE.
3. DO NOT DISTURB ANY OTHER ELECTRICAL ITEMS EXCEPT AS
NECESSARY TO ACCOMMODATE OTHER WORK SPECIFIED.
4. ALL EXISTING DEVICES & EQUIPMENT SHALL BE CONSIDERED TO BE
EXISTING TO REMAIN UNLESS SPECIFICALLY INDICATED OTHERWISE.
5. REMOVE ALL UNUSED CONDUCTORS BACK TO SOURCE OR TO THE FIRST
JUNCTION POINT SUPPLYING EXISTING OR NEW LOADS TO REMAIN.
6. ALL EXPOSED UNUSED CONDUIT SHALL BE REMOVED. ALL UNUSED
CONCEALED CONDUIT SHALL BE ABANDONED IN PLACE AFTER
INSTALLING A PULL-STRING.
7. DEVICES SHOWN INSIDE THE RENOVATION AREA ARE NOT INTENDED TO
REPRESENT ALL DEVICES WITHIN SPACE. ADDITIONAL DEMOLITION
WORK MAY BE REQUIRED FOR INSTALLING NEW WORK. CONTRACTOR
SHALL ASSUME ADDITIONAL ITEMS NOT INDICATED ARE PRESENT AND
SHALL THOROUGHLY INSPECT PROJECT AREA PRIOR TO BIDDING.
8. DEMOLITION SHALL INCLUDE ANY REMOVAL AND REPLACEMENT OF
EXISTING MATERIALS TO MAKE PROVISION FOR NEW FINISHES IF
REQUIRED TO ACCOMMODATE WORK BY OTHER DIVISIONS OF THIS
CONTRACT.
GENERAL DEMOLITION NOTES
KEY NOTES
1. DEMOLISH ALL LIGHTING FIXTURES AND CONTROLS IN THIS SPACE.
F F
A
B
C
2 4 5 6 7
C
2LC
2LA
JURY ROOM
JURY ROOM
TOILET
TOILET
TOILET
TOILET
PRISONER DETENTION
PRISONER DETENTION
CIRCUIT JUDGE JUDICIAL ASSISTANT
TOILET
Unoccupied
Unoccupied
CIRCUIT JUDGE
248 CIRCUIT JUDGE JUDICIAL ASSISTANT
TOILET
TOILET
HEARING ROOM
OFFICE
VISITING JUDGE
STORAGE
226A
NORTH COURTROOM
DEPUTY'S ROOM
DEPUTY'S ROOM
SOUTH COURTROOM
CORRIDOR
MENS
WOMENS
ELEVATOR
CUSTODIAL
SECRETARY
JUDICIAL HEARING OFFICER
COURTROOM
203B
COORIDOR
PUBLIC
203C
LACTATION ROOM
JURY ROOM
203A
TOILET
TOILET
Unoccupied
Unoccupied
CORRIDOR
LIBRARY
COUNTY JUDGE
HEARING ROOM
STAFF
HALL
COURT REPORTER
COURT REPORTER
OFFICE
OFFICE
2LB
REROUTE EXISTING CABLES GOING THRU
FLOOR IN THIS AREA. COORDINATE WITH
OWNER.
DEMOLISH EXISTING CABINETS IN WALL
1 1
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:22 PM
ELECTRICAL SECOND FLOOR PLAN
- DEMOLITION
100% CONSTRUCTION
DOCUMENTS
E112
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 ELECTRICAL SECOND FLOOR PLAN - DEMOLITION
REVISIONS
NO: DATE: REF: BY:
1. APPLIES TO ALL DEMO PLANS.
2. PROVIDE MATERIALS AND LABOR AS NECESSARY TO:
A. REMOVE ALL ELECTRICAL ITEMS INDICATED TO BE REMOVED OR
DEMOLISHED.
B. REMOVE, STORE, CLEAN, AND REINSTALL ALL ELECTRICAL ITEMS
INDICATED AS EXISTING TO BE RELOCATED OR REINSTALLED.
C. MAINTAIN IN SERVICE - TO THE ORIGINAL CONDITION, TO THE
SATISFACTION OF THE OWNER AND THE ENGINEER - ANY
ELECTRICAL ITEMS OUTSIDE OF THE RENOVATION AREA WHICH ARE
SERVED BY OR SUPPLIED BY ELECTRICAL ITEMS WITHIN THE
RENOVATION AREA.
D. PERFORM ELECTRICAL DEMOLITION NECESSARY TO ACCOMMODATE
ARCHITECTURAL WORK SPECIFIED ON DEMOLITION SHEET.
COORDINATE EXACT REQUIREMENTS WITH ARCHITECTURAL
DOCUMENTS AND FIELD CONDITIONS PRIOR TO BID.
E. REPAIR OR REPLACE - TO THE ORIGINAL CONDITION & TO THE
SATISFACTION OF THE OWNER AND THE ENGINEER - ANY EXISTING
DEVICES, FINISHES, SURFACES, OR EQUIPMENT TO REMAIN WHICH
IS DAMAGED DURING DEMOLITION OR CONSTRUCTION WITH NO
CHANGE TO THE CONTRACT AMOUNT OR TIME SCHEDULE.
3. DO NOT DISTURB ANY OTHER ELECTRICAL ITEMS EXCEPT AS
NECESSARY TO ACCOMMODATE OTHER WORK SPECIFIED.
4. ALL EXISTING DEVICES & EQUIPMENT SHALL BE CONSIDERED TO BE
EXISTING TO REMAIN UNLESS SPECIFICALLY INDICATED OTHERWISE.
5. REMOVE ALL UNUSED CONDUCTORS BACK TO SOURCE OR TO THE FIRST
JUNCTION POINT SUPPLYING EXISTING OR NEW LOADS TO REMAIN.
6. ALL EXPOSED UNUSED CONDUIT SHALL BE REMOVED. ALL UNUSED
CONCEALED CONDUIT SHALL BE ABANDONED IN PLACE AFTER
INSTALLING A PULL-STRING.
7. DEVICES SHOWN INSIDE THE RENOVATION AREA ARE NOT INTENDED TO
REPRESENT ALL DEVICES WITHIN SPACE. ADDITIONAL DEMOLITION
WORK MAY BE REQUIRED FOR INSTALLING NEW WORK. CONTRACTOR
SHALL ASSUME ADDITIONAL ITEMS NOT INDICATED ARE PRESENT AND
SHALL THOROUGHLY INSPECT PROJECT AREA PRIOR TO BIDDING.
8. DEMOLITION SHALL INCLUDE ANY REMOVAL AND REPLACEMENT OF
EXISTING MATERIALS TO MAKE PROVISION FOR NEW FINISHES IF
REQUIRED TO ACCOMMODATE WORK BY OTHER DIVISIONS OF THIS
CONTRACT.
GENERAL DEMOLITION NOTES
KEY NOTES
1. DEMOLISH ALL LIGHTING FIXTURES AND CONTROLS IN THIS SPACE.
VT
V
A
B
C
2 4 5 6 7
IT ROOM
Room
Unoccupied
Unoccupied
STORAGE
ELEVATOR
Room
Room
Room
Room
KITCHEN
Unoccupied
Unoccupied
Room
Room
Room
CUSTODIAL
Room
Room
Room
TOILET
Room
Room
TOILET
VESTIBULE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
VSTIBULE
CORRIDOR
VESTIBULE
Room
Room
Room
CLERKS OFFICE
STORAGE
148C
OFFICE
VESTIBULE
148A
STAIR
ELECTRIC
CONFERENCE
CORRIDOR
139A
VESTIBULE
OFFICE
143T
OFFICE
148G
OFFICE
148F
CORRIDOR
148M
OFFICE
148L
WORK ROOM
TOILET
STORAGE
148J
SMALL OFFICE
148I
WOMENS
MENS
TOILET
ADA TOILET
148H
BOOKS/RECORDS
LOBBY
OFFICE
148E
STORAGE
148B
Room
Room
ILC
C
ILA
VAULT BACK OF HOUSE
143A
VAULT BACK OF HOUSE
143A
2 2
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:24 PM
ELECTRICAL FIRST FLOOR PLAN -
POWER
100% CONSTRUCTION
DOCUMENTS
E211
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 ELECTRICAL FIRST FLOOR PLAN - POWER
REVISIONS
NO: DATE: REF: BY:
KEY NOTES
1. PROVIDE 1-1/2"C FROM FLOORBOX TO BOX BEHIND TV FOR OWNER AV
CABLES.
2. CONNECT TO 20/1 CB CKT FREED UP FROM DEMOLITION OR TO A NEW
20/1 CB IN AVAILABLE SPACE.
SHEET NOTES
A. - B. - C. -
V
T V
T V
T V
A
B
C
2 4 5 6 7
Unoccupied
Unoccupied
TOILET
Unoccupied
Unoccupied
TOILET
TOILET
STORAGE
Unoccupied
Unoccupied
JURY ROOM
COUNTY JUDGE
JURY ROOM
PRISONER DETENTION
PRISONER DETENTION
CIRCUIT JUDGE JUDICIAL ASSISTANT
CIRCUIT JUDGE JUDICIAL ASSISTANT
STORAGE
COUNTY JUDGE
LIBRARY
CORRIDOR
TOILET
CUSTODIAL
ELEVATOR
WOMENS
MENS
212 TOILET
JURY ROOM
203A
SECRETARY
JUDICIAL HEARING OFFICER
WAITING
CORRIDOR
OFFICE
OFFICE
COURT REPORTER
OFFICE
COURT REPORTER
HEARING ROOM
VISITING JUDGE
OFFICE
DEPUTY'S ROOM
DEPUTY'S ROOM
Unoccupied
Unoccupied
Unoccupied
Unoccupied
SECURE AREA
HEARING ROOM
STAFF
COORIDOR
TOILET
TOILET
HALL
OFFICE / RECEPTION
COURTROOM
203B
PUBLIC
203C
VAULT
FILES
STORAGE
STORAGE
TOILET
CIRCUIT JUDGE
Unoccupied
Unoccupied
TOILET
TOILET
LACTATION ROOM
VESTIBULE
229B
SOUTH COURTROOM
STORAGE
229A
STORAGE
226A
NORTH COURTROOM
VESTIBULE
226B
C
2LC
2LA
2LB
2LB
2LB
2LB
2LA
2LA
2LA
2LB2
2LA
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:25 PM
ELECTRICAL SECOND FLOOR PLAN
- POWER
100% CONSTRUCTION
DOCUMENTS
E212
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 ELECTRICAL SECOND FLOOR PLAN - POWER
REVISIONS
NO: DATE: REF: BY:
KEY NOTES
1. DUE TO DEMOLITION, CONNECT EXISTING RECEPTACLE TO ADJACENT
RECEPTACLE CIRCUIT AS SHOWN.
2. CONNECT TO 20/1 CB CKT FREED UP FROM DEMOLITION OR TO A NEW
20/1 CB IN AVAILABLE SPACE.
SHEET NOTES
A. - B. - C. -
O D
O D
O D
O D
O D
O D
O1
O1
D
D3
D
D3
D
D3
S1 D1
S
RN
IO
IO
RD
RD IO
RD
IO
RD
IO
RN
IO
IO
O
O
RD
RN IO
D1
O1
D
RD
IO
RD
IO
IO IORD RD
A
B
C
2 4 5 6 7
IT ROOM
Room
Unoccupied
Unoccupied
STORAGE
ELEVATOR
Room
Room
Room
Room
KITCHEN
Unoccupied
Unoccupied
Room
Room
Room
CUSTODIAL
Room
Room
Room
TOILET
Room
Room
TOILET
VESTIBULE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
VSTIBULE
CORRIDOR
VESTIBULE
Room
Room
Room
CLERKS OFFICE
STORAGE
148C
OFFICE
VESTIBULE
148A
STAIR
ELECTRIC
CONFERENCE
CORRIDOR
139A
OFFICE
143T
OFFICE
148G
OFFICE
148F
CORRIDOR
148M
OFFICE
148L
WORK ROOM
TOILET
STORAGE
148J
SMALL OFFICE
148I
WOMENS
MENS
TOILET
ADA TOILET
148H
BOOKS/RECORDS
LOBBY
OFFICE
148E
STORAGE
148B
Room
Room a a a a a a aaaa b b c c c
22PS, TYP
C
24PS, TYP
6PS, TYP THIS ROOM
PEN1PEN1PEN1
PEN1PEN1 PEN1
b b bb a aa a c c c a b
XEB, TYP
EM
EM
EM
EM EM
EM
EM
EM
EM
EM
EM
EM EM
EM
EM
EM
EM
EM EM
EM
EM
EM
EM
EM EM
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:27 PM
ELECTRICAL FIRST FLOOR PLAN -
LIGHTING
100% CONSTRUCTION
DOCUMENTS
E221
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 FIRST FLOOR PLAN - LIGHTING
REVISIONS
NO: DATE: REF: BY:
KEY NOTES
1. DIMMABLE ROOM: FOR DRAWING CLARITY, NOT ALL WIRING SHOWN
HERE. CONNECT ALL LIGHTS (POWER & 0-10V DIMMING) AND ALL
CONTROL DEVICES. SEE ROOM CONTROLLER DIAGRAM.
2. NON-DIMMABLE ROOM: FOR DRAWING CLARITY, NOT ALL WIRING SHOWN
HERE. CONNECT ALL LIGHTS AND ALL CONTROL DEVICES. SEE ROOM
CONTROLLER DIAGRAM.
SHEET NOTES
A. CONNECT NEW LIGHTS TO EXISTING LIGHTING CIRCUITS FROM
DEMOLITION.
F
D
D
D
D
D
D
D
O
O
O1
O1
D
D
D
D
F F F F F
F
F
F
F F
F F
RD
IO
RD
IO
RD
IO
RD IO
RD IO RD
IO
RL RL
RL
RL
RL
RL
F
F
RN
IO
RN
IO
F F
RD
IO
RDIO
RD RD
S1
IO
RN
RD
IO
O1
O1
S1O1
O1 O1
RL RL
RL RL
A
B
C
2 4 5 6 7
Unoccupied
Unoccupied
TOILET
Unoccupied
Unoccupied
TOILET
TOILET
STORAGE
Unoccupied
Unoccupied
JURY ROOM
COUNTY JUDGE
JURY ROOM
PRISONER DETENTION
PRISONER DETENTION
CIRCUIT JUDGE JUDICIAL ASSISTANT
CIRCUIT JUDGE JUDICIAL ASSISTANT
STORAGE
COUNTY JUDGE
LIBRARY
CORRIDOR
TOILET
CUSTODIAL
ELEVATOR
WOMENS
MENS
TOILET
JURY ROOM
203A
SECRETARY
JUDICIAL HEARING OFFICER
WAITING
CORRIDOR
OFFICE
OFFICE
COURT REPORTER
OFFICE
COURT REPORTER
HEARING ROOM
VISITING JUDGE
OFFICE
DEPUTY'S ROOM
DEPUTY'S ROOM
Unoccupied
Unoccupied
Unoccupied
Unoccupied
SECURE AREA
HEARING ROOM
STAFF
COORIDOR
TOILET
TOILET
HALL
OFFICE / RECEPTION
COURTROOM
203B
PUBLIC
203C
VAULT
FILES
STORAGE
STORAGE
TOILET
246CIRCUIT JUDGE
Unoccupied
Unoccupied
TOILET
TOILET
LACTATION ROOM
VESTIBULE
229B
SOUTH COURTROOM
STORAGE
229A
STORAGE
226A
NORTH COURTROOM
VESTIBULE
226BC
FIXTURE TYPE 22PS, TYP
6PS, TYP
PEN2
PEN2
PEN2PEN2
PEN2
PEN2
12REC
12REC
12REC
6PS
12REC
12REC
12REC
4REC
QTY (4) COVE
6PS
6PS
6PS
6PS
6PS
6PS
6PS
6PS
6PS6PS
6PS6PS
6PS
6PS
6PS
6PS
6PS
6PS
6PS
c c c c b bb a a af ff ff f d e e e
6PS
e e e c c c c b b b b a a a d
4REC
6PS
6PS6PS
6PS 6PS
f fff f f
6PS
6PS
6PS
6PS
6PS
6PS
6PS
6PS
2 2
1 1 a,b,c d,e,f a,b,c d,e,f
3 3
3 333
EM EM EM EM EM EM
EM
EM
EM
EM
EM
EM
EM
EM
EM EM
QTY (6) COVE
QTY (2) COVE
QTY (6) COVE
QTY (2) COVE
b
QTY (4) COVE
QTY (6) COVE
QTY (3) COVE
QTY (6) COVE
QTY (3) COVE
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:28 PM
ELECTRICAL SECOND FLOOR PLAN
- LIGHTING
100% CONSTRUCTION
DOCUMENTS
E222
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026 N
SCALE: 1/8" = 1'-0"
1 SECOND FLOOR PLAN - LIGHTING
REVISIONS
NO: DATE: REF: BY:
KEY NOTES
1. DIMMABLE ROOM: FOR DRAWING CLARITY, NOT ALL WIRING SHOWN
HERE. CONNECT ALL LIGHTS (POWER & 0-10V DIMMING) AND ALL
CONTROL DEVICES. SEE ROOM CONTROLLER DIAGRAM.
2. NON-DIMMABLE ROOM: FOR DRAWING CLARITY, NOT ALL WIRING SHOWN
HERE. CONNECT ALL LIGHTS AND ALL CONTROL DEVICES. SEE ROOM
CONTROLLER DIAGRAM.
3. CONNECT TO LIGHTING CIRCUIT FROM DEMOLITION.
SHEET NOTES
A. CONNECT NEW LIGHTS TO EXISTING LIGHTING CIRCUITS FROM
DEMOLITION.
F F
F
F
F
FFFF
FF
F
F
F
F
F F
F F
F
RL
RL
RL
RL
RL
RL
RL
F
F
F
RL
RL
RL
RL RL
F
F
F
A
B
C
2 4 5 6 7
CORRIDOR
148M
SMALL OFFICE
148I
STORAGE
148J
ADA TOILET
148H
OFFICE
143T
OFFICE
148E
OFFICE
148F
OFFICE
148G
OFFICE
148L
CORRIDOR
139A
CONFERENCE
WORK ROOM
TOILET
TOILET
LOBBY
BOOKS/RECORDS
WOMENS
CUSTODIAL
MENS
VSTIBULE
VESTIBULE
Room
129CORRIDOR
IT ROOM
CLERKS OFFICE
Room
Room
Room
75cd75cd
15cd
15cd
15cd
60cd
15cd
15cd
30cd
15cd 15cd
30cd
C
75cd
15cd15cd
75cd
75cd
15cd
EXISTING FACP
75cd
75cd
75cd
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:28 PM
ELECTRICAL FIRST FLOOR PLAN -
FIRE ALARM
100% CONSTRUCTION
DOCUMENTS
E231
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 FIRST FLOOR PLAN - FIRE ALARM
REVISIONS
NO: DATE: REF: BY:
F F F F F
F
F
F
F F
F F
RL RL
RL
RL
RL
RL
F
F F F
RL RL
RL RL
A
B
C
2 4 5 6 7
Unoccupied
Unoccupied
TOILET
Unoccupied
Unoccupied
TOILET
TOILET
STORAGE
Unoccupied
Unoccupied
JURY ROOM
COUNTY JUDGE
JURY ROOM
PRISONER DETENTION
PRISONER DETENTION
CIRCUIT JUDGE JUDICIAL ASSISTANT
CIRCUIT JUDGE JUDICIAL ASSISTANT
STORAGE
COUNTY JUDGE
LIBRARY
CORRIDOR
TOILET
CUSTODIAL
ELEVATOR
WOMENS
MENS
TOILET
JURY ROOM
203A
SECRETARY
JUDICIAL HEARING OFFICER
WAITING
CORRIDOR
OFFICE
OFFICE
COURT REPORTER
OFFICE
COURT REPORTER
HEARING ROOM
VISITING JUDGE
OFFICE
DEPUTY'S ROOM
DEPUTY'S ROOM
Unoccupied
Unoccupied
Unoccupied
Unoccupied
SECURE AREA
HEARING ROOM
STAFF
COORIDOR
TOILET
TOILET
HALL
OFFICE / RECEPTION
COURTROOM
203B
PUBLIC
203C
VAULT
FILES
STORAGE
STORAGE
TOILET
CIRCUIT JUDGE
Unoccupied
Unoccupied
TOILET
TOILET
LACTATION ROOM
VESTIBULE
229B
SOUTH COURTROOM
STORAGE
229A
STORAGE
226A
NORTH COURTROOM
VESTIBULE
226B C
15cd
15cd
15cd
15cd 15cd 15cd 15cd
15cd
15cd 15cd
15cd 15cd
110cd
110cd 75cd 75cd
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:28 PM
ELECTRICAL SECOND FLOOR PLAN
- FIRE ALARM
100% CONSTRUCTION
DOCUMENTS
E232
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 SECOND FLOOR PLAN - FIRE ALARM
REVISIONS
NO: DATE: REF: BY:
VT
V
CR
C R
CR
C R
CR
C R
A
B
C
2 4 5 6 7
IT ROOM
Room
Unoccupied
Unoccupied
STORAGE
ELEVATOR
Room
Room
Room
Room
KITCHEN
Unoccupied
Unoccupied
Room
Room
Room
CUSTODIAL
Room
Room
Room
TOILET
Room
Room
TOILET
VESTIBULE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
VSTIBULE
CORRIDOR
VESTIBULE
Room
Room
Room
114 CLERKS OFFICE
STORAGE
148C
OFFICE
VESTIBULE
148A
STAIR
ELECTRIC
CONFERENCE
CORRIDOR
139A
VESTIBULE
OFFICE
143T
OFFICE
148G
OFFICE
148F
CORRIDOR
148M
OFFICE
148L
WORK ROOM
TOILET
STORAGE
148J
SMALL OFFICE
148I
WOMENS
MENS
TOILET
ADA TOILET
148H
BOOKS/RECORDS
LOBBY
OFFICE
148E
STORAGE
148B
Room
Room
C
EXISTING
ELECTRONIC
ACCESS CONTROL
SYSTEM
TV
TV
TV
TV
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:30 PM
ELECTRICAL FIRST FLOOR PLAN -
SYSTEMS
100% CONSTRUCTION
DOCUMENTS
E241
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 ELECTRICAL FIRST FLOOR PLAN - SYSTEMS
REVISIONS
NO: DATE: REF: BY:
V
T V
T V
T V
A
B
C
2 4 5 6 7
Unoccupied
Unoccupied
TOILET
Unoccupied
Unoccupied
TOILET
TOILET
STORAGE
Unoccupied
Unoccupied
JURY ROOM
COUNTY JUDGE
JURY ROOM
PRISONER DETENTION
PRISONER DETENTION
CIRCUIT JUDGE JUDICIAL ASSISTANT
CIRCUIT JUDGE JUDICIAL ASSISTANT
STORAGE
COUNTY JUDGE
LIBRARY
CORRIDOR
TOILET
CUSTODIAL
ELEVATOR
WOMENS
MENS
212 TOILET
JURY ROOM
203A
SECRETARY
JUDICIAL HEARING OFFICER
WAITING
CORRIDOR
OFFICE
OFFICE
COURT REPORTER
OFFICE
COURT REPORTER
HEARING ROOM
VISITING JUDGE
OFFICE
DEPUTY'S ROOM
DEPUTY'S ROOM
Unoccupied
Unoccupied
Unoccupied
Unoccupied
SECURE AREA
HEARING ROOM
STAFF
COORIDOR
TOILET
TOILET
HALL
OFFICE / RECEPTION
COURTROOM
203B
PUBLIC
203C
VAULT
FILES
STORAGE
STORAGE
TOILET
CIRCUIT JUDGE
Unoccupied
Unoccupied
TOILET
TOILET
LACTATION ROOM
VESTIBULE
229B
SOUTH COURTROOM
STORAGE
229A
STORAGE
226A
NORTH COURTROOM
VESTIBULE
226B
C
EXISTING
ELECTRONIC
ACCESS CONTROL
SYSTEM
EXISTING TELCOM
RACKS
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:31 PM
ELECTRICAL SECOND FLOOR PLAN
- SYSTEMS
100% CONSTRUCTION
DOCUMENTS
E242
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
N
SCALE: 1/8" = 1'-0"
1 ELECTRICAL SECOND FLOOR PLAN - SYSTEMS
REVISIONS
NO: DATE: REF: BY:
KEY NOTES
1. PROVIDE (2)1-1/2"C SLEEVES THRU FLOOR FOR OFOI CABLING.
COORDINATE LOCATION WITH OWNER.
2. PROVIDE (1)1"C SLEEVE THRU FLOOR FOR OFOI MIC CABLING.
COORDINATE LOCATION WITH OWNER.
SHEET NOTES
A. FIOR EACH OF 2 COURTROOMS: PROVIDE FOR QTY (5) ADDITIONAL WALL
BOXES INCLUDING 1" CONDUIT TO ABOVE CIELING FOR OFOI CABLING.
LOCATION BY OWNER. COORDINATE WITH OWNER.
WASHER & LOCKNUT
ON UNDERSIDE
LOCKING SQUARE
WASHER & LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD, TYP.
CONDUIT
CONDUIT CLAMP SIZE
AS REQUIRED
INTEGRAL GALVANIZED
STEEL MOUNTING
CHANNEL
GENERAL NOTES:
1. CHANNEL LONGER THAN 36" SHALL BE INSTALLED WITH A CENTER SUPPORT ROD. SUPPORT RODS SHALL NOT BE
GREATER THAN 18" APART.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD. FIELD VERIFY EXACT CONDITIONS.
PROVIDE MACHINE PRINTED
SELF ADHESIVE LABEL (BLACK
LETTERS ON CLEAR
BACKGROUND) ON ALL DEVICE
COVERPLATES INDICATING
PANEL AND CKT
PANEL 4L1
CKT #14
LABEL EXAMPLES
PANEL 2P2
CKT #17
CONCEALED DUCT
MOUNTED SMOKE
DETECTOR ABOVE
CEILING
DUCT
DUCT SMOKE DETECTOR
REMOTE INDICATOR FACE
DOWN IN CEILING
CEILING MNT OCCUPANCY
SENSORS, DO NOT
LOCATE NEAR TO HVAC
DIFFUSERS, SEE
MANUFACTURER SPEC
CEILING MNT FIRE
ALARM A/V DEVICE
IN EXPOSED STRUCTURE
CEILING MOUNT ELECTICAL
DEVICES SUCH AS: LIGHTS,
OCC SENSORS, FIRE
ALARM NAC DEVICES,ETC.
PENDANT TO BOTTOM OF
OBSTRUCTIONS SUCH AS:
DUCTWORK, ETC.
BUILDING STRUCTURE
PIPING/DUCTWORK/ETC
SMOKE DETECTOR
48"
60"
80"
BOTTOM
OF
STROBE
<80"
SEE PLANS
TYPICAL MOUNTING:
RECEPTACLES SHALL BE
INSTALLED WITH
GROUND PIN UP.
(TYPICAL FOR DUPLEX,
QUADRAPLEX, AND GFI)
VERIFY LOCATIONS OF FLOORBOXES AND
POKETHRUS WITH ARCHITECT PRIOR TO ROUGH-IN.
18"
8"
TV RECEPTACLE MOUNTING:
TV RECEPTACLES SHALL BE
MOUNTED ADJACENT TO TELCOM
TV OUTLET. VERIFY MOUNTING
HEIGHT WITH TELCOM PRIOR TO
ROUGH-IN.
FA PULL STATION
FIRE ALARM OR
GENERATOR
ANNUNCIATOR
48"
UNDERCABINET LIGHT FIXTURES:
1. CONCEAL ALL WIRING.
2. IF REMOTE DRIVERS ARE
USED, LOCATE ABOVE
ACCESSIBLE CEILING.
3. COORDINATE WITH
ARCHITECT PRIOR TO
ROUGHIN.
EXIT
WALL MOUNT FIRE
ALARM STROBE
<5' <18"
LIGHT
SWITCH
FINISHED GRADE
30"
EXTERIOR RECEPTACLE WITH
IN - USE COVER
CKT LABELS FOR
EACH PHASE AND
NEUTRAL
ALL WIRES NEATLY
TRAINED, BUNDLED
AND SECURED
PANEL CLEANED OF
DEBRIS
INSULATED THROATS
(OR BUSHINGS) ON
ALL CONNECTORS
WIRE JACKETS
COLOR CODED (NO
PHASE TAPE)
COMPUTER
PRINTED
DIRECTORY
WITH SPECIFIC
& CLEAR
LOADS FOR
EACH CIRCUIT
PANEL COVER PANEL INTERIOR
EMT TO RGS
TRANSITION
SLAB
ON
GRADE
EXTENSION RINGS NOT ALLOWED. SIZE
BOXES APPROPRIATELY WITHOUT
NEED FOR EXTENSION RINGS.
CONCEALED
RISERS:
RGS OR RNC
CONCEALED ABOVE
CEILING: EMT
CONCEALED
IN WALL: EMT
ELBOWS <1.5": RNC
EXPOSED
MECH/ELEC
ROOM ABOVE
6'AFF: EMTEXPOSED IN MECH/ELEC
ROOM BELOW 6'AFF: RGS
CONNECTION TO
EQUIPMENT: FLEX <=36"
FROM BELOW GRADE
CONCEALED IN WALL: RNC
RGS OR RNC
ELBOWS >=1.5": RGS
EXPOSED
RISERS: RGS
VIBRATING
EQUIPMENT:
PUMP, AHU, ETC
PANEL
SWITCHBOARD
CEILING
NOTE: THE SPECIFICATIONS ALWAYS PREVAIL OVER THIS DETAIL. SEE
SPECIFICATIONS FOR ADDITIONAL INFORMATION, EXCEPTIONS, ETC.
DUPLEX
RECEPTACLE
RECESSED IN
WALL
STARTER OR
DISCONNECT
RGS TO FLEX
TRANSITION
NOTE: THIS DETAIL IS NOT
INTENDED FOR FIRE PUMP
INSTALLATIONS.
6'-0"
METAL CONDUIT INSTALLED BELOW GRADE
SHALL HAVE 2 COATS OF BITUMASTIC
BUILDING COLUMN OR
WALL
TYPICAL FLUSH MOUNTED JUNCTION BOX
FLOOR
PORTABLE OFFICE PARTITION
TYPICAL FLEXIBLE CONDUIT FROM JUNCTION
BOX TO PARTITION RACEWAY
POWER SECTION OF PARTITION RACEWAY
COMMUNICATIONS SECTION OF PARTITION RACEWAY
TYPICAL CONDUIT TO PANELBOARD FOR
POWER, CONDUIT STUBBED AT CABLE TRAY
FOR COMMUNICATIONS
WRITE ON THE FRONT OF EACH WIRING DEVICE THE
CORRESPONDING CIRCUIT DESIGNATION SO THAT
IT IS NOT VISIBLE WITH THE COVERPLATE ON.
LETTERING SHALL BE BY ULTRA FINE POINT
PERMANENT FELT TIP BLACK MARKER, BY HAND.
USE LIGHT COLOR MARKER ON BLACK DEVICES.
CKT #
2p1 8 p 1-l 1-
F S D TS
NAC(S) SLC(S)
FACP
TYPICAL VISUAL CIRCUIT
TYPICAL AUDIBLE CIRCUIT SLC
FIRE ALARM RISER NOTES:
1. CIRCUITS AND DEVICES ARE SHOWN DIAGRAMMATICALLY.
2. NOT ALL DEVICES ARE SHOWN.
3. SEE PLANS FOR DEVICE QUANTITIES.
4. PROVIDE QTY OF NAC CIRCUITS AS REQUIRED PER SPECIFICATIONS.
5. ALL CABLING SHALL BE IN CONDUIT.
6. MINIMUM CONDUIT SIZE IS 3/4".
7. WIRE NUTS SHALL NOT BE USED. ALL WIRES SHALL BE CONNECTED/TERMINATED VIA SCREW TERMINALS.
8. LABEL ALL WIRES IN JUNCTIONS AND AT TERMINATIONS.
FFFF
FFFF
A
LA
R M
A T
F A
C P
F
A A
N
S U
P E
R V
IS
O
R Y
A T
F A
C P
F
A A
N
T R
O U
B
LE
A T
F A
C P
F
A A
N
A
LA
R M
A T
R E
C E
IV
IN
G S
T A
T
IO
N
S U
P E
R V
IS
O
R Y
A T
R E
C E
IV
IN
G S
T A
T
IO
N
T R
O U
B
LE
A T
R E
C E
IV
IN
G S
T A
T
IO
N
A C
T
IV
A T
E A
U D
IB
LE
A N
D V
IS
U
A L
N O
T
IF
IC
A
T
IO
N D
E V
IC
E
S
S H
U T
D O
W N
R E
S P
E C
T
IV
E A
H U
MANUAL PULL STATION
WATERFLOW SWITCH
DUCT SD
SYSTEM INPUT
S Y
S T
E M
O U
T P
U T
FIRE/SMOKE DOOR SD
ANNUNCIATION NOTIFICATION FIRE SAFETY CONTROL
NOTE: NOT ALL INPUTS AND FUNCTIONS
MAY BE APPLICABLE TO PROJECT.
SD = SMOKE DETECTOR
HD = HEAT DETECTOR
S H
U T
D O
W N
R E
S P
E C
T
IV
E S
M O
K E
D A
M P
E R
S
A C
T
IV
A T
E E
LE
V
A T
O R
H O
IS
T
W A
Y V
E N
T
R E
LE
A
S E
/C
LO
S E
R E
S P
E C
T
IV
E M
A G
N E
T
IC
H E
LD
D
O O
R S
S W
IT
C
H T
O S
E C
O N
D A
R Y
P O
W E
R
LI
G
H T
IN
G
R E
LA
Y
U R
N O
N E
G R
E S
S L
IG
H
T S
TAMPER SWITCH OR PIV
KNOX BOX
FA TROUBLE CONDITION (OPENS, SHORTS, OR GNDS)
FA AC POWER FAIL
ALL OTHER SD AND ALL OTHER HD
GENERATOR RUNNING, FAULT, ATS IN NON-AUTO
FIRE PUMP RUNNING, PWR LOSS, PH REV, LOW PRES
4"x4"x2-1/8" DEVICE BOX
18" AFF
(TYPICAL)
FINISHED FLOOR
1" CONDUIT
CONCEALED IN WALL
CEILING
WAO MOUNTING HEIGHT
MAY VARY AT CABINETS
OR CASEWORK. LOCATE
AND MOUNT WAO's AS
DIRECTED BY ARCHITECT
IN FIELD. MATCH HEIGHT
OF ADJACENT ELECTRICAL
POWER OUTLETS.
STUB CONDUIT ABOVE ACCESSIBLE
CEILING & PROVIDE BUSHING
8129 SW 75TH STREET
GAINESVILLE, FLORIDA 32608
352-256-6785 www.superlative.design
T O
T H
E B
E S
T O
F T
C
H
IT
E C
T 'S
O R
T
G
IN
E E
R 'S
K N
O W
L
E D
G E
T
H E
P L
A N
S A
E
C
IF
IC
A
T
IO
N S
C O
M P
H
T H
E A
P P
L
IC
A B
IM
U M
B U
IL
D
D
E S
T
P
L
IC
A B
L E
F
IR
E S
A F
E
A N
D A
R D
S
T E
R M
IN
E
D B
Y T
C
A L
A U
T H
O R
IT
Y
C
O R
D A
N C
E W
IT
H
T
C T
IO
N
A N
D C
H A
P T
F
L S
T A
T U
T E
S
SHEET NO.
DRAWING TITLE:
PROJECT NUMBER:
DRAWING STATUS:
ISSUE DATE:
DRAWN BY: CHECKED BY:
DATE/TIME STAMP:
AKIN BROOKS ENGINEERING, INC.
14260 W NEWBERRY RD #115
NEWBERRY, FL 32669 AB24115
FL LICENSE 35307
352.281.7104
AKINBROOKS.COM 2/27/2026 3:25:31 PM
ELECTRICAL DETAILS
100% CONSTRUCTION
DOCUMENTS
E301
B R
A D
F O
R D
C O
U N
T Y
C O
U R
T H
O U
S E
R E
N O
V A
T
IO
N S
N
T e m p le A v e S ta rk e F
L
24003
02/27/2026
REVISIONS
NO: DATE: REF: BY:
NOT TO SCALE
1 CONDUIT TRAPEZE MOUNTING DETAIL
NOT TO SCALE
6 COVERPLATE LABEL DETAIL
NOT TO SCALE
3 TYPICAL DEVICE MOUNTING DETAIL
NOT TO SCALE
22 TYPICAL PANEL DETAIL
NOT TO SCALE
4 POWER & DISTRIBUTION RACEWAY APPLICATION DETAIL
NOT TO SCALE
5 WALL CONNECTIONS AT OFFICE PARTITIONS
NOT TO SCALE
7 WIRING DEVICE LABEL DETAIL
NOT TO SCALE
2 FIRE ALARM SYSTEM RISER DIAGRAM
NOT TO SCALE
8 FIRE ALARM SYSTEM INPUT/OUTPUT MATRIX
NOT TO SCALE
9 TELCOM OUTLET MOUNTING W/O CABLE TRAY DETAIL
RECESSED
FIXTURES, TYP
PLAN VIEW
MAX 6' FLEX
CONDUIT TO
FIXTURES, TYP
JBOX
NOTES:
1. CIRCUITING SHOWN ON
PLANS IS
DIAGRAMMATIC.
2. DO NOT RUN CONDUIT
DIRECTLY FROM
FIXTURE TO FIXTURE.
3. JBOXES SHALL BE
ACCESSIBLE.
4. SUPPORT FIXTURES
DIRECTLY FROM
STRUCTURE.
CONDUIT TO
NEXT JBOX
SECTION VIEW - RECESSED LIGHTS
FOR FIXTURES <2' AND DOWNLIGHTS, PROVIDE ONE
SUPPORT WIRE DIRECTLY TO STRUCTURE ABOVE
FOR FIXTURES WITH ANY DIMENSIONS 2'
AND LARGER, PROVIDE TWO SUPPORTS
WIRES ON OPPOSITE CORNERS OF
FIXTURE DIRECTLY TO STRUCTURE ABOVE
CEILING CEILING TEE
SECTION VIEW - RECESSED PANEL LIGHTS
CEILING CEILING TEE
PROVIDE LISTED GRID
CLIPS FROM FIXTURE
HOUSING TO TEE
INTEGRAL CLIPS
OR SPRINGS
FIXTURE BAR HANGARS
WIRE TIE BAR HANGARS
TO GRID TEE, TYP
FOR FIXTURES WITH ANY DIMENSIONS 2' AND LARGER,
PROVIDE TWO SUPPORTS WIRES ON OPPOSITE
CORNERS OF FIXTURE DIRECTLY TO STRUCTURE ABOVE
PROVIDE LISTED GRID CLIPS FROM
FIXTURE HOUSING TO TEE
2X2, 2X4, 1X4
2X2, 2X4, 1X4
ROUND
DOWNLIGHT
ROUND
DOWNLIGHT
NOTES:
1. COORDINATE FLOORBOX WITH GENERAL CONTRACTOR, STRUCTURED CABLING CONTRACTOR, BUILDING STRUCTURE, AND
ARCHITECT PRIOR TO INSTALLATION.
2. FINAL LOCATION OF EACH FLOORBOX SHALL BE BY THE ARCHITECT IN THE FIELD.
3. PROVIDE MANUFACTURER'S "FIRE-PAN" FOR INSTALLATIONS WHERE IT IS NOT SLAB ON GRADE.
4. COVERS SHALL BE PAINTED ALUMINUM.