A04_0040559329_Attach_0002_Drawings_LISQ_Modernize_ADA_Elevator.pdf

PDF 3 MB Posted

Attached to
Modernize ADA Elevator at LISQ Federal contract opportunity
Solicitation number
140P5122R0002
Issued by
Department of the Interior National Park Service Southeast Region

About this file

This document package includes construction drawings and specifications for the modernization of an ADA elevator located at the Liberty Square Visitor Education Center Fort Sumter National Historic Park in Charleston, South Carolina. The project involves the replacement of an existing elevator to improve accessibility compliance. Work includes demolition of the existing elevator equipment and installation of a new ADA-compliant elevator and associated mechanical, electrical and plumbing systems. The construction drawings provide details on the scope of demolition and new construction work at the elevator shaft and machine room on three levels. Specifications identify equipment to be installed such as a new elevator car, control systems, lighting, sump pump and ductless HVAC unit. The electrical drawings show locations for new disconnects, switches, receptacles and conduit runs.

View the file

Other files for this federal contract opportunity

Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KI

NG

S

RO

AD

HARBOR VIEW ROAD

CHARLESTON

HARBOR

SHUTES

FOLLY

ISLAND

MORRIS

ISLAND

JAMES ISLAND

SULLIVAN'S

ISLAND

DRUM

ISLAND

FORT

MOULTRIE

FORT

SUMTER

MID

DL

E

ST

CHARLESTON

MT. PLEASANT

V.C. HQ.&

DOCKSIDE II

ATLANTIC

OCEAN

C O O P E R

R

IV

E R

A S H

LE

Y

R

IV

E R

MAINTENANCE

AREA

526TO

CITY

MARINA

ASHLEY

RIVER

FORT

JOHNSON

SPOIL

AREA

UTILITY

EASEMENT

JAS

PE

R

BL

VD

INTERCOASTAL

WATERWAY

526TOCOLEMAN

BLVD.

PATRIOTS

POINT

COUNTY LINE

PARK HEADQUARTERS

VISITOR CENTER

PARK BOUNDARY

LEGEND

HQ.

V.C.

FORT SUMTER NATIONAL MONUMENT

SCALE OF METERS

SCALE OF FEET

2,000

0 4,000

500 1,000

2,000

C O N C O R D

S T

BROAD

ST.

TRADD

ST.

CALH

OUN

ST.

M E E

TIN

G

S T.

FORT SUMTER

NATIONAL

MONUMENT

SULLIVAN'S

ISLAND

MORRIS

ISLAND

JAMES

ISLAND

DANIEL

ISLAND

C O O P E R

R

IV

E R

AS

H

LE

Y

RI

VE

R

CO.

BERK LEY

CHAR ESTON CO.

E L

LONG POINT ROAD

MATHIS FERRY

RIFL

E R

ANG

E

RO

AD

ATLANTIC

OCEAN

CHARLESTON

MOUNT

PLEASANT

DEPARTMENT OF THE INTERIOR

UNITED STATES

NATIONAL PARK SERVICE

DENVER SERVICE CENTER OF

PKG.

NO.

SHEET

STATEREGION

LOCATION WITHIN PARK

NAME OF PARK

TITLE OF DRAWING DRAWING NO.

xxxxxx

COUNTY

REVISIONS Date InitialSheetMarkA/E FIRMS QE#:

P Li b e rt y S q u a re V C D w g s R e v it Li b e rt y S q u a re R .r v t

REPLACEMENT OF ADA ELEVATOR

LIBERTY SQUARE VISITOR

EDUCATION CENTER

FORT SUMTER NATIONAL MONUMENT

SOUTHEAST S. CAROLINA

FINAL CONSTRUCTION

DOCUMENTS

CONTRACT #: P16PC00063

PARK FOSU

CHARLESTON

42024150

CHARLESTON, SC

SCALE OF MILES

0 11

ARCHITECT: QUINN EVANS

ANN ARBOR, MI

DETROIT, MI

ELEVATOR

CONSULTANT:

VERTRAN ENTERPRISES

ANNAPOLIS, MD

MEP: APOGEE CONSULTING GROUP

RALEIGH, NC

PROJECT

LOCATION

SHEET# TITLE OF SHEET

G00 COVER SHEET

G01 SYMBOLS AND ABBREVIATIONS

AS00 KEYPLAN & SITE PLAN STAGING

D01 DEMOLITION PLANS

A01 NEW WORK PLANS

A02 SECTIONS

A03 SCHEDULES & DETAILS

A04 DETAILS

DRAWING INDEX

DETAIL / PLAN

BLDG SECTION CUT

DRAWING REFERENCE

SHEET REFERENCE

DRAWING REFERENCE

SHEET REFERENCE

INTERIOR ELEVATION

DETAIL CUT

DRAWING REFERENCE

SHEET REFERENCE

DRAWING REFERENCE

SHEET REFERENCE

A101

1 SIM

A101

SIM

A101

1 SIM

A101

1 SIM

WALL SECTION CUT

DRAWING REFERENCE

SHEET REFERENCE

A101

SIM1

A101

SIM

DRAWING REFERENCE

SHEET REFERENCE

EXTERIOR ELEVATION

A101

1 SIM

1i

XX

ROOM NUMBER

FINISH TYPE

DOOR NUMBER

WALL TYPES

WINDOW NUMBER

CONCRETE-PLAN

DIMENSIONAL LUMBER

(SIZE AS INDICATED)

STEEL

RIGID INSULATION

DISCONTINUOUS LUMBER

(SIZE AS INDICATED)

ELEVATION

CMU

BATT INSULATION

Room name

KEYNOTE

EARTH

ALUMINUM

WOOD

PLYWOOD

XX-XX

MATERIAL DESIGNATION

(REFER TO MATERIALS

SCHED. ).

XX

XX LOUVER TAG

REVISION CLOUD

AND INDICATOR

XX

CONSTRUCTION

ASSEMBLY

A COLUMN LINE

BRICK

GROUT

CONCRETE-SECTION

PRECAST CONCRETE

SPRAY

FIREPROOFING

GRAVEL

PARTICLE BOARD

PLASTIC

GLASS

SHIM

2 4

GYPSUM BOARD /

PLASTER

SEALANT & BACKER ROD

(SIZE AS INDICATED)

METAL STUD

METAL TRACK

2 4

ACOUSTICAL CEILING

3/8"

SPRAY FOAM

INSULATION

GEN

INDICATOR LIGHT (G=GREEN,

R=RED)

GENERATOR

WITH KW

MOTOR WITH

HORSEPOWER

GROUND

CONTACT (NORMALLY CLOSED)

THERMAL OVERLOAD RELAY

CONTACT (NORMALLY OPEN)

REMOVABLE ELEMENT

CIRCUIT BREAKER

FUSE

HOMERUN CONDUIT

DISCONNECT SWITCH

DUPLEX RECEPTACLE SUBSCRIPT DENOTES TYPE

GFCI DENOTES GROUND FAULT INTERRUPT

WP DENOTES WEATHER PROOF

METER

CURRENT TRANSFORMER

SINGLE POLE SWITCH

M

CT

S

3/4" X 10' COPPER CLAD

STEEL DRIVEN GROUND ROD

2 AWG BARE TINNED

CU UNLESS NOTED

UNDERGROUND CONDUIT

JUNCTION BOXJ

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEETA/E FIRM:

OF

PKG.

NO.

SHEET

xxxxxxQUINN EVANS

ARCHITECT:

DRAWING NO.

ANN ARBOR, MI

DETROIT, MI

MECHANICAL &

ELECTRICAL:

APOGEE

RALEIGH, NC

P L ib e rt y S q u a re V C D w g s R e v it L i b e rt y S q u a re R .r v t

08/20/2021

SYMBOLS AND

ABBREVIATIONS

REPLACEMENT OF ADA ELEVATOR

FORT SUMTER NATIONAL MONUMENT

G01

T TREAD

T&G TONGUE AND GROOVE

T.O. TOP OF

TECH TECHNOLOGY

TEL TELEPHONE

TEMP TEMPERED

THK THICK(NESS)

THRESH THRESHOLD

TOC TOP OF CURB

TOL TOLERANCE

TOM TOP OF MASONRY

TOS TOP OF STEEL

TOW TOP OF WALL

TRANS TRANSPARENT, TRANSFORMER

TV TELEVISION

TYP TYPICAL

UL UNDERWRITER'S LABORATORY

UNFIN UNFINISHED

UON UNLESS OTHERWISE NOTED

VAR VARIES

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VU VENTILATION UNIT

VWC VINYL WALLCOVERING

W WIDE, WEST, WIRE

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WD WOOD

WDW WINDOW

WH WALL HUNG

WP WORK POINT, WEATHERPROOF

WT WEIGHT

WTR WATER

WWF WELDED WIRE FABRIC

" INCHES

# NUMBER

& AND

' FEET

@ AT

C CENTER LINE

L ANGLE

± EXIST (OR APPROX) DIM - VIF

PT POINT

PTD PAINT(ED)

PVMT PAVEMENT

QTY QUANTITY

R RADIUS, RISER

RB RUBBER BASE

RC REINFORCED CONCRETE

REF REFERENCE

REINF REINFORCED

REQ /

REQS

REQUIREMENT(S)

REQD /

REQ'D

REQUIRED

RES RESILIENT

RET RETAINING

REV REVISION(S) / REVISE(D)

RFG ROOFING

RH RIGHT HAND

RL RAIN LEADER

RM ROOM

RO ROUGH OPENING

RT RIGHT

S SOUTH, SEAL

SC SOLID CORE

SCHED SCHEDULE

SECT SECTION

SF SQUARE FEET

SHT SHEET

SIM SIMILAR

SL SLOPE

SLL SOUND / LIGHT LOCK

SPEC(S) SPECIFICATION(S)

SQ SQUARE

SS STAINLESS STEEL

ST STAINLESS

STA STATION

STD STANDARD

STL STEEL

STM STEAM

STN STAIN

STO STORAGE

STRUC STRUCTURAL

SUSP SUSPENDED

SYM SYMMETRICAL

SYS SYSTEM

MEMB MEMBRANE

MFR MANUFACTURE(R)

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MO MASONRY OPENING

MTD MOUNTED

MTG MOUNTING

MTL METAL

N NORTH

N NEUTRAL

NAT NATURAL

NCSBC NORTH CAROLINA STATE BUILDING

CODE

NEC NATIONAL ELECTRICAL CODE

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NPS NATIONAL PARK SERVICE

NTE NOT TO EXCEED

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OFF OFFICE

OH OVERHEAD

OPNG OPENING

OPP OPPOSITE

OPP HD OPPOSITE HAND

PAR PARALLEL

PART PARTITION

PC PRECAST

PED PEDESTAL

PERF PERFORATE(D)

PI POINT OF INTERSECTION

PL PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLWD PLYWOOD

PNL PANEL(ED)

PR PAIR

PREP PREPARE (SURFACE)

PROV PROVIDE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

HDWD HARDWOOD

HDWR HARDWARE

HGT HEIGHT

HM HOLLOW METAL

HORIZ HORIZONTAL

HP HIGH POINT

HP HORSEPOWER

HR HOUR

HT HEIGHT

HVAC HEATING, VENTILATION & AIR

CONDITIONING

IBC INTERNATIONAL BUILDING CODE

ID INSIDE DIAMETER

IG ISOLATED GROUND

IN INCH(ES)

INCAN INCANDESCENT

INCL INCLUDE(D,ING)

INSUL INSULATION, INSULATED

INT INTERIOR

INV INVERT

JAN JANITOR

JB JUNCTION BOX

JC JANITOR CLOSET

JT(S) JOINT(S)

N NORTH

KIT KITCHEN

KW KILOWATT

LAM LAMINATE(D)

LAV LAVATORY

LBL LABEL

LF LINEAR FOOT

LH LEFT HAND

LL LIVE LOAD

LP LOW POINT

LTG LIGHTING

LTL LINTEL

M METER

MAS MASONRY

MATL MATERIAL(S)

MAX MAXIMUM

MBJ MAIN BONDING JUMPER

MCB MAIN CIRCUIT BREAKER

MECH MECHANICAL

MED MEDIUM

ENCL ENCLOS(E,URE)

EQ EQUAL

EQUIP EQUIPMENT

EST ESTIMATE(D)

EXH EXHAUST

EXIST/EX EXISTING

EXP EXPOSED, EXPANSION

EXT EXTERIOR

FA FIRE ALARM

FAS FASTEN(ER)

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISHED FACE/FINISHED FLOOR

FGL FIBERGLASS

FHC FIRE HOSE CABINET

FIN(S) FINISH(ES)

FIXT FIXTURE

FL FLOOR(ING)

FLAM FLAMMABLE

FLUOR FLUORESCENT

FMC FLEXIBLE METAL CONDUIT

FOC FACE OF CONCRETE

FOS FACE OF STUDS

FP FIREPROOF(ING)

FR FRAME(D,ING)

FT FEET

FTG FOOTING

FUR FURR(ED,ING)

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACT(OR)

GEC GROUNDING ELECTRODE CONDUCTOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GL GLASS, GLAZING

GOVT GOVERNMENT

GT GROUT

GWB GYPSUM WALLBOARD

H HIGH

HB HOSE BIB

HC HOLLOW CORE

HDR HEADER

C CONDUIT

CAB CABINET

CEM CEMENT

CI CAST IRON

CJ CONTROL JOINT

CKT CIRCUIT

CLG CEILING

CLO CLOSET

CLR CLEAR(ANCE)

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COL COLUMN

COM COMMUNICATIONS

CONC CONCRETE

COND CONDITION

CONFIG CONFIGURATION

CONST CONSTRUCTION

CONT CONTINUOUS

COORD COORDINATE

CORR CORRIDOR

CP CONTROL PANEL

CPT CARPET(ED)

CT CERAMIC TILE

CTR CENTER

CU COPPER

D DEEP

DED DEDICATED CIRCUIT

DEG DEGREE

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DIV DIVISION

DN DOWN

DR DOOR

DTL DETAIL

DWG(S) DRAWING(S)

E EAST

E-P EPOXY PAINT

EA EACH

EG EQUIPMENT GROUND

EJ EXPANSION JOINT

EL ELEVATION (TOPO)

ELEC ELECTRICAL

ELEV ELEVATION (ARCH),ELEVATOR

EMER EMERGENCY

PC PHOTOCELL

RTU REMOTE (OR RADIO) TELEMETRY UNIT

SE SERVICE ENTRANCE

SPD SURGE PROTECTION DEVICE

STP SHIELDED TWISTED PAIR

TCL TOTAL CONNECTED LOAD

TDL TOTAL DEMAND LOAD

TVSS TRANSIENT VOLTAGE SURGE & SPIKE

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

VFD VARIABLE FREQUENCY DRIVE

A AMP

A/C AIR CONDITIONING

ABA ARCHITECTURAL BARRIERS ACT

ABT ABOUT

ACCESS ACCESSIBLE

ACM ASBESTOS CONTAINING MATERIAL

ACOUS ACOUSTIC

ACP ACOUSTICAL CEILING PANEL

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AGG AGGREGATE

AIC AMPS INTERRUPTING CAPACITY

ALT ALTERNATE

ALUM ALUMINIUM

APPROX APPROXIMATELY

ARCH ARCHITECT(URAL, URE)

ASPH ASPHALT(IC)

ASSOC ASSOCIATED

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AWG AMERICAN WIRE GAUGE

AWP ACOUSTICAL WALL PANEL

BD BOARD

BFG BELOW FINISHED GRADE

BIT BITUMINOUS, BITUMEN

BLDG BUILDING

BLKG BLOCKING

BM BEAM

BOT BOTTOM

BR BRICK

BS BOTH SIDES

BTWN BETWEEN

ABBREVIATIONS

MATERIALS & SYMBOLS ELECTRICAL SYMBOLS

C O O P E R

R

IV

E R

L

IB

E R T Y

W A Y

FREEDOM LN

AQUARIUM WHARF

C O N C O R D

S T.

SOUTH CAROLINA AQUARIUM

FORT SUMTER

VISITOR EDUCATION

CENTER

LOCATION OF

ELEVATOR TO

BE REPLACED

MAIN PANEL WITH ELEVATOR SHUNT

TRIP BREAKER. REMOVE SHUNT TRIP

FUNCTION FROM ELEVATOR BREAKER.

SITE PLAN LEGEND

GREENERY

HARDSCAPE

CONSTRUCTION LIMIT LINE

LOCATION FOR CONTRACTOR

SUPPLIES AND EQUIPMENT

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEETA/E FIRM:

OF

PKG.

NO.

SHEET

xxxxxxQUINN EVANS

ARCHITECT:

DRAWING NO.

ANN ARBOR, MI

DETROIT, MI

MECHANICAL &

ELECTRICAL:

APOGEE

RALEIGH, NC

P L ib e rt y S q u a re V C D w g s R e v it L i b e rt y S q u a re R .r v t

PR

08/20/2021

KEYPLAN & SITE PLAN

STAGING

REPLACEMENT OF ADA ELEVATOR

FORT SUMTER NATIONAL MONUMENT

AS00

1"= 30' - 0" SCALE OF FEET

15'30' 0' 30' 60'

1" = 30'-0"AS00

1 STAGING & MOBILIZATION

3GFI

GFI

UP

GFI

DN

1. BIDDERS SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME FAMILIAR WITH EXISTING CONDITIONS

AND THE EXTENT OF MATERIAL AND EQUIPMENT REMOVAL AT EACH FLOOR.

2. PROTECT EXISTING CONSTRUCTION TO REMAIN FROM DAMAGE. PROVIDE TEMPORARY ENCLOSURES, PROTECTION

AND BARRICADES AS NECESSARY TO PROTECT AND SECURE THE BUILDING.

3. FOR AREAS TO RECEIVE NEW FINISH, CONTRACTOR SHALL REMOVE FINISHES AS WELL AS ALL ATTACHMENTS AND

ACCESSORIES IN PREPERATION FOR A NEW WALL FINISH.

4. VERIFY EXISTING FIELD CONDITIONS AND NOTIFY THE CONTRACTING OFFICER OF INCONSISTENCIES BETWEEN THESE DRAWINGS AND ACTUAL CONDITIONS BEFORE PROCEEDING WITH CONSTRUCTION OR DEMOLITION.

5. VERIFY EXISTING CONDITIONS AND SCOPE OF DEMOLITION WORK WITH REQUIREMENTS FOR NEW CONSTRUCTION.

COORDINATE SCOPE OF DEMOLITION WITH REQUIREMENTS FOR NEW CONSTRUCTION SHOWN. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE EXTENT OF DEMOLITION THAT IS REQUIRED TO EXECUTE NEW WORK.

6. PERFORM SURVEY AND ANALYSIS OF EXISTING BUILDING PRIOR TO COMMENCING WITH DEMOLITION OPERATIONS.

DO NOT REMOVE CONSTRUCTION IF THE STRUCTURAL INTEGRITY OF THE BUILDING MAY BE COMPROMISED UNTIL APPROPRIATE TEMPORARY SUPPORTS ARE IN PLACE. GENERAL CONTRACTOR IS FULLY RESPONSIBLE FOR DESIGN AND INSTALLATION OF ALL NECESSARY SHORING AND BRACING OF EXISTING STRUCTURE REQUIRED FOR

IMPLEMENTATION OF DESIGN.

7. CONTRACTOR IS RESPONSIBLE FOR THE LEGAL DISPOSAL OF ALL DEMOLISHED MATERIALS.

8. GENERAL CONTRACTOR SHALL COORDINATE ALL DISCONNECTS AND SHUT OFFS THAT MAY BE REQUIRED FOR

DEMOLITION.

9. LEAVE FLOOR IN BROOM CLEAN CONDITION AND READY FOR CONSTRUCTION; TYPICAL FOR ALL AREAS OF WORK.

ITEMS TO BE REMOVED

EXISTING WALLS TO REMAIN

EXIST. DOOR

3 4

D

F

16'-0" ±

8'-4" ±

ELEVATOR

UTILITY

02-03

02-04

02-06

02-03

02-08

3 4

D

F

16'-0" ±

8'-4" ±5

R .9

T@

ELEVATOR

ELEVATOR

MECH.

STAIR

02-01

02-02

02-05

02-06

@CEILING

02-07

3 4

D

F

16'-0" ±

ELEVATOR

TEL/COM

CORRIDOR

STAIR

8'-4" ±

02-06

02-0302-03

13121110987654321

F

D

C

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

KEY NOTES

GENERAL NOTES

A/E FIRM:

OF

PKG.

NO.

SHEET

xxxxxxQUINN EVANS

ARCHITECT:

DRAWING NO.

ANN ARBOR, MI

DETROIT, MI

MECHANICAL &

ELECTRICAL:

APOGEE

RALEIGH, NC

P L ib e rt y S q u a re V C D w g s R e v it L i b e rt y S q u a re R .r v t

D01 08/20/2021

DEMOLITION PLANS

REPLACEMENT OF ADA ELEVATOR

FORT SUMTER NATIONAL MONUMENT

1/4" = 1' - 0" SCALE OF FEET

2'4' 0 8'4'

02-01 ELECTRICAL DISCONNECTS TO BE REMOVED. EXISTING CIRCUITS TO REMAIN.

02-02 ELECTRICAL DISCONNECTS AND LIGHTING TO BE REMOVED. EXISTING CIRCUITS TO REMAIN. EXISTING FIRE ALARM

DEVICES TO REMAIN.

02-03 EXISTING TO REMAIN

02-04 REMOVE EXISTING ELECTRICAL EQUIPMENT IN PIT. REUSE EXISTING CIRCUIT.

02-05 REMOVE EXISTING DIFFUSER AND RETURN AND CAP DUCTWORK.

02-06 REFER TO ELEVATOR SPECIFICATIONS FOR DETAILED DESCRIPTION OF ELEVATOR COMPONENTS TO BE REMOVED.

02-07 APPROXIMATE LOCATION OF EXISTING FAN COIL UNIT OVER OFFICE CEILING. DEMOLISH UNIT AND ASSOCIATED SUPPLY/RETURN DUCTWORK TO/FROM ELEVATOR MACHINE ROOM. DEMOLISH HYDRONIC PIPING BACK TO MAINS

AND CAP. DEMOLISH THERMOSTAT AND ASSOCIATED CONDUIT AND WIRING.

02-08 SAW CUT DEPRESSION IN ELEVATOR PIT FLOOR. COORDINATE LOCATION WITH INSTALLATION OF SUMP PUMP. SEE

KEYNOTE 22-01 AND DETAIL ON A04.

DEMOLITION LEGEND_PLAN

REFERRED FROM:1/4" = 1'-0"D01 A02

1 ELEVATOR DEMOLITION PLAN - PIER LEVEL

REFERRED FROM:1/4" = 1'-0"D01 A02

2 STAIR/ELEV DEMOLITION PLAN - 1ST FLOOR

REFERRED FROM:1/4" = 1'-0"D01 A02

3 STAIR/ELEV DEMOLITION PLAN - 2ND FLOOR

KEYPLAN

ALSO SHOWN:

ELECTRICAL,

MECHANICAL,

& PLUMBING

GFI

M M

GFI

UP

GFI

M

DN

1. BIDDERS SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND THE

EXTENT OF MATERIAL AND EQUIPMENT REMOVAL AT EACH FLOOR.

2. OBTAIN APPROVAL FROM CONTRACTING OFFICER IF ANY PORTIONS OF CONSTRUCTION ARE REQUIRED TO BE PERFORMED

OUTSIDE OF NORMAL WORKING HOURS.

3. DO NOT SCALE PRINTS, USE FIGURED DIMENSIONS ONLY, CONTRACTOR SHALL FIELD VERIFY ALL EXISTING BUILDING DIMENSIONS, PARTITIONS, WALL LOCATIONS, FLOOR ELEVATIONS AND NOTIFY CO OF ANY DISCREPANCIES IN WRITING PRIOR

TO START OF WORK.

4. PROTECT EXISTING CONSTRUCTION TO REMAIN.

5. ALL DIMENSIONS PROCEEDED BY A +/- SHALL BE REVIEWED AND ALL NECESSARY ADJUSTMENTS MADE PRIOR TO

FABRICATION AND/OR INSTALLATION OF AFFECTED WORK.

6. PATCH, TAPE, SAND ALL DEMOLITION SCARS, INCLUDING BUT NOT LIMITED TO REMOVED PARTITIONS, MILLWORK, SURFACE

MOUNTED ELECTRICAL, ETC.

7. FIRESTOP AND PATCH ALL OPENINGS IN CORE WALLS AT REMOVED CONDUITS AND PIPING UNLESS OTHERWISE NOTED FOR

REUSE.

8. FIRESTOP AND PATCH ALL FLOOR CORES AT REMOVED FLOOR OUTLETS AND PLUMBING UNLESS OTHERWISE NOTED FOR

REUSE.

9. PREP AND PRIME ALL INTERIOR WALLS FOR NEW FINISH.

10. FOR ALL ELECTRICAL EQUIPMENT PROVIDE CORROSION RESISTANT.

11. FIRE SUPPRESSION WORK TO REQUIRE NICET 2 CERTIFICATION.

3 4

D

F

A02

A02

ELEVATOR

UTILITY

16'-0" ±

8'-4" ±

T

CU

SP

23-01

23-02

22-01

23-03

23-04

NP1W:18

NP1W:2,4

26-07

26-16 26-17

26-08

26-09

26-11

26-12

WP

WP

WP

26-10

26-08

WP

TO TOP

OF SHAFT

NP1W:29

NP1W:12

23-05

23-09

23-10

09-01

14-03

05-02

3 4

D

F

A02

A02

ELEVATOR

ELEVATOR

MECH.

STAIR

16'-0" ±

8'-4" ±5

R .9

T@

A04

T

23-07

NP1W:8

NP1W:6

26-03

26-05

26-02

NP1W:20

26-14

NP1W:14,16

NP1W:11

26-06

05-01

07-01

08-01

09-0314-01

TO LIGHT

ABOVE DOOR

14-03

14-04

14-03

TYP.

23-08

23-03

26-03

3 4

D

F

A02

A02

ELEVATOR

STAIR

TEL/COM

CORRIDOR

16'-0" ±

8'-4" ±

A04

26-01

TO

PIT

NP1W:29

26-18

26-19

10-01

14-03

13121110987654321

F

D

C

3 4

D

F

ELEVATOR

ELEVATOR

MECH.

STAIR

26-04

09-0209-02

TO SWITCH

14-02

TYP.

21-01

09-02

05-01 PROVIDE BREAK METAL STAINLESS STEEL CLOSURE. SEAL WITH A SILICONE SEALANT JOINT AT THE LEADING EDGE

OF THIS TRIM. PROVIDE TWO PLASTIC WEEPS PRIOR TO SEALING.

05-02 EXISTING LADDER TO REMAIN

07-01 PATCH AND SEAL ALL MACHINE ROOM AND HOISTWAY PENETRATIONS TO MAINTAIN A MIN. 1 HR FIRE RESISTANCE

RATING.

08-01 PROVIDE NEW DOOR STAINLESS STEEL STOREROOM FUNCTION LOCKSET MATCHING OPERATING TRIM AND TYPE OF

EXISTING DOORS.

09-01 REMOVE EXISTING OIL AND DEBRIS FROM PIT. PREP FOR NEW FINISH PER ELEVATOR SPECIFICATIONS.

09-02 PATCH VACATED OPENINGS WITH GYPSUM SHAFTWALL SYSTEM TO RESTORE FIRE RESISTANCE RATING TO MIN. OF 1

HR.

09-03 CLEAN AND PAINT ELEVATOR MACHINE ROOM WALLS AND FLOORS. REFER TO ELEVATOR SPECIFICATIONS.

10-01 PROVIDE NEW STAINLESS STEEL FRAME FOR EVACUATION SIGN. STYLE TO MATCH ELEVATOR CONTROL PANEL.

14-01 PROVIDE NEW ELEVATOR HOISTWAY DOORS

14-02 PROVIDE NEW ELEVATOR CEILING, LIGHTING, AND FLOORING. REFER TO ELEVATOR SPECIFICATIONS.

14-03 PROVIDE NEW PUSHBUTTON STATIONS AND SIGNAL FIXTURES IN CORRIDOR AND ELEVATOR CAR. TYP EACH FLOOR.

14-04 REFER TO ELEVATOR SPECIFICATIONS FOR DETAILED DESCRIPTION OF ELEVATOR COMPONENTS TO BE UPGRADED

AND MODIFIED.

21-01 RELOCATE MECHANICAL ROOM FIRE SUPPRESSION SPRINKLER TO INDICATED NEW LOCATION. PROVIDE NEW SPRINKLER HEAD CONNECTED TO EXISTING SYSTEM. PROVIDE NEW SPRINKLER PIPING AS REQUIRED. MATERIALS AND INSTALLATION SHALL BE IN COMPLIANCE WITH NFPA 13 (2019) AND OTHER APPLICABLE CODES AND

STANDARDS.

22-01 PROVIDE NEW SUMP PUMP (SP-1). INSTALL IN NEW SAW-CUT DEPRESSION IN ELEVATOR PIT FLOOR. REFER TO DETAIL ON SHEET A04. FIELD COORDINATE EXACT LOCATION OF NEW DEPRESSION WITH EXISTING DRY SUMP AND

ELEVATOR HYDRAULIC LINES.

23-01 PROVIDE NEW INLINE EXHAUST FAN EF-1, SUSPENDED.

23-02 PROVIDE NEW THERMOSTAT FOR EXHAUST FAN. SET THERMOSTAT TO 95 DEGREES F (ADJUSTABLE).

23-03 REFRIGERANT PIPING FROM ABOVE. SIZE, ROUTE AND INSTALL IN STRICT ACCORDANCE WITH EQUIPMENT

MANUFACTURER'S INSTRUCTIONS.

23-04 PROVIDE WALL-MOUNTED CONDENSING UNIT (CU-1), MOUNT ON WALL @ 7' AFF.

23-05 2" SUMP PUMP DISCHARGE, PROVIDE INDIRECT OPEN HUB CONNECTING INTO EXISTING 4" WASTE STACK IN

ADJACENT ROOM. FIRESTOP PENETRATION THROUGH ELEVATOR HOISTWAY.

23-07 1" PUMPED CONDENSATE LINE, CONNECT TO EXISTING CONDENSATE THAT SERVED FAN COIL UNIT. FIELD VERIFY LOCATION OF TIE-IN CONDENSATE PIPING SHALL BE ASTM B88 TYPE L COPPER TUBING WITH SOLDERED JOINTS (95/5 TIN/ANTIMONY SOLDER). FITTINGS SHALL BE ASME B16.18 CAST COPPER OR ASME B16.22 WROUGHT

COPPER.

23-08 PROVIDE DUCTLESS SPLIT SYSTEM ON WALL OVER DOOR. (DAC-1)

23-09 12 X 10 EXHAUST DUCT

23-10 NEW 32 X 12 EXHAUST LOUVER OVER DOOR. PROVIDE PLENUM BOX ON BACK OF LOUVER FULL SIZE OF LOUVER.

26-01 INSTALL NEW LIGHT AT TOP OF SHAFT WITH 3-WAY SWITCH TIED TO PIT LIGHTING

26-02 INSTALL NEW 400A ELEVATOR DISCONNECT WITH 100A SHUNT TRIP BREAKER. SHUNT TRIP TO BE ACTIVATED BY ACTUATION OF THE SPRINKLER FLOW SWITCH(S) DESIGNED TO AUTOMATICALLY OPEN THE POWER SUPPLY TO THE ELEVATOR. TIE ELEVATOR EQUIPMENT INTO THE EXISTING FIRE ALARM PANEL. REUSE EXISTING ELEVATOR FEEDER.

26-03 INSTALL TWO NEW 30A DISCONNECTS FOR ELEVATOR CAB LIGHTING AND CONTROLS.

26-04 INSTALL NEW LIGHTING IN ELEVATOR MACHINE ROOM TIED TO EXISTING CIRCUIT, NP1W-11.

26-05 INSTALL NEW GFCI RECEPTACLE TIED TO EXISTING CIRCUIT, NP1W-13

26-06 INSTALL NEW MOTOR RATED SWITCH FOR AC UNIT.

26-07 INSTALL NEW 208V, 2-POLE MOTOR RATED SWITCH FOR NEW SPLIT SYSTEM CONDENSER UNIT.

26-08 INSTALL NEW PIT LIGHTING ON BOTH SIDES OF THE PIT AS SHOWN.

26-09 INSTALL NEW PIT LIGHTING 10' ABOVE PIT FLOOR OR JUST BELOW ELEVATOR CAB WHEN STOPPED ON LEVEL 1.

26-10 INSTALL NEW SIMPLEX RECEPTACLE FOR OIL SCAVENGER-PUMP 3' ABOVE PIT FLOOR.

26-11 INSTALL NEW GFCI RECEPTACLE FOR SERVICE RECEPTACLE IN PIT, NP1W-27.

26-12 INSTALL NEW SIMPLEX RECEPTACLE 5' ABOVE PIT FLOOR FOR SUMP PUMP, NP1W-10.

26-14 INSTALL NEW SWITCH FOR CONDENSATE PUMP.

26-16 INSTALL NEW 120V MOTOR RATED SWITCH FOR EXHAUST FAN.

26-17 NEW ELECTRICAL EQUIPMENT, CONDUIT, LIGHT FIXTURES AND BOXES TO BE IMPERVIOUS TO LIQUID TO A HEIGHT

OF 6' ABOVE LANDING.

26-18 EXISTING SECURITY PANEL.

26-19 EXISTING FIRE ALARM PANEL.

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

GENERAL NOTES

KEY NOTES

A/E FIRM:

OF

PKG.

NO.

SHEET

xxxxxxQUINN EVANS

ARCHITECT:

DRAWING NO.

ANN ARBOR, MI

DETROIT, MI

MECHANICAL &

ELECTRICAL:

APOGEE

RALEIGH, NC

P L ib e rt y S q u a re V C D w g s R e v it L i b e rt y S q u a re R .r v t

A01 08/20/2021

NEW WORK PLANS

REPLACEMENT OF ADA ELEVATOR

FORT SUMTER NATIONAL MONUMENT

1/4" = 1' - 0" SCALE OF FEET

2'4' 0 8'4'

REFERRED FROM:1/4" = 1'-0"A01 A02

1 ELEVATOR NEW WORK PLAN - PIER LEVEL

REFERRED FROM:1/4" = 1'-0"A01 A02

2 STAIR/ELEV NEW WORK PLAN - 1ST FLOOR

REFERRED FROM:1/4" = 1'-0"A01 A02

4 STAIR/ELEV NEW WORK PLAN - 2ND FLOOR

KEYPLAN

REFERRED FROM:1/4" = 1'-0"A01 A02

3 STAIR/ELEV RCP - 1ST FLOOR

ALSO SHOWN:

ELECTRICAL,

1. BIDDERS SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND THE

EXTENT OF MATERIAL AND EQUIPMENT REMOVAL AT EACH FLOOR.

2. OBTAIN APPROVAL FROM CONTRACTING OFFICER IF ANY PORTIONS OF CONSTRUCTION ARE REQUIRED TO BE PERFORMED

OUTSIDE OF NORMAL WORKING HOURS.

3. DO NOT SCALE PRINTS, USE FIGURED DIMENSIONS ONLY, CONTRACTOR SHALL FIELD VERIFY ALL EXISTING BUILDING DIMENSIONS, PARTITIONS, WALL LOCATIONS, FLOOR ELEVATIONS AND NOTIFY CO OF ANY DISCREPANCIES IN WRITING PRIOR

TO START OF WORK.

4. PROTECT EXISTING CONSTRUCTION TO REMAIN.

5. ALL DIMENSIONS PROCEEDED BY A +/- SHALL BE REVIEWED AND ALL NECESSARY ADJUSTMENTS MADE PRIOR TO

FABRICATION AND/OR INSTALLATION OF AFFECTED WORK.

6. PATCH, TAPE, SAND ALL DEMOLITION SCARS, INCLUDING BUT NOT LIMITED TO REMOVED PARTITIONS, MILLWORK, SURFACE

MOUNTED ELECTRICAL, ETC.

7. FIRESTOP AND PATCH ALL OPENINGS IN CORE WALLS AT REMOVED CONDUITS AND PIPING UNLESS OTHERWISE NOTED FOR

REUSE.

8. FIRESTOP AND PATCH ALL FLOOR CORES AT REMOVED FLOOR OUTLETS AND PLUMBING UNLESS OTHERWISE NOTED FOR

REUSE.

9. PREP AND PRIME ALL INTERIOR WALLS FOR NEW FINISH.

10. FOR ALL ELECTRICAL EQUIPMENT PROVIDE CORROSION RESISTANT.

11. FIRE SUPPRESSION WORK TO REQUIRE NICET 2 CERTIFICATION.

FIRST FLOOR

114' - 0"±

PIER LEVEL

100' - 0"±

SECOND FLOOR

129' - 0"±

D F2 A02

ELEVATOR PIT

96' - 0"±

A04

ELEVATOR

MECH.

101ELEVATOR

26-04

23-08

26-14

26-06

09-0309-03

08-01

UTILITY

STAIR

CORRIDOR

26-08

02-03

26-08

26-01

26-01

FIRST FLOOR

114' - 0"±

PIER LEVEL

100' - 0"±

SECOND FLOOR

129' - 0"±

3 41 A02

ELEVATOR PIT

96' - 0"±

26-08

26-11

26-12

05-02

14-03

14-02

14-0414-04

14-02

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEET

KEY NOTES

GENERAL NOTES

A/E FIRM:

OF

PKG.

NO.

SHEET

xxxxxxQUINN EVANS

ARCHITECT:

DRAWING NO.

ANN ARBOR, MI

DETROIT, MI

MECHANICAL &

ELECTRICAL:

APOGEE

RALEIGH, NC

P L ib e rt y S q u a re V C D w g s R e v it L i b e rt y S q u a re R .r v t

A02 08/20/2021

SECTIONS

REPLACEMENT OF ADA ELEVATOR

FORT SUMTER NATIONAL MONUMENT

02-03 EXISTING TO REMAIN

05-02 EXISTING LADDER TO REMAIN

08-01 PROVIDE NEW DOOR STAINLESS STEEL STOREROOM FUNCTION LOCKSET MATCHING OPERATING TRIM AND TYPE OF

EXISTING DOORS.

09-03 CLEAN AND PAINT ELEVATOR MACHINE ROOM WALLS AND FLOORS. REFER TO ELEVATOR SPECIFICATIONS.

14-02 PROVIDE NEW ELEVATOR CEILING, LIGHTING, AND FLOORING. REFER TO ELEVATOR SPECIFICATIONS.

14-03 PROVIDE NEW PUSHBUTTON STATIONS AND SIGNAL FIXTURES IN CORRIDOR AND ELEVATOR CAR. TYP EACH FLOOR.

14-04 REFER TO ELEVATOR SPECIFICATIONS FOR DETAILED DESCRIPTION OF ELEVATOR COMPONENTS TO BE UPGRADED

AND MODIFIED.

23-08 PROVIDE DUCTLESS SPLIT SYSTEM ON WALL OVER DOOR. (DAC-1)

26-01 INSTALL NEW LIGHT AT TOP OF SHAFT WITH 3-WAY SWITCH TIED TO PIT LIGHTING

26-04 INSTALL NEW LIGHTING IN ELEVATOR MACHINE ROOM TIED TO EXISTING CIRCUIT, NP1W-11.

26-06 INSTALL NEW MOTOR RATED SWITCH FOR AC UNIT.

26-08 INSTALL NEW PIT LIGHTING ON BOTH SIDES OF THE PIT AS SHOWN.

26-11 INSTALL NEW GFCI RECEPTACLE FOR SERVICE RECEPTACLE IN PIT, NP1W-27.

26-12 INSTALL NEW SIMPLEX RECEPTACLE 5' ABOVE PIT FLOOR FOR SUMP PUMP, NP1W-10.

26-14 INSTALL NEW SWITCH FOR CONDENSATE PUMP.

1/4" = 1' - 0" SCALE OF FEET

2'4' 0 8'4'

REFERRED FROM:1/4" = 1'-0"A02 A01

1 STAIR SECTION

REFERRED FROM:1/4" = 1'-0"A02 A01

2 ELEVATOR SECTION

ALSO SHOWN:

ELECTRICAL,

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED CONNECTION

ON FAN SIDE

WASHER

1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm]

NOMINAL WITH MATERIAL TAUT

FLEXIBLE MATERIAL

AS SPECIFIED

1"x1/8" [25x3mm] DRAW BAND

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

5/16" [8mm] FLANGE

DUCT

SHEET METAL SCREWS ON

12" [300mm] CENTERS

RIVET ON 4"

[100mm] CENTERS

SHEET METAL AS SPECIFIED FOR DUCTWORK.

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

1" [25mm] FLANGE & HEM

ALTERNATE

POSITION OF

BOLT

1 1/2" [40mm]

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

[15mm] [15mm] [40mm]

1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm]

NOMINAL WITH MATERIAL TAUTFLANGED CONNECTION ON FAN SIDE

WASHER

FLEXIBLE MATERIAL

AS SPECIFIED

1/2" 1/2"

1/2"

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEETA/E FIRM:

OF

PKG.

NO.

SHEET

xxxxxxQUINN EVANS

ARCHITECT:

DRAWING NO.

ANN ARBOR, MI

DETROIT, MI

MECHANICAL &

ELECTRICAL:

APOGEE

RALEIGH, NC

P L ib e rt y S q u a re V C D w g s R e v it L i b e rt y S q u a re R .r v t

Designer

Author A03 Checker

08/20/2021

SCHEDULES & DETAILS

REPLACEMENT OF ADA ELEVATOR

FORT SUMTER NATIONAL MONUMENT

B 4' LED STRIPLIGHT, WET LOCATION SURFACE

LED

80 CRI / 4000K

0-10V DIMMABLE

DRIVER

120-277V 23.8

LITHONIA

OR EQUAL

FEM L48 4000LM LPPFL MD MVOLT GZ10 40K 80CRI

E10WMCP

WET LOCATION RATED

INCLUDE EMERGENCY

BATTERY PACK OPTION

A 4' LED STRIPLIGHT SURFACE

LED

80 CRI / 4000K

LED DRIVER 120-277V 34

LITHONIA

OR EQUAL

ZL1N L48 5000LM FST MVOLT 40K 80CRI E10WLCP WH

INCLUDE EMERGENCY

BATTERY PACK OPTION

TYPE DISCRIPTION MOUNTING LAMP BALLAST/DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER NOTE

LIGHT FIXTURE SCHEDULE

ELEVATOR 208 3 25 hp 100 3 3 - - 8 1/1/2004

NEMA 1 100A BREAKER

ENCLOSURE WITH SHUNT TRIP

CONDENSATE PUMP 115 1 .016kVA 15 1 14 14 14 3/4 1-POLE SWITCH

SP-1 SUMP PUMP 115 1 1/2 hp 20 1 14 14 14 3/4 CORD & PLUG

EF-1 EXHAUST FAN 115 1 1/6 hp 15 1 14 14 14 3/4 MOTOR RATED 1-POLE SWITCH

CU-1 SPIT UNIT (OUTDOOR) 208 1 3.43kVA 20 2 12 - - 12 3/4 MOTOR RATED 2-POLE SWITCH

DAC-1 SPIT UNIT (INDOOR) 208 1 .125kVA 15 2 14 - - 14 3/4 MOTOR RATED 2-POLE SWITCH

TAG DESCRIPTION VOLTS PHASE LOAD MOCP CONDUCTORS NEUTRAL GROUND CONDUIT PLUG DISCONNECT TYPE

EQUIPMENT CONDUCTOR SCHEDULE

PANEL 'NP1W'...

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 0

PANEL / FEEDER (TOTAL KVA) 0.00

TOTAL DEMAND AMPERES PER PHASE 0 0 0

NOTE:

ALL MOTOR CIRCUIT BREAKERS SHALL BE HACR RATED.

(N) NEW CIRCUIT

TOTAL KVA PER PHASE 0.00 0.00 0.00 0.00 0.00 0.00

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED RECEPT 0.00 0.00 0.00 100% 0.00 0.00 0.00

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 250A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00

MCB RATING 250A ALL OTHERS 0.00 0.00 0.00 100% 0.00 0.00 0.00

MINIMUM AIC (K AMPS) 10 MOTORS AND

EQUIPMENT

LARGEST 0.00 0.00 0.00 125% 0.00 0.00 0.00

SERVICE ENTR. RATED X YES NO >10KVA@50% 0.00 0.00 0.00

MAIN CIRCUIT BREAKER X YES NO GENERAL USE

RECEPT

0.00 0.00 0.00

<=10 KVA@100% 0.00 0.00 0.00

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 0.00 0.00 0.00 125% 0.00 0.00 0.00

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA NEC DEM

FACTOR

DEMAND KVA

2.44 2.23 2.64 TOTAL

SUB TOTAL 0.00 0.18 0.00 2.44 2.05 2.64 SUB TOTAL

001 & COL. 8 RECEPT. PIER... --- --- 0.00 1P-20 41 42 1P-20 --- --- 0.00 SPACE

001 LIGHTING --- 0.00 --- 1P-20 39 40 1P-20 --- 0.00 --- LIGHTING TIME CLOCK

GFI-RECPT. PIER LEVEL @ ELEV. 0.00 --- --- 1P-20 37 38 1P-20 0.00 --- --- SPACE

GFI --- --- 0.00 1P-20 35 36 1P-20 --- --- 0.00 RECEPT. NORTH WALL 108

GFI-ENTRY WAY --- 0.00 --- 1P-20 33 34 1P-20 --- 0.00 --- SPARE

105-RECEPTACLE 0.00 --- --- 1P-20 31 32 1P-20 0.00 --- --- BATTERY POWER

ELEVATOR PIT LIGHTING (N) --- --- 0.00 1P-20 29 30 1P-20 --- --- 0.00 SPARE

ELEVATOR PIT GFI RECEPT. --- 0.18 --- 1P-20 27 28 1P-20 --- 0.00 --- SPARE

105 & 107-RECEPTACLE 0.00 --- --- 1P-20 25 26 1P-20 0.00 --- --- SPARE

108-RECEPTACLE --- --- 0.00 1P-20 23 24 1P-20 --- --- 0.00 108 FLOOR RECEPT.

SPARE --- 0.00 --- 1P-20 21 22 1P-20 --- 0.00 --- 105-FAB COIL UNIT

SPARE 0.00 --- --- 1P-20 19 20 1P-20 0.02 --- --- CONDENSATE PUMP (N)

EXTERIOR LIGHTING-WEST --- --- 0.00 1P-20 17 18 1P-15 --- --- 0.51 EF-1 EXHAUST FAN (N)

HANDYCAP DOOR --- 0.00 --- 1P-20 15 16 --- 0.06 ---

ELEV. RM. RECEPT 0.00 --- --- 1P-20 13 14

2P-15

0.06 --- --- DAC-1 ELEV. RM. HVAC SPLIT UNIT -

INDOOR UNIT (N)

ELEV. RM. LIGHTING --- --- 0.00 1P-20 11 12 1P-20 --- --- 1.13 ELEV. PIT OIL RECOVERY (N)

FRONT STEP LIGHTING --- 0.00 --- 1P-20 9 10 1P-20 --- 1.13 --- SP-1 ELEV. PIT SUMP PUMP (N)

EXTERIOR LIGHTING-NORTH 0.00 --- --- 1P-20 7 8 1P-20 1.50 --- --- ELEV. CONTROL (N)

ENTRY WAY LIGHTING --- --- 0.00 1P-20 5 6 1P-20 --- --- 1.00 ELEV. CAB LIGHTING (N)

RM. 103- LIGHTING --- 0.00 --- 1P-20 3 4 --- 1.7 ---

RM. 105-107-LIGHTING 0.00 --- --- 1P-20 1 2

2P-20

1.7 --- --- CU-1 ELEV. RM. HVAC SPLIT UNIT -

OUTDOOR UNIT (N)

A B C A B C

LOAD SERVED

KVA / Phase

CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase

LOAD SERVED

2. PROVIDE DISCONNECT SWITCH, MOTORIZED DAMPER (POWERED FROM FAN CIRCUIT), ELECTRONICALLY COMMUTATED MOTOR, INLET GUARD, AND COOLING THERMOSTAT TO CONTROL FAN OPERATION.

1. INSTALL PER MANUFACTURER'S INSTRUCTIONS.

REMARKS

EF-1 500 0.25 SQUARE INLINE

BACKWARD INCLINED

CENTRIFUGAL

9.5 36% DIRECT 1,274 0.06 1/6 1 115 1750 CONSTANT 1, 2

CFM IN IN BHP HP

TYPE WHEEL

DIAMETER MIN %

EFF

DRIVE

FAN MAX

RPM

NOMINAL

POWER PHASE VOLT RPM

SPEED

CONTROL

MARK

AIR

FLOW

EXT. STATIC

PRESSURE

FAN MOTOR ELECTRICAL

REMARKS

FAN SCHEDULE

3. PROVIDE MANUFACTURER'S PROGRAMMABLE THERMOSTAT.

2. PROVIDE CONDENSATE PUMP. BASIS OF DESIGN IS ASPEN PUMPS "MINI LIME" (OR EQUAL), 100-250 VAC, 0.16 AMPS, 16 WATTS, 3.2 GALLONS/HOUR PUMPING CAPACITY

1. INSTALL PER MANUFACTURER'S INSTRUCTIONS. REFRIGERANT PIPING SHOWN ON PLANS IS FOR REFERENCE ONLY. SIZE, ROUTE AND INSTALL REFRIGERANT PIPING IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

REMARKS:

DAC-1/CU-1

ELEVATOR

MACHINE ROOM

ELEVATOR

MACHINE ROOM

635/470 24 18 17.6 80 67 95 0.6 15 208/1 16.5 20 208/1 1, 2, 3

CFM MBH MBH °F °F °F MCA MOP VOLTS/PHASE MCA MOP VOLTS/PHASE

Db Wb

MIN TOTAL

CAPACITY

MIN SENS

CAPACITY

MIN SEER

EAT OSA

DESIGN

TEMP

INDOOR UNIT OUTDOOR UNITMARK LOCATION

AREA AND/OR BLDG

SERVED

SUPPLY AIRFLOW,

HI/LOW

COOLING CAPACITY ELECTRICAL DATA

REMARKS

DUCTLESS SPLIT SYSTEM AIR CONDITIONER

3. PROVIDE NEMA 4X WEATHERTIGHT CORROSION RESISTANT ENCLOSURE, CONTROL PANEL, CORD AND PLUG, FLOATS AND ALARMS.

2. BASIS OF DESIGN IS STANCOR "OIL MINDER" (OR EQUAL).

1. INSTALL PER MANUFACTURER'S INSTRUCTIONS.

REMARKS

SP-1 ELEVATOR PIT

SIMPLEX

"OIL-MINDER"

EFFLUENT WATER 50 18 1 45 0.5 1 115 3450 CONSTANT 1, 2, 3

GPM FT HP

FLUID

FLOW HEAD

SP. GR.

MIN. %

EFF

NOMINAL

POWER

PHASE VOLT

MAX

RPM

SPEED

CONTROL

REMARKS

MARK LOCATION TYPE

CIRCULATING FLUID ELECTRICAL MOTOR

SUMP PUMP SCHEDULE

REFERRED FROM:1" = 1'-0"A03

1 FLEXIBLE DUCT CONNECTIONS

ALSO SHOWN:

ELECTRICAL,

Y"

X"

W"

Z"

MOUNT UNIT A

MINIMUM OF 7' AFF

BOLT UNIT TO FRAME (TYP.)

UNISTRUT FRAME

CLEARANCE IN

ACCORDANCE WITH

EQUIPMENT

MANUFACTURER'S

INSTRUCTIONS

REFRIGERANT

LIQUID AND SUCTION

LINES

W

ALL

CLEARANCE IN

ACCORDANCE WITH

EQUIPMENT

MANUFACTURER'S

INSTRUCTIONS

CLEARANCE IN

ACCORDANCE WITH

EQUIPMENT

MANUFACTURER'S

INSTRUCTIONS

W1

W

NOTES:

1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND

INSTALLED AS DETAILED BY SMACNA.

2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE

SINGLE THICKNESS VANE TYPE REGARDLESS OF W

DIMENSION.

3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2"

[50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm]

TRAILING EDGE.

4. WHEN W EQUALS W2 AND W1 IS GREATER THAN

20" [500mm] VANES SHALL BE DOUBLE VANE

TYPE.

SECTION

"A-A"

ACCESS PANEL

ACCESS DOOR

SECTION

"B-B"

"A"

"A"

INSULATION

DUCT

GASKET

INSULATION

NOTES:

1. LATCHES SHALL BE OF THE

WEDGE TYPE TO CLOSE

DOORS TIGHTLY.

2. HINGES ON THE ACCESS

DOORS SHALL HAVE NON-

CORROSIVE PINS.

3. SEE SMACNA 2006, FIGURE

9-15.

"B" "B"

CASING

INSULATION

GASKET

HANDLE INSIDE

FLEXIBLE WASHER

FACTORY

FABRICATED LATCH

EXISTING

ELEVATOR

PIT/HOISTWAY

ELECTRIC

OUTLET BY

ELECTRICAL

CONTRACTOR

POWER SUPPLY

MULTI-PIN CONNECTOR

AND CORD IN CONDUIT.

LENGTHS AS REQUIRED.ELEVATOR

MACHINE

ROOM

UTILITY

ROOM

FLOOR

JUNCTION BOX

GATE

VALVE

1. STANCOR "OIL MINDER" (OR EQUAL) SURFACE-

MOUNTED EFFLUENT PUMP, 0.5HP, 115 VOLT, 3450

RPM, 2" DISCHARGE. SURFACE MOUNT PUMP IN NEW

DEPRESSION IN PIT FLOOR. MOUNT ALUMINUM ANGLE

AND EXPANDED METAL CAGE OVER TOP OF SUMP

PUMP.

2. STANCOR (OR EQUAL) CHECK VALVE.

3. STANCOR OIL-MINDER (OR EQUAL), 115V, 1Ø

CONTROL SYSTEM WITH OPTIONAL BUILT IN AUDIBLE

AND VISUAL ALARM WHEN PUMP DOES NOT RUN DUE

TO OIL IN PIT, HIGH AMPERAGE OF HIGH LIQUID

CONDITION. PROVIDE SILENCING BUTTON FOR AUDIBLE

ALARM BUILT INTO PANEL. PANEL SHALL HAVE

ADDITIONAL CONTACT FOR A REMOTE ALARM

LOCATION.

4. JUNCTION BOX WILL BE PROVIDED WITH MULTI-PIN

CONNECTOR AND CORD IN LENGTHS AS REQUIRED;

25 FT. IS STANDARD, OPTIONAL 25FT. INCREMENTS

AVAILABLE.

5. ALL BURIED PUMP PRESSURE DISCHARGE PIPING

SHALL BE PROTECTED WITH TAPECOAT CT (OR

EQUAL) CORROSION PROTECTION TAPE.

6. OIL-MINDER POWER CABLE, PROBE CABLE AND

FLOAT CABLE (ALL 16' LONG).

7. HIGH LIQUID ALARM FLOAT WITH CLAMP DEVICE TO

MOUNT TO PUMP DISCHARGE PIPING.

8. ORIENT FLOAT AS LOW AS POSSIBLE WITHIN

DEPRESSION TO ACTIVATE WHEN DEPRESSION FILLS

WITH WATER AND DEACTIVATE WHEN EMPTY. FLOATS

ARE SHOWN DIAGRAMMATICALLY ONLY.

9. SAW CUT A NEW DEPRESSION IN ELEVATOR PIT

FLOOR SLAB TO ALLOW FOR ADEQUATE COLLECTION

OF WATER INTO SUMP PUMP INLET. DEPRESSION

SHALL BE 6" DEEP, APPROXIMATELY 18"x18" SQUARE

(COORDINATE ACTUAL LENGTH AND WIDTH WITH SUMP

PUMP AND FLOAT SYSTEM).

05-01

A04

SEALANT &

BACKER ROD

1 1/2" X 1/4" THK.

STL. PLATE (CONT.)

ON STL SHIMS

3/4 X 3/4 X 1/8

SS ANGLE, CONT.

EXIST ELEV.

DOOR & FRAME

MIN. 18 GA. S.S.

PROVIDE 3/8" DIA.

WEEP HOLES AT 6"

FROM EACH END

NOTE: SET EDGE OF S.S.

BRAKE METAL IN CONT. BED

OF CONCEALED SILICONE

SEALANT AT S.S. ANGLE

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO. TITLE OF SHEETA/E FIRM:

OF

PKG.

NO.

SHEET

xxxxxxQUINN EVANS

ARCHITECT:

DRAWING NO.

ANN ARBOR, MI

DETROIT, MI

MECHANICAL &

ELECTRICAL:

APOGEE

RALEIGH, NC

P L ib e rt y S q u a re V C D w g s R e v it L i b e rt y S q u a re R .r v t

A04 08/20/2021

DETAILS

REPLACEMENT OF ADA ELEVATOR

FORT SUMTER NATIONAL MONUMENT

05-01 PROVIDE BREAK METAL STAINLESS STEEL CLOSURE. SEAL

WITH A SILICONE SEALANT JOINT AT THE LEADING EDGE OF

THIS TRIM. PROVIDE TWO PLASTIC WEEPS PRIOR TO SEALING.

A04

3 DUCTWORK SQUARE VANE ELBOWS

A04

4 ACCESS PANEL AND DOOR DETAIL

A04

6 SECTION AT SUMP PUMP

ALSO SHOWN:

ELECTRICAL,

MECHANICAL,

& PLUMBING

A04

WALL MOUNTED CONDENSING

UNIT INSTALLATION DETAIL

REFERRED FROM:1/4" = 1'-0"A04 A01

2 TYPICAL ELEVATOR DOOR ELEVATION

REFERRED FROM:1" = 1'-0"A04 A02

5 HEADER AT PIER LEVEL DOOR

Sheets
G00 - COVER SHEET
G01 - SYMBOLS AND ABBREVIATIONS
AS00 - KEYPLAN & SITE PLAN STAGING
D01 - DEMOLITION PLANS
A01 - NEW WORK PLANS
A02 - SECTIONS
A03 - SCHEDULES & DETAILS
A04 - DETAILS

File details come from the government source that posted it. Updated .